Guardmaster PROSAFE RPSE Series Installation Instructions
Text of Guardmaster PROSAFE RPSE Series Installation Instructions
(b) Installation Instructions
Notice d'installation
Deutch / Français
(a) Description
The Prosafe rotary key switch is a trapped key unit that isolates power when the
coded trapped key is removed. The key can only be romoved by rotating 90°
anti-clockwise which in turn changes the state of the switch contacts. Re-
insertion of the correct key and rotation 90° clockwise reverts the contacts to
the original state, and trapping the key in
(a) WIRING / VERDRAHTUNG / CÂBLAGE
All types excluding RPS 11
4 N/O shown with key free
(b)
RPS11 type
2 N/O + 2 N/C shown with key free
(c)
5
(a) OPERATION / BEDIENUNG / UTILISATION
Check for correct operation.
Ensure power is isolated when the key is free.
Upon correct installation, fixing screws should
be coated with a tamper evident varnish or
similar compound.
Key 'C' Rotated and Free, Power Off.
Key 'C' Trapped, Power On.
Adjust Position of Flip C
Deutsch / Français
Technical Specifications
Conforming to standard
EN 292, EN 1088,
IEC 947-5-1, GS-ET -19
Contacts
all types except RPS11
4 N/O
type RPS11
2 N/O + 2 N/C
Rating
IP20
Finger protection
DIN 57106/VDE 0106 T.100
Ambient temp.
-10°C to +40°C
Mechanical operations
1 x 105
Max. shear force to key
15.1kN
Max. torque to key
14Nm
Relative operating humidity
25% to 95%
Weight
0.85kg
Code barrels
Tested to 1,000,000 operations
Isolator approv
Drg No: 7200029 / Issue No: 1
REPARATUR
(t) REPAIR
RÉPARATION
If there is any malfunction or damage to the unit or key, replace
where necessary. No attempt to repair should be made. The unit or
key should be replaced before the system is reinstated.
This is to declare that the RPSE units conform with the Essential Health & Safety Requirements (EHSR's) of the European Machinery Directive (98/37/EC)
and the relevant requirements of the Low Voltage Direc