Arthur Grillo DPC200 Manual
Text of Arthur Grillo DPC200 Manual
Description and operating
Differential Pressure Controller DPC 200
Low pressure sensor with analog output
and PI controlling mode
Diagraphm element with differential transformer
Measuring ranges: 0...50 Pa, 0...500 Pa, 0...1000 Pa, 0...4000 Pa
Analog output 0...10 V
Controlling mode or measuring mode selectable
LCD-Display
Controlling mode with PI algori
Attention! Read this instruction carefully, before you insert connect this
item. Only qualified personal who is familar with installation, construction and operating
of the equipment should work around these sensors.
2
Application
The differential pressure controller DPC200 measures low pressure of non-aggressive gases, particulary
of
After opening the front cover, the electrical connection is made by using screw terminals.
Terminals:
1+ 2-
Excitation 10...30 Vdc
or 24 Vac (+/-15%)
3+ 4-
Output 0...10 V
5 6
floating contact input for
setpoint 1 or 2
Readjustment of the zero point
The zero point can be, regardless of the menu, readjust with a small bar
The differential pressure controller DPC 200 is designed for wall mounting.
Installation must be done vertically.
The connection of the pressure lines is performed with plastic tubing, inner diameter ø5 mm and ø6 mm.
Device is position depended, therefore it is important that the assembly is vertical.
4
Operation
Start up:
- The device must be mou
The device can use metric or imperial units.
operation mode:
In the software menu two operating modes can be set.
‘controlling mode’ and ‘measuring mode’.
parameter:
The device can use differential pressure (Pa or InH2O)
or volume flow (m3/h or cfm)
k-factor:
For volume flow calculation, a k-factor can be entered.