Distech Controls ECLYPSE Installation Manual

Brand: Distech Controls
Category: Controller
Model: ECLYPSE (Installation Manual)
File Type: PDF
File Size: —
Pages: 22
Text of Distech Controls ECLYPSE Installation Manual

ECLYPSE™ Connected System Controller

Figure 1: ECLYPSE Controller shown with the following Modules: ECY-PS24, ECY-S1000, ECY-RS485, and ECY-8UI6UO-HOA (front view) Product Description This document describes the hardware installation procedures for the ECLYPSE Connected System Controller. The ECLYPSE Connected System Con- troller is a modular and scalable platform that is used to control a wide range of HVAC equipment, as well as lighting and power mete

2 / 22

Device Markings (Symbols) Certain markings (symbols) can be found on the controller and are defined as follows: Symbol Description CE marking: the device conforms to the requirements of applicable EC directives. Double Insulation marking: These controllers are built using double insulation. Products must be disposed of at the end of their useful life according to local regulations. Read the Hardware Installation Guide for more information. For indoo

Distech Controls ECLYPSE 3 / 22

Module Enclosure Dimensions 3.18" 80.82 18.54 0.73 21.08 0.83 3.33" 84.47 0.4" 1.09 3.57" 90.67 Inches Millimeters Inter-Connection Gap: 0.01" 0.40 5.13" 130.29 0.06" 1.44 4.74" 120.31 0.39" 9.98 Front Back 2.31" 58.56 Figure 3: ECY-S1000 Module 4.74" 120.31 72.38 0.01" 0.40 Inter-Connection Gap: 2.61" 66.19 0.06" 1.44 0.40" 10.25 2.85" 5.20" 132.00 Front 3.18" 80.82 18.39 0.72 21.13 0.83 Inches Millimeters Back 2.31" 58.56 Figure 4: 24V Power Sup

Distech Controls ECLYPSE 4 / 22

0.06" 1.44 103.65 4.08" 5.24 133.03 4.74" 120.31 0.44" 11.13 3.83" 97.33 Front 0.01" 0.40 Inter-Connection Gap: 3.18" 80.82 18.39 0.72 21.13 0.83 Back Inches Millimeters 2.31" 58.56 Figure 5: 100 to 240 VAC Power Supply IO Modules come in the following widths. Models Width Narrow models: ECY-8UI, ECY-16DI, ECY-6UO, ECY-6UO-HOA, ECY-4UI4UO, ECY-4UI4UO-HOA, ECY-8UI6UO, ECY-8UI6UO-HOA, ECY-8UI6DOT, and ECY-8UI6DOT-HOA 3.20 inches (81.17mm) Wide models

Distech Controls ECLYPSE 5 / 22

4.74" 120.31 Front O6 O3 O1 O4 O7 O8 O5 O2 MAN AUTO OFF Inter-Connection Gap: 0.01" 0.40 5.15" 130.07 4.94" 125.32 0.06" 1.44 4.80" 121.75 Back 3.18" 80.82 18.54 0.73 21.08 0.83 Inches Millimeters 2.31" 58.56 Figure 7: IO Module: Wide Width 3.18 [80.82] 0.73 [18.54] 0.83 [21.08] Back Inches [Millimeters] 2.95 [74.99] 4.74 [120.31] 3.20 [81.17] Inter-Connection Gap: 0.01 [0.40] Front 0.06 [1.44] 5.30 [134.65] 0.51 [12.90] RX2 TX2 RX1 TX1 2.31" 58.56

6 / 22

2.95 [74.99] 4.74 [120.31] 3.20 [81.17] 2.31 [58.56] 3.18 [80.82] 0.73 [18.54] 0.83 [21.08] Inter-Connection Gap: 0.01 [0.40] Front Back Profile 0.06 [1.44] 5.30 [134.65] Inches [Millimeters] 0.51 [12.90] L2- L2- L1+ M-Bus MBUS HOST 1x POWER STATUS TX RX Figure 9: ECY-MBUS Communication Module See the ECLYPSE Selection Tool to determine the width of a specific assembly and the assembly order. Status LED, DIP Switch, and Jumper Identification and Co

7 / 22

ECY-8UI, ECY-6UO, ECY-6UO-HOA, ECY-4UI4UO, ECY-4UI4UO-HOA, ECY-8UI6UO, ECY-8UI6UO-HOA, ECY-8UI6DOT, and ECY-8UI6DOT-HOA These IO modules have the following onsite configurable DIP switches located inside the cover. Orient the circuit board as shown in the figure below. ·1 ·2 ·3 · · · UO2 UO1 UO3 ·1 ·2 ·3 · · · UO Output Option Configuration O N 1 2 3 4 5 6 7 8 UI Input Option Configuration UI2 UI1 UI3 UI4 UI5 UI6 UI7 UI8 UO Output Option

8 / 22

EOL BIAS+ BIAS- RS-485 EOL Termination Configuration Settings for DIP Switches S1 & S2 S1 Operates on Port #1 S2 Operates on Port #2 S1 S2 ON OFF RS-485 EOL Termination * Factory-default positions Internal View 1 2 3 ON OFF* Figure 12: ECY-RS485 DIP Switch Locations Mounting Instructions Each module can be mounted on a DIN rail for fast installation and easier maintenance. Each module also has two pre-molded mounting holes allowing the module to be

9 / 22

HD15 cable The ECY-PS Module Supplies Power to Modules Connected to the Right; up to the next ECY-PS Module The ECY-S1000 Module Controls all Modules Connected to the Right Electrical Enclosure ECY-PS ECY-S1000 ECY-IO ECY-IO ECY-IO ECY-PS ECY-IO ECY-IO ECY-IO ECY-RS485 When a Communications Module is used, install it immediately to the right of the ECY-S1000 before any input/output module. ECY-PS Figure 14: Assembly Order DIN Rail-Mounted Installat

Distech Controls ECLYPSE 10 / 22

Figure 17: Latches to Unlock a Module’s Front Assembly (ECY-S1000, left; ECY IO Module, right) ð For ECY IO modules: Separate the front and back base by opening and pulling the hinged gull-wing covers, thereby separating the electrical connectors between the two halves. 1 3 2 Figure 18: ECY IO Modules have Gull-wing Front Assembly 2. Once the front assembly has been removed, use the back plate’s mounting holes to mark the location of any hol

Distech Controls Controller Owners Instructions: