ULTRASONIC LEVEL TRANSMITTER COMPACT AND SEPARATE VERSIONS Instruction Manual Ident. 427998P ...
1.2 General Safety Instuctions ............................................................................................................................. 3 2 QUICKSTART 2.1 Installation ...................................... ...
Indicates information which must be followed. Failure to follow the information could endanger the user and affect the function of the device. Indicates that the page contains general information. Indicates a quickstart guide for quickly commissioning the transmitter. Indicates that the page contains information about installation. Indicates that the page contains information about configuration, programmi ...
Unpacking Verify Ident. No. Select the mounting position Have you a separate version? Have you a cable plug version? Connect power supply cable Connect output cable Reassemble housing or plug Turn on the power Distance displayed coherent? Program the transmitter 2.1 INST ...
required with no decimal points. Choose filters 0-2 if no echo filtering of obstructing obstacles is required and filters 3-9 if echo filtering is required. Typically 331.4 m/s within the air with a deviation of 0.59m/s/°C. To determine a new zero point and sound velocity. 4mA -> 100cm 20mA -> 250cm 2.2 PROGRAMMING The electronics within the 8175 ultrasonic level transmitter allows the unit to b ...
for 5 seconds. G The ‘Enter‘ key can be locked to avoid accidental or unauthorised access - section 3.3. G Reference can additionally be made to the menu guide - section 4.2. ` 2.2.2 PROGRAMMING - LEVEL The actions which are highlighted in grey must be fully completed for accurate measurement. Select level and the units required with 2 decimal points. Choose ...
for 5 seconds. G The ‘Enter‘ key can be locked to avoid accidental or unauthorised access - section 3.3. G Reference can additionally be made to the menu guide - section 4.2. G It is important to exit the menu calibration after entering the desired distance units and re-enter the menu to configure the volume units. 2.2.3 PROGRAMMING - VOLUME The actions which are hig ...
for 5 seconds. 2.3 TESTING 0......9 ENTER Control of 4 mA Control of 20 mA Adjustment of the temperature Display of the signal strength Simulation of the outputs Reseting of the stored parameters The unit is now ready The mode Offset fixes the output current of 4mA. (optional) The mod ...
Prior to the installation of the 8175 ultrasonic level transmitter, a clear mounting location for the product must be determined. G The level transmitter or sensor types 8175 / 8170 are designed for liquid level measurement. It is the user responsability to test the functionality of the device for any other material such as powders, granuals etc. G The 8175 ultrasonic level transmitter or ...
standard G 2“ (NPT) fitting or equivalent tapped flange according to the type of level transmitter. Steps for successful installation: G Before installation of the transmitter or sensor ensure that the fitting has been tested for leaks and the threads are not damaged or worn. If a damaged fitting is evident a new fitting sh ...
For installation and insertion of the panel version follow the instructions on the enclosed delivery film and as follows: 1. Put gasket on the cover and place the complete unit in the cut-away panel. 2. Screw the spacer bolts onto the panel fixing screws . 3. Insert the cable clips , to secure the various cables (power supply, outputs, sensor) of the transmitter, onto the plate . 4. Fas ...
This section allows easy identification of the features and electrical connections within the 8175 level transmitter depending on the version. 18-32VDC ELECTRONIC CARD 115 / 230VAC ELECTRONIC CARD (Compact version only) G The Coax cable and PT1000 connections must be connected in all cases to ensure the device functions correctly. G The key can be locked to avoid accidental or unauthorised ...
G Use cables with a temperature limit of 80°C minimum. G For normal operating conditions the measuring signal can be transmitted by a simple cable of 0.75 mm2 cross section. G The line must not be installed in combination with carrying lines with a higher voltage or frequency. G If a combined installation cannot be avoided, a minimum space of 30 cm (1 ft) or shielded cables should be adopted ...
WIRING Remove the cover via the screws on the front display and pull the cable through the PG 13.5 and wire according to one of the pin assignment diagrams below. The electronics within the 8175 allows a sourcing or sinking PLC to be connected. Position A (Fig 3.5) provides a sourcing configuration and Position B (Fig 3.6) a sinking configuration. Fig. 3.5 Pin assignment ...
WIRING Remove the cover via the screws on the front display and pull the cable through the PG 13.5 and wire according to one of the pin assignment diagrams below. The electronics within the 8175 allows a sourcing or sinking PLC to be connected. Position A (Fig 3.5) provides a sourcing configuration and Position B (Fig 3.6) a sink ...
CONNECTION OF THE 8170 SENSOR G Pass the cable through the wall / panel and use the PG 9 to secure the cable. G Connect the coax and PT1000 temperature cables shown in the diagram below. G Secure all the cables onto the protection plate as indicated via the 2 plastic ties provided. PT ...
The relay version is connected as follows : 3.4.3 Fig. 3.13 Pin assignment for relays SW 1 G The device can be easily connected to a PLC independently of the respective version. G The ‘Enter‘ key can be locked by placing the SW 1 swich into the up position to avoid accidental or ...
Remove the cover via the screws on the front display and pull the cable through the PG 9 and wire according to one of the pin assignment diagrams below. The electronics within the 8175 allows a sourcing or sinking PLC to be connected. Position A (Fig 3.15) provides a sourcing configuration ...
Example of LINK between the 8175 level transmitter 18-32VDC and the 8630 Top Control mounted on a diaphragm valve type 2031. NETWORKING provided by the relay outputs 3.5 CONTINUOUS PNEUMATIC LEVEL CONTROL PLC Jumper ...
and the 1067 positioner mounted on an angle seat valve type 2632. NETWORKING provided by the relay outputs. 3.5 CONTINUOUS PNEUMATIC LEVEL CONTROL 8175 4-20 mA 24 V= - + PLC POSITIONER TYPE 1067 ...