Vakuum-Leistungsschalter 3AH52 (Shunt)

24 kV Vacuum Circuit-Breaker 3AH52 (Shunt) 24 kV Alle Rechte vorbehalten. All rights reserved. © Siemens AG 2009 Betriebsanleitung/Operating Instructions Bestell-Nr./Order-No.: 9229 0037 174 0- Bestell-Nr./Order No.: 9229 0037 174 0- Bestell-Ort/Place of order: E D MV C MF 115 AG 01.2010 Kb De-En

9229 0037 174 0-

2010-03-22 Inhalt Seite 1 Allgemeines ................................................... 1-1 2 Technische Daten ....................................... 2-1 2.1 Typbezeichnung ................................................... 2-1 2.2 Leistungsschild .................................................... 2-2 2.3 Vorschriften .......................................................... 2-2 2.4 Umgebungstemperatur/ Luftfeuchte und Belastbarkeit 2-2 2.5 Aufstellhöhen ....................................................... 2-4 2.6 Bemessungsdaten Vakuum-Leistungsschalter 3AH5 2-5 2.7 Schaltzeiten ......................................................... 2-5 2.8 Hilfsschalter (S1) 3SV92 ...................................... 2-6 2.9 Einschaltmagnet (Y9) 3AY1510 ........................... 2-6 2.10 Arbeitstromauslöser (Y2) 3AX1101 ..................... 2-6 2.11 Unterspannungsauslöser (Y7) 3AX1103 (optional) 2-7 2.12 Wandlerstromauslöser (Y4) 3AX1102 (optional) . 2-7 2.13 Wandlerstromauslöser (Y6) 3AX1104 (energiearmer Auslöser 0,1 Ws optional) 2-7 2.14 Hilfsschütz (K1) .................................................... 2-8 2.15 Überspannungsschutz Sekundärausrüstung ....... 2-8 2.16 Anzeige "Feder gespannt" ................................... 2-8 2.17 Motor (M1) ........................................................... 2-8 2.18 Mechanische Schaltstellungsabfrage (optional) .. 2-9 2.19 Maße und Gewichte ............................................. 2-9 3 Beschreibung ................................................ 3-1 3.1 Aufbau .................................................................. 3-1 3.2 Ausstattung .......................................................... 3-3 4 Montage ........................................................... 4-1 4.1 Befestigung in Schaltzelle oder auf Schaltwagen 4-1 4.2 Stromschienenanschluss ..................................... 4-2 4.3 Steuerleitungen .................................................... 4-2 4.4 Erdung ................................................................. 4-2 4.5 Schaltpläne .......................................................... 4-3 5 Betrieb .............................................................. 5-1 5.1 Inbetriebnahme .................................................... 5-1 5.2 Einschalten .......................................................... 5-3 5.3 Ausschalten ......................................................... 5-3 6 Instandhaltung ............................................. 6-1 6.1 Wartung ............................................................... 6-1 6.2 Reinigen ............................................................... 6-1 6.3 Sonder-Betriebsbedingungen .............................. 6-2 6.4 Kontrolle des Kontaktsystems .............................. 6-2 6.5 Vakuum-Kontrolle ................................................ 6-2 6.6 Lebensdauer ........................................................ 6-2 6.7 Zubehör und Ersatzteile ....................................... 6-3 6.8 Produkthaftung des Herstellers ............................ 6-3 7 Entsorgung .................................................... 7-1 8 Service ............................................................. 8-1 Contents Page 1 General .............................................................. 1-1 2 Technical data ................................................ 2-1 2.1 Type designation ................................................... 2-1 2.2 Rating plate ........................................................... 2-2 2.3 Standard specifications ......................................... 2-2 2.4 Ambient temperature/humidity and loadability ...... 2-2 2.5 Site altitude ........................................................... 2-4 2.6 Rated data 3AH5 vacuum circuit-braker ............... 2-5 2.7 Operating times ..................................................... 2-5 2.8 Auxiliary switch (S1) 3SV92 .................................. 2-6 2.9 Closing solenoid (Y9) 3AY1510 ............................ 2-6 2.10 Shunt release (Y2) 3AX1101 ................................. 2-6 2.11 Undervoltage release (Y7) 3AX1103 (additional feature) 2-7 2.12 CT-Operated release (Y4) 3AX1102 (additional feature) 2-7 2.13 CT-Operated release (Y6) 3AX1104 (low energy re- lease 0.1 Ws additional feature) 2-7 2.14 Auxiliary contactor (K1) ......................................... 2-8 2.15 Surge protection secondary equipment ................. 2-8 2.16 Indication "spring tensioned" ................................. 2-8 2.17 Motor (M1) ............................................................. 2-8 2.18 Mechanical switching position sensing (additional feature) 2-9 2.19 Dimensions and weights ....................................... 2-9 3 Description ...................................................... 3-1 3.1 Construction .......................................................... 3-1 3.2 Equipment ............................................................. 3-3 4 Installation ....................................................... 4-1 4.1 Installing in cubicle or on truck .............................. 4-1 4.2 Flat bar connection ................................................ 4-2 4.3 Control leads ......................................................... 4-2 4.4 Earthing ................................................................. 4-2 4.5 Wiring diagrams .................................................... 4-3 5 Operation .......................................................... 5-1 5.1 Commissioning ...................................................... 5-1 5.2 Closing .................................................................. 5-3 5.3 Opening ................................................................. 5-3 6 Maintenance .................................................... 6-1 6.1 Servicing ................................................................ 6-1 6.2 Cleaning ................................................................ 6-1 6.3 Abnormal operating conditions .............................. 6-2 6.4 Checking the contact system ................................ 6-2 6.5 Checking the vacuum ............................................ 6-2 6.6 Service life ............................................................. 6-2 6.7 Accessories and spare parts ................................. 6-3 6.8 Manufacturer's product liability .............................. 6-3 7 Disposal note ................................................. 7-1 8 Service ............................................................... 8-1

9229 0037 174 0-

2010-03-22 1-1 1 Allgemeines Die Siemens-Vakuum-Leistungsschalter (V-Schalter) 3AH5, in der Sonderbauform Shunt-Schalter, sind dreipolige Innen- raum-Leistungsschalter für eine Bemessungsspannung von 24 kV, bei denen jeder Pol einzeln angetrieben wird. Die Einbaulage des V-Schalters bezogen auf die Vakuum- Schaltröhren ist senkrecht. Unter normalen Betriebsbedingungen ist der V-Schalter war- tungsfrei nach IEC 62271-1 und VDE 0671-1. WARNUNG Beim Betrieb elektrischer Geräte stehen zwangsläufig bestimmte Teile dieser Geräte unter gefährlicher Span- nung und es können sich mechanische Teile, auch ferngesteuert, schnell bewegen. Bei Nichtbeachtung der Warnhinweise können deshalb schwere Körperverletzungen oder Sachschäden auf- treten. Nur entsprechend qualifiziertes Personal sollte an diesem Gerät oder in dessen Nähe arbeiten. Dieses Personal muß gründlich mit allen Warnungen und Instandhaltungsmaß- nahmen gemäß dieser Betriebsanleitung vertraut sein. Der einwandfreie und sichere Betrieb dieses Gerätes setzt sachgemäßen Transport, fachgerechte Lagerung, Aufstel- lung und Montage sowie sorgfältige Bedienung und Instandhaltung voraus. Hinweis V-Schalter 3AH5 sind in der Standardausführung und mit allen listenmäßigen Ausstattungsvarianten typgeprüfte Geräte nach IEC. Bei nachträglichen An- und Einbauten, z. B. Verriegelungs- bauteilen in Verbindung mit Schaltanlagen, ist darauf zu achten, daß schnell bewegte Teile nicht durch Massen oder Kräfte zusätzlich belastet werden und Zusatzteile einen ausreichenden Abstand insbesondere zu bewegten und spannungsführenden Teilen haben. Sollen Schalter kundenseitig mit Zusatzfunktionen ausge- rüstet werden, empfehlen wir mit dem Werk Rücksprache zu nehmen, da häufig schon bewährte und geprüfte Lösun- gen vorliegen. 1 General Siemens 3AH5 vacuum circuit-breakers (V-breaker), in the special design as shunt breaker, are of the triple-pole indoor type for rated voltages of 24 kV, where each pole is driven separately. The vacuum circuit-breaker is installed vertically (in relation to the vacuum interrupters). Under normal operating conditions the vacuum circuit-breaker is maintenance-free in accordance with IEC 62271-1 and VDE 0671-1. WARNING This equipment contains hazardous voltages and mechanical parts which move at high speed and may be controlled remotely. Non-observance of the safety instructions can result in severe personal injury or property damage. Only qualified personnel should work on or around this equipment after becoming thoroughly familiar with all warn- ings, safety notices, and maintenance procedures con- tained herein. The successful and safe operation of this equipment is dependent on proper handling, installation, operation and maintenance. Note In their basic design and with all standard listed equipment options, 3AH5 V-breakers are type-tested components in accordance with IEC. If any attachments or installations, e. g. interlocking com- ponents in connection with switchgear, are made to the breakers at a later stage, it must be ensured that quickly moving parts are not loaded additionally by masses or forces and that any added parts have an adequate clearence particularly to moving and live parts. If the customer intends to fit the breakers with additional functions, we recommend that he should first consult our factory as in most cases proven and tested solutions are already available.

9229 0037 174 0-

2010-03-22 2-1 2 Technical data 2.1 Type designation 3AH5 vacuum circuit-breakers are identified by a machine- readable product designation made up of a series of figures and letters, whose first 8 places can be found on the name plate of the circuit-breakers. In connection with the serial number stated on the name plate, the machine-readable product designation provides a full description of the circuit- breaker. The figure below shows what the individual places of the basic machine-readable product designation stand for: 1 Basic type 2 Rated voltage code and pole-center distance code 3 Rated short circuit breaking current code 4 Rated normal current code Fig. 2/1 Product designation 2 Technische Daten 2.1 Typbezeichnung Die V-Schalter 3AH5 sind mit einer maschinenlesbaren Fabri- katebezeichnung (MLFB) gekennzeichnet. Sie besteht aus einer mehrstelligen Ziffern-Buchstabenkombination, deren erste 8 Stellen auf dem Leistungsschild des Schalters darge- stellt sind. In Verbindung mit der auf dem Leistungsschild vermerkten Fabriknummer ermöglicht die MLFB die vollstän- dige Beschreibung des Schalter. Die Bedeutung der einzelnen Stellen der Grund-MLFB ist nachfolgend dargestellt: 1 Grundtypbezeichnung 2 Kennzahl für Bemessungsspannung und Polmittenabstand 3 Kennzahl für Bemessungs-Kurzschlussausschaltstrom 4 Kennzahl für Bemessungsbetriebsstrom Fig. 2/1 Fabrikatebezeichnung 3 A H 5 2 6 2 - 1 ... 1 2 3 4

9229 0037 174 0-

2010-03-22 2-2 2.2 Leistungsschild Der V-Schalter hat für jeden der drei Antriebe ein Leistungs- schild, auf dem die Grund-MLFB des Schalters mit jeweiliger Phasenbezeichnung R, S, T angegeben ist. Außerdem enthält es die folgenden Angaben: 1 Qualitätskontrollstempel 2 Hersteller 3 Baujahr 4 Bemessungsbetriebsstrom Ir 5 Bemessungs-Kurzschlussdauer tk 6 Masse m 7 Bemessungsschaltfolge 8 Klassifizierung nach IEC 62271-100 9 Bemessungs-Kurzzeitwechselspannung Ud 10 Bemessungs-Blitzstoßspannung Up 11 Bemessungs-Kurzschlussausschaltstrom Isc 12 Bemessungsspannung Ur, Bemessungsfrequenz 13 Fabriknummer 14 Typ- und Phasenbezeichnung Fig. 2/2 Leistungsschild 2.3 Vorschriften Die Vakuum-Leistungsschalter 3AH5 entsprechen den Vor- schriften IEC 62271-100, IEC 62271-1, BS EN 62271-100 und IEC (DIN EN) 60265-1. Alle Vakuum-Leistungsschalter 3AH5 erfüllen die Vorschriften für die Leistungsschalter-Klassen C2, E2 und M2 gemäß IEC 62271-100. Sie erfüllen die Forderungen nach RöV vom 8. 1. 1987 (BGBl. I, Seite 114) § 8 und Anl. II Nr. 5 bis zur Höhe der nach DIN VDE/IEC festgelegten Bemessungsspannung. 2.4 Umgebungstemperatur/Luftfeuchte und Belastbarkeit Die V-Schalter 3AH5 sind für die in den Vorschriften festge- legten normalen Betriebsbedingungen ausgelegt. Die zulässige Umgebungstemperatur beträgt: Die zulässige relativen Luftfeuchte beträgt: Hinweis Bei Fragen bitte Typbezeichnung und Fabriknummer ange- ben. Höchstwert = +40 °C Höchstwert des 24-Stunden-Mittels = +35 °C Tiefstwert = –5 °C Höchstwert, gemessen über 24 Std. 95 % Höchstwert, gemessen über 1 Monat 90 % 2.2 Rating plate The V-breaker has a rating plate for each of the three mech- anisms, on which the order code of the breaker with the single phase-designation R, S, T is mentioned. Furthermore it con- tains the following information: 1 Quality control 2 Manufacturer 3 Year of manufacture 4 Rated normal current Ir 5 Rated operation sequence tk 6 Weight m 7 Rated operation sequence 8 Classification with IEC 62271-100 9 Rated short-duration power-frequency withstand voltage Ud 10 Rated lightning impulse withstand voltage Up 11 Rated short-circuit breaking current Isc 12 Rated voltage Ur, Rated frequency 13 Serial number 14 Type- and Phase designation Fig. 2/2 Rating plate 2.3 Standard specifications The 3AH5 vacuum circuit-breakers comply with the standards of 62271-100, IEC 62271-1, BS EN 62271-100 and IEC (DIN EN) 60265-1. All 3AH5 vacuum circuit-breakers comply with the standards of the circuit-breaker classes C2, E2 and M2 in accordance with IEC 62271-100. They conform to the requirements of the X-ray regulations of January 8, 1987 (Federal Law Gazette Page 114) § 8 and Annex II No. 5 up to rated short-time AC voltage stipulated in accordance with DIN VDE/IEC. 2.4 Ambient temperature/humidity and loadabil- ity The 3AH5 V-breakers are designed for the normal operating conditions laid down in the standards. Permissible ambient temperatures: Permissible relative atmospheric humidity: Note In the event of any queries please state the type designation and the serial number. Maximum value = +40 °C Average over a period of 24 hours = +35 °C Minimum value = –5 °C Maximum value, 24 hour mean 95 % Maximum value, 1 month mean 90 %

9229 0037 174 0-

2010-03-22 2-3 Unter diesen Bedingungen kann gelegentlich Kondensation auftreten. Weiterhin ist der Schalter für den Einsatz in den folgenden Klimaklassen nach IEC 60721, Teil 3-3 geeignet: Der Einsatz des Schalters bei Abweichungen von diesen normalen Betriebsbedingungen ist durch Sondermaßnahmen möglich. Bitte erfragen Sie die notwendigen Maßnahmen bei Ihrer nächsten Siemens-Vertretung. Der in den elektrischen Daten in Fig. 2/5 angegebene Bemes- sungsbetriebsstrom wurde nach IEC 62271-1 für eine Umge- bungstemperatur von +40 °C festgelegt. In Fig. 2/3 ist der Grenzwert für den Belastungsstrom in Abhängigkeit von der Umgebungstemperatur der V-Schalter 3AH5 aufgezeichnet. Der angegebene Belastungsstrom gilt für offene Schaltanla- gen. Bei gekapselten Schaltanlagen ist eine Reduzierung nach Angaben des Schaltanlagenherstellers durchzuführen. Fig. 2/3 Grenzwerte für den Belastungsstrom I in Abhängigkeit von der Umgebungstemperatur T des V-Schalters 3AH5 für Bemessungs-Betriebsstrom von 800 A Klimatische Umweltbedingungen: Klasse 3K41) Biologische Umweltbedingungen: Klasse 3B1 Mechanische Umweltbedingungen: Klasse 3M2 Chemisch-aktive Stoffe: Klasse 3C22) Mechanisch-aktive Stoffe: Klasse 3S23) 1) Untere Temperaturgrenze: -5 °C 2) ohne Eisbildung und windgetriebenen Niederschlag 3) EInschränkung: Saubere Isolierteile Under these conditions condensation may occasionally occur. Furthermore, the breaker is also suitable for use in the following climatic categories per IEC 60721, Part 3-3: Use of the breaker under conditions other than normal is possible when certain measures are implemented. Please ask your local Siemens office about the necessary measures. The rated normal currents listed in Fig. 2/5 were laid down for an ambient temperature of +40 °C in accordance with IEC 62271-1. The maximum permissible load current as a function of the breaker ambient temperature has been plotted in Fig. 2/3. The load currents indicated apply to open-type switch- gear. Metal-enclosed switchgear must be derated as specified by the switchgear manufacturer. Fig. 2/3 Maximum permissible load current I as a function of the switch ambient temperature T for rated normal currents from 800 A Climatic environmental conditions: Category 3K41) Biological environmental conditions: Category 3B1 Mechanical environmental conditions: Category 3M2 Chemically active materials: Category 3C22) Mechanically active materials: Category 3S23) 1) Lower temperature limit: -5 °C 2) Without ice formation and wind-driven precipitation 3) Prerequisite: clean insulating parts

9229 0037 174 0-

2010-03-22 2-4 2.5 Aufstellhöhen Das Isoliervermögen einer Isolierung in Luft nimmt mit stei- gender Höhe wegen der geringeren Luftdichte ab. Die in Fig. 2/5 angegebenen Bemessungs-Blitzstoßspannungs- werte sind nach IEC 62271-1 bis zu einer Aufstellhöhe von 1000 m über Normalnull gültig. Ab einer Höhe von 1000 m ist der Isolationspegel gemäß Fig. 2/4 zu korrigieren. Fig. 2/4 Korrekturfaktor a in Abhängigkeit von der Aufstellungshöhe h Beispiel Für eine geforderte Bemessungs-Stehspannung von 75 kV in 2500 m Höhe wird ein Isolationspegel von mindestens 90 kV unter Norm-Bezugsatmosphäre benötigt: U  U0  Ka U Bemessungs-Stehspannung U unter Norm-Bezugsat- mosphäre U0 Geforderte Bemessungs-Stehspannung für den Auf- stellungsort Ka Höhenkorrekturfaktor Ka = em  (H - 1000)/8150 Berechnung des Höhenkorrekturfaktors Ka: H = Aufstellungshöhe in Metern m = 1 für Wechselspannung, Blitzstoß-Spannung (zwischen den Leitern, Leiter-Erde, Längsbeanspru- chung) 90 kV  75 kV  e1  (2500 - 1000)/8150  75 kV  1,2 2.5 Site altitude The dielectric strength of an insulation is sinking by an ascend- ing altitude because of the lower air density. The rated lightning surge voltages in Fig. 2/5 are valid to a site altitude of 1.000 m above sea level in accordance with IEC 62271-1. About 1.000 m the insulation level has to be configured in accordance with Fig. 2/4. Fig. 2/4 Relationship between the correction factor a and the altitude h Example A minimal insulation level of at least 90 kv under a normal reference atmosphere is necessary for a required rated with- stand voltage of 75 kv in 2500 m high.: U  U0  Ka U Rated withstand U under a normal reference atmos- phere U0 Required rated withstand voltage for the place of as- sembly Ka Altitude correction factor Ka = em  (H - 1000)/8150 Calculation of the altitude correction factor Ka: H = Site altidude in meters m = 1 for AC voltage, rated lightning surge voltage (between the conductors, conductor-earthing, alternat- ing stress of the length) 90 kV  75 kV  e1  (2500 - 1000)/8150  75 kV  1,2

9229 0037 174 0-

2010-03-22 2-5 2.6 Rated data 3AH5 vacuum circuit-braker 1 Rated voltage Ur in kV 2 Rated lightning impulse withstand voltage Up in kV 3 Rated power frequency withstand voltage Ud in kV 4 Rated short-circuit breaking current Isc in kA 5 Rated short-circuit duration tk in s 6 Rated normal current Ir in A 7 Rated short-circuit making current Ima in kA 8 Pole centre distance in mm 9 Weight in kg - Basic version; the weight can be up to 10 kg higher depending on the equipment level 10 Type designation Fig. 2/5 Electrical data for 3AH5 vacuum circuit-breakers 2.7 Operating times Fig. 2/6 Operating times Closing time = the interval of time between the initiation of the closing operation and the instant when the contact touch in all poles. Opening time = the interval of time between the initiation of the opening operation and the instant when the contacts separate in all poles. Arcing time = the interval of time between the instant of the first initiation of an arc and the instant of final arc extinction in all poles. Break time = the interval of time between the initiation of the opening operation and the instant of final arc extinction in the last circuit-breaker pole extinguished (= opening time + arcing time). Close-open time = the interval of time (in a make-break operating cycle) between the instant when the contacts touch 2.6 Bemessungsdaten Vakuum-Leistungsschal- ter 3AH5 1 Bemessungsspannung Ur in kV 2 Bemessungs-Stehblitzstoßspannung Up in kV 3 Bemessungs-Stehwechselspannung Ud in kV 4 Bemessungs-Kurzschlussausschaltstrom Isc in kA 5 Bemessungs-Kurzschlussdauer tk in s 6 Bemessungsbetriebsstrom Ir in A 7 Bemessungs-Kurzschlusseinschaltstrom Ima in kA 8 Polmittenabstand in mm 9 Gewicht in kg - Standardausführung; je nach Ausstattung kann das Gewicht um bis zu 10 kg höher sein 10 Typenbezeichnung Fig. 2/5 Bemessungsdaten der Vakuum-Leistungsschalter 3AH5 2.7 Schaltzeiten Fig. 2/6 Schaltzeiten Einschalteigenzeit (Schließzeit) = Zeitspanne zwischen dem Einleiten (Kommandogabe) der Einschaltbewegung und dem Augenblick der Kontaktberührung in allen Polen. Ausschalteigenzeit (Öffnungszeit) = Zeitspanne zwischen dem Einleiten (Kommandogabe) der Ausschaltbewegung und dem Öffnen des letzten Poles. Lichtbogenzeit = Zeitspanne vom Beginn des ersten Licht- bogens bis zum Erlöschen der Lichtbögen in allen Polen. Ausschaltzeit = Zeitspanne zwischen dem Einleiten (Kom- mandogabe) der Ausschaltbewegung und dem Erlöschen des Lichtbogens im letztlöschenden Pol (= Ausschalteigenzeit + Lichtbogenzeit). Ein-Aus-Kontaktzeit = Zeitspanne bei einem Ein-Aus-Schalt- spiel zwischen dem Zeitpunkt der Kontaktberührung im ersten 1 2 3 4 5 6 7 8 9 10 24 125 50 16 1 800 40 275 70 3AH5 262-1 Einschaltzeit bei Speicherantrieb Closing time with stored energy mechanism ms < 75 Spannzeit Spring charging time (M1) s < 15 Ausschalteigenzeit Opening time Arbeitsstromauslöser Shunt release ms < 50 Lichtbogenzeit Arcing time ms < 15 Ausschaltzeit Break time Arbeitsstromauslöser Shunt release ms < 65 Pausenzeit Dead time ms 300 Ein-Aus-Kontaktzeit Close-open-time Arbeitsstromauslöser Shunt release ms < 60 Gleichlauffehler zwischen den Polen Synchronizing error between the poles ms < 5 Mindestkommandodauer Minimum pulse duration Einschaltmagnet Closing solenoid (Y9) ms 45 Zusatzauslöser 3AX 110 Supplementary release 3AX 110 (Y2) ms 20 (Y4) ms 20 (Y6) ms 20 (Y7) ms 20 kürzeste Impulsdauer der Schalterfallmeldung min. pulse duration of breaker signal Arbeitsstromauslöser Shunt release ms 10

9229 0037 174 0-

2010-03-22 2-6 in the first pole in the closing process and the instant when the arcing contacts separate in all poles in the subsequent opening process. Deadtime = The interval of time between final arc extinction in all poles in the opening operation and the first re-establish- ment of current in any pole in the subsequent closing operation. 2.8 Auxiliary switch (S1) 3SV92 The auxiliary switch supplied with 6 NO and NC contacts. Fig. 2/7 Breaking capacity of 3SV92 auxiliary switch 2.9 Closing solenoid (Y9) 3AY1510 The closing solenoid unlatches the charged closing spring and thus closes the circuit-breaker electrically. It is available for both AC and DC operation. The closing solenoid is not designed for continuous operation and it is automatically de- energized internally. The supply voltage of the closing solenoid may deviate from the rated value by -15 % to +10 %. If required, rectifier modules and varistors are integrated. Power consumption approx. 140 W / VA 2.10 Shunt release (Y2) 3AX1101 The 3AX1101 shunt release it belongs standard equipment. With its design, the electrical opening command is transferred in boosted form to the „Open“ latching mechanism via a solenoid armature through unlatching of a energy store and thus the circuit-breaker is opened. The stored energy mecha- nism is automatically recharged by the V-breaker. This open- ing solenoid is not designed for continuous operation and it is automatically de-energized internally. If required, rectifier modules and varistors are integrated. Power consumption approx. 70 W / 50 VA Rated insulation voltage: AC/DC 250 V Insulation class: C to DIN VDE 0110 Current: 10 A Making capacity: 50 A Pol beim Schließen und dem Zeitpunkt, in dem beim nachfol- genden Öffnen die Kontaktberührung in allen Polen aufgeho- ben ist. Pausenzeit = Zeitspanne vom Ende des Stromflusses in allen Polen, bis zum Beginn des Stromflusses im ersten Pol. 2.8 Hilfsschalter (S1) 3SV92 Der Hilfsschalter wird mit 6 Schließern und Öffnern geliefert. Fig. 2/7 Ausschaltvermögen des Hilfsschalters 3SV92 2.9 Einschaltmagnet (Y9) 3AY1510 Der Einschaltmagnet dient zum Entklinken der gespannten Einschaltfeder und damit zum Einschalten des Leistungs- schalters auf elektrischem Wege. Er ist für Gleich- oder Wech- selspannung lieferbar. Der Einschaltmagnet ist nicht für Dau- erbetrieb ausgelegt und es erfolgt eine schalterinterne auto- matische Abschaltung. Die Versorgungsspannung des Ein- schaltmagneten darf -15 % bis +10 % von der Bemessungs- Versorgungsspannung abweichen. Eventuell erforderliche Gleichrichter und Varistoren sind integriert. Leistungsaufnahme ca. 140 W / VA 2.10 Arbeitstromauslöser (Y2) 3AX1101 Der Arbeitsstromauslöser 3AX1101 gehört zur Standardaus- stattung. Bei dieser Ausführung wird der elektrische Aus- schaltbefehl mittels eines Magnetankers durch Entklinken eines Kraftspeichers auf die "AUS"-Verklinkung weitergege- ben und damit der Schalter ausgeschaltet. Das erneute Span- nen des Kraftspeichers erfolgt automatisch durch den Schal- ter. Dieser Ausschaltmagnet ist nicht für Dauerbetrieb ausge- legt und es erfolgt eine schalterinterne automatische Abschal- tung. Eventuell erforderliche Gleichrichter und Varistoren sind integriert. Leistungsaufnahme ca. 70 W / 50 VA Bemessungs-Isolationsspannung: AC/DC 250 V Isolationsgruppe: C nach VDE 0110 Dauerstrom: 10 A Einschaltvermögen: 50 A Betriebsspannung/Voltage Ausschaltvermögen (A)/Breaking capacity bis/to U (V) ohmsche Belastung/Resistive load induktive Belastung/Inductive load 230 AC 10 10 24 DC 10 10 48 DC 10 9 60 DC 9 7 110 DC 5 4 220 DC 2,5 2

9229 0037 174 0-

2010-03-22 2-7 2.11 Unterspannungsauslöser (Y7) 3AX1103 (opti- onal) Unterspannungsauslöser bestehen aus einem Kraftspeicher, einer Entklinkungsvorrichtung und einem Elektromagnetsy- stem, das im eingeschalteten Zustand des Schalters dauernd an Spannung liegt. Sinkt die Spannung unter einen bestimm- ten Wert, wird die Entklinkung des Auslösers freigegeben und somit über den Kraftspeicher die Ausschaltung des Leistungs- schalters eingeleitet. Die willkürliche Auslösung des Unterspannungsauslösers erfolgt im allgemeinen durch einen Öffnerkontakt im Auslöse- stromkreis, kann aber auch mittels eines Schließers durch Kurzschließen der Magnetspule ausgeführt werden. Bei dieser Auslöseart wird der Kurzschlussstrom durch die eingebauten Widerstände begrenzt (siehe Schaltplan, Fig. 4/3b). Es ist aber dafür Sorge zu tragen, daß der Kurzschluss der Magnet- spule nicht länger als 1 Minute andauert. Unterspannungsauslöser können auch an Spannungswandler angeschlossen werden. Bei unzulässigem Absinken der Betriebsspannung wird der Leistungsschalter selbsttätig aus- gelöst. Eventuell erforderliche Gleichrichter und Varistoren sind integriert. Leistungsaufnahme ca. 20 W / VA 2.12 Wandlerstromauslöser (Y4) 3AX1102 (optio- nal) Wandlerstromauslöser bestehen aus einem Kraftspeicher, einer Entklinkungsvorrichtung und einem Elektromagnetsy- stem. Bei Überschreiten des Auslösestroms (90 % des Wand- lerstromauslöser-Bemessungsstromes) wird die Verklinkung des Kraftspeichers freigegeben und damit die Ausschaltung des Leistungsschalters eingeleitet. Das erneute Spannen des Kraftspeichers erfolgt automatisch durch den Leistungsschal- ter. Für den Einsatz der Wandlerstromauslöser sind neben den Hauptstromwandlern noch Hilfswandler zur Anpassung erforderlich. Leistungsaufnahme für Auslöser mit 0,5 A und 1 A Bemes- sungsauslösestrom = 10 VA bei -90 % des Auslöserbemes- sungsstromes und offenem Anker. 2.13 Wandlerstromauslöser (Y6) 3AX1104 (ener- giearmer Auslöser 0,1 Ws optional) Mit dem 3AX1104 kann in Verbindung mit einem elektroni- schen Auslösegerät (Überstromzeitschutz 7SJ41 oder ähnli- chem) und leistungsschwachen Primärstromwandlern (Auf- steckwandler) ein Wandlerstromauslöser ohne zusätzliche Versorgungsspannung realisiert werden. Der Auslöser 3AX1104 entspricht in seinem Aufbau den Aus- lösern 3AX1101/1102. Mit seinen Spulendaten und seinem geringem Energiebedarf von  0,1 Ws ist er für die direkte Betätigung durch einen Auslöseimpuls ausgelegt, der aus einem Kondensator der o. g. elektronischem Auslösesysteme bereitgestellt wird. Hinweis Für Schaltungen (mechanisch oder elektrisch) muss der Unterspannungsauslöser (Y7) 3AX1103 an Steuerspan- nung angeschlossen sein, da sonst keine Einschaltung möglich ist. 2.11 Undervoltage release (Y7) 3AX1103 (addi- tional feature) Undervoltage releases consist of a stored-energy mechanism, an unlatching mechanism and an electromagnet system which is connected continuously to the supply when the circuit- breaker is in the close state. If this voltage drops to below a certain value the unlatching mechanism is released and open- ing of the circuit-breaker is thus initiated via the stored-energy mechanism. The deliberate tripping of the undervoltage release generally takes place via an NC contact in the tripping circuit. But it can also be carried out via an NO contact by short-circuiting of the magnet coil. With this type of tripping, the short-circuit current is limited by the built-in resistors (see circuit diagram Fig. 4/3b), but make sure that short-circuiting of the solenoid does not last for longer than 1 minute. Undervoltage releases can also be connected to voltage transformers. When the operating voltage drops to impermis- sibly low levels, the circuit-breaker is tripped automatically. If required, rectifier modules and varistors are integrated. Power consumption approx. 20 W / VA 2.12 CT-Operated release (Y4) 3AX1102 (additional feature) CT-operated releases consist of a stored-energy mechanism, an unlatching mechanism and an electromagnet system. When the tripping current is exceeded (90 % of the CT- operated release rated current) the unlatching device of the stored-energy mechanism is released and thus opening of the circuit-breaker is initiated. The stored energy mechanism is automatically recharged by the V-breaker. In addition to the primary current transformers, matching transformers are required for application of the CT-operated releases. Power consumption for releases with 0.5 A and 1 A rated tripping current = approx. 10 VA at -90 % of the release rated current and with open armature. 2.13 CT-Operated release (Y6) 3AX1104 (low energy release 0.1 Ws additional feature) In connection with a solid-state release (7SJ41 overcurrent time protection or similar) and low-power primary current transformers (window-type transformers), it is possible with the 3AX1104 to create a CT-operated release without addi- tional supply voltage. The 3AX1104 is of similar design as the 3AX1101/1102 releases. With its coil data and its low energy requirement of  0.1 Ws, its designed to be directly actuated by a release impulse provided by a capacitor of the above-mentionend electronic release systems. Note For switching (mechanic or electric) the undervoltage release (Y7) 3AX1103 has to be connected to control voltage. Without it, closing is impossible.

9229 0037 174 0-

2010-03-22 2-8 2.14 Hilfsschütz (K1) Das Hilfsschütz dient der Pumpverhinderung bei Motor-Spei- cherantrieben. Das Pumpen tritt ein, wenn ein Dauerkom- mando auf den Einschaltmagneten gegeben wird, die Ein- schaltfeder nach dem Einschalten immer wieder gespannt wird und dadurch Leerschaltungen durchgeführt werden. Das Hilsschütz verhindert den Dauerbetrieb des Motors und damit dessen Zerstörung. 2.15 Überspannungsschutz Sekundärausrüstung Durch das Abschalten von induktiven Verbrauchern in Gleich- stromkreisen können Schaltüberspannungen entstehen, die elektronische Steuergeräte gefährden. Um dies zu verhindern, sind die Induktivitäten des Schalterantriebes und der Steue- rung (Motor, Einschaltmagnet, Arbeitsstromauslöser und Hilfsschütz) bei Gleichstrombetrieb von DC 60 V bis DC 220 V mit integrierten Varistoren ausgerüstet. 2.16 Anzeige "Feder gespannt" Der Positionsschalter S4 meldet den Spannzustand der Ein- schaltfeder. Gleichzeitig wird über ein Gestänge die mecha- nische Anzeige "Feder gespannt" betätigt. 2.17 Motor (M1) Der Motor läuft nach Anlegen der Versorgungsspannung bei entspannter Einschaltfeder sofort an und wird nach erfolgtem Spannvorgang automatisch intern abgeschaltet. Bei Gleichspannung beträgt die max. Leistungsaufnahme ca. 350 W. Bei Wechselspannung beträgt die max. Leistungsauf- nahme ca. 400 VA. Eventuell erforderliche Varistoren sind integriert. Bei Betrieb mit Gleichspannung ist ein Gleichrich- terbaustein 39X1525-1F eingebaut. Im Dauerbetrieb sind die Motoren für max. 2 Schaltspiele pro Minute ausgelegt. Die Antriebsmotoren arbeiten in der kurzen Spannzeit zeitweise im Überlastbereich. Der Bemessungs- strom für den erforderlichen Motorkurzschlussschutz ist in der Fig. 2/8 zu entnehmen (die Motorschutzgeräte gehören nicht zur V-Schalter-Lieferung und müssen gesondert bestellt wer- den). Fig. 2/8 Bemessungsströme der Schutzeinrichtungen für den Motorantrieb Wir empfehlen zum Motorschutz einen Automaten mit G- Charakteristik. Die Versorgungsspannung des Motorantriebes darf -15 % bis +10 % von der Bemessungs-Versorgungsspannung abwei- chen. Bemessungs-Versorgungs- spannung U (V) Rated supply voltage U (V) 24 DC 48 DC 60 DC 110 DC/AC 50 / 60Hz 220DC / 230AC 50 / 60Hz Empfohlener Bemessungs- strom der Schutzeinrichtung I (A) Recommended rated current I (A) of protection device 8 6 4 2 1,6 2.14 Auxiliary contactor (K1) The auxilary contactor is used for the anti-pumping device of the motor operated stored-energy mechanism. The pumping is activated if a permanent command is signaled to the closing magnet, the closing spring gets always charged after closing again and by that a discharging operation is done. The auxiliary contactor avoids the permanent operation of the motor and its destruction. 2.15 Surge protection secondary equipment The disconnection of inductive loads in DC circuits may cause switching overvoltages which pose a risk to electronic control units. In order to prevent this, the inductances of the circuit - breaker mechanism (motor, closing solenoid, shunt release and auxiliary contactor) are connected to integrated varistors (with DC operation voltages of 60 V to 220 V DC). 2.16 Indication "spring tensioned" The position switch S4 signals the state of charging to the closing spring. Simultaneously the indication "spring charged" is activated by a linkage. 2.17 Motor (M1) The motor-operated mechanism starts operating immediately once the power supply has been connected and the closing spring is discharged and is automatically de-energized inter- nally after charging. The maximum DC power input is 350 W (approx.). The max- imum AC power input is 400 VA (approx.). Required varistors are integrated. For Operation with DC voltage a rectifier block 39X1525-1F is installed. The motors are designed for max two operating cycles per minute in continous operation. During part of the short spring charging time, the motors operate in the overload range. The recommended ratings for motion protection devices are shown in Fig. 2/8 (the protection devices are not supplied with the vacuum circuit-breakers and must be ordered separately). Fig. 2/8 Rated currents of motor protection devices To protect the motors, we recommend an MCB with G char- acteristics. The supply voltage of the motor-operated mechanism may deviate from the rated value by -15 % to +10 %.

9229 0037 174 0-

2010-03-22 2-9 2.18 Mechanische Schaltstellungsabfrage (optio- nal) Zum schaltstellungsabhängigen Verriegeln von Schaltwagen, Schaltereinschüben oder Trennschaltern können die Spei- cherantriebe der 3AH5-Schalter mit einer mechanischen Schaltsstellungsabfrage ausgerüstet werden. Ein anlagenseitiges Abfragebauteil tastet die Stellung des Leistungsschalters ab und sperrt dabei zuverlässig die mecha- nische und elektrische Einschaltung des ausgeschalteten Lei- stungsschalters. Das anlagenseitige Abfrageteil soll so gestaltet sein, daß bei eingeschaltetem Leistungsschalter eine Betätigung von Trennschalter, Einschub oder Wagen nicht möglich ist. 2.19 Maße und Gewichte Die Abmessungen des V-Schalters sind dem zugehörigen Maßbild zu entnehmen. Es ist im Bedarfsfall bei Ihrer Siemens- Vertretung erhältlich. Das Gewicht ist auf dem Leistungsschild des Schalters ange- geben, der Fig. 2/2 oder dem zugehörigen Maßbild zu entneh- men. 2.18 Mechanical switching position sensing (addi- tional feature) The stored-energy mechanisms of the 3AH5 circuit-breakers can be equipped with a mechanical switching position sensing to interlock breaker trucks, withdrawable breaker parts or disconnectors in a certain position. A sensing component provided by the customer senses the switch position of the circuit-breaker and in this way prevents mechanical and electrical closing of the circuit-breaker when the circuit-breaker is open. The sensing component must be designed in such a way that is not possible to operate the disconnector, withdrawable part or truck when the circuit-breaker is closed. 2.19 Dimensions and weights The dimensions of the vacuum circuit-breaker are shown in the relevant drawing, which can be ordered through your Siemens office. The weight can be found on the breaker rating plate, in Fig. 2/2 or in the relevant drawing.

9229 0037 174 0-

2010-03-22 3-1 3 Description 3.1 Construction The vacuum circuit-breaker consists of the 3 mechanism housings (60.), the 3-pole assemblies with vacuum interrup- ters (30.), cast-resin post insulators (16.), struts and of the operating rods (39.5). The mechanism housings (60.) accom- modate all electrical and mechanical elements required for opening and closing the vacuum circuit-breakers. The mecha- nism housings (60.) have detachable covers (60.1) which have cut-outs for the actuating and indicating devices. 16. Post insulator 30. Vacuum interrupter 39.5 Operating rod 50.1 Opening for hand crank 51. Rating plate 54. “OPEN” pushbutton 55. Spring state indicator 58. Operating cycle counter 59. “CLOSED/OPEN” indicator 60. Mechanism housing 60.1 Cover Fig. 3/1 3AH5 vacuum circuit - breaker 3 Beschreibung 3.1 Aufbau Der V-Schalter besteht aus 3 Antriebskästen (60.), den 3 Schalterpolen mit Vakuumschaltröhren (30.), Gießharzstüt- zern (16.) und Versteifungsstreben und den zur Kontaktbetä- tigung erforderlichen Schaltstangen (39.5). In den Antriebs- kästen (60.) sind alle zum Ein- und Ausschalten des V-Schal- ters erforderlichen elektrischen und mechanischen Bauele- mente untergebracht. Die Antriebskästen (60.) sind durch die abnehmbaren Abdeckungen (60.1) verschlossen, in denen für die Bedien- und Anzeigeelemente entsprechende Öffnungen vorhanden sind. 16. Gießharzstützer 30. Vakuumschaltröhre 39.5 Schaltstange 50.1 Öffnung für Handkurbel 51. Leistungsschild 54. Druckknopf AUS 55. Federzustandsanzeige 58. Schaltspielzähler 59. Schaltstellungsanzeige 60. Antriebskasten 60.1 Abdeckung Fig. 3/1 Vakuum-Leistungsschalter 3AH5

9229 0037 174 0-

2010-03-22 3-2 Fig. 3/2 shows one of the 3 mechanism housings without cover and the full individual mechanism subassemblies in the mech- anism housing. 50.2 Gearbox 50.4.1 Position switch 50.5 Motor M1 53.1 Closing solenoid Y9 54. Pushbutton “OPEN“ 54.2 Shunt release Y2 55. Spring state indicator 58. Operating cycle counter 62. Closing spring 68. Auxiliary switch S1 68.7.1 Low-voltage plug connector X0 80. Auxiliary contactor K1 Fig. 3/2 Mechanism housing without cover Fig. 3/2 zeigt einen der 3 Antriebskästen ohne Abdeckung und die Anordnung der einzelnen Antriebs-Baugruppen im Antriebskasten. 50.2 Getriebe 50.4.1 Positionsschalter 50.5 Motor M1 53.1 Einschaltmagnet Y9 54. Druckknopf ”AUS“ 54.2 Arbeitsstromauslöser Y2 55. Anzeige ”Einschaltfeder gespannt“ 58. Schaltspielzähler 62. Einschaltfeder 68. Hilfsschalter S1 68.7.1 Niederspannungssteckvorrichtung X0 80. Hilfsschütz K1 Fig. 3/2 Antriebskasten ohne Abdeckung

9229 0037 174 0-

2010-03-22 3-3 3.2 Ausstattung In der Grundausführung ist der V-Schalter (Shunt) wie folgt ausgerüstet: - Motor-Speicherantrieb für die Einschaltung, - Einschaltmagnet (Y9), - Arbeitsstromauslöser (Y2), - Schaltspielzähler, - Hilfsschalter 6S + 6Ö, - Hilfsschütz (K1), - Positionsschalter für Meldung ”Einschaltfeder gespannt” (S4) - herausgeführter Kabelbaum mit 64-poliger Steckvorrich- tung, - Varistorbeschaltung bei 60 V DC. Jeder V-Schalter (Shunt) kann optional mit folgenden Ausrü- stungen bestückt werden: - Wandlerstromauslöser 3AX 1102 (Y4)1) - Unterspannungsauslöser 3AX 1103 (Y7)1) - Wandlerstromauslöser 3AX 1104 (Y6)1) - Mechanische Schaltstellungsabfrage (optional) - Verdrahtung der elektrischen Ausrüstung auf 24-poligen Klemmleiste mit herausgeführtem Kabelbaum. Alternative Ausstattungen, sowie besondere Ausführungen, auf Anfrage. 1) Zusätzlich oder anstelle des serienmäßigen Arbeitsstromauslö- sers (Y1) kann der V-Schalter 3AH5 mit max. 1 Auslöser vom Typ 3 AX 11... bestückt werden. 3.2 Equipment The basic version of the V-breaker (Shunt) comprises: - Motor operating stored-energy mechanism for closing, - Closing solenoid (Y9), - Shunt release (Y2), - Operating cycle counter, - Auxiliary switch 6NO/6NC, - Auxiliary contactor (K1), - Position switch for signalling "Closing spring charged" (S4) - led through cable harness with 64-way plug led through cable harness connector, - varistor circuit with 60 V DC. Each V-breaker (shunt) can be equipped with the following supplementary devices: - Current transformer-operated release 3AX 1102 (Y4)1) - Undervoltage release 3AX 1103 (Y7)1) - Current transformer-operated release 3AX 1104 (Y6)1) - Mechanical switching position sensing (additional feature) - Wiring of the electrical equipment to 24-pole terminal strip with led through cable harness. Alternative equipment and special versions are available on request. 1) The 3AH5 vacuum circuit-breaker can be fitted with a maximum of 1 release of type 3AX 11… in addition to or instead of the standard shunt release (Y1).

9229 0037 174 0-

2010-03-22 4-1 4 Installation 4.1 Installing in cubicle or on truck The vacuum circuit-breaker is installed perpendicular to the vacuum interrupters. Please contact your local Siemens agency about other installation positions. The 3AH5 vacuum circuit-breakers are supplied in the open (Off) state with the closing spring discharged. Before installing the 3AH5 V-breaker, remove the transport devices (skids and spacers). Mount phase barriers supplied loose with the break- ers in accordance with the drawings supplied. Before installing the 3AH5 vacuum circuit-breaker in a cubicle or a truck check its rating plate data (to avoid confusion) and compare the rated voltage indicated in the delivery documents with the power supply voltage available at the site. On the vacuum circuit-breaker with undervoltage release (Y7) 3AX 1103, the arresting screw of the hammer must be moved from position A to B (see instruction card for release or note card in the mechanism housing of vacuum circuit-breaker). On the 2 traverses (14.1) and (14.2) and on the 3 mechanism housings has, there are a total of 22 fixing holes (a) and (b) to suit the various types of installation (Fig. 4/1). Use M10 (mech- anism housing) and M12 (traverses) fixing bolts of strength Class 8.8, making reference to the mandatory dimension drawings. When installing the V-breaker in a rack or frame the four lugs supplied as loose items may also be used. Four M12 fixing boIts of Strength Class 8 must be used here. The rack or frame must be adapted to the operating conditions and have adequate load bearing capacity and stability. 14.1 Traverse above 14.2 Traverse below 70. Earthing bolt M12 a Fixing hole for screws M10 b Fixing hole for screws M12 Fig. 4/1 Means of fixing 3AH5 vacuum circuit-breaker 4 Montage 4.1 Befestigung in Schaltzelle oder auf Schaltwa- gen Die Einbaulage des V-Schalters bezogen auf die Vakuum- schaltröhren ist senkrecht. Bei anderen Einbaulagen fragen Sie bitte Ihre nächste Siemens-Vertretung. Die V-Schalter 3AH5 werden in Schaltstellung AUS und ent- spannter Einschaltfeder geliefert. Vor dem Einbau der V- Schalter die Transporthilfen (Tragwinkel und Tragbleche) ent- fernen. Lose mitgelieferte Trennwände nach mitgelieferter Anbauzeichnung montieren. Vor der Montage des V-Schalters 3AH5 in eine Schaltzelle oder auf einen Schaltwagen sind zur Vermeidung von Ver- wechslungen die Leistungsschildangaben zu kontrollieren und die in den Lieferpapieren angegebene Bemessungsspannung mit der am Einbauort zur Verfügung stehenden Versorgungs- spannung zu vergleichen. Beim V-Schalter mit Unterspannungsauslöser (Y7) 3AX 1103 ist zusätzlich die Arretierungsschraube des Schlagbolzens von Stellung A nach B zu versetzen (siehe Hinweiskarte im Antriebskasten des V-Schalters). Für die verschiedenen Einbauarten sind an den 2 Traversen (14.1) und (14.2) und an den 3 Antriebskästen insgesamt 22 Befestigungsbohrungen (a) und (b) vorhanden (Fig. 4/1). Die Befestigung ist mit Schrauben M10 (Antriebskasten) und M12 (Traversen) Festigkeitsklasse 8.8 durchzuführen. Maßgebend sind hierzu die verbindlichen Maßzeichnungen. Zum Einbau in ein Gerüst oder einen Rahmen können auch die als Beipack mitgelieferten 4 Laschen verwendet werden. Zur Befestigung sind hierbei 4 Schrauben M12 - Festigkeits- klasse 8 - zu verwenden. Das Gerüst bzw. der Rahmen muß den Betriebsbedingungen angepaßt sein und eine ausreichende Tragkraft und Stabilität aufweisen. 14.1 Traverse oben 14.2 Traverse unten 70. Erdungsschraube M12 a Befestigungsbohrung für Schrauben M10 b Befestigungsbohrung für Schrauben M12 Fig. 4/1 Befestigungsmöglichkeiten des V-Schalters 3AH5

9229 0037 174 0-

2010-03-22 4-2 4.2 Stromschienenanschluss Die Stromschienen so anpassen, dass sie vor dem Befestigen zwanglos flach und mit Lochdeckung an den Anschlussflächen des V-Schalters anliegen. Die sich berührenden Kontaktflächen der Stromschienen und des V-Schalters vor dem Verschrauben sorgfältig mit Stahl- bürste im Kreuzstrich bearbeiten, bis sie metallisch blank sind und die Rückstände mit sauberen Lappen abwischen. 4.3 Steuerleitungen Wir empfehlen, Steuerleitungen mit einem Nennquerschnitt von 1,5 mm2 zu verwenden. Die verwendeten elektrischen Bauteile sind für den Anschluss von 6,3 mm Flachsteckern vorbereitet. Die Verdrahtung sollte entsprechend der Betriebs- mittelplan-Beispiele in Fig. 4/2 bis Fig. 4/3 ausgeführt werden. Ist der Schalter als Zusatzausstattung mit der 24-/64-poligen Niederspannungs-Steckvorrichtung bzw. einer 24-poligen Klemmenleiste ausgerüstet, ist der externe Anschluss für Steuerleitungen mit einem Nennquerschnitt von 2,5 mm2 geeignet. Die Verdrahtung und Schaltung der V-Schalter ist abhängig von Ausführung und Ausstattung und aus den Betriebsmittelplan-Beispielen in Fig. 4/2 bis Fig. 4/3 zu erse- hen. 4.4 Erdung Jeder Antriebskasten des V-Schalters ist an der vorhandenen und gekennzeichneten Erdungsschraube M12 (70., Fig. 4/1) mit Flachkupfer, Kupferseil oder feuerverzinktem Bandeisen vorschriftsmäßig an die Hochspannungsschutzerde anzu- schließen. Sofern der V-Schalter mit den Antriebskästen in ein geerdetes Metallgerüst eingebaut und fest und elektrisch leitend verbun- den ist, brauchen die Antriebskästen nicht gesondert geerdet werden. Bei der Schalterbefestigung sind in diesem Fall außen gezahnte Fächerscheiben (DIN 6798) unter die Schrauben- köpfe zu legen. Hinweis Spritzverkupferte und spritzversilberte Anschlussflächen mit Lappen reinigen, nicht bürsten. Unterschiedliche Anschlussmaterialien (AI/CU) dürfen nicht mit gleichem Reinigungswerkzeug bearbeitet werden. Die blanken Kontaktflächen nach der Reinigung hauchdünn und mit säurefreier Vaseline (z. B. Shell-Vaseline 8420) einfetten und sofort zusammenschrauben. Versilberte Teile dürfen nicht mit Aluminiumschienen ver- schraubt werden. Für den Anschluss Schrauben und Muttern M12 - Festig- keitsklasse 8.8 - und die entsprechenden Federelemente und Scheiben verwenden. Beim Anziehen der Anschlussschrauben Anziehdrehmo- ment (70 Nm) durch Gegenhalten mit einem passenden Schrauben- oder Steckschlüssel abfangen. 4.2 Flat bar connection Prior to fitting the conductors fix them so as to ensure smooth contact with their connecting parts and with the holes in full alignment. Rub the contact faces to be bolted together with criss-crossing strokes using a wire brush until bright metal shows and wipe then with a clean rag. 4.3 Control leads We recommend the use of a control lead with a nominal sectional area of 1.5 mm2. The electrical components used are designed for connecting 6.3 tab connectors. Wiring must be carried out in accordance with equipment plan examples in Fig. 4/2 to Fig. 4/3. If the breaker is equipped as an additional feature with a 24- /64-pole low voltage plug connector or a 24-pole terminal strip, the external for control leads with a nominal sectional area of up to 2.5 mm2 is suitable. The wiring and circuitry of the vacuum circuit-breakers depend on the particular version and level eqipment; refer to the equipment plan examples in Fig. 4/2 to Fig. 4/3. 4.4 Earthing Connect the vacuum circuit-breaker to the appropriate high voltage protective earth by means of the suitable marked M12 (70., Fig. 4/1) terminal on the top of the mechanism housings using flat copper, copper cable or hot-galvanized steel strip. If the vacuum circuit-breaker and mechanism housings are installed in an earthed metal rack so that firm electrical contact is established, the mechanism housings need not to be earthed separately. When installing the breaker externally, toothed serrated washers (DIN 6798) must be placed under the bolt heads. Note Copper-sprayed and spray silver-plated surfaces should be cleaned with a rag and not rubbed (brushed). Differing contact materials (AI/CU) must not be worked with the same cleaning tool. Thinly grease the bright contact faces with acid-free Vase- line (e.g. Shell Vaseline 8420) or equivalent anti-corrosion agent and bolt them together immediately. Silver-plated parts must not be bolted together with alumin- ium bars. Use the appropriate M12 nuts and bolts of strength class 8.8 and corresponding spring elements and plain washers. When tightening the terminal screws, counteract the torque (70 Nm) by resisting it with a suitable spanner or socket wrench.

9229 0037 174 0-

2010-03-22 4-3 4.5 Wiring diagrams Wiring diagrams includes all possible circuit arrangements; selection dependend on order of circuit breaker. Fig. 4/2 to Fig. 4/3 illustrate non-committal examples for vacuum circuit- breakers. 1) Integrated varistor for voltages DC  60 V 2) Integrated rectifier for voltages AC/DC  100 V 3) Wiring DIN 47727-H07V-K1x2,5sw in case of 24 V / 48 V and 60 motors DC 4) Only supplied if mechanical interlocking is ordered a) Motor operating mechanism for AC b) Motor operating mechanism with rectifier for DC c) Closing d) Closing with anti-pumping device Fig. 4/2 Circuit diagram example (part 1) of 3AH5 vacuum circuit-breaker 4.5 Schaltpläne Die Schaltpläne zeigen alle lieferbaren Bauteile mit ihren Beschaltungsmöglichkeiten; Auswahl in Abhängigkeit von Schalterbestellung. Fig. 4/2 bis Fig. 4/3 zeigen unverbindliche Beispiele für V-Schalter. 1) Integrierter Varistor für DC  60 V 2) Integrierter Gleichrichter für AC/DC  100 V 3) Bei Einsatz von 24 V / 48 V und 60 Motoren DC Leitung DIN 47727-H07V-K1x2,5sw 4) Nur bei gleichzeitiger Bestellung einer mechanischen Einschaltverriegelung a) Motoraufzug für AC b) Motoraufzug mit Gleichrichter für DC c) Einschaltung d) Einschaltung mit Pumpverhinderung Fig. 4/2 Schaltplanbeispiel (Teil 1) des V-Schalters 3AH5 a) b) c) d)

9229 0037 174 0-

2010-03-22 4-4 1) Integrated varistor for voltages DC  60 V 2) Integrated rectifier for voltages AC/DC  100 V 3) Attention: For DC connect L+ a) Shunt release for 24/64-pole plug connector b) Undervoltage release c) Low energy release d) 1st C.T. operated release e) Signal: spring charged with 24-pole plug connector Fig. 4/3 Circuit diagram example (part 2) of 3AH5 vacuum circuit-breaker 1) Integrierter Varistor für DC  60 V 2) Integrierter Gleichrichter für AC/DC  100 V 3) Achtung: Bei DC L+ anschließen a) Arbeitsstromauslöser für 24/64-pol. Steckvorrichtung b) Unterspannungsauslöser c) Energiearmer Auslöser d) 1. Wandlerstromauslöser e) Meldung: Feder gespannt Fig. 4/3 Schaltplanbeispiel (Teil 2) des V-Schalters 3AH5 a) b) c) d) e)

9229 0037 174 0-

2010-03-22 5-1 5 Betrieb 5.1 Inbetriebnahme Zur Inbetriebnahme ist die einwandfreie Funktionsbereitschaft des V-Schalters entsprechend den folgenden Punkten zu überprüfen: 1. Den Schalter von eventuellen Verunreinigungen säubern (Einzelheiten hierzu im Abschnitt “Reinigen” auf Seite 6-1) 2. Alle Befestigungs- und Anschlussschrauben auf festen Anzug überprüfen. 3. Den Schalter auf äußere Beschädigungen überprüfen, insbesondere Steuerleitungen, Stützer und Vakuum-Schaltröhren. GEFAHR Hochspannung! Das Berühren der spannungsführenden Teile führt zum Tode oder hat schwere Körperverletzungen zur Folge. Das Gerät darf nur von qualifiziertem Personal betrieben werden, das mit der Betriebsanleitung vertraut ist und ins- besondere die Warnhinweise beachtet. WARNUNG Das Berühren der spannungsführenden Teile führt zu schweren Körperverletzungen oder hat Sachschäden- zur Folge. Beim Betrieb elektrischer Geräte stehen zwangsläufig bestimmte Teile dieser Geräte unter gefährlicher Span- nung und es können sich mechanische Teile, auch ferngesteuert, schnell bewegen. Insbesondere muß beachtet werden: Die Abdeckung des Antriebskastens nicht entfernen. Nicht in vorhandene Öffnungen des Antriebes greifen. Schalter- pole und Schaltstangen nicht berühren. 5 Operation 5.1 Commissioning Prior to commissioning, check the V-breaker in accordance with the following points: 1. Clean the circuit-breaker as applicable (for details, refer to “Cleaning” auf Seite 6-1). 2. Check all fixing and terminal screws for tightness. 3. Examine the circuit-breaker for any external damage, especially to the control leads, post insulators and vacuum interrupters. DANGER High voltage! Touching of live parts will result in death or severe personal injury. This equipment shall be operated only by qualified person- nel after becoming thoroughly familiar with the respective instruction manual and in particular all safety instructions. WARNING Touching of live parts will result personal injury or severe property damage. This equipment contains hazardous voltages and mechanical parts which move at high speed and may be controlled remotely. In particular: Do not remove the cover of the mechanim housing. Do not reach inside any openings in the operating mechanism. Do not touch pole assemblies and operating rods.

9229 0037 174 0-

2010-03-22 5-2 50.1 Öffnung für Handkurbel 54. Druckknopf AUS 55. Federzustandsanzeige 59. Schaltstellungsanzeige 60.1 Abdeckung Fig. 5/1 Einschalten des V-Schalters 3AH5 4. Beim V-Schalter 3AH5 mit Unterspannungsauslöser (Y7) 3AX1103 ist zusätzlich die Arretierungsschraube des Schlagbolzens von Stellung A nach B zu versetzen (siehe Hinweiskarte im Antriebskasten des V-Schalters 3AH5). Dazu die 4 Befestigungsschrauben der Abdeckung (60.1) entfernen, Abdeckung öffnen und nach Abschluss der Arbeiten die Abdeckung (60.1) in umgekehrter Reihen- folge montieren. 5. Zum Probeschalten Niederspannungsstecker kundensei- tig anschließen und Versorgungsspannung einschalten. Der Motor spannt automatisch die Einschaltfeder und wird nach erfolgtem Spannvorgang automatisch intern abgeschaltet. Alternativ kann die Einschaltfeder mit der Handkurbel, über die Kupplung (50.1), gespannt werden (ca. 20 Umdrehungen), bis ein hörbares Klicken die Verklinkung anzeigt. • In der Federzustandsanzeige (55.) wird das Symbol „Einschaltfeder gespannt“ sichtbar. • Den V-Schalter elektrisch einschalten. • Die Schaltstellungsanzeige (59.) wechselt von „AUS“ in „EIN“. • Die Federzustandsanzeige (55.) wechselt auf „Ein- schaltfeder entspannt“. • Bei anliegender Versorgungsspannung wird die Ein- schaltfeder sofort wieder vom Motor gespannt und die VORSICHT Verletzungsgefahr bei Einsatz falscher Hilfsmittel zum Spannen der Einschaltfeder. Bei anliegender Versorgungsspannung spannt der Motor nach dem Einschalten die Einschaltfeder sofort wieder nach. Der V-Schalter darf nur mit der Originalhandkurbel (gehört nicht zum Lieferumfang) aufgezogen werden, um Verlet- zungen durch den plötzlich anlaufenden Motor zu vermei- den. 50.1 Opening for hand crank 54. “OPEN” pushbutton 55. Spring state indicator 59. “CLOSED/OPEN” indicator 60.1 Cover Fig. 5/1 Closing the 3AH5 vacuum circuit-breaker 4. On the 3AH5 V-breaker with undervoltage release (Y7) 3AX1103, the arresting screw of the hammer must be moved from position A to B (see instruction card in the mechanism housing of the 3AH5 vacuum circuit-breaker). In addition loose the screws of the cover (60.1) and open it. Mount the cover (60.1) after the end of work again. 5. Connect the low-voltage plug connector on the customer side and close the supply voltage for test switching. The motor charges the opening spring automatically is deactivated internally and automatically after the execut- ion of the charging process. The closing spring can be charged automatically, by the coupling (50.1), which is activated by a crank-handle (ca 20 revolutions) until an audible clicking indicates the acti- vation of the latching. • The spring state indicator (55.) indicates the symbol "closing spring charged". • Close the V-breaker electrically. • The "CLOSED/OPEN" indicator (59.) switches from "CLOSE" to "OPEN". • The Spring state indicator (55.) indicates "closing spring discharged". • When the supply voltage is applied the closing spring gets charged by the motor and the spring state indicator CAUTION Risk of injury by using wrong aids for charging the closing spring. When the supply voltage is applied, the motor imme- diately recharges the closing spring. The V-breaker may be operated only with the original hand crank (if fitted as an additional feature), in order to avoid injuries that may occur if the motor starts up suddenly.

9229 0037 174 0-

2010-03-22 5-3 Federzustandsanzeige (55.) wechselt auf „Einschaltfe- der gespannt“ • Der V-Schalter kann mechanisch über den Druckknopf (54.) oder elektrisch über einen entsprechenden Befehlsgeber ausgeschaltet werden. • Die Schaltstellungsanzeige (59.) wechselt von „EIN“ in „AUS“. • Die Federzustandsanzeige (55.) ändert sich nicht. Bei den Schaltvorgängen die mechanische und elektri- sche Schaltstellungsanzeige (59.) kontrollieren. 6. Die Funktion der vorhandenen Ausschalthilfsauslöser durch elektrische Betätigung überprüfen. 7. Um die Einschaltfeder zu entspannen, ist • die elektrische Versorgungsspannung abzuschalten, • der Schalter manuell einzuschalten und dann • manuell auszuschalten. 8. Die elektrischen Betriebsmittel können gemäß Schaltplan elektrisch durchgeprüft werden. Nach Feststellung der einwandfreien Funktionsbereitschaft kann der V-Schalter 3AH5 in Betrieb gesetzt werden. 5.2 Einschalten Für den Betrieb muß die Versorgungsspannung eingeschaltet sein. Der Motor spannt automatisch die Einschaltfeder und wird nach erfolgtem Spannvorgang automatisch intern abgeschal- tet. Alternativ kann die Einschaltfeder mit der Handkurbel, über die Kupplung (50.1), gespannt werden (ca. 20 Umdrehungen), bis ein hörbares Klicken die Verklinkung anzeigt. Der Schalter kann jetzt elektrisch über einen entsprechenden Befehlsgeber eingeschaltet werden. Die dadurch entspannte Einschaltfeder wird bei anliegender Versorgungsspannung automatisch durch den Motor wieder gespannt. 5.3 Ausschalten Der V-Schalter kann mechanisch über den Druckknopf (54.) oder elektrisch über einen entsprechenden Befehlsgeber aus- geschaltet werden. (55.) indicates "closing spring charged". • The V-breaker can be switched off mechanical by the "OPEN" pushbutton (54., Fig. 5/1) or electrical by the related control unit. • The "CLOSED/OPEN" indicator (59.) changes from "CLOSED" to "OPEN". • The spring state indicator (55.) does not change. Check the mechanical or electric "CLOSED/OPEN" indi- cator (59.) when switching is in progress. 6. Also check (by electrical actuation) whether the shunt closing and opening releases fitted operate properly. 7. For discharging the spring, switch off the closing spring, • switch off the supply voltage, • switch on the circuit-breaker manually and after that, • switch it off again. 8. The electric operational equipment can be checked elec- trically in accordance to the attached circuit diagram. Once correct functioning of the 3AH5 V-breaker has been ascertained, it can be put into service. 5.2 Closing The supply voltage hast to be closed for operation. The motor charges the opening spring automatically is deac- tivated internally and automatically after the execution of the charging process. The closing spring can be charged automatically, by the coupling (50.1), which is activated by a crank-handle (ca 20 revolutions) until an audible clicking indicates the activation of the latching. The V-breaker can now be closed electrical by the related control unit. The not charged closing spring will be charged again in case of closed supply voltage automatically by the motor. 5.3 Opening The V-breaker can be switched off mechanical by the "OPEN" pushbutton (54., Fig. 5/1) or electrical by the related control unit.

9229 0037 174 0-

2010-03-22 6-1 6 Instandhaltung 6.1 Wartung Der V-Schalter 3AH5 ist unter normalen Betriebsbedingungen wartungsfrei nach IEC 62271-1. Wir empfehlen jedoch eine regelmäßige Sichtkontrolle, um den durch äußere Verschmut- zung (z. B. hervorgerufen durch Staub, Salznebel, Schimmel- bildung etc.) bedingten Zustand des Schalters zu überprüfen. 6.2 Reinigen Zur Sicherstellung des Isoliervermögens ist es notwendig, daß die Isolierteile sauber sind. Isolierteile und gegebenenfalls äußere Schalterteile mit einem angefeuchteten Tuch abrei- ben. Als Reinigungsmittel nur warmes Wasser unter Zusatz eines milden, flüssigen Haushaltsreinigers verwenden. GEFAHR Hochspannung! Bei Nichtbeachtung können Tod, schwere Körperver- letzung oder erheblicher Sachschaden die Folge sein. Instandhaltungs-, Reparatur-, und nachträgliche Umbauar- beiten sind nur von fachkundigem Personal und unter Beachtung der Betriebsanleitung bzw. spezieller Umbau- anweisungen auszuführen. Schulung und Information von Fachpersonal kann durch die zuständige Siemens-Abtei- lung durchgeführt werden. Vor dem Beginn der Arbeiten am V-Schalter sind die örtli- chen Sicherheitsbestimmungen für Hochspannungsgeräte, z. B. die „5 Sicherheitsregeln“ nach EN 50110-1, zu beach- ten, die Versorgungsspannung auszuschalten und anschließend der V-Schalter von Hand ein- und auszu- schalten (V-Schalter in Schaltstellung AUS, Anzeiger „Ein- schaltfeder gespannt“ nicht sichtbar), um sicherzustellen, daß die Einschaltfeder entspannt ist. WARNUNG Bei Nichtbeachtung können Tod oder schwere Körper- verletzungen eintreten. Wicklungen und Anschlüsse dürfen nicht berührt werden, solange die Versorgungsspannung nicht abgeschaltet ist. VORSICHT Bei Nichtbeachtung können Körperverletzungen ein- treten. Alle Federn des Antriebs müssen entspannt werden und der V-Schalter in Schaltstellung AUS, Anzeiger „Einschalt- feder entspannt“ sichtbar, gebracht werden. 6 Maintenance 6.1 Servicing Under normal operating conditions, the 3AH5 vacuum circuit- breaker is maintenance-free in accordance with IEC 62271-1. We recommend nonetheless a regular visual inspection to check for soiling (e. g. dust, saline fog, fungus etc.) of the circuit-breaker. 6.2 Cleaning To assure the insulating capacity, it is necessary that the insulating components are clean. Insulating components and external breaker parts must be wiped with a damp cloth. Use only warm water with the addition of a mild liquid household detergent as cleaning agent. DANGER High voltage! Non-observance can result in death, severe personal injury or substantial property damage. Maintenance, repair and subsequent conversion work may be carried out only by specially trained personnel in accord- ance with the operating instructions and/or special conver- sion instructions. Training and information sessions for personnel can be provided by the competent Siemens department. Before starting any work on vacuum circuit-breakers, refer- ence must be made to the local safety regulations for high- voltage switchgear, e. g. the five safety rules (EN 50110-1). Switch off the power supply and then close and open the vacuum circuit-breaker by hand (V-breaker in open state “closing spring charged” indication not visible), to ensure that the closing spring is discharged. WARNING Non-observance can result in death or serious personal injury. Windings and terminals must not be touched if the power supply has not been disconnected. CAUTION Non-observance can result in personal injury. All springs of the operating mechanism must be discharged and the vacuum circuit-breaker be brought into the open state, “Closing spring discharged” indication visible.

9229 0037 174 0-

2010-03-22 6-2 6.3 Sonder-Betriebsbedingungen Wird der V-Schalter 3AH5 unter ungünstigen Innenraumbe- dingungen betrieben, die außerhalb der normalen Betriebsbe- dingungen liegen (starke häufige Betauung, staubhaltige Luft usw.), empfehlen wir eine regelmäßige Reinigung der äußeren Schalterteile und ggf. Erneuerung der Korrosionsschutzfet- tung. Hierfür dürfen an den einzelnen Funktionsstellen des Schalters nur die nachfolgend angegebenen Mittel verwendet werden. 1. Lagerstellen, Gleitflächen: Isoflex Topas L 32 2. Für Fett, unzugängliche Lagerstellen und Lagerstellen des Hilfsschalters S1: Shell Tellus Öl 32 Gelenke und Lagerstellen, die nicht auseinandergenommen werden können, vor der Nachbehandlung nicht mit einem Reinigungsmittel auswaschen! Nach der Behandlung den V-Schalter mehrmals mechanisch zur Probe schalten. Schmiermittel (für besondere Einsatzbedingungen) sind über die zuständige Siemens-Vertretung erhältlich: 6.4 Kontrolle des Kontaktsystems Über die gesamte Nutzungsdauer der Vakuum-Schaltröhre kann eine Veränderung des Kontakthubes auftreten. Diese wird durch Stauchung und/oder Abbrand verursacht. Durch konstruktive Maßnahmen sind derart geringe Hubänderungen ohne Rückwirkungen auf das Schaltverhalten unserer Lei- stungsschalter. 6.5 Vakuum-Kontrolle Wenn der Verdacht besteht, daß eine Vakuum-Schaltröhre durch Beschädigung undicht geworden ist, muß eine Vakuum- Kontrolle vorgenommen werden. Hierzu ist es notwendig, daß Sammelschienen- und Kabelverbindungen aufgetrennt wer- den. Die Kontrolle erfolgt mit einem Hochspannungs-Prüfge- rät. 6.6 Lebensdauer Alle Vakuum-Leistungsschalter erfüllen die Schalterklassen E2, M2 und C2 gemäß IEC 62271-100. Unter normalen Betriebsbedingungen sind die Schalter für eine Schaltspielzahl von 10 000 ausgelegt. Aufgrund der Lebensdaueroptimierung aller Teile nimmt die Zuverlässigkeit bei darüberhinausgehenden Schaltspielzahlen ab. Eine wei- tere Verwendung des Schalters kann daher seitens des Her- stellers selbst bei Austausch bestimmter Baugruppen nicht empfohlen werden. Die zulässige elektrische Schaltspielzahl ist von der Höhe der geschalteten effektiven Kurzschlussausschaltströme abhän- gig. Danach sind die kompletten Schalterpole auszutauschen. Mit den Ersatzpolen wird eine detaillierte Austauschanwei- sung geliefert. Bei der Bestellung von Ersatzpolen ist die Angabe von Schal- tertyp und Fabriknummer (siehe Leistungsschild) erforderlich. Schmiermittel Bestell-Nr. 180 g Klüber -Isoflex Topas L32 3AX11 33-3H 1 kg SHELL Tellus Öl 32 3AX11 33-2D 1 kg Klüber -Isoflex Topas L32 3AX11 33-3E 6.3 Abnormal operating conditions If the 3AH5 vacuum circuit-breaker is used in abnormally unfavourable indoor conditions (e. g. frequent heavy conden- sation, dust-ridden air etc.), we recommend regular cleaning of the breaker external components and, if necessary, renewal of the anti-corrosion protection. Only the following products may be used for the respective working parts of the VCB. 1. Bearings, sliding surfaces: Isoflex Topas L 32 2. Bearings inaccessible to grease and bearings of the aux- iliary switch S1: Shell Tellus Oil 32 Joints and bearings which cannot be dismantled must not be treated with a cleaning agent prior to reapplication of anticor- rosives. After renewal of the anti-corrosion protection, several mechan- ical test-switching operations should be performed on the vacuum circuit-breaker. Lubricants (for special conditions) are available from the Sie- mens agency responsible: 6.4 Checking the contact system In the course of the service life of an interrupter, the contact travel may out of true. This is caused by compression and/or erosion. We have taken measures in design to ensure that such minor changes in the travel do not affect the switching perfomance of our circuit-breakers. 6.5 Checking the vacuum Such a check should be made if there is any risk of an interrupter having developed a leak. Busbar and cable con- nections must be split. The check is performed with an HV test unit. 6.6 Service life All 3AH5 vacuum circuit-breakers comply with the standards of the breaker classes E2, M2 and C2 in accordance with IEC 62271-100. Under normal operating conditions, the circuit-breakers are designed for 10,000 operating cycles. Due to the optimization of the service life of all parts, the level of reliability falls if the breakers are used for a greater number of opening cycles. The manufacturer can therefore not recommend continued use of the circuit-breakers, even if certain subassemblies are renewed. The permissible number of electrical operating cycles depend on the capacity of the short-circuit breaking currents. When this permissible maximum has been attained, the complete pole assemblies must be renewed. Detailed instructions are supplied with the replacement pole assemblies. When ordering replacement pole assemblies, state the circuit- breaker type, design code and serial number (see name plate). Lubricants Order-No: 180 g Klüber -Isoflex Topas L32 3AX11 33-3H 1 kg SHELL Tellus Oil 32 3AX11 33-2D 1 kg Klüber -Isoflex Topas L32 3AX11 33-3E

9229 0037 174 0-

2010-03-22 6-3 6.7 Zubehör und Ersatzteile Wegen der lebensdauerbezogenen Optimierung aller Teile dieses Schaltertyps ist eine Ersatzteilempfehlung nicht erfor- derlich. Sollen trotzdem Ersatzteile benötigt werden, bei der Bestellung folgende Daten angeben: - Typbezeichnung und Fabriknummer des V-Schalters 3AH5 (siehe Leistungsschild). - Für Teile, die nicht als Ersatzteile aufgeführt sind, Benen- nung und Teil-Nr., ggf. unter Bezugnahme auf Abbildungen dieser Betriebsanleitung oder ein Foto oder eine Skizze (bzw. Einsendung eines Musterteiles). 6.8 Produkthaftung des Herstellers Die Produkthaftung des Herstellers entfällt, wenn mindestens eines der folgenden Kriterien zum Tragen kommt: - Es werden keine originalen Siemens-Teile eingesetzt. - Monteure, die den Austausch durchführen, sind nicht durch Siemens geschult und zertifiziert. - Die Teile werden fehlerhaft montiert oder eingestellt. - Die Einstellungen werden nicht nach Siemens-Vorgaben durchgeführt. Hinweis Ersatzteile dürfen nur durch geschultes und zertifiziertes Personal getauscht werden, um die Funktionstüchtigkeit des Gerätes zuverlässig sicher zu stellen. 6.7 Accessories and spare parts Owing to the fact that all parts of this breaker type have been optimized to last the normal service life, it is no need to recommend any particular spare parts for keeping in stock. Nevertheless, if you require further spare parts, state the following data when ordering them: - Type designation, design code and serial number of the 3AH5 vacuum circuit-breaker (see rating plate). - For components not listed as spare parts, state the desig- nation and part number, making reference to illustrations in these Operating instructions or to a photograph or sketch as applicable. Alternatively, a sample may be submitted. 6.8 Manufacturer's product liability The manufacturer's product liability shall be nullified if at least one of the following criteria applies: - Original Siemens spare parts are not used. - Fitters performing replacement have not been trained and certified by Siemens. - Parts have been incorrectly fitted or adjusted. - Settings are not made in accordance with Siemens speci- fications. Note Only trained and certified personnel is allowed to change spare parts to ensure the functional efficiency of the unit.

9229 0037 174 0-

2010-03-22 7-1 7 Entsorgung Das Schaltgerät ist ein umweltfreundliches Erzeugnis. Der Wiederverwendung der Materialien ist bei der Entsorgung der Vorzug zu geben. Die Entsorgung des Schaltgerätes ist auf der Grundlage der bestehenden Rechtsvorschriften umwelt- freundlich möglich. Die Verwertung erfolgt als Mischschrott. Das Schaltgerät besteht aus folgenden Werkstoffen: Stahl, Kupfer, Aluminium, PTFE, Gießharz- bzw. gießharzge- tränkten Gewebeteilen, glasfaserverstärkten Kunststoffen und anderen Kunststoffen, Gummiwerkstoffen als Dichtungsma- terialien, Keramik, Schmierstoffen und Ölen. Gefahrstoffe im Sinne der Gefahrstoff-Verordnung sind nicht vorhanden. Vor der Entsorgung ist darauf zu achten, daß die im Gerät vorhandenen mineralischen oder synthetischen Öle bzw. Fette als Sonderabfall getrennt werden. Die örtlichen Kundendienststellen stehen für die Beantwortung von Entsor- gungsfragen beratend zur Verfügung 7 Disposal note The switching equipment is environment-friendly.Recycling should give priority to the disposal of the materials.The switch- ing equipment can be disposed of in an environment-friendly manner as stipulated by the current legislation.It is to be treated as mixed scrap.The switching equipment consist of the follow- ing materials: Steel, copper, aluminium, PTFE, cast resin im-pregnated fab- ric, glassfiber reinforced plastics and other plastics, rubber materials used for sealing purposes, ceramics, lubricants and oils. The equipment contains no hazardous materials as defined by law. Before disposal, make sure that all mineral or synthetic oils and greased have been removed from the equipment for seperate disposal. The local customer service centers will be pleased to advise you on all matters concerning disposal

9229 0037 174 0-

2010-03-22 8-1 8 Service Sie haben uns als Hersteller von Mittelspannungsschaltgerä- ten und Komponenten – und damit unserer Gerätetechnik – Ihr Vertrauen geschenkt. Dafür danken wir Ihnen. Personen- und Anlagensicherheit sowie Verfügbarkeit und Service sind Ihnen und uns äußerst wichtig. Darüber hinaus helfen uns Ihre Anregungen, unsere Produkte stetig zu verbessern. Sprechen Sie uns bitte an. Ihre regionalen Ansprechpartner der jeweiligen SIEMENS- Niederlassungen vor Ort und weitere Siemens-Adressen fin- den Sie über - Tel.: +49 180/5247000 - Fax: +49 180/5242471 oder - Internet unter der Web-Adresse: www.sie- mens.com/energy-support - E-Mail: [email protected] Unser Ziel ist es , Sie umgehend und kompetent zu unterstüt- zen. 8 Service Thank you for placing your trust in us as a manufacturer of medium-voltage switchgear and components - and thus in our technology as a whole. We attach great importance to personal safety, system reliability, availability and service. Your sug- gestions enable us to keep on improving our products. Please do not hesitate to contact us. You can find your contact at the SIEMENS Regional Offices in your area and other Siemens addresses via - Tel.: +49 180/5247000 - Fax: +49 180/5242471 or - Internet under the Web-Adresse: www.sie- mens.com/energy-support - E-Mail: [email protected] Our aim is to provide you with prompt and expert support.

Power Distribution Group

Medium Voltage Components Schaltwerk Berlin Nonnendammallee 104 D - 13629 Berlin Änderungen vorbehalten Published by the Sector Energy Power Distribution Group Medium Voltage Components Schaltwerk Berlin Nonnendammallee 104 D - 13629 Berlin Subject to change Siemens Aktiengesellschaft