Hubbell 4-PLEX Wiring And Assembly Instruction
Text of the manual
Receptacles, Adapter Plate, and Portable Box
Wiring and Assembly Instructions
READ INSTRUCTIONS
COMPLETELY
PRIOR TO INSTALLATION.
GENERAL WIRING INFORMATION:
Notice: For installation
only by a qualilied electri-
cian in accordance with the National Electrical
Code9 Canadian Electrical Code, and local code
requirements,
and the following instructions.
.
Caution: Risk of electric shock. Disconnect
power before installing. Never wire energized
electrical components.
Attention: Risque de chock electrique.
D6branchef le circuit avant I'installation. Ne ia-
mais faire les connections sur circuit vivant.
Caution: Use with copper conductors only.
Attention: Employer uniquement ave fil de
culver.
Binding head terminal screws accept up to #12
AWG solid or stranded conductors.
Do not use tinned'conductors.
Refer to NECoTable
400-5 or CEC Table 12 lor
ampacity of flexible cords. Use ampacities from
the 60oC column. Portable box accepts cord
ranges 16/3SJ to 12l3SO.
.
Reler to NECOTable
310-16 or CEC Table 2 tor
ampacity
ot insulated
conductors.
Use conduc-
tors with insulation
rated 90oC or higher having
sufficient ampacity in accordance with the 60oC
column.
NOTE TO INSTALLER:
lnstructions
should be left
with end user tor tuture reference.
SURGE SUPPRESSOR
RECEPTACLE
Refer to general wiring inlormation (above and be-
low).
Connect this device only to 1 25 VAC max. grounded
branch circuit with listed or certilied over-current
orotectlon rateclz$Fmax. (U.S.) or attffibff
current rating (Canada). Inadvertent
connection to
a higher voltage will damage the device. Oiscon-
nection of neutral conductor while circuit is ener-
gized on a 1251250
VAC service could produce a
damaging higher voltage.
CAUTION: RISK OF ELECTRIC
SHOCK. This
device is intended for installation on a SINGLE
branch circuit (2-wire plus ground) only" DO
NOT separately wire the outlets of this device to
a multFwire branch circuit (3-wire plug ground).
ATTENTION: RISQUE DE CHOC ELECTRIOUE.
Ce dispositil est pour un installation sur un
courant SIMPLE (2 lils et mise A la terre) seule-
ment. NE pas brancher s6parement les prises
du dispositif sur un A circuit multiple branche'
ments (3 fils et mise a la terre).
This device may be wired as a feed-thru unit t0
protect additional outlets on tf'e same ci::rt
OPERATION
GREEN-Light
Emittin Diode (LED) "ON" indicates
that power is on and surge protection is tunctioning.
A faint glow of ihe red LED is noticeable
and indi-
cates LED is lunctioning
and is in a standby condi-
tion.
When the green LED light goes oui and the red LED
is BRIGHTLY
LlT, the receptacle
is no longer able
to provide surge protection because of damage
caused by large transient surges beyond the recep-
tacle's rating. The receptacle
will continue
to func-
tion without surge protection. Replace the entire
unit immediately
to restore surge protection.
This device is not a lightning
arrestor and lightning
may damage the unit.
NOTICE
Do not hot wire surge suppressor receptacle -
doing so will damage the unit and void warranty.
Turn off power to outlet by removing fuse or turning
ofl circuit breaker. lf an existing duplex receptacle
is being replaced, shut oft power to receptacle,
confirm that both outlets are not powered by using
a test lamp. lf both outlets are not powered' pro-
ceed to Step 1. lf power is present in eithet outlet,
the existing outlet was split-wired. Surge suppres-
sor receotacles cannol be used to replace a split-
wire receotacle.
Adapter Plate
(2) Knockouts for op'
tional 4 screw mount-
ing to adapter plate.
one receptacle), consult a qualified electrician
for prop€r wiring and installation. Should this
situation exist, do not anempt installation with-
out a oualified electrician.
4. 4-PLEX lsolated Ground lnstallations: The 4-
PLEX may be installed as an "lsolated
ground" device it a separate insulated equip-
ment grounding wire has been installed trom
the ground bus at service entrance. When in-
stalled this way, the metallic raceway and de-
vice box MUST Oe grounded to the normal
building ground system and the isolated
ground wire MUST be connected to the receP
tacte. Tne "lsolated ground" label MUST be
placed on the front surface of the 4-PLEX
where visible after installation for identifica-
tion required by the National Electrical Codeo
Section 410-56(c).
4-PLEX
RECEPTACLE
' SN€AK OFF.TAES
TERMINAL SCREWS
EACK V|EW
STRIP GAUGE
t Not accesible or removeable on 4-PLEX receptacles with surge suppression.
@
Anchor Hole
1. Mount adapter date to box using (2) *32 x7l8
inch flat head screu6. Position flange side
facing box and pull cable ftrougilt opening in
adapter Plate.
2. Strip insulation on individual conductors 3/4
inch and wire each to proper terminal; black
conductor to brass screw, white conductor to
silver screw, green or bare conductor to
green grounding screw. Anchor conductor in
anchor hole provided and wrap in a counter-
clockwise direction. For larger size conduc-
tors, form loop and place under head of termi-
nal screw. Tighten terminal screws 1G12
pound-inches
(1.2 - 1,4 N.m) in a clockwise
direction.
A grounding ftilail is provid€d to ground recepta-
cle to a metallic box where no grounding con-
ductor is available. (See Step 4 for isolated
Ground installations.)
lf box contains additional conductors to feed
other recegtacles on the same circuit, use re-
maining terminal screws to connect the con-
ductors. Follow the color code designations
above. Consult a qualified electrician
if you
have any questions concerning
the installa-
tion of this device: Take extra caution that
there are no loose strands.
3. 4-PLEX without Surge Suppression: Two
break ofl trabs are grovided for split circuit wir
ing. A and B circuit identitication is molded
into face of recegtacle.
lf you control a receptacle or portion of the fe
ceptacle lrom a wall switch, or if the recepta-
cle has split circuit wiring (two circuits feeding
to adapler plate usiirg two #B x 5/16 pan-head screws. lnstallation
is complete. For optional 4 screw mounting, remove two knockouts on
receptacle
and c{rmplele
installation
using lwo additional
pan head screws provided.
CONCRETE
OCTAGON RING
(Flush Mounted)
Bemove knockouts
indicated
and
mount receptacle using #B x l
rnch mounting
screws provided
with
4 . P L E X .
4'' OCTAGON
Remove knockouts
indicated
and
mount receptacle using #8 x 1
inch mounting screws provided
with 4-PLEX.
4" SQUARE
SURFACE
MOUNTED: Mount re-
ceptacle using two #8 x 1 inch
mounting
screws provided
with 4-
PLEX.
FLtiSH MOUNTED: For {tush
mounting,
mount adapter plate to
box using two #8 x 1 inch mount-
ing screws and mount 4-PLEX to
adapter plate using two #8 x 5/.16
inch pan-head screws provided
With 4-PLEX.
2-GANG
Mount adapter plate to 2 gang
box using two 6-32 x 7/8 inch flat
head screws provided with
adapter. Mount 4-PLEX to
adapter plate using two #8 x 5/16
inch pan-head screws.
4" SQUARE WITH PLASTER
RING (Flush Mounted)
Mount adapter plate to plaster
using two 6-32 x 718 inch flat
head screws provided with
adapter plate. Mount 4-PLEX to
adapter plate using two #8 x 5/1 6
inch pan-head screws.
SINGLE GANG
(Flush Mounted)
Mount adapter plate to single
gang box using two 6-32 x 718
inch flat head screws provided
with adapter. Mount 4-PLEX to
adapter ptate using two #8 x 5/1 6
inch Dan-head
screws.
Hubbell Portable Non-Metallic Boxes
PORTABI F ROX
.
Suitable for use with 4-Plex Receptacles
only.
.
For 15A, use 12-14 AWG wires.
.
For 20A, use 12 AWG wires.
.
Use stranded copper wire only.
.
Do not use tinned conductors.
Strip cord jackel 4 inches and individual conductors 3/4
inch. Insert cord through opening in box and wire individ-
ual conductors to proper terminals; black conductor to
brass screw, white conductor to silver screw, green or
bare conductor to green grounding screw. Place top hall
of cord grip over cord allo$,ing 1/4 inch of cord iacket to
extend beyond cord grip. Tighten two assembly screws
until cord is secure. Mount receptacle to box using two
#8 x 5/16 inch pan-head screws.