Bodine BSL06M5 Installation Instructions
Text of Bodine BSL06M5 Installation Instructions
SAVE THESE INSTRUCTIONS
THIS PRODUCT CONTAINS A RECHARGEABLE LITHIUM-ION BATTERY.
THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.
��������
CLASS 2 OUTPUT
Self-Testing Emergency LED Driver
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
! IMPORTANT SAFEGUARDS !
WHEN USING ELECTRICAL EQUIPMENT, BASIC
SAFETY PRECAUTIONS SHOULD ALWAYS BE
FOLLOWED,
INSTALLING THE EMERGENCY DRIVER
> Disconnect AC power from the LED luminaire.
> Mount the emergency LED driver by the mounting tabs using the supplied screws. The luminaire’s installation
instructions may provide guidance on the recommended mounting location.
> Mounting Height: Many factors infl uence emergency illumination levels, such as the
Applying AC power to the unit activates the unit to enable the emergency circuit, the charger circuit, and supplies power to
the control/monitor circuit and charging indicator light. When AC power fails, the emergency driver automatically switches
to emergency mode, keeping the LED load illuminated at a reduced lumen output for a minimum of 90 minutes. Wh
EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT
TYPICAL SCHEMATICS ONLY. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
TROUBLESHOOTING GUIDE
INDICATOR
LIGHT STATE
ERROR
CORRECTIVE ACTION
0x Flashes
Light On Steady
None
No Action. The Unit is Operating Correctly.
2x Flashes
Battery
Indicates that a self-test/self-diagnostic test di