OIL-FIRED CAST IRON

HOT WATER INSTALLATION, OPERATION & MAINTENANCE MANUAL Maximum Allowable Working Pressure 50 psi. Models 3EWC0.80(T) 4EWC1.00(T) 4EWC1.25(T) 5EWC1.55(T) Manufactured by: ECR International Inc. 2201 Dwyer Avenue, Utica, NY 13501 Tel. 800 325 5479 www.ecrinternational.com PN 240013012 REV. B [12/15/2020] ...

Empire Water boiler is a natural draft oil fired hot water

boiler comprised of cast iron sections. Empire Water boiler is available with 3, 4, or 5 cast iron sections. These sections are held together by cast iron push nipples. Empire Water boiler is capable of firing #2 fuel oil from 0.80 gph up to 1.55 gph. All packaged boilers include a swi ...

BOILER RATINGS AND CAPACITIES

BOILER MODEL NO. Without Tankless Coil INPUT **HEATING CAPACITY *Mbh ‡NET AHRI RATING WATER *Mbh A.F.U.E. ++ NO. SEC. MINIMUM CHIMNEY SIZE/ HEIGHT DIMENSIONS (inches) +gph *Mbh A B C 3EWC0.80(T) 0.80 112 98 85 86.0 3 8” X 8” X 15” 14 ½ 6 8 4EWC1.00(T) 1.00 140 122 106 86.2 4 8” X 8” X 15” 17¾ 6 9 5⁄8 4EWC1.25 ...

Indicates a hazardous situation which, if not

avoided, could result in minor or moderate injury. ! WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury. ! DANGER Indicates a hazardous situation which, if not avoided, WILL result in death or serious injury. ! This is the safety alert ...

1. Check your local codes and utility requirements before

installation. Installation must be in accordance with their directives, or follow NFPA 31 Standard for the Installation of Oil Burning Equipment, latest revision. 2. Before servicing, allow boiler to cool. Always shut off any electricity and oil to boiler when working on it. 3. Inspect oil line and ...

Complete Prior To Installing Boiler.

A. Verify you have selected the right size boiler with proper capacity. AHRI rating of boiler selected should be greater than or equal to calculated peak heating load (heat loss) for building or area(s) served by boiler and associated hot water heating systems. See boiler rating and capacity table previously listed in t ...

OR AFTER THE

EXPANSION TANK SHUT OFF VALVE OIL FILTER OIL LINES FOUNDATIONS TO OUTSIDE LINES TO OTHER APPLIANCES SERVICE LINE OVERCURRENT PROTECTED SAFETY SWITCH ...

Installation shall comply with NFPA-31 Standard for the

Installation of Oil Burning Equipment (latest edition), and applicable provisions of local building codes to provide combustion and ventilation air. Provide enough fresh air to assure proper combustion. Fire in the boiler uses oxygen. It must have continuous supply. Air in the house contains only enou ...

B. All Air from Outdoors: Confined space shall

be provided with two permanent openings, one commencing within 12 inches of top and one commencing within 12 inches of bottom of enclosure. Openings shall communicate directly, or by ducts, with outdoors or spaces (crawl or attic) that freely communicate with outdoors. 1. When directly communicating with ...

1. Installation of boiler for new heating system,

Install all of radiation units (panels, radiators, baseboard, or tubing) and supply and return mains first. After all heating system piping and components have been installed, make final connection of system piping to boiler. It is recommended to mount circulating pump on supply side piping, such that it p ...