Contax KC130TM Installation
Text of Contax KC130TM Installation
SOLAR PHOTOVOLTAIC POWER MODULES
Please read this manual carefully before installing the modules.
KYOCERA
1. INTRODUCTION
As the world leader in development and application of high technology
ceramic/silica materials, Kyocera offers a wide range of highly efficient
and reliable crystalline silicon solar photovoltaic (PV) power modules.
Kyocera began to extensively research PV technology in 1975 and
commenced manufacturing
Table 1. Recommended Tilt Angles for Fixed Systems—Based on
Winter Performance
7. INSTALLING KC MODULES
The minimum spacing of 0.6 in. (15 mm) is required between the solar
module and the mounting surface around the perimeter of the solar
module. The frame of each module has 0.28”φ diameter (7 mm) mounting
holes (Refer to Module Mounting Specifications). These are used to
secure the modules to the supporting structure. An example of a ground
moun
Figure 4. Ring or Spade Terminal Connectors
Figure 5. Installation Example of Cable Clamp
9. GROUNDING
We recommend you attach all module frames to an earth ground. Attach a
separate ground wire to one of the holes marked ‘ground’ on the module
frame with a screw and bonding or external tooth washer. This is to ensure
positive electrical contact with the frame. The racks must also be
grounded unless
Contax KC130TM Table 2. Kyocera KC Series Module Specification
NOTES
(1) Standard Test Conditions of irradiance of 1000 W/m2, spectrum of 1.5 air mass, and cell temperature of 25 deg C.
(2) Nominal Operating Cell Temperature (NOCT) of 800 W/m2, spectrum of 1.5 air mass, and cell temperature of 20 deg C.
(3) See module drawing for mounting and grounding hole locations.
Electrical Characteristics:@ STC
Model Number
KC40T
KC50T
KC65T
KC85T
KC85TS
KC125TM
KC130TM
Rated Po