Bailey Infi 90 NIAC04 Instruction
Text of the manual
Process Control and
Automation Solutions
from Elsag Bailey Group
E96-421
Analog Input Calibration Module
(NIAC04)
WARNING notices as used in this instruction apply to hazards or unsafe practices that could result in
personal injury or death.
CAUTION notices apply to hazards or unsafe practices that could result in property damage.
NOTES highlight procedures and contain information that assists the operator in understanding the
information contained in this instruction.
The NIAC04 Analog Input Calibration Module provides a
means to calibrate 10 ohm RTD inputs for the IMASM04 Ana-
log Slave Module.
This manual explains how to install and use the NIAC04 mod-
ule on the INFI 90 Strategic Process Management System. It
has sections that describe the setup and cabling. The appendix
contains information about
List of Effective Pages
Total number of pages in this instruction is 20, consisting of the following:
Page No.
Change Date
Preface
Original
List of Effective Pages
Original
iii through vi
Original
1-1 through 1-5
Original
2-1 through 2-4
Original
3-1
Original
4-1
Original
5-1
Original
A-1
Original
Index-1
Original
When an update is received, in
All components, whether in transportation, operation or storage,
must be in a noncorrosive environment.
Electrical Shock Hazard During Maintenance
Disconnect power or take precautions to insure that contact with
energized parts is avoided when servicing.
SPECIFIC
CAUTIONS
Remove modules fro
Sommaire de Sécurité
®
AVERTISSEMENTS
D’ORDRE
GÉNÉRAL
Environnement de l’équipement
Ne pas soumettre les composants à une atmosphère corrosive lors
du transport, de l’entreposage ou l’utilisation.
Possibilité de chocs électriques durant l’entretien
Débrancher l’alimentation ou prendre les précautions pour éviter
tout c
Table of Contents
Page
I-E96-421A
iii
SECTION 1 - INTRODUCTION....................................................................................................1-1
OVERVIEW ..................................................................................................................1-1
INTENDED USER......................................................
List of Figures
®
1-1.
Application Example for the NIAC04 Module .......................................................... 1-2
2-1.
NIAC04 Module Jumper Locations......................................................................... 2-3
2-2.
Cable Connections for the NIAC04 Module ...........................................
1 - 1
SECTION 1 - INTRODUCTION
OVERVIEW
The NIAC04 Analog Input Calibration Module is required to
calibrate the IMASM04 Analog Slave Module (10 ohm RTD).
Calibration resistances are read from the NIAC04 module
through the IMASM04 module. Calibration values are read
across the slave expander bus and processed by the IMAMM03
master module.
1 - 2
I-E96-421A
®
•
Each calibration module fits in a standard termination
mounting unit.
•
Resistance temperature detector (RTD) input calibration for
the 10 ohm RTD inputs on the IMASM04 module.
•
Individual channel precision calibration resistors.
•
Jumpers select correct resistance for zero or span calibra-
tion for each