BINMASTER CNCR-210 Operating Instructions Manual
Text of the manual
CNCR-210 • Two-wire 4-20
1
Operating Instructions
Radar sensor for continuous level measurement
CNCR-210
Two-wire 4-20 mA
Document ID: 925-0395 Rev B
CNCR-210 • Two-wire 4-20
2
Contents
1
About this document ............................................................................................................. 3
2
For your safety ....................................................................................................................... 3
2.1 Authorized personnel ....................................................................................................... 3
2.2 Appropriate use. ............................................................................................................... 3
2.3 Warning about incorrect use ............................................................................................ 4
3
Product description ............................................................................................................... 4
�
3.1���Configuration. ................................................................................................................... 4
3.2 Principle of operation ....................................................................................................... 5
3.3 Adjustment ....................................................................................................................... 5
4
Mounting ................................................................................................................................. 6
4.1 General instructions ......................................................................................................... 6
4.2 Mounting versions ............................................................................................................ 6
5
Connecting to power supply ................................................................................................. 9
5.1 Preparing the connection ................................................................................................. 9
5.2 Connecting ..................................................................................................................... 10
5.3 Wiring plan ..................................................................................................................... 11
6
Setup with smartphone/tablet (Bluetooth) ........................................................................ 11
6.1 Preparations ................................................................................................................... 11
6.2 Connecting ..................................................................................................................... 12
6.3 Parameter adjustment .................................................................................................... 13
7
Menu overview ..................................................................................................................... 14
8
Diagnostics and servicing .................................................................................................. 15
8.1 Maintenance .................................................................................................................. 15
8.2 Status messages ........................................................................................................... 15
9
Removal ................................................................................................................................ 17
10
Certificates and approvals .................................................................................................. 17
10.1 Radio licenses. ............................................................................................................. 17
11
Supplement .......................................................................................................................... 17
11.1 Technical data .............................................................................................................. 17
11.2 Dimensions. .................................................................................................................. 19
CNCR-210 • Two-wire 4-20
3
Information, note, tip: This symbol indicates helpful additional
information and tips.
Note: This symbol indicates notes to prevent failures, malfunctions,
damage to devices or facility.
Caution: Non-observance may result in personal injury.
Warning: Non-observance may result in serious or fatal personal injury.
Danger: Non-observance of the information marked with this symbol
results in serious or fatal personal injury.
Ex applications
This symbol indicates special instructions for Ex applications.
List
The dot set in front indicates a list with no implied sequence.
Sequence of actions
Numbers set in front indicate successive steps in a procedure.
Battery disposal
This symbol indicates special information about the disposal of
batteries and accumulators.
1
About this document
2 For your safety
2.1 Authorized personnel
All�operations�described�in�this�documentation�must�be�carried�out�only�by�trained,�qualified�
personnel authorized by the plant operator. Required personal protective equipment must always
be worn when working on or with the device.
2.2 Appropriate use
CNCR-210 is a sensor for continuous level measurement. Operational reliability is ensured only if
the�instrument�is�properly�used�according�to�the�specifications�in�the�operating�instructions.
CNCR-210 • Two-wire 4-20
4
Safety instructions for Ex areas
Take�note�of�the�Ex�specific�safety�instructions�for�Ex�applications.�These�instructions�
are attached as documents to each instrument with Ex approval and are part of the
operating instructions.
2.3 Warning about incorrect use
Inappropriate�or�incorrect�use�of�this�product�can�result�in�application-specific�hazards,�e.g.�vessel�
overfill�by�incorrect�mounting�or�adjustment.�Damage�to�property�and�persons�or�environmental
contamination can result.
3 Product Description
3.1 Configuration
Fig. 1: Components of CNCR-210
1
Radar antenna
2�
Process�fitting
3
Process seal
4
Electronics housing
5
Ventilation/pressure compensation
CNCR-210 • Two-wire 4-20
5
3.3 Adjustment
Devices with integrated Bluetooth module can be adjusted wirelessly via software adjustment tools:
• Smartphone/tablet (iOS or Android operating system)
• PC/notebook with Bluetooth USB adapter (Windows operating system)
Fig. 2: Wireless connection to standard operating devices with integrated Bluetooth LE
1
Sensor
2
Smartphone/Tablet
3
PC/Notebook
3.2 Principle of operation
CNCR-210 is a radar sensor for continuous level measurement. It is suitable for liquids and sol-
ids in practically all industries.
The instrument emits a continuous, frequency-modulated radar signal from its antenna. The emit-
ted�signal�is�reflected�by�the�material�and�received�by�the�antenna�as�an�echo�with�a�modified�
frequency. The frequency change is proportional to the distance to the material.
CNCR-210 • Two-wire 4-20
6
4.2 Mounting
The radar emits pulses of electromagmetic waves which are polarized. By adjusting the rotation of
the instrument the polarization can be changed to reduce false echoes.
The narrow portion of the radar signal is in the middle of the conduit entry on the instrument. This
should be pointed towards the center of the vessel or any obstacle that may cause any unwanted
reflections�to�minimize�false�echos,�for�example,�the�sidewall�or�vessel�structure.
4 Mounting
4.1 General instructions
The instrument is suitable for standard and extended ambient conditions according to DIN/EN/IEC/
ANSI/ISA/UL/CSA 61010-1. It can be used indoors as well as outdoors.
Protect your instrument against moisture ingress through the following measures:
• Use a suitable connection cable
�����•��Tighten�the�cable�gland�or�plug�connector�firmly
• Face the cable connection or conduit entry downward, never upward
This applies mainly to outdoor installations, in areas where high humidity is expected (e.g. through
cleaning processes) or on cooled or heated vessels.
Fig. 3: Polarization position
Cable / conduit entry
Note:
When�the�housing�is�rotated,�the�direction�of�polarization�changes�and�hence�the�influence�of�the�false�
echo on the measured value. Please keep this in mind when mounting or making changes later.
CNCR-210 • Two-wire 4-20
7
In vessels with cone bottoms, the sensor can be mounted in the center of the vessel to mea-
sure material down to the outlet.
When mounting the sensor, distance it at least 200 mm (7.874 in) from the vessel wall. If the sensor
is installed in the center of dished or round vessel tops, multiple echoes can arise. However, these
can be suppressed by a false signal suppression (see chapter “Setup”).
If you cannot maintain this distance, you should carry out a false signal suppression during initial
setup. This applies particularly if buildup on the vessel wall is expected. If this is the case, we
recommend repeating the false signal suppression later with the additional buildup.
Fig. 5: Mounting the radar sensor with conical bottom
Fig. 4: Mounting the radar sensor on round vessel tops
CNCR-210 • Two-wire 4-20
8
Do�not�mount�the�instrument�in�or�above�the�fill�stream.�Make�sure�that�it�is�pointed�towards�the
material�surface,�not�the�fill�stream.
For socket or stand pipe mount, the pipe should be as short as possible and its bottom end
rounded�to�reduce�false�reflections�from�the�end�of�the�pipe.�
When using a threaded coupling, the antenna end should protrude at least 5 mm (0.2 in) out
of the coupling.
Fig. 6: Reference plane
1 Reference plane
Fig.�7:�Mounting�the�radar�sensor�with�inflowing�material
The lower side of the radar antenna is the reference plane for the min./max. adjustment, see
following diagram:
CNCR-210 • Two-wire 4-20
9
Socket diameter d
Socket length h
40 mm
1½”
≤�150�mm
≤�5.9�in
50 mm
2”
≤�200�mm
≤�7.9�in
80 mm
3”
≤�300�mm
≤�11.8�in
100 mm
4”
≤�400�mm
≤�15.8�in
150 mm
6”
≤�600�mm
≤�23.6�in
If�the�reflective�properties�of�the�material�are�good,�you�can�mount�the�CNCR-210�on�sockets�
or stand pipes longer than the antenna. The pipe end should be smooth, burr-free and the end
rounded.
Note:
When mounting on longer sockets, we recommend carrying out a false signal suppression after
install (see chapter “Parameter adjustment”).
Recommended values for socket or stand pipe lengths and heights are in the following table. The
values come from typical applications.
Fig. 8: Mounting the radar sensor with stand pipes
5 Connecting to power supply
5.1 Preparing the connection
•��Electrical�connection�should�be�completed�by�trained,�qualified�personnel�authorized�by�
the plant operator.
• If overvoltage surges are expected, overvoltage arresters should be installed.
CNCR-210 • Two-wire 4-20
10
Warning:
Only connect or disconnect in de-energized state.
Note:
Power the instrument via an energy-limited circuit (power max. 100 W) according to IEC 61010-1,
e.g.
• Class 2 power supply unit (acc. to UL1310)
• SELV power supply unit (safety extra-low voltage) with suitable internal or external limitation
of the output current
Use�round�cable�to�ensure�effective�sealing�of�the�cable�gland�to�the�appropriate�IP�rating�and�
check�the�cable�diameter�versus�the�cable�gland�before�wiring�for�proper�fit.
The instrument is connected with standard two-wire cable.
If electromagnetic interference is expected which is above the test values of EN 61326-1 for
industrial areas, shielded cable should be used.
Note:
If the temperatures are too high, the cable insulation can be damaged.
5.2 Connecting
Fig. 9: Connection
CNCR-210 • Two-wire 4-20
11
5.3 Wiring plan
Connect the instrument as described in the following wiring plan.
Fig. 10: Connection compartment CNCR-210
1 Voltage supply +24 VDC, signal output
6
Setup with smartphone/tablet (Bluetooth)
6.1 Preparations
Make sure that your smartphone/tablet meets the following system requirements:
• Operating system: iOS 8 or newer
• Operating system: Android 5.1 or newer
• Bluetooth 4.0 LE or newer
Download�the�Wireless�Device�Configurator�app�from�the�“Apple�App�Store”�or�“Google�Play�
Store” to your smartphone or tablet. To enable the Bluetooth software enter the BinMaster
company ID code BMYQXZ.
CNCR-210 • Two-wire 4-20
12
6.2 Connecting
Start the adjustment app and select the function “Setup”. The smartphone/tablet searches
automatically for Bluetooth-capable instruments in the area.
The message “Connecting …” is displayed.
The devices found are listed and the search is automatically continued.
Select the requested instrument in the device list.
When�establishing�the�connection�for�the�first�time,�the�operating�tool�and�the�sensor�must�
authenticate�each�other.�After�the�first�correct�authentication,�each�subsequent�connection�is�
made without a new authentication query.
For�authentication,�enter�the�6-digit�Bluetooth�access�code�in�the�next�menu�window.�You�can�find�
the code on the outside of the device housing and on the setup information sheet in the device
packaging.
Note:
If an incorrect code is entered, the code can only be entered again after a delay time and the delay
gets longer after each incorrect entry.
The message “Waiting for authentication” is displayed on the smartphone/tablet.
After connection, the sensor adjustment menu is displayed on the smartphone/tablet.
If the Bluetooth connection is interrupted, e.g. due to a too large distance between the two devices,
this is displayed on the smartphone/tablet. The message disappears when the connection is restored.
Parameter adjustment of the device is only possible if the parameter protection is deactivated, which
is default. Parameter protection can be activated later if desired.
Fig. 11: Enter Bluetooth access code
CNCR-210 • Two-wire 4-20
13
6.3 Parameter adjustment
The sensor adjustment menu is divided into two areas, which are arranged next to each other or
one below the other, depending on the smartphone/tablet.
• Navigation section
• Menu item display
The selected menu item can be recognized by the color change.
Enter�the�requested�parameters�and�confirm�via�the�keyboard�or�the�editing�field.�The�settings�are�
then active in the sensor.
Close the app to terminate connection.
Note
If�the�CNCR�fails�to�connect�to�the�Wireless�Device�Configuration�App�(WDCA)�via�Bluetooth,�
close the (WDCA), power cycle the CNCR and attempt to reconnect.
If further action is required, power cycle the Bluetooth on your device, and repeat the steps above.
Fig. 12: Example of an app view - Setup sensor adjustment
CNCR-210 • Two-wire 4-20
14
Menu item
Selection
Default settings
False signal suppression
False signal suppression
0 m
Sounded distance to the material
0 m
Reset
Delivery status, basic settings
-
Menu item
Selection
Default settings
Measurement loop name
Alphanumeric characters
Sensor
Medium
Liquid
Bulk solid
Liquid
Application liquid
Storage tank, agitator tank, dosing tank, pumping
station/pump�shaft,�rain�overflow�basin,�tank/�collection�
basin, plastic tank (measurement through tank top),
mobile plastic tank (IBC), level measurement in waters,
flow�measurement�flume/over-�flow,�demonstration
Storage tank
Application bulk solid
Silo (slim and high), bunker (large
volume), stockpile (point measurement/
profile�detection),�crusher,�demonstration
Silo
(slender and high)
Units
Distance unit of the device
Temperature unit of the instrument
Distance in ft.
Temperature in °F
Adjustment
Max. adjustment (distance A) - 20mA (100%)
Min. adjustment (distance B) - 4mA (0%)
Distance from sensor
Max. adjustment 0.0 m
Min. adjustment 8.0 m
Menu item
Selection
Default settings
Damping
Integration time
0 s
Current output
Output characteristics
4 to 20 mA = 0% to 100%
Current range
Min. current 4 mA and
max. current 20.5 mA
Reaction when malfunctions occur
Failure mode < 3.6 mA
Linearization
Linearization type
Linear
Scaling
Scaling size
Scaling unit
Scaling format
0% correspond to 0 l
100% correspond
to 100 l
Display
Menu language
Displayed value
Backlight
English
Distance
On
Access protection
Bluetooth access code
-
Parameter Protection
Deactivated
Menu item
Selection
Default settings
Status
Sensor status
Measured value status
Status output
Status additional measured values
-
Echo curve
Indication of echo curve
-
7
Menu overview
CNCR-210 • Two-wire 4-20
15
Code
Text message
Cause
Rectification
F013
No measured value
available
No measured value in the boot
up phase or during operation
Check or correct installation and/
or parameter settings
Clean the antenna system
F017
Adjustment span
too small
Adjustment not within
specification
Change adjustment according to the
limit�values�(difference�between�min.�
and�max.�≥�10�mm)
F025
Error in the
linearization table
Linearization values are not
continuously rising, for example
illogical value pairs
Check linearization table
Delete table/Create new
F036
No operable software
Checksum error if software update
failed or aborted
Repeat software update
Send instrument in for repair
F040
Error in the electronics
Limit value exceeded in signal
processing
Hardware error
Restart instrument
Send instrument in for repair
F080
General software error
General software error
Restart instrument
8 Diagnostics and servicing
8.1 Maintenance
If the device is used properly, no special maintenance is required in normal operation.
In�some�applications,�buildup�on�the�antenna�system�can�influence�the�measurement.�
Depending on the sensor and application, be careful to avoid heavy soiling of the antenna
system. If necessary, clean the antenna system periodically.
8.2 Status messages
The status messages are divided into the following categories:
• Failure
• Function check
•��Out�of�specification
• Maintenance required
Failure
CNCR-210 • Two-wire 4-20
16
Code
Text message
Cause
Rectification
S600
Impermissible electronics
temperature
Temperature of the electronics out of
specified�range
Check ambient temperature
Insulate electronics
S601
Overfilling
Danger�of�vessel�overfilling
Make�sure�that�there�is�no�further�filling
Check level in the vessel
S603
Impermissible
operating voltage
Terminal voltage too low
Check terminal voltage,
increase operating voltage
Code
Text message
Cause
Rectification
C700
Simulation active
A simulation is active
Finish simulation
Wait for the automatic end after 60 mins.
Code
Text message
Cause
Rectification
F105
Determine
measured value
The instrument is still in the boot up
phase, the measured value could not
yet be determined
Wait for the end of the boot up phase
Duration up to 3 minutes depending on
the measurement environment and
parameter settings
F260
Error in the calibration
Checksum error in the calibration values
Error in the EEPROM
Send instrument for repair
F261
Error in the instrument
settings
Error during setup
False signal suppression faulty
Error when carrying out a reset
Repeat setup
Reset instrument
F265
Measurement function
disturbed
Program sequence of the
measuring function disturbed
Device restarts automatically
Code
Text message
Cause
Rectification
M500
Error in the delivery status
M501
Error in the delivery status
M504
Error at a device interface
Hardware defect
Check connections
Replace the electronics
Send instrument in for repair
Failure
Function check
Out of specification
Maintenance
CNCR-210 • Two-wire 4-20
17
9 Removal
The device is made of recyclable materials that can be disposed of by specialty recycling companies.
Observe the applicable local regulations for proper disposal.
10 Certificates and approvals
10.1 Radio licenses
Radar
The device has been tested and approved in accordance with the current edition of the applicable
country-specific�norms�or�standards.
Bluetooth
The Bluetooth radio module in the device has been tested and approved according to the current edition
of�the�applicable�country-specific�norms�or�standards.
11 Supplement
11.1 Technical data
Note for approved instruments
The technical data in the respective safety instructions which are included are valid for approved
instruments�(e.g.�with�Ex�approval).�These�data�can�differ�from�the�data�listed�herein,�for�example�
regarding the process conditions or the voltage supply.
Code
Text message
Cause
Rectification
M505
No echo available
Sensor does not detect an echo
during operation
Antenna dirty or defective
Clean the antenna
Use a more suitable antenna/sensor
Remove possible false echoes
Optimize sensor position and orientation
M507
Error in the instrument
settings
Error during setup
Error when carrying out a reset
False signal suppression faulty
Reset instrument and repeat setup
M508
Data error in program
memory Bluetooth controller
M509
Software update
M510
No communication with
the sensor
CNCR-210 • Two-wire 4-20
18
Fig. 13: Data of the input variable
1 Reference plane
2 Measured variable, max. measuring range
Materials and weights
Materials, wetted parts
–�Antenna,�process�fitting�
PVDF
– Process seal
FKM
Materials, non-wetted parts
– Housing
Plastic PBT (Polyester)
– Housing seals
O-rings (silicone)
– Cable gland
PA
– Sealing, cable gland
NBR
– Blind plug, cable gland
PA
– Weight
0.7 kg (1.543 lbs)
Torques
Max. torque mounting boss
7 Nm (5.163 lbf ft)
Max. torque for NPT cable glands and conduit tubes
10 Nm (7.376 lbf ft)
Input variable
Measured variable
The measurement range is the distance between the
antenna face of the sensor and the material surface.
The antenna face is also the reference plane for
the measurement.
Max. measuring range4)
8 m (26.25 ft)
Recommended measuring range5)
up to 5 m (16.4 ft)
CNCR-210 • Two-wire 4-20
19
Output
Output signal
4 to 20 mA
Range of the output signal
3.8 to 20.5 mA (default setting)
Signal�resolution��
0.3�μA
Resolution, digital
1 mm (0.039 in)
Fault�signal,�current�output�(adjustable)��
≤�3.6�mA,�>=21�mA,�last�valid�measured�value
Max. output current
22 mA
Load
See load resistance under Power supply
Starting�current��
≤�3.6�mA;�≤�10�mA�for�5�ms�after�switching�on
Damping (63 % of the input variable), adjustable
0 to 999 s
Ambient conditions
Ambient temperature
-40 to +60 °C (-40 to +140 °F)
Storage and transport temperature
-40 to +80 °C (-40 to +176 °F)
Process conditions
For�the�process�conditions,�please�also�note�the�specifications�on�the�printed�label.�The�lowest�value
(amount) always applies.
Process temperature
-40 to +60 °C (-40 to +140 °F)
Process pressure
-1 to 3 bar (-100 to 200 kPa/-14.5 to 43.51 psig)
Voltage supply
Operating voltage UB
– at 4 mA
12 to 35 V DC
– at 20 mA
9 to 35 V DC
Reverse voltage protection
Integrated
Electrical protective measures
Altitude above sea level
5000 m (16404 ft)
Protection class
III
Pollution degree
4
CNCR-210 • Two-wire 4-20
20
11.2 Dimensions
CNCR-210
Fig. 14: Dimensions CNCR-210
1
Thread G1½
2
Thread 1½ NPT
3
Thread R1½
CNCR-210 • Two-wire 4-20
21
All statements concerning scope of delivery, application, practical use and operating
conditions of the sensors and processing systems correspond to the information
available at the time of printing.
Subject to change without prior notice.