Faraday 8701 Installation Instructions And Wiring
Text of the manual
PAGE 1 OF 2
P/N 315-049480FA-2
Figure 1
8701 Module
The 8701 contact monitoring module interfaces direct shorting devices to the
System’s Addressable Device Circuit.
The 8701 can monitor a normally open or closed dry contact and it can report
the status of the contact.
PROGRAMMING
Refer to Figure 1 to locate the red and black Addressable Device Circuit
wir
PAGE 2 OF 2
P/N 315-049480FA-2
Figure 2
Installing the 8701 Wiring
NOTES:
1. All supervised switches must be held closed and/or open for at least a quarter of a second to guarantee detection.
2. End of line device: 470 ohm, 1/4W resistor, P/N 140-820164.
3. 8701 is polarity insensitive. Line 1 and Line 2 can be either line of the loop.
4. The supervised swit