IN-COMMAND NCSP35 Troubleshooting Manual
| Brand: | IN-COMMAND |
| Category: | Control Systems |
| Model: | NCSP35 (Troubleshooting Manual) |
| File Type: | |
| File Size: | — |
| Pages: | 9 |
Text of IN-COMMAND NCSP35 Troubleshooting Manual
IN-COMMAND NCSP35 BCM Pin Values
Pin
Name
BCM Function
Note
A DMM
Tanks
1
Fresh 1Tank In
Input from Sending Unit
0-.74V = EMPTY (○○○)
.75-1.74V = 1/3 (●○○)
1.75-3.59V = 2/3 (●●○)
3.6V = FULL (●●●)
MEASURE FROM PIN 11 TO
EACH INPUT
VDC
2
Fresh 2 Tank In
Input from Sending Unit
VDC
3
Black 1 Tank In
Input from Sending Unit
VDC
4
Black 2 Tank In
Input from Sending Unit
VDC
5
Gray 1 Tank In
Input from Sending Unit
VDC
6
Gray 2 Tank In
Input from Sending
IN-COMMAND NCSP35 BCM Pin Values (Cont.)
Pin
Name
BCM Function
Note
A
DMM
Electric Motors
29
Motor 5 Retract Out
Output
Reversing Polarity DC Motor
30A
12V/GND
30
Motor 5 Extend Out
Output
Reversing Polarity DC Motor
12V/GND
31
Motor 4 Retract Out
Output
Reversing Polarity DC Motor
12V/GND
32
Motor 4 Extend Out
Output
Reversing Polarity DC Motor
12V/GND
33
Motor 3 Retract Out
Output
Reversing Polarity DC Motor
12V/GND
34
Motor 3 Extend Out
Output
Reversing Polarity DC Motor
NCSP3 Functionality Test
The Body Control Module (BCM) should be wired correctly, without
loose connections, and connected to 12 VDC at pin 42. A RED LED will
indicate that the BCM is receiving 12 VDC.
The BCM has override switches available. There is a knob and switch
that correspond to motor functions 1 – 5. The knob chooses the
motor and the switch actuates the motor to go in or out. There are
also buttons labeled AW1 In & Out and AW2 In & Out that
When testing the HVAC (Climate Function), make sure each “Zone” is
displaying a room (Zone) temperature. Use the “Mode” button to
cycle through Fan, Cool, Heat and Auto modes. (Heat and Auto
modes availability depend on the floor plan.)
Use the “Set” temperature up and down arrows to set the desired
temperature. The “Set” temperature can be adjusted between 55 to 90F.
Please review the NCSP35 User Manual for further HVAC operational
instructions. You can scan the QR code shown below or use the
following link: https://in-command.net/wp-
content/uploads/2018/08/owners-manual_ncsp35.pdf
Troubleshooting
HVAC
(Dometic Systems) If the room temp reads 100F, remove the room
sensor cover and pull the room sensor out of the holding clip. The
temp should read normally. Adjust the holding clip down on the
room sensor so tha
(RV-C) Communication issues
Make sure the CAN-Low does not have a short to +12V.
Make sure the CAN-High does not have a short to ground.
Make sure there is not a short between CAN-Low and CAN-High.
Check RV-C plugs and pins to make sure there is not a loose
connection. Try and power cycle all the components.
Make sure the RV-C connector is pinned correctly.
Try a different RV-C cable.
Press the reset button on the BCM.
No BCM
IN-COMMAND Control Systems Owners Instructions:
| Device Model | Type of Document | Pages | Size | Views | Downloads | Updated |
|---|---|---|---|---|---|---|
NCSP35CM |
#7V7ZZ9: NCSP35CM Control Systems Installation and operation manual |
47 | 482 | 78 | 26-09-2026 | |
NCSP35 |
NCSP35 (Control Systems ePDF User Manual, #GG4GKT) |
9 | 656 | 125 | 29-07-2026 | |
Lite |
PDF User Manual (@YOO49V), IN-COMMAND Lite Control Systems (30-05-2026) |
20 | 476 | 105 | 30-05-2026 | |
NCS40T |
Manual: IN-COMMAND NCS40T (E4R55M, Upd.08-09-2026) |
26 | 121 | 28 | 08-09-2026 | |
JRVCS2 |
PDF User Guide (@JT2O7A), IN-COMMAND JRVCS2 Control Systems (03-09-2026) |
36 | 1241 | 224 | 03-09-2026 |