Hanbell RC2 Series Technical Manual
Text of the manual
1. General ........................................................................................................................................ 1
2. Specifications and concept of design ...................................................................................... 1
2.1 Compressor nomenclature.............................................
HANBELL RC2 series semi-hermetic screw compressor is developed especially for applications in air-conditioning
and refrigeration. With high operating load design, each HANBELL compressor is of high efficiency and reliability in all
operating conditions such as thermal storage, heat pump system & refrigeration. Each HANBELL compressor has the
la
2.2 High Voltage compressor specifications
a. RC2-A
COMPRESSOR
MOTOR
Displacement
60 / 50Hz
Cap. Control (%)
Nominal
Hp
Voltage (V)
Hydrostatic
Pressure
Test
WEIGHT
MODEL
m3/hr
Rated
Speed
60 / 50Hz
VI
STEP
STEPLESS
Type
60Hz 50Hz
Starting
60Hz 50Hz
Insulation
Protection
kg/cm2g
kg
RC2-1090A
1310/1089
35, 50, 75, 100
35~100
247
205
1710
RC2-1280A
1535/127
2.4 Design features
HANBELL screw compressors feature simple and robust construction by elimination of some components such as
pistons, piston rings, valve plates, oil pumps which are found in reciprocating compressors. Without these components,
screw compressors run with low noise level, minimized vibration, high reliability and durability. HANBELL screw
2.5 Compression process
As shown in Figure 2 below, during the rotation of the rotors, the meshing shifts from the suction side to the discharge
side. The meshing rotors enclose a working space, which is continuously reduced as it moves in the axial direction.
This causes a V-shaped lobe space between each male and female lobes. This lobe space is maximum
Figure 3: 4-step capacity control
Note: For 4-step capacity control system, Hanbell equips
normally closed (NC) solenoid valves as standard
accessory. To equip normally open (NO) solenoid
valves, please specify it to Hanbell when placing
orders.
2.6.2 Continuous (step-less) capacity control system
In continuous (step-less) capacity control system, a norma