CMR Electrical LD32 Manual
| Brand: | CMR Electrical |
| Category: | Measuring Instruments |
| Model: | LD32 (Manual ) |
| File Type: | |
| File Size: | — |
| Pages: | 14 |
Text of CMR Electrical LD32 Manual
CMR Electrical LD32 CMR Electrical Ltd
Bolton House
Five Chimneys Lane
Hadlow Down
East Sussex
TN22 4DX
Tel: 01825 733600
LD32
Water Leak Detection Manual
1) System Overview
2) Display and Control
3) Water Detected Alarm
4) Sensor Fault Alarm
5) Relay outputs
6)“Mute” push button
7) “Light” push button
8) “Info” push button
9) Beacon and beacon sounder
10) Fitting SCA repeat alarm or SMS / Email messaging system
11) Outstation
12) Positioning the Outstations
13) Fitting and wiring Alarm unit
14) Outstation wiring
15) RS485 data cable End of Line Resistor
16) Positioning the water detec
1) System Overview The unit has been designed to interrogate individual outstations and report back to the main controller if
water or a disconnected sensor is found. On powering up, the unit will display “SETTING UP PLEASE
WAIT” until all remote outstations have been interrogated for their current status. Providing there are no
alarms or faults on the system, the displays backlight will change to green and all zones will be shown as
“NORMAL”. Wi
2) Display and Control
Screen 1
Normal, no alarm or faults
Screen 2
Unacknowledged (new) water leak detected
Screen 3
Acknowledged water detected alarm
Screen 4
Unacknowledged (new) Cable fault
Screen 5
Acknowledged Cable fault
Screen 6
System information
3) Water Detected Alarm
When the detection cable comes into contact with water anywhere along its length, the audible warning
device will start, the New alarm and common alarm relay will operate and dis
CMR Electrical LD32 5a) Outstation common alarm relay
Each outstation has its own common alarm relay for just the zones fitted to the outstation.
Located on the top left of the outstation board (see above) use the two terminals provided. Note; this
contact is only Normally open, Close in alarm.
6)“Mute” push button
The mute button is provided to silence the audible warning device. This button will also silence the
remote sounder if fitted.
7) “Light” push button
In
10) Fitting SCA repeat alarm or SMS / Email messaging system
SCA
Terminal
No.
SMS
Terminal
No.
Cable wire colours fitted
to the messaging system
+V
DC
RED
Sig
Z1
BLUE
0V
COM
BLACK
11) Outstation
Standard outstation
Outstation with shutdown valve control
Zone water & fault
lights
One set for each zone
Terminal connection to
detection cable or sensor
one for each zone
Test push button used to
put the zone into alarm
one for each zone
RS485 data and
power c
12) Positioning the Outstations
All outstations are wall mounted using the fixing points located in each corner behind the removable front
cover. Outstations should be mounted in a position to allow accessibility to the internal components and
cables.
13) Fitting and wiring Alarm unit
Main control unit
THIS EQUIPMENT SHOULD ONLY BE CONNECTED AND WORKED ON BY A QUALIFIED
ELECTRICIAN.
To mount the unit to a wall, first remove the front cover to expose the
CMR Electrical LD32 Output Volt Free contacts for use by a Building Management System.
Function Required
Function
New alarm
Operates on each new water leak alarm or sensor fault, reset by muting
Common Alarm
Any zone in water alarm, clears with no water alarms on the system
Common Fault
Operates on disconnected sensor or power fault (See Item 5 above)
Power Fault
See Common Fault
14) Outstation wiring
The maximum cable length is dependent upon the number of fitted outstatio
Valve control Outstation
Water detection and signal cable
16) Positioning the water detection cable
The detection cable is susceptible to damage and should not be fitted to areas where the cable is likely to
be damaged or walked on unless a perforated steel cover is used. If fitting the cable around Air
Conditioning Units with humidifiers, ensure that cable is positioned at least one metre from the ACU to
stop intermittent alarms bein
17) Fitting Cable Clips
If Cable Clips are required, to protect the small sensor wires and to stop false water detected alarms from
occurring insulating tape should be first applied around the detection cable before the clip tongue is
closed. Clips should be fitted approximately every 1 to 1.5 metres apart. When using clips make sure that
the cable touches the floor between the clips, DO NOT tighten the cable so that the cable does not touch
the floor.
CMR Electrical LD32 motor open, automatic close
Voltage
230VAC
Buren
5 watt moving, <1 watt maintaining
Operation
Powered Open, capacitor reserve used to close
Controlled fluid temperature -15 to 100°C
Maximum pressure
½”
¾”
1”
1 ½”
2”
0-10 bar
0-10 bar
0-10 bar
0-10 bar
0-10 bar
WARNING, In order to shut properly, this type of valve need powering for at least 3 minutes.
Connection of Water Shutdown Solenoid Valve
PLEASE NOTE;
We don’t re