5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected] EM-7802-A Rev.7 P. 1 / 10 INSTRUCTION MANUAL DC VOLTAGE/CURRENT INPUT MODULE, 4 points (DeviceNet) MODEL R7D-SV4 BEFORE USE .... Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below. If you have any problems or questions with the product, please contact M-System’s Sa ...

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected] EM-7802-A Rev.7 P. 2 / 10 COMPONENT IDENTIFICATION 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 MS X10 X1 NODE ADD. B.RATE CNFG. 1 2 3 4 5 6 7 8 10 11 12 13 2 3 4 1 15 16 17 18 7 8 9 6 14 5 NS 2 3 4 1 5 (A) Status Indicator LED (B) Node Address Setting Rotary SW (C) Baud Rate Setting Rotary SW (D) Operatin ...

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected] EM-7802-A Rev.7 P. 3 / 10 ■ INPUT RANGE • Wide span: -10 – +10V DC, -5 – +5V DC, 0 – 10V DC, 0 – 5V DC, 1 – 5V DC • Narrow span: -1 – +1V DC, 0 – 1V DC, -0.5 – +0.5V DC • Current input: -20 – +20mA DC, 0 – 20mA DC, 4 – 20mA DC ■ EXTENSION MODULE Combinations with all extension modules ar ...

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected] EM-7802-A Rev.7 P. 4 / 10 TERMINAL CONNECTIONS Connect the unit as in the diagram below. ■ EXTERNAL DIMENSIONS unit: mm (inch) 10 11 12 13 2 3 4 1 15 16 17 18 7 8 9 6 14 5 2 3 4 1 5 30 (1.18) [5 (.20)] 3 (.12) 3 (.12) 5.5 (.22) DIN RAIL 35mm wide 54 (2.13) 17 (.66) 50 (1.97) 18.5 (.73) 115 (4.53) 18–M3 SCREW TERMINA ...

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected] EM-7802-A Rev.7 P. 5 / 10 DATA ALLOCATION ‘Begin’ address is determined by the R7D’s node address and the master setting. Analog Input Module R7D-EA16 Status CH0 CH1 CH2 CH3 Begin +0 +1 +2 +3 +4 +5 Output Data Input Data None • Example 3. Analog Input Module + R7D-EA16, with Status Analog Input Module CH0 CH1 CH2 ...

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected] EM-7802-A Rev.7 P. 6 / 10 ■ STATUS Bit 0 to 7: Analog input module can show input status of each channel. Bit 8 to 10: Shows the power supply status. 0 15 Input 0 (Input range error) Input 1 (Input range error) Input 2 (Input range error) Unused Input 3 (Input range error) Input 0 (ADC error) Input 1 (ADC error) Inpu ...

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected] EM-7802-A Rev.7 P. 7 / 10 CONFORMITY WITH CE MARKING ■ CE MARKING CE marking requires to integrate safety regulations existed in each country in EU territory and to secure smooth distribution of products of which safety is guaranteed. It is mandatory by law that products distributed and sold in EU territory to have CE ...

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected] EM-7802-A Rev.7 P. 8 / 10 Use (e.g.) a shield cover when noise leaks through the opening. To external apparatus Keep the opening for cabling as small as possible. Install an electromagnetically shielded gasket when noise leaks through the opening. Shielding is strengthened by using an electro- magnetically shielded contr ...

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected] EM-7802-A Rev.7 P. 9 / 10 ■ WARNINGS AND CAUTIONS WHEN LAYING CABLES Signal cables connected to the R7D contain high-frequency components. Since these cables has the same effect as an anten- na, they emit these high-frequency components to the external space as noise or overlaps noise from the external space on themse ...

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected] EM-7802-A Rev.7 P. 10 / 10 Noise Filter Motor Drive Cable Maintain distance between cables and noise sources. Grounding in pig tail form is not effective. • Points of cautions applicable when wiring the R7D Series To external apparatus Keep the cable as short as possible. To external apparatus Shielded Cable Earth Clam ...