Harrington Signal HS-3100 Programming Manual
Text of the manual
Fire Alarm Control Unit
Programming Manual
Revision 1 January 2009
Document # LT-2001HAR
HARRINGTON
FIRE ALARM
SIGNAL INC.
HS-3100/3200 Programming Manual
i
Table of Contents
1.0 Operation and Programming Concepts ......................................................................... 1
1.1 Introduction ................................................................................................................... 1
1.2 General Information ..................................
HS-3100/3200 Programming Manual
iii
List of Figures & Tables
Figure 1: Four Wire Device Wiring (Typical) ....................................................................... 5
Figure 2: Network Plus System Window ............................................................................. 7
Figure 3: Switches Window ......................................
HS-3100/3200 Programming Manual
1
1.0 Operation and Programming Concepts
1.1 Introduction
This chapter provides an overview of the HS-3100/3200’s (hereafter called the HS-3200) features
and supported devices.
1.2 General Information
Warnings: Before Programming
1.
All applicable codes and standards should be considered when programming the Control
Unit.
2.
HS-3100/3200 Programming Manual
2
1.3 Addressable Devices
Supported Devices
The HS-3030 can use analog/addressable devices. There are two general types of devices:
sensors and modules. The following devices are supported:
The M500S control module can be used to control a supervised output, such as a bell or strobe
circuit. The control module monitors the cir
HS-3100/3200 Programming Manual
3
circuit is shorted. Also there are options in NP that affect the M500S control module but not the
M500R relay module.
The M500R relay provides two Form C relays. Choose “Control (relay)” for the M500R module.
There are options in NP that affect the M500R relay module that do not affect the M500S control
module.
The M500X
HS-3100/3200 Programming Manual
4
Device Faults
The following troubles (with condition code letter) can be reported by or for addressable devices:
•
Missing (M): A device listed in the database is not reporting back when polled by the
panel. For a new installation, this is generally indicative of devices that have been mis-
addressed. This error can also o