(4) Bypass module

(5) Power modules (6) Monitor display unit 1 Issue: 05 Part Number: 31500BBT Date: 2020-11-24 UPS5000-S-(50 kVA-300 kVA) Quick Guide (Isolation Protection) UPS Model Cabling Mode Capacity Weight Dimensions (H x W x D) UPS5000-S-200K-FM Routed in and out from the top 50 kVA, 100 kVA, ...

1. Before installation, read the user manual carefully to get familiar with product information

and safety precautions. 2. Use insulated tools during installation and operation. 3. Only Huawei engineers or engineers certified by Huawei are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage may occur, and th ...

2. Check whether the bottom of the cabinet is

horizontal by using a level. If the cabinet is not leveled, adjust the leveling feet. 1. Lower the four leveling feet at the bottom of the cabinet by using a wrench until all the four castors at the bottom hang in the air and the leveling feet bear the whole cabinet weight. 3 Connecting Cables Non-Secured Insta ...

1. Ensure the maintenance bypass switch is OFF.

Open the front door, remove the front cover, and remove covers from the top of the cabinet based on the site requirements. Connecting Cables to the UPS5000-S-200K-FM 3.2 2. (Skip this step if the mains input and bypass input share a power source.) Remove the copper bars between the mains input an ...

4. Connect battery cables and output cables.

1. Ensure the maintenance bypass switch is OFF. Open the front door, remove the front cover, and remove covers from the top of the cabinet based on the site requirements. 2. (Skip this step if the mains input and bypass input share a power source.) Remove the copper bars between the mains input and bypass input. ...

3. Connect the ground cable, power cables, and signal cable. There is no need to connect the

bypass input power cable if the mains input and bypass input share a power source. Port Description Bolt Specifications Torque Mains input M12 x 45 46N•m Bypass input M12 x 45 46N•m Battery input M12 x 45 46N•m Output M12 x 45 46N•m PE M12 x 30 46N•m sign ...

(1) Rear of modules

(2) Cabinet top (3) Wiring terminal blocks (4) Switches UPS5000-S-200K-FM UPS5000-S-300K-SMT 4 Verifying the Installation 1. Check that there is no foreign matter in the cabinet. Paper protective film Sealing putty Dustproof cover 2. After verifying the installation, reinstall all the covers. 3. (Remove the paper protective film from th ...

Download and install the Service Expert app.

After login, tap Power-on password activation on the screen. A message is displayed, indicating whether to start the UPS. Tap OK. Insert the WiFi module into the USB port on the MDU. Enable the mobile phone WLAN, search for the UPS_WIFI signal, and connect to the WiFi signal. The password is ...

To ensure system security,

change the LCD and WebUI passwords after the first login. 1. On the main menu, choose Common Functions and tap Inv. ON. 2. In the displayed login window, enter the user name and password, and tap . 3. In the displayed dialog box, tap Yes to start the inverter. Starting inverter 5.3 2. Set the language, time, date, netwo ...

Powering On Loads

5.4 1. After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears from the MDU. 2. After confirming that the battery strings are properly connected, turn on the battery string input circuit breaker. If there are multiple battery strings, turn on the circuit breaker for each battery string and then turn on t ...