TA STA Quick Start Manual
Text of the manual
Application: Heating installations, pota-
ble water installations.
Functions: Balancing-s hutting-draini ng-
filling-measuring pressure drop and
flow.
Nominal pressure: PN 20
Max. working pressure:
2.0 MPa = 20 bar z 300 psi
Max. working temperature: 150 "C
Material: The valves are made comple-
tely of AMETAL@ and are fitted with a red
nylon handwheel. Prefa
52 170 STA
,
-
L
d
l
y
*) DrainIEntleerunglRobinet de vidange
52 171 STA-D
52 173 STA-D R
*) DrainIEntleerunglRobinet de vidange
52 189
Prefab insulation
Vorgefertigte Varmedammung
Calorifuge preforme
, -1
Kvs = m3/h at a pressure drop of 1 bar and fully open valve
-
Kvs = m3/h bei einem ~ruckverlust von 1 bar und-vol1 geöffnetem Ventil
Kvs = m3/h pour une
This graph shows the pressure drop
over the pressure test points of the
valve.
A straight line connecting the bars for
flow rate, Kv and pressure drop shows
the relationship between these varia-
bles.
Example:
Wanted: Presetting for DN 25 at a desi-
red flow rate of 1,6 m3/h and a pressure
drop of 10 kPa.
Solution:
Draw a straight line joining 1,6 m3/h and
1
A valve that operates with a high level
of flow capacity naturally has a large
cross-section area when fully open.
TA
works with high tolerance de-
mands with respect to valve seat and
cone diameters. The level of accuracy
is highest when the valve is open. The
smaller the valve opening, the greater
the importance of manufacturing tole-
rances, since the var
When calculating and dimensioning
pipe systems, the following values or
formulas for valve resistance must be
used. In calculating work, they provide
the actual capacity of the valve since
the pressure drop is based on measu-
rements (see SMS 1000) at the feed
outlet at such a distance from the
valve that turbulente inside the valve
itself does not influence
The actual pressure drops in water
distribution pipework are difficult to
calculate accurately. This means that
in practice, the flow rate, and conse-
quently the caloric distribution, is
often incorrect. With the STA-D valve,
however, it is easy to set the desired
flow rate.
Die tatsachlichen Druckverluste in den
verschiedenen Steigstrangen und Grup-
pen ei