Type CO Overcurrent Relay
2
Figure 1: Type CO Relay Without Case. 1 = Indicating Instantaneous Trip (IIT). 2 = IIT Adjusting Screw.
3 = Indicating Contactor Switch (ICS). 4 = Indicating Contactor Switch Tap Block.
Figure 2: Time Overcurrent Unit (Front View). 1 = Tap block. 2 = Time Dial.
3 = Control Spring Assembly. 4 = Disc. 5= Stationary Contact Assembly.
6 = Magnetic Plugs. 7 = Permanent Magnet.
Type CO Overcurrent Relay
41-101U
3
Figure 3: “E” Type Electromagnet.
1= Magnet Plugs.
2= Tap Block.
3= Tap Screw.
Figure 4: Indicating Instantaneous Trip Unit (IIT).
Figure 5: Indicating Contactor Switch (ICS).
Type CO Overcurrent Relay
4
2.0
CONSTRUCTION AND OPERATION
The type CO relays consist of an overcurrent unit
(CO), an indicating contactor switch (ICS), and an in-
dicating instantaneous trip unit (IIT) when required.
The principal component parts of the relay and their
location are shown in Figures 1 through 5.
2.1
ELECTROMAGNET
The electromagnets for the types CO-5, CO-6,
CO-7, CO-8 and CO-9 relays have a main tapped
coil located on the center leg of an “E” type laminat-
ed structure that produces a flux which divides and
returns through the outer legs. A shading coil causes
the flux through the left leg to lag the main pole flux.
The out-of-phase fluxes thus produced in the air gap
cause a contact closing torque. A torque controlled
CO has the lag coil connections of the electromagnet
brought out to separate terminals. This permits con-
trol of the closing torque such that only when these
terminals are connected together will the unit oper-
ate.
The electromagnets for the types CO-2 and CO-11
relays have a main coil consisting of a tapped prima-
ry winding and a fixed secondary winding. Identical
coils are on the outer legs of the lamination structure
and are connected to the main coil fixed secondary
in a manner so that the combination of all the fluxes
produced by the electromagnet result in out-of-
phase fluxes in the air gap. The out-of-phase air gap
fluxes produced cause a contact closing torque.
2.2
INDICATING CONTACTOR SWITCH UNIT
(ICS)
The dc indicating contactor switch is a small clapper
type device. A magnetic armature, to which leaf-
spring mounted contacts are attached, is attracted to
the magnetic core upon energization of the switch.
When the switch closes the moving contacts bridge
two stationary contacts, completing the trip circuit.
Also during this operation two fingers on the arma-
ture deflect a spring located on the front of the
switch, which allows the operation indicator target to
drop.
The front spring, in addition to holding the target,
provides restraint for the armature and thus controls
the pickup value of the switch.
2.3
INDICATING INSTANTANEOUS TRIP UNIT
(IIT)
The instantaneous trip unit is a small ac operated
clapper type device. A magnetic armature, to which
leaf-spring mounted contacts are attached, is at-
tracted to the magnetic core upon energization of the
switch. When the switch closes, the moving contacts
bridge two stationary contacts completing the trip cir-
cuit. Also, during the operation, two fingers on the ar-
mature deflect a spring located on the front of the
switch which allows the operation indictor target to
drop.
Figure 6: External Schematic of the Circuit-Closing Type CO Relay for Phase and Ground Overcurrent
Protection on a Three-Phase System.
Sub 3
182A755
Type CO Overcurrent Relay
41-101U
5
ENERGY REQUIREMENTS
TYPE CO-2 RELAY
VOLT AMPERES**
Continuous
One Second
Power
At
At 3 Times
At 10 Times
At 20 Times
Ampere
Rating
Rating*
Factor
Tap Value
Tap Value
Tap Value
Tap Value
Range
Tap
(Amperes)
(Amperes)
Angle ø
Current
Current
Current
Current
0.5
0.91
28
58
4.8
39.6
256
790
0.6
0.96
28
57
4.9
39.8
270
851
0.8
1.18
28
53
5.0
42.7
308
1024
0.5/2.5
1.0
1.37
28
50
5.3
45.4
348
1220
1.5
1.95
28
40
6.2
54.4
435
1740
2.0
2.24
28
36
7.2
65.4
580
2280
2.5
2.50
28
29
7.9
73.6
700
2850
2.0
3.1
110
59
5.04
38.7
262
800
2.5
4.0
110
55
5.13
39.8
280
920
3.0
4.4
110
51
5.37
42.8
312
1008
2/6
3.5
4.8
110
47
5.53
44.3
337
1120
4.0
5.2
110
45
5.72
46.0
360
1256
5.0
5.6
110
41
5.90
50.3
420
1500
6.0
6.0
110
37
6.54
54.9
474
1800
4.0
7.3
230
64
4.92
39.1
268
848
5.0
8.0
230
50
5.20
42.0
305
1020
6.0
8.8
230
47
5.34
44.1
330
1128
4/12
7.0
9.6
230
46
5.53
45.8
364
1260
8.0
10.4
230
43
5.86
49.9
400
1408
10.0
11.2
230
37
6.60
55.5
470
1720
12.0
12.0
230
34
7.00
62.3
528
2064
VOLT AMPERES**
Continuous
One Second
Power
At
At 3 Times
At 10 Times
At 20 Times
Ampere
Rating
Rating*
Factor
Tap Value
Tap Value
Tap Value
Tap Value
Range
Tap
(Amperes)
(Amperes)
Angle ø
Current
Current
Current
Current
0.5
2.7
88
69
3.92
20.6
103
270
0.6
3.1
88
68
3.96
20.7
106
288
0.8
3.7
88
67
4.01
21.0
120
325
0.5/2.5
1.0
4.1
88
66
4.07
22.3
130
400
1.5
5.7
88
62
4.19
23.2
147
462
2.0
6.8
88
60
4.30
24.9
168
548
2.5
7.7
88
58
4.37
26.2
180
630
2
8.0
230
67
3.88
21.0
110
308
2.5
8.8
230
66
3.90
21.6
118
342
3
9.7
230
64
3.93
22.1
126
381
2/6
3.5
10.4
230
63
4.09
23.1
136
417
4
11.2
230
62
4.12
23.5
144
448
5
12.5
230
59
4.20
24.8
162
540
6
13.7
230
57
4.38
26.5
183
624
4
16.0
460
65
4.00
22.4
126
376
5
18.8
460
63
4.15
23.7
143
450
6
19.3
460
61
4.32
25.3
162
531
4/12
7
20.8
460
59
4.35
26.4
183
611
8
22.5
460
56
4.40
27.8
204
699
10
25.0
460
53
4.60
30.1
247
880
12
28.0
460
47
4.92
35.6
288
1056
*
Thermal capacities for short times other than one second may be calculated on the basis of time being inversely proportional to the square of the current.
ø
Degrees current lags voltage at tap value current.
**
Voltages taken with Rectox type voltmeter.
CO-5 LONG TIME AND CO-6 DEFINITE MINIMUM TIME RELAYS
Type CO Overcurrent Relay
6
ENERGY REQUIREMENTS
CO-7 MODERATELY INVERSE TIME RELAY
VOLT AMPERES**
Continuous
One Second
Power
At
At 3 Times
At 10 Times
At 20 Times
Ampere
Rating
Rating*
Factor
Tap Value
Tap Value
Tap Value
Tap Value
Range
Tap
(Amperes)
(Amperes)
Angle ø
Current
Current
Current
Current
0.5
2.7
88
68
3.88
20.7
103
278
0.6
3.1
88
67
3.93
20.9
107
288
0.8
3.7
88
66
3.97
21.1
114
320
0.5/2.5
1.0
4.1
88
64
4.00
21.6
122
356
1.5
5.7
88
61
4.08
22.9
148
459
2.0
6.8
88
58
4.24
24.8
174
552
2.5
7.7
88
56
4.38
25.9
185
640
2
8.0
230
66
4.06
21.3
111
306
2.5
8.8
230
64
4.07
21.8
120
230
3
9.7
230
63
4.14
22.5
129
366
2/6
3.5
10.4
230
62
4.34
23.4
141
413
4
11.2
230
61
4.34
23.8
149
448
5
12.5
230
59
4.40
25.2
163
530
6
13.7
230
58
4.62
27.0
183
624
4
16
460
64
4.24
22.8
129
392
5
18.8
460
61
4.30
24.2
149
460
6
19.3
460
60
4.62
25.9
168
540
4/12
7
20.8
460
58
4.69
27.3
187
626
8
22.5
460
55
4.80
29.8
211
688
10
25
460
51
5.20
33.0
260
860
12
28
460
46
5.40
37.6
308
1032
CO-8 LONG TIME AND CO-9 DEFINITE MINIMUM TIME RELAYS
VOLT AMPERES**
Continuous
One Second
Power
At
At 3 Times
At 10 Times
At 20 Times
Ampere
Rating
Rating*
Factor
Tap Value Tap Value
Tap Value
Tap Value
Range
Tap
(Amperes)
(Amperes)
Angle ø
Current
Current
Current
Current
0.5
2.7
88
72
2.38
21.0
132
350
0.6
3.1
88
71
2.38
21.0
134
365
0.8
3.7
88
69
2.40
21.1
142
400
0.5/2.5
1.0
4.1
88
67
2.42
21.2
150
440
1.5
5.7
88
62
2.51
22.0
170
530
2.0
6.8
88
57
2.65
23.5
200
675
2.5
7.7
88
53
2.74
24.8
228
800
2
8.0
230
70
2.38
21.0
136
360
2.5
8.8
230
66
2.40
21.1
142
395
3
9.7
230
64
2.42
21.5
149
430
2/6
3.5
10.4
230
62
2.48
22.0
157
470
4
11.2
230
60
2.53
22.7
164
500
5
12.5
230
58
2.64
24.0
180
580
6
13.7
230
56
2.75
25.2
198
660
4
16.0
460
68
2.38
21.3
146
420
5
18.8
460
63
2.46
21.8
158
480
6
19.3
460
60
2.54
22.6
172
550
4/12
7
20.8
460
57
2.62
23.6
190
620
8
22.5
460
54
2.73
24.8
207
700
10
25.0
460
48
3.00
27.8
248
850
12
28.0
460
45
3.46
31.4
292
1020
*
Thermal capacities for short times other than one second may be calculated on the basis of time being inversely proportional to the square of the current.
ø
Degrees current lags voltage at tap value current.
**
Voltages taken with Rectox type voltmeter.
Type CO Overcurrent Relay
41-101U
7
VOLT AMPERES**
Continuous
One Second
Power
At
At 3 Times
At 10 Times
At 20 Times
Ampere
Rating
Rating*
Factor
Tap Value
Tap Value
Tap Value
Tap Value
Range
Tap
(Amperes)
(Amperes)
Angle ø
Current
Current
Current
Current
0.1
0.04
11.5
34
0.64
6.5
70.3
240
0.12
0.04
11.5
32
0.67
6.66
75.4
264
0.16
0.04
11.5
30
0.76
7.3
82.4
297
0.1/0.5
0.2
0.04
11.5
26
0.83
8.3
87.8
336
0.3
0.04
11.5
22
1.01
10.3
117.6
420
0.4
0.04
11.5
18
1.21
11.22
140.0
520
0.5
0.04
11.5
16
1.38
13.8
168.0
630
0.5
1.7
56
36
0.72
6.54
71.8
250
0.6
1.9
56
34
0.75
6.80
75.0
267
0.8
2.2
56
30
0.81
7.46
84.0
298
0.5/2.5
1.0
2.5
56
27
0.89
8.30
93.1
330
1.5
3.0
56
22
1.13
10.04
115.5
411
2.0
3.5
56
17
1.30
11.95
136.3
502
2.5
3.8
56
16
1.48
13.95
160.0
610
2.0
7.0
230
32
0.73
6.30
74.0
264
2.5
7.8
230
30
0.78
7.00
78.5
285
3 .0
8.3
230
27
0.83
7.74
84.0
309
2/6
3.5
9.0
230
24
0.88
8.20
89.0
340
4.0
10.0
230
23
0.96
9.12
102.0
372
5.0
11.0
230
20
1.07
9.80
109.0
430
6.0
12.0
230
20
1.23
11.34
129.0
504
4.0
14.0
460
29
0.79
7.08
78.4
296
5.0
16.0
460
25
0.89
8.00
90.0
340
6.0
17.0
460
22
1.02
9.18
101.4
378
4/12
7.0
18.0
460
20
1.10
10.00
110.0
454
8.0
20.0
460
18
1.23
11.1
124.8
480
10.0
22.0
460
17
1.32
14.09
131.6
600
12.0
26.0
460
16
1.8
16.3
180.0
720
*
Thermal capacities for short times other than one second may be calculated on the basis of time being inversely proportional to the square of the current.
ø
Degrees current lags voltage at tap value current.
**
Voltages taken with Rectox type voltmeter.
ENERGY REQUIREMENTS
TYPE CO-11 RELAY
INSTANTANEOUS TRIP UNIT (IIT)
RANGE IN
BURDEN IN VOLT-AMPS AT
AMPERES
MINIMUM SETTING
MAXIMUM SETTING
2
-
8
4.5
32
4
-
16
4.5
32
10 - 40
4.5
40
10 - 80
6.5
70
40 - 160
9.0
144
Type CO Overcurrent Relay
8
Figure 7: Typical Time Curves of the Type CO-2 Relay
Sub 1
619584
Type CO Overcurrent Relay
41-101U
9
Figure 8: Typical Time Curves of the Type CO-5 Relay
Sub 2
418245
Type CO Overcurrent Relay
10
Figure 9: Typical Time Curves of the Type CO-6 Relay
Sub 2
418246
Type CO Overcurrent Relay
41-101U
11
*Sub 2
418247
Figure 10: Typical Time Curves of the Type CO-7 Relay
*Denotes Change
Type CO Overcurrent Relay
12
Figure 11: Typical Time Curves of the Type CO-8 Relay
Sub 2
418248
Type CO Overcurrent Relay
41-101U
13
Figure 12: Typical Time Curves of the Type CO-9 Relay.
Sub 2
418249
Type CO Overcurrent Relay
14
Figure 13: Typical Time Curves of the Type CO-11 Relay.
Sub 2
288B655
Type CO Overcurrent Relay
41-101U
15
A core screw accessible from the top of the switch
provides the adjustable pickup range.
3.0
CHARACTERISTICS
The relays are generally available in the following
current ranges.
These relays may have either single or double circuit
closing contacts for tripping either one or two circuit
breakers.
The time vs. current characteristics are shown in Fig-
ures 7 to 13. These characteristics give the contact
closing time for the various time dial settings when
the indicted multiples of tap value current are applied
to the relay.
3.1
TRIP CIRCUIT
The main contacts will close 30 amperes at 250 volts
dc and the seal-in contacts of the indicating contac-
tor switch will carry this current long enough to trip a
circuit breaker.
The indicating instantaneous trip contacts will close
30 amperes at 250 volts dc, and will carry this cur-
rent long enough to trip a breaker.
The indicating contactor switch has two taps that
provide a pickup setting of 0.2 to 2 amperes. To
change taps requires connecting the lead located in
front of the tap block to the desired setting by means
of a screw connection.
3.2
TRIP CIRCUIT CONSTANTS
Contactor Switch -
0.2 ampere tap = 6.5 ohms dc resistance
2.0 ampere tap = 0.15 ohms dc resistance
4.0
SETTINGS
CAUTION
!
Since the tap block screw on both the CO unit
and IIT unit carries operating current, be sure
that the screws are turned tight.
In order to avoid opening current transformer
circuits when changing taps under load, the re-
lay must be first removed from the case. Chassis
operating shorting switches on the case will short the
secondary of the current transformer. The taps
should then be changed with the relay outside of the
case and then re-inserted into the case.
Range
Taps
† .1 - .5
0.1
0.12 0.16
0.2
0.3
0.4
0.5
.5 - 2.5
0.5
0.6
0.8
1.0
1.5
2.0
2.5
2.0 - 6.0
2.0
2.5
3.0
3.5
4.0
5.0
6.0
4.0 - 12.0 4.0
5.0
6.0
7.0
8.0 10.0 12.0
† Available for Type CO-11 Relay Only.
Figure 14: Internal Schematic of the Double Trip Circuit
Closing Relay. For the Single Trip Relay the
Circuits Associated with Terminal 2 are Omit-
ted.
Figure 15: Internal Schematic of the Single Trip Circuit-
Closing Relay with Indicating Instantaneous
Trip Unit.
Sub 3
57D4524
Sub 7
57D4525
Type CO Overcurrent Relay
16
4.1
CO UNIT
The overcurrent unit settings can be defined either
by tap setting and time dial position or by tap setting
and a specific time of operation at some multiple of
the current tap setting (e.g., 4 tap setting, 2 time dial
position or 4 tap setting. 0.6 seconds at 6 times tap
value current).
To provide selective circuit breaker operation, a min-
imum coordinating time of 0.3 seconds plus circuit
breaker time is recommended between the relay be-
ing set and the relays with which coordination is to
be effected.
The screw on the terminal plate above the time dial
makes connections to various turns on the operating
coil. By placing this screw in the various terminal
plate holes, the relay will respond to multiples of tap
value currents in accordance with the various typical
time-current curves.
4.2
INSTANTANEOUS RECLOSING
The factory adjustment of the CO unit contacts pro-
vides a contact follow. Where circuit breaker reclos-
ing will be initiated immediately after a trip by the CO
contact, the time of the opening of the contacts
should be a minimum. This condition is obtained by
loosening the stationary contact mounting screw, re-
moving the contact plate and then replacing the plate
with the bent end resting against the contact spring.
For double trip relays, the upper stationary contact is
adjusted such that the contact spring rests solidly
against the back stop. The lower stationary contact is
then adjusted such that both stationary contacts
make contact simultaneously with their respective
moving contact.
4.3
INDICATING CONTACT SWITCH (ICS)
The only setting required on the ICS unit is the selec-
tion of the 0.2 or 2.0 ampere setting. This selection is
made by connecting the lead located in front of the tap
block to the desired setting by means of the connect-
ing screw.
4.4
INDICATING INSTANTANEOUS TRIP ( IIT)
The IIT setting is the level of ac current at which it will
pickup. It should be set to coordinate with other de-
vices so it will never operate for a fault in protective
zone where tripping should be produced by other de-
vices. The transient reach will not exceed 130% for an
80° circuit angle or 108% for a 60° circuit.
The proper tap must be selected and the core screw
must be adjusted to the value of pick-up current de-
sired.
5.0
INSTALLATION
The relays should be mounted on switchboard panels
or their equivalent in a location free from dirt,
moisture, excessive vibration and heat. Mount the re-
lay vertically by means of the rear mounting stud or
studs for the type FT projection case or by means of
the four mounting holes on the flange for the
semi-flush type FT case. Either the stud or the mount-
ing screws may be utilized for grounding the relay. Ex-
ternal toothed washers are provided for use in the lo-
cations shown on the outline and drilling plan to
facilitate making a good electrical connection be-
tween the relay case, its mounting screws or studs,
and the relay panel. Ground wires should be affixed to
the mounting screws or studs as required for poorly
grounded or insulating panels. Other electrical con-
nections may be made directly to the terminals by
means of screws for steel panel mounting or to the
terminal stud furnished with the relay for thick panel
mounting. The terminal stud may be easily removed
or inserted by locking two nuts on the stud and then
turning the proper nut with a wrench.
Figure 16: Internal Schematic of the Single Trip Circuit-
Closing Relay with Indicating Instantaneous
Trip Unit.
*Sub 5
182A754
Type CO Overcurrent Relay
41-101U
17
For detail information on the FT case refer to Instruc-
tion Leaflet 41-076.
6.0
ADJUSTMENTS AND
MAINTENANCE
Proper adjustments for correct operation of this relay
have been made at the factory. Upon receipt of the
relay no customer adjustments, other than those
covered under Section 4 "Settings" should be re-
quired.
For relays which include an indicating instantaneous
trip unit (IIT), the junction of the induction and indi-
cating instantaneous trip coils is brought out to
switch jaw #3. With this arrangement the overcurrent
units can be tested separately.
6.1
PERFORMANCE CHECK
The following check is recommended to verify that
the relay is in the proper working order:
6.1.1
Contact
a. By turning the time dial, move the moving con-
tacts until they deflect the stationary contact to a
position where the stationary contact is resting
against its backstop. The index mark located on
the movement frame should coincide with the “O”
mark on the time dial. For double trip relays, the
follow on the stationary contacts should be ap-
proximately 1/64”.
a. For relays identified with a “T”, located at lower
left of stationary contact block, the index mark on
the movement frame will coincide with the “O”
mark on the time dial when the stationary contact
has moved through approximately one-half of its
normal deflection. Therefore, with the stationary
contact resting against the backstop, the index
mark is offset to the right of the “O” mark by ap-
proximately .020". The placement of the various
time dial positions in line with the index mark will
give operating times as shown on the respective
time-current curves. For double trip relays, the fol-
low on the stationary contacts should be
approximately 1/32”.
6.1.2
Minimum Trip Current
Set the time dial to position 6 using the lowest tap
setting, alternately apply tap value current plus 3%
and tap value current minus 3%. The moving contact
should leave the backstop at tap value current plus
Figure 17: Internal Schematic of the Double Trip Circuit
Closing Relay with Torque Control Terminals.
For the Single Trip Relay, the Circuits Associ-
ated with Terminal 2 are Omitted.
Figure 18: Internal Schematic of the Single Trip Circuit
ClosinF:g Relay with Torque Control Termi-
nals and Indicating Instantaneous Trip Unit.
CO
IIT
IIT
CO
TERMINAL
CHASSIS
OPERATED
SHORTING
SWITCH
CURRENT
TEST JACK
TEST SWITCH
RED HANDLE
INDICATING
INSTANTANEOUS
UNIT
INDUCTION UNIT
LAG COIL
INDUCTION UNIT
ICS
ICS
INDICATING
CONTACTOR
SWITCH
CLOSE FOR RELAY TO TRIP
EXTERNAL CONTACTS MUST
FRONT VIEW
2
4
3
1
5
6
8
10
7
9
*Sub 7
57D4529
9
7
10
8
6
5
1
3
4
2
FRONT VIEW
EXTERNAL CONTACTS MUST
CLOSE FOR RELAY TO TRIP
INDICATING
CONTACTOR
SWITCH
ICS
INDUCTION
LAG COIL
RED HANDLE
TEST SWITCH
CURRENT
TEST JACK
CHASSIS
OPERATED
SHORTING
SWITCH
TERMINAL
CO
CO
CO
ICS
INDUCTION
UNIT
UNIT
*Sub 5
57D4528
Type CO Overcurrent Relay
18
3% and should return to the backstop at tap value
current minus 3%.
6.1.3
Time Curve
For type CO-11 relay only, the 1.30 times tap value
operating time from the number 6 time dial position
is 53.5 ±5% seconds and should be checked first. It
is important that the 1.30 times tap value current be
maintained accurately. The maintaining of this cur-
rent accurately is necessary because of the steep-
ness of the slope of the time-current characteristic
(Figure 13). A slight variation, ±1%, in the 1.3 times
tap value current (including measuring instrument
deviation) will change the timing tolerance to ±10%
and the effects of different taps can make the total
variations appear to be ±15%.
Table 2 shows the time curve calibration points for
the various types of relays. With the time dial set to
the indicated position and the relay set on the lowest
tap setting, apply the currents specified by Table 2,
(e.g., for the CO-2, 3 and 20 times tap value current)
and measure the operating time of the relay. The op-
erating times should equal those of Table 2 plus or
minus 5% (Use .5 tap for .1 to .5 range).
6.1.4
Indicating Instantaneous Trip Unit (IIT)
The core screw which is adjustable from the top of
the trip unit determines the pickup value. The trip unit
has a nominal ratio of adjustment of 1 to 4 and an ac-
curacy within the limits of 10%.
The making of the contacts and target indication
should occur at approximately the same instant. Po-
sition the stationary contact for a minimum of 1/32”
wipe. The bridging moving contact should touch both
stationary contacts simultaneously.
Apply sufficient current to operate the IIT. The oper-
ation indicator target should drop freely.
6.1.5
Indicating Contactor Switch (ICS)
Close the main relay contacts and pass sufficient dc
current through the trip circuit to close the contacts
of the ICS. This value of current should be not great-
er than the particular ICS tap setting being used. The
operation indicator target should drop freely.
For proper contact adjustment, insert a .030" feeler
gauge between the core pin and the armature. Hold
the armature closed against the core pin and gauge
and adjust the stationary contacts such that they just
make with the moving contact. Both stationary con-
tacts should make at approximately the same time.
The contact follow will be approximately 1/64” to
3/64”.
6.2
CALIBRATION
Use the following procedure for calibrating the relay
if the relay has been taken apart for repairs or the ad-
justments disturbed. This procedure should not be
used until it is apparent that the relay is not in proper
working order. (See Section 6.1, Performance
Check.)
6.2.1
Contact
a. By turning the time dial, move the moving con-
tacts until they deflect the stationary contact to a
position where the stationary contact is resting
against its backstop. The index mark located on
the movement frame should coincide with the “O”
mark on the time dial. For double trip relays, the
follow on the stationary contacts should be ap-
proximately 1/64”.
b. For relays identified with a “T”, located at lower
left of stationary contact block, the index mark on
the movement frame will coincide with the “O”
mark on the time dial when the stationary contact
has moved through approximately one-half of its
normal deflection. Therefore, with the stationary
contact resting against the backstop, the index
mark is offset to the right of the “O” mark by
approximately .020". The placement of the vari-
ous time dial positions in line with the index mark
will give operating times as shown on the respec-
tive time-current curves. For double trip relays,
the follow on the stationary contacts should be ap-
proximately 1/32”.
6.2.2
Minimum Trip Current
The adjustment of the spring tension in setting the
minimum trip current value of the relay is most con-
veniently made with the damping magnet removed.
With the time dial set at “O”, wind up the spiral spring
by means of the spring adjuster until approximately
6 3/4 convolutions show.
Set the relay on the minimum tap setting, the time
dial to position 6.
Adjust the control spring tension so that the moving
contact will leave the backstop at tap value current
+1.0% and will return to the backstop at tap value
current -1.0%.
6.2.3
Time Curve Calibration
Install the permanent magnet. Apply the indicated
current per Table 2 for permanent magnet adjust-
ment (e.g., CO-8, 2 times tap value) and measure
Type CO Overcurrent Relay
41-101U
19
the operating time. Adjust the permanent magnet
keeper until the operating time corresponds to the
value of Table 2.
For type CO-11 relay only, the 1.30 times tap value
operating time from the number 6 time dial position
is 53.5 ±5% seconds. It is important that the 1.30
times tap value current be maintained accurately.
The maintaining of this current accurately is neces-
sary because of the steepness of the slope of the
time-current characteristic (Figure 13). A slight vari-
ation ±1%, in the 1.3 times tap value current (includ-
ing measuring instrument deviation) will change the
timing tolerance to ±10% and the effect of different
taps can make the total variations appear to be
±15%. If the operating time at 1.3 times tap value is
not within these limits, a minor adjustment of the
control spring will give the correct operating time
without any undue effect on the minimum pick-up of
the relay. The check is to be made after the 2 times
tap value adjustment has been completed.
Apply the indicated current per Table 2 for the elec-
tromagnet plug adjustment (e.g., CO-8, 20 times tap
value) and measure the operating time. Adjust the
proper plug until the operating time corresponds to
the value in Table 2. (Withdrawing the left hand plug,
front view, increases the operating time and with-
drawing the right hand plug, front view, decreases
the time.) In adjusting the plugs, one plug should be
screwed in completely and the other plug run in or
out until the proper operating time has been ob-
tained.
Recheck the permanent magnet adjustment. If the
operating time for this calibration point has changed,
readjust the permanent magnet and then recheck
the electromagnet plug adjustment.
6.2.4
Indicating Contactor Switch (ICS)
Close the main relay contacts and pass sufficient dc
current through the trip circuit to close the contacts
of the ICS. This value of current should be not great-
er than the particular ICS tap setting being used. The
operation indicator target should drop freely.
6.2.5
Indicating Instantaneous Trip Unit (IIT)
The core screw must be adjusted to the value of
pick-up current desired.
The nameplate data will furnish the actual current
range that may be obtained from the IIT unit.
6.3
ROUTINE MAINTENANCE
All relays should be inspected and checked periodi-
cally to assure proper operation. Generally a visual
inspection should call attention to any noticeable
changes. A minimum suggested check on the relay
system is to close the contacts manually to assure
that the breaker trips and the target drops. Then re-
lease the contacts and observe that the reset is
smooth and positive.
If an additional time check is desired, pass second-
ary current through the relay and check the time of
operation. It is preferable to make this at several
times pick-up current at an expected operating point
for the particular application. For the .5 to 2.5 am-
pere range CO-5 and CO-6 induction unit use the al-
ternative test circuit in Figure 16 as these relays are
affected by a distorted wave form. With the connec-
tion the 25/5 ampere current transformers should be
worked well below the knee of the saturation (i.e.,
use 10L50 or better).
All contacts should be periodically cleaned. A con-
tact burnisher #182A836H01 is recommended for
this purpose. The use of abrasive material for clean-
ing contacts is not recommended, because of the
danger of embedding small particles in the face of
the soft silver and thus impairing the contact.
7.0
RENEWAL PARTS
Repair work can be done most satisfactorily at the
factory. However, interchangeable parts can be fur-
nished to the customers who are equipped for doing
repair work. When ordering parts, always give the
complete nameplate data.
Type CO Overcurrent Relay
20
Table 2:
TIME CURVE CALIBRATION DATA - 50 & 60 HERTZ
PERMANENT MAGNET ADJUSTMENT
ELECTROMAGNET PLUGS
TIME
CURRENT
OPERATING
CURRENT
OPERATING
RELAY
DIAL
(MULTIPLES OF
TIME
(MULTIPLES OF
TIME
TYPE
POSITION
TAP VALUE)
SECONDS
TAP VALUE)
SECONDS
CO - 2
6
3
0.57
20
0.22
CO - 5
6
2
37.80
10
14.30
CO - 6
6
2
2.46
20
1.19
CO - 7
6
2
4.27
20
1.11
CO - 8
6
2
13.35
20
1.11
CO - 9
6
2
8.87
20
0.65
CO -11
6
2
11.27
20
0.24 ∆
∆ For 50 Hertz CO-11 relay 20 times operating time limits are 0.24 + 10%, -5%.
Type CO Overcurrent Relay
22
*Denotes Change
Figure 19: Outline and Drilling Plan for the Type CO Relay in the Type FT-11 Case
*Sub 19
57D7900
Type CO Overcurrent Relay
41-101U
23
Figure 20: Internal Schematic of the Double Trip Circuit Closing Relay with Indicating Instantaneous Trip Unit.