Comelit 48BFC000 Manual
Text of the manual
OPTICAL BEAM LINEAR SMOKE
DETECTOR WITH REFLECTOR 3-30 M
48BFC000
Please read this manual before using the equipment and keep it safe for future reference
The linear optical smoke detector consists of two parts positioned one in front of the other:
–
An “Emitter/Receiver” part (E / R),
–
A reflector consisting of 1 safety reflector.
A.2.
USAGE LIMITS
The linear smoke detector cannot be installed inside buildings.
OPTICAL BLOCK
1 fastener screws
2 built-in laser pointer
3 button
4 te
INSTALLATION OF THE ELEMENTS
The main detector installation steps are as follows:
Step
Step description
1
Securing the detector base
2
Electrical connections
3
Securing the optical block
4
Activating the laser pointer (press button)
5
Securing the reflector
6
Deactivating the laser pointer (press button)
Caution:
Leave a free area of at least 30 cm aro
A.2.6. Laser pointer
During installation, the reflector is positioned with the help of the laser pointer built into the E / R.
This pointing function is independent and does not require an external power supply.
To activate the laser pointer: press the button and hold for more than a second, then release.
To deactivate the laser pointer: press the button a
Description of the 10-pole terminal block:
Terminal reference
Description
L1+
“+” Power supply
L1-
“-” Power supply
SHLD
Shield
COM+ | Dt+
(2)
“+” remote box communication line
COM- | Dt-
(2)
“-” remote box communication line
NC
Not connected
Caution:
The type of cable to use for electrical connection depends on the unit to which it is