IFM ZZ0600 Instructions For Setup

Text of IFM ZZ0600 Instructions For Setup

Fluid monitoring system - Application package

2 Contents 1 Preliminary note � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �3 1�1 Symbols used� � � � � � � � � � � � � � � � � � � � � � �
Fluid monitoring system - Application package UK 1 Preliminary note You will find detailed instructions, technical data, approvals and further information using the QR code on the individual units / packagings or at www�ifm�com� 1.1 Symbols used ► Instruction > Reaction, result […] Designation of keys, buttons or indications → Cross-reference Important note Non-compliance may result in malfunction or interference� Information Supplementary
Fluid monitoring system - Application package 4 2 Safety instructions ● The devices described are integrated into a system as components� – The manufacturer is responsible for the safety of the system� – The system manufacturer undertakes to perform a risk assessment and to create a documentation in accordance with legal and normative requirements to be provided to the operator and user of the system� This documentation must contain all necessa
Fluid monitoring system - Application package UK 5 Function 5.1 Fluid monitoring system The ZZ0600 fluid monitoring system contains the following components: ● SM6000 flow meter for monitoring and display of the flow temperature and the cooling water volumetric flow quantity� The setting of 2 switch points allows the detection of overflow (leakage / burst pipes / worn caps). ● String regulator valve to regulate the volumetric flow quantity ● TA24
Fluid monitoring system - Application package 6 2 1 ZZ0600 5 LR DEVICE + 3 4 Fig� 1: Overview application package 1: Power supply 2: AL13nn IO-Link master 3: SM6000 flow meter 4: TA2405 temperature sensor 5: ifm memory stick with LR DEVICE parameter setting software 6 Installation ► Disconnect the power of the machine before installation� ► Adhere to the instructions enclosed to the individual devices� 6.1 Fluid monitoring system ► Mount the fl
Fluid monitoring system - Application package UK ► Use 2 mounting screws and washers of size M5 for fixing�Tightening torque: 1�8 Nm� 6.3 Power supply ► Integrate the power supply into the control cabinet� The following has to be observed: – Suited for DIN rails according to EN 60715 with a height of 7�5 or 15 mm� – Align the input terminals downwards� – In case of continuous full load adhere to the following installation distance
Fluid monitoring system - Application package 8 AL1350 2 1 3 5 4 7 6 1: IoT interface to the PC with LR DEVICE 2: Not connected 3: Power supply 4: SM6000 5: TA2405 6: Not connected 7: Not connected 5 Set-up When the operating voltage has been applied, the components of the application package function according to the factory settings. The LEDs show the status of the devices and interfaces (→ Instructions of the individual components). 5.1 Install LR DEV
Fluid monitoring system - Application package UK Example: Parameter Ethernet interface (PC) IoT interface (IO-Link master) IP address 192�168�0�50 192�168�0�1 Subnet mask 255�255�255�0 255�255�255�0 Gateway address 0�0�0�0 0�0�0�0 ► Click on the symbol [ IO-LINK ] to write the changed values to the IO-Link master� > LR DEVICE reads the unit with the changed values once again� > LR DEVICE has access to the paramet
Fluid monitoring system - Application package 10 7 Operation 7.1 Monitor the process data In normal operation, LR DEVICE can display the process data of the application package graphically� In LR DEVICE: ► Click on the symbol [ IO-LINK ] to scan the network for available devices� > LR DEVICE finds the connected IO-Link master� ► In the [ONLINE] area: Click on the IO-Link master found� ► Click on the symbol [Cockpit]� > The current state and