Camille Bauer KINAX 3W2 Operating Instructions

Specifications

Brand: Camille Bauer
Category: Transmitter
Model: KINAX 3W2 (Operating Instructions)
File Type: PDF
File Size: —
Pages: 5

Read Online

Read the Camille Bauer KINAX 3W2 Operating Instructions online using the built-in PDF viewer.

Text of the manual

1. Safety instructions

1.1 Symbols The symbols in these instructions point out risks and have the following meaning: Warning in case of risks. Non-observance can result in malfunctioning. Non-observance can result in malfunctioning and personal injury. Information on proper product handling. 1.2 Intended use • The KINAX 3W2 is a precision instrument. It is used to determine angular po- sitions, processing and providing measured values of electrical output signals for the downstream device. Encoders use for this purpose only. • The angular position transmitter is not intended to measure rotation speed. • The device is intended for installation in industrial plants and meets the requi- rements of EN 61010-1. • Device versions with explosion protection may only be used in the planned purposes and have to be installed in a housing with an ingress protection of at least IP20 according to EN 60529. The operation in other explosive atmospheres is not permissible. • Manufacturer is not liable for any damage caused by inappropriate handling, modifi cation or any application not according to the intended purpose. 1.3 Commissioning • Installation, assembly, setup and commissioning of the device has to be carried out exclusively by skilled workers. • Observe manufacturer’s operating instructions. • Check all electric connections prior to commissioning the plant. • If assembly, electric connection or other work on the device and the plant are not carried out properly, this may result in malfunctioning or breakdown of the device. • Safety measures should be taken to avoid any danger to persons, any damage of the plant and of the equipment due to breakdown or malfunctioning of the device. • Do not operate the device outside of the limit values stated in the operating instructions. • Operation of device versions with explosion protection is only permissible when... - the details on the type label of the device match the on- site conditions for the permissible Ex area in use (group of equipment, equipment category, zone, temperature class or maximum surface temperature) - the details on the type label of the device match the electrical supply network - the device is undamaged and - it has been checked that there is no explosive atmos- phere, oils, acids, gases, vapors, radiation etc. present during installation. 1.4 Repair work and modifi cations Repair work and modifi cations shall exclusively be carried out by the manufacturer. In case of any tampering with the device, the guaranty claim shall lapse. We reserve the right of changing the product to improve it. 1.5 Disposal The disposal of devices and components may only be realised in accordance with good professional practice observing the country-specifi c regulations. 1.6 Transport and storage Transport and store the devices exclusively in their original packaging. Do not drop devices or expose them to sub- stantial shocks. Transmitter for angular position KINAX 3W2 57-3W2 Be 997 223-10 05.17 PM1000606 000 01 Camille Bauer Metrawatt AG Aargauerstrasse 7 CH-5610 Wohlen/Switzerland Telefon +41 56 618 21 11 Telefax +41 56 618 21 21 [email protected] www.camillebauer.com Operating Instructions 2. Scope of delivery - Transmitter for angular position KINAX 3W2, acc. made to order - 3 clamps - 1 Operating instructions in German, French and English - 1 Type examination certifi cate, only with ATEX-approval 3. Application The KINAX 3W2 transmitter converts the angular position of a shaft into a load independent direct current signal, proportional to the angular position. Due to the compact design, the angular position transmitters are particularly suitable for installation in or mounting / on devices and apparatuses. Explosion-proof “Intrinsically safe Ex ia IIC T6 Gb” versions with I.S. meas uring output rounds off this series of transmitters. 4. Main features • Compact angular position transmitters for installation or mounting • Capacitive scanning system • 0/4...20mA analog output signal with 2-, 3- or 4-wire connection • Drive shaft without stops, rotating • Low starting troque • Non-wearing and low-maintenance • With explosion prevention „Ex ia IIC T6 Gb“ according to ATEX and IECEx available • With GL (Germanic Lloyd) available 5. Technical data 5.1 Measuring input Measuring ranges: 0…≥ 5 to 0… ≤ 270° Preferred range 0…10°, 0…30°, 0…60°, 0…90°, 0…180° or 0…270° Shaft-diameter ∅ 2 mm, ∅ 6 mm ans 1/4” Starting torque: max 0.001 Ncm [0.0014 oz-in] at 2 mm shaft max 0.03 Ncm [0.0425 oz-in] at 6 mm resp. 1/4” shaft Direction of rotation: selectable when ordering 5.2 Measuring output Output variable IA: Load-independent DC current, proportional to the input angle Standard ranges: 0…1 mA, 3- or 4-wire connection 0…5 mA, 3- or 4-wire connection 0…10 mA, 3- or 4-wire connection 4…20 mA, 2-wire connection or 0…20 mA, 3- or 4-wire connection adjustable with potentiometer 4…20 mA, 3- or 4-wire connection Non-standard ranges: 0…> 1.00 to 0…< 20 mA 3- or 4-wire connection DC voltage: Standard (Non-Ex): Input voltage Ui: 12...33 V Explosion protection intrinsic ia: Input voltage Ui: 12...30 V max. input current Ii: 160 mA max. input power Pi: 1 W max. internal capacitance Ci: 10 nF max. internal inductance Li: is negligible Max. residual ripple: < 0.3 % p.p.

< 3.5 ms

External resistance: Rext max. [kΩ] = H [V] – 12 V IA [mA] H = Power supply IA = Output signal end value 5.3 Accuracy Reference value: Measuring range Basic accuracy: Limit of error ≤ 0.5 % for ranges 0…≤ 150° Limit of error ≤ 1.5 % for ranges from 0…> 150 to 0…270° Reproducibility: < 0.2 % Infl uence of temperature (-40...+70 °C) [-40...+158 °F]: ± 0.2 % / 10 K 5.4 Installation Data Material: Housing: Metal (aluminium), Surface chromated Alodine 400 Mounting position: Any Admissible static loading of shaft: 5.5 Regulations Spurious radiation: En 61000-6-3 Immunity: EN 61000-6-2 Test voltage: 500 Veff, 50 Hz, 1 min. all electrical connections against housing Common-mode voltage: 100 V, 50 Hz Housing protection: IP 50 acc. to EN 60529 5.6 Environmental conditions Climatic rating: Standard version Temperature – 25 to + 70 °C [-13...158 °F] Annual mean relative humidity ≤ 90 % or Version with improved climatic rating Temperature – 40 to + 70 °C [-40...158 °F] Annual mean relative humidity ≤ 95 % Ex version Temperature – 40 to + 55 °C [-40...131° F] at T6 resp. – 40 to + 70 °C [-40...158 °F] at T5 resp. – 40 to + 75 °C [-40...167 °F] at T4 Altitude: 2000 m max. Transportation and storage temperature: – 40 to 80 °C [-40...176 °F] Vibration resistance: 5 g per 2h in 3 directions Shock resistance: 3x50 g per 10 splicing in all directions 5.7 Operation in potentially explosive environments: Gas explosion prevention: Labeling: Ex ia IIC T6 Gb Conform to standard: ATEX: EN 60079-0:2012 EN 60079-11:2012 IECEx: IEC 60079-0:2011 IEC 60079-11:2011-06 Type of protection: ia Temperature class: T6 Group according to EN 60079-0:2012: II • The operation in other explosive atmospheres is not permissible. • It is not permissible to make any alteration to equipment that is used in poten- tially explosive environments. Devices with explosion prevention must be operated in accor- dance with the stipulations of the operating instructions. The rele- vant laws, regulations and standards for the planned application must be observed. 5.8 Dimensional drawing M3 4.5 low 48 30 ±0.1 120° 7 26.1 Ø 2 Ø 20 f7 Ø 40 f7 –0.008 –0.014 1 1 6 1 [1.889] [0.177] [1.181] [1.027] [0.275] [0.078] [0.787] [1.574] [0.039] [0.039] [0.236] Fig. 1. KINAX 3W2 with standard drive shaft at front only, Ø 2 mm [0.078”], length 6 mm [0.236”]. M3 4.5 low 48 30 ±0.1 120° 7 26.1 Ø 2 Ø 20 f7 Ø 40 f7 –0.008 –0.014 1 1 12 6 1 [1.889] [0.177] [1.181] [0.275] [1.027] [0.078] [0.787] [1.574] [0.236] [0.039] [0.039] [0.472] Fig. 2. KINAX 3W2 with special drive shaft at front and at rear. At front: Ø 2 mm [0.078”], length 12 mm [0.472”]. At rear: Ø 2 mm [0.078”], length 6 mm [0.236”]. M3 4.5 low 48 30 ±0.1 120° 7 26.1 Ø6 g6 Ø 20 f7 Ø 40 f7 1 1 12 1 –0.004 –0.012 [0.039] [0.039] [0.472] [1.889] [0.177] [1.181] [0.275] [1.027] [0.787] [1.574] [0.236] Fig. 3. KINAX 3W2 with special drive shaft at front only, ∅ 6 mm [0.236”], length 12 mm [0.472”]. M3 4.5 low 48 30 ±0.1 120° 7 26.1 Ø 20 f7 Ø 40 f7 1 1 12 1 6 Ø2 Ø6 g6 –0.004 –0.012 [1.889] [0.177] [1.181] [0.039] [0.039] [0.472] [0.275] [1.027] [0.787] [1.574] [0.236] [0.236] [0.078] Fig. 4. KINAX 3W2 with special drive shaft at front and at rear. At front: ∅ 6 mm [0.236”], length 12 mm [0.472”]. At rear: ∅ 2 mm [0.078”], length 6 mm [0.236”]. M3 4.5 low 48 30 ±0.1 120° 7 26.1 Ø1/4˝ (6.35 g6) Ø 20 f7 Ø 40 f7 1 1 12 1 –0.005 –0.014 [1.889] [0.177] [1.181] [0.039] [0.039] [0.472] [0.275] [1.027] [0.787] [1.574] [0.25] Fig. 5. KINAX 3W2 with special drive shaft at front only, ∅ 1/4”, length 12 mm [0.472”]. M3 4.5 low 48 30 ±0.1 120° 7 26.1 Ø1/4˝ (6.35 g6) Ø 20 f7 Ø 40 f7 1 1 12 1 –0.005 –0.014 6 Ø2 [0.25] [1.889] [0.177] [1.181] [0.039] [0.039] [0.472] [0.275] [1.027] [0.787] [1.574] [0.236] [0.078] Fig. 6. KINAX 3W2 with special drive shaft at front and at rear. At front: ∅ 1/4”, length 12 mm [0.472”]. At rear: ∅ 2 mm [0.078”], length 6 mm [0.236”]. Sense Drive shafts dia. 2 mm 6 mm resp. 1/4” radial max. 16 N 83 N axial max. 25 N 130 N

All versions of the transmitter which differ in appearance by the type of shaft can

be mounted either directly or by means of 3 mounting clips to the item being measured. The screws are not supplied, because the required length varies ac- cording to the thickness of the mounting surface. Both methods of mounting and the relevant drilling and cut-out plans can be seen from Table. Mounting versions Drilling and cut-out diagrams for mounting transmitters) directly M3 4.5 low [0177] 20 + 0.021 + 0 30 ±0.1 120° Ø 3.2 [1.181] [0.126] [0.787] with 3 clamps 65 ±0.1 M4 120° 40 + 0.025 + 0 [1.574] [2.559] When deciding where to install the transmitter (measuring location), take care that the “Ambient conditions” given in Section “5. Technical data” are not exceeded. Make the cut-out and drill the holes in the item onto which the transmitter is to be mounted according to the corresponding drilling and cut-out diagram given in Table 1 and then fi t the transmitter. Pay attention when aligning and tightening the transmitter that the transmitter zero and the zero of the item being measured coincide. Alignment is achieved by rotating the transmitter. To facilitate alignment in the case of “direct” mounting, it is recom- mended to elongate the 3 mounting holes (diam. 3.2 mm). When using mounting clips, the clips permit the transmitter to be rotated to the correct position. The electrical zero of angular transmitters with measuring ranges 0 to … ° is marked on both the front and the back (see upper illustration). It is only marked on the front, however, in the case of angular transmitters with ranges having a V characteristic and at instruments with both senses of rotation, see lower illustration. OUT V ZERO SPAN S1 (1) (2) Front view Rear view + – (1) (2) (1) (2) (1) = Zero point mark on the housing (2) = Zero point mark on the disk of shaft 7. Electrical connections 7.1 Electrical connections via sondering posts There are 3 soldering posts (3) on the back of the transmitter for attaching the electrical connec- tions. The soldering gosts suffi ce Protection Class IP 00 according to EN 60 529. Note that, … … the data required to carry out the prescribed measurement must correspond to those marked on the nameplate of the KINAX 3W2 (Range, Output, Supply voltage)! … the total loop resistance connected to the output (receiver plus leads) does not exceed the maximum permissible value Rext.! See “Measuring output” in Section “5. Technical data” for the maximum values of Rext! … twisted cores must be use for the measured variable input and output leads and routed as far away as possible from power cables! In all other respects, observe all local regulations when selecting the type of electrical cable and installing them! In the case of “Intrinsically safe” explosion-proof versions with I.S. measuring output, the supplementary information given on the Ex approval and also local regulations applicable to electrical installations in explosion hazard areas must be taken into account! Solder the connections as shown in the corresponding wiring diagram (Fig. 7). Do not excessively heat the soldering posts (3)! Do not mechanical load the soldering posts (3)! Solder using a small pencil bit soldering iron! OUT + - OUT + - OUT + - OUT V + – Rext. Bridge – + + – OUT V + – Rext. H – + + – OUT V + – – + + – A Rext. A H A and H 2-wire connection 3-wire connection 4-wire connection (4…20 mA) (different mA-signals) (different mA-signals) A = Measuring output … … as 2-wire connection (4…20 mA, signal in output/powering circuit) … as 3- or 4-wire connection (different mA-signals) H = DC power supply H = 12…33 V resp. H = 12…30 V with Ex version Rext. = External resistance Fig. 7. Connection diagrams for 2-, 3- or 4-wire connection. 7.2 Electrical connection via wiring print with pads There are 3 pads of the transmitter for attaching the electrical connections. For Non-Ex version only. OUT + - Bridge Rext. – + + – A H OUT + - Rext. – + + – A H OUT + - Rext. + – H – + A 2-wire connection 3-wire connection 4-wire connection (4…20 mA) (different mA-signals) (different mA-signals) A = Measuring output … … as 2-wire connection (4…20 mA, signal in output/powering circuit) … as 3- or 4-wire connection (different mA-signals) H = DC power supply H = 12…33 V Rext. = External resistance Fig. 8. Connection diagrams for 2-, 3- or 4-wire connection. (3)

7.3 Electrical connection via wiring print with screw terminals

There are 4 screw terminals of the transmitter for attaching the electrical connec- tions. For Non-Ex and ATEX version only. Bridge A H 4 3 2 1 + – Rext. – + A H 4 3 2 1 + – Rext. + H 4 3 2 1 + – + – + – A + – Rext. – + + + – 2-wire connection 3-wire connection 4-wire connection (4…20 mA) (different mA-signals) (different mA-signals) A = Measuring output … … as 2-wire connection (4…20 mA, signal in output/powering circuit) … as 3- or 4-wire connection (different mA-signals) H = DC power supply H = 12…33 V resp. H = 12…30 V with Ex version Rext. = External resistance Fig. 9. Connection diagrams for 2-, 3- or 4-wire connection. 7.4 Electrical connection via wiring print with AMP-connections There are 4 AMP-connections of the transmitter for attaching the electrical con- nections. For Non-Ex version only. A H – Rext. + – OUT – + 4-wire connection (different mA-signals) A = Measuring output … … as 2-wire connection (4…20 mA, signal in output/powering circuit) … as 3- or 4-wire connection (different mA-signals) H = DC power supply H = 12…33 V Rext. = External resistance Fig. 10. Connection diagram for 4-wire connection. 7.5 Electrical connection via wiring print with trans-zorb-diode There are 3 pads of the transmitter for attaching the electrical connections. For Non-Ex version only. OUT + - Bridge Rext. – + + – A H OUT + - Rext. – + + – A H OUT + - Rext. + – H – + A 2-wire connection 3-wire connection 4-wire connection (4…20 mA) (different mA-signals) (different mA-signals) A = Measuring output … … as 2-wire connection (4…20 mA, signal in output/powering circuit) … as 3- or 4-wire connection (different mA-signals) H = DC power supply H = 12…33 V Rext. = External resistance Fig. 11. Connection diagrams for 2-, 3- or 4-wire connection. 8. Setting the beginning and end of the measuring range The coarse adjustment of the beginning of the measuring range consists in aligning the zero of the measured device with the external zero mark on the transmitter. The procedure was described in Section “6. Mounting”. This Section concerns the fi ne adjustment not only of the beginning of the range (ZERO), but also of the end of the scale (SPAN). Firstly, switch on the power supply to the transmitter. Remove the ZERO/SPAN sealing plug (4) (Fig. 12, left). Place the measured device at its zero position, i.e. the position at which the KINAX 3W2 should produce 0 mA (3- or 4-wire connection) resp. 4 mA (2-wire connection) at its output. Should the output current differ by more than 2 % from its initial value, repeat the coarse zero setting procedure described in Section “6. Mounting”. Then adjust the “ZERO” potentiometer (Fig. 12, right) using a watchmaker’s screw- driver (2.3 mm diam.) so that the desired output current fl ows. (4) Fig. 12 Adjustments «ZERO», «SPAN» and «S1». Left: Adjustments covered by the sealing plug (4) Right: Adjustments exposed. Now rotate the measured device to its opposite limite position, i.e. the position at which the KINAX 3W2 should produce the prescribed full-scale output current (see rating plate). Adjust the “SPAN” potentiometer with the screwdriver as before until precisely the prescribed full-scale output current is measured at the output. Now recheck the zero value and readjust on the ZERO potentiometer and then recheck the full-scale value. 9. Adaptation from 2-wire connection to 3- or 4-wire connection and vice versa Transmitters with the ordering code 708 – ...D (see Section “13. Specifi cation and ordering information”, number 4) are designed for either a 2-wire connection with an output range of 4…20 mA or a 3- or 4-wire connection with an output range of 0…20 mA. If, however, a transmitter be changed from one to the other (see wiring diagrams in Fig. 7, 8, 9 and 11), the beginning and end of the measuring range must be readjusted. 10. Reversing the rotation for instruments with measuring ranges > 150° A switch is provided on angular transmitters with a measuring range > 150° for reversing the direction of rotation. It is marked S1 and can be operated through the opening in the rear part of the transmitter (Fig. 12). To reverse the direction of rotation, remove the sealing plug (4) covering the switch S1. Then operate the switch by turning it a quarter of a turn with a watchmakers screwdriver (2.3 mm Ø), and reset the beginning and end of the measuring range. 11. Electric commissioning • Provide a separate power supply for the device in case of consumer loads with high interference levels. • Install the entire plant in an EMC-compatible manner. Installation environment and wiring can affect the EMC of the device. • For Versions with explosion protection: The regulations according to EN 60079-14, the equip- ment safety law, the generally acknowledged rules of the industry and these operating instructions are applicable for installation and operation. 12. Maintenance The device is free of maintenance. Repairs may only be carried out by autho- rized authorities.

13. Specifi cation and ordering information

Signifi cance of the digits 1. to 11. Description Order code 1. Version of the transmitter (with standard drive shaft at front only, Ø 2 mm, length 6 mm, see “Note” 708- Standard version 1 ATEX II 2 G Ex ia IIC T6 Gb version 2 IECEx Ex ia IIC T6 Gb version A 2. Sense of rotation Calibrated for sense of rotation clockwise 1 Calibrated for sense of rotation counterclockwise 2 V characteristic 3 Calibrated for both senses of rotation and marked 4 3. Measuring range 0 … 10° 1 0 … 30° 2 0 … 60° 3 0 … 90° 4 0 … 180° 5 0 … 270° 6 Non-standard 0 … ≥ 5 to 0 … < 270° 9 V characteristic A 4. Output signal (measuring output) / Connection mode (Power supply 12 … 33 VDC resp. 12 … 30 VDC with Ex version 0 … 1 mA / 3- or 4-wire connection A 0 … 5 mA / 3- or 4-wire connection B 0 … 10 mA / 3- or 4-wire connection C 4 … 20 mA / 2-wire connection or 0 … 20 mA / 3- or 4-wire connection D 4 … 20 mA / 3- or 4-wire connection E Non-standard / 3- or 4-wire connection 0 … > 1.00 to 0 … < 20 mA Z 5. Special features Without (order code complete) 0 With special feature 1 6. Adjustability (span adjustment) Without increased adjustability 0 Increased adjustability + 5 % / – 60 % A 7. Drive shaft special Standard 0 Dia. 2 mm [0.078”] at front, length 12 mm [0.472”], dia. 2 mm [0.078”] rear, length 6 mm [0.236”] C Dia. 6 mm [0.236”] at front, length 12 mm [0.472”] D Dia. 6 mm [0.236”] at front, length 12 mm [0.472”], dia. 2 mm [0.078”] rear, length 6 mm [0.236”] E Dia. 1/4 ˝ at front, length 12 mm [0.472”] F Dia. 1/4 ˝ at front, length 12 mm [0.472”], dia. 2 mm [0.078”] rear, length 6 mm [0.236”] G 8. Climatic rating Without improved climatic rating 0 Improved climatic rating (standard version) H Improved climatic rating (Ex/Ex i version) J 9. Marine version Without Version GL (“Germanischer Lloyd”) 0 Version GL (“Germanischer Lloyd”) L Description Order code 10. Wiring print Standard 0 Wiring print with pads, only for NEX 1 Wiring print with screw terminals, only for NEX and ATEX 2 Wiring print with AMP-connections, only for NEX 3 Wiring print with trans-zorb-diode, only for NEX 4 11. Test protocole Without test protocole 0 Protocole German D Protocole English E