Wallstation circuits are classified as Class 2 circuits

(USA) and PELV circuits (IEC). As Class 2 circuits, they comply with the requirements of NFPA® 70, National Electrical Code® (NEC®). As PELV circuits, they comply with the requirements of IEC 60364-4- 41, VDE 0100 Part 410, BS7671:1992, and other equivalent standards. When installing and wiring to these wallstations, follow all applicable national and/ or local wiring regulations. External circuits ...

Warning! Shock hazard. May result in

serious injury or death. Always turn OFF the circuit breaker/MCB or remove the main fuse from the power line before doing any work. 1. Turn Power OFF. Turn power OFF as circuitbreaker/MCB (or remove fuse). 2. Mount Wallbox. Wallstations mount in a Lutron wallbox (P/N 241-683) or in German and UK backboxes (60.30 mm measured center to center of mounting holes). 3 ...

5. Connect the Wallstation to the Control Link.

Connect two 1.0 mm2 (#22 AWG) ­shielded, twisted pair wires to terminals 3 and 4 of the wallstation’s control link connector. Shielding (drain) of the twisted pair wires must be connected together as shown, but do not connect the shielding to earth/ground or the wallstation and do not allow it to contact the grounded wallbox. Note: Use the wire connector required ...

7. Mount Wallstation. Carefully mount and align

the wallstation as shown. Screw top and bottom mounting screw into the control and wallbox. Replace the adapter (for insert versions) with the adapter screws. Then snap in the buttons and faceplate. 8. Turn Power ON. Turn ON control breaker, or replace main fuse. Notes • Unprogrammed (out of the box) QS wallstations and control units will all work together until ...

2. Select wallstation function (optional).

The info screen on the GRAFIK Eye® QS control unit will display a prompt to change your wallstation’s function (type). Press the OK button on the QS control unit to display the current wallstation function/type. To change, use the master buttons to scroll through the available choices until the function you want displays on the info screen. The keypad menu will display only functions that are available ...

3b. For wallstations with partition function:

2-button wallstations that control one partition: The LEDs on the wallstation will alternately blink. On each GRAFIK Eye QS control unit within the partitioned space, press and hold the top button on the lighting column until its LEDs flash in unison. The control units will then function together when the partition is open. All other partition wallstations: On the wallstation, press the button you want to us ...

3c. For wallstations with fine tune function: On the

GRAFIK Eye® QS control unit, press simultaneously the raise and lower buttons for the zone you want the wallstation to fine tune. Repeat for each zone you wish to “listen” to the selected wallstation, or for zones on additional control units. When listening, zone LEDs flash. When unassigned (not “listening”), the 3 middle zone LEDs light. Note: To ...

Or -Press any button on an EDU to toggle between

unassignment and assignment for that EDU’s window treatment to the wallstation. Check window treatment assignments: EDUs for window treatments assigned to the wallstation will be at their close limit, and EDUs for window treatments not assigned to the wallstation will be at their open limit. Note: Once you have assigned window treatments to a wallstation a ...

International seeTouch® QS Wallstation

Button Functions The following functions are menu choices when the wallstation is in setup mode and the GRAFIK Eye® QS is displaying the keypad menu. Each function choice is explained below. See the next page for a summary table of wallstations and their function choices. Scenes: Choose from the list of preset groups of scenes to assign to the buttons on this wallstation. ...

International seeTouch® QS Wallstation Button Functions Summary

Button Configuration EGN Functionality E01 Functionality NST ­Options Scene Options Zone Partition Function 2B Partition Function Zone Lockout Function Fine Tune Function Sequence Function Panic Function Window Treatments Function 2B 3B 4B 5BRL 5BRLIR 6BRL Left Right 7BRL Left Right 8BRL 8BRLIR Left Right 10BRL Left ...

Adjusting Window Treatment

Settings Setting Limits Note: Entering Limit Setup mode may cause window treatments to move approximately 203 mm (8 in.) up or down. Be sure that each window treatment is positioned so that the fabric can safely move 203 mm (8 in.) up or down before entering Limit Setup mode. To be able to adjust window treatment limits, your wallstation must have raise and lower buttons. If your mode ...

Preset Adjustment: Simple Method

Note: The top button will always open the shades fully, and the bottom button will always close the shades fully. Only the shade presets activated by the intermediate buttons can be reprogrammed. 1. Use the raise and lower buttons on the shade keypad to set all EDUs (electronic drive units of the window treatments) to the desired preset levels. 2. Press and hold the respecti ...

No communication with

GRAFIK Eye® control unit. Wallstation buttons do not work; LEDs do not track. LEDs do not light. Contact closure inputs or sensor input do not produce the desired result in the system. • Miswire or loose connection at the control link data lines 3 and 4. • Wallstation has not been programmed or has been programmed incorrectly. • Wallstat ...

Troubleshooting: Window Treatment Functions

Symptom EDU (electronic drive unit of the window treatment) will not move EDU (electronic drive unit of the window treatment) does not fully open or fully close Window treatment moves in the opposite direction when raise/lower buttons are pushed Keypad LEDs are off and keypad will not control any window treatment Keypad LEDs are on but keypad will not control any w ...

­Lutron Electronics Co., Inc.

Made and printed in U.S.A. P/N 030-1005 Rev. A 06/10 Contact Information Warranty Lutron Electronics Co., Inc. Limited Warranty Lutron EA Ltd. (“Lutron EA”) warrants each unit to be free from defects in material and workmanship and to perform under normal use and service. To the extent permitted by law, Lutron EA and Lutron Electronics Co. Inc. (“Lutron”) make no warranties or representations as to the units except a ...