Burkert FieldConnect ME64 Operating Instructions Manual
Read Online
Read the Burkert FieldConnect ME64 Operating Instructions Manual online using the built-in PDF viewer.
Key Pages of Document
© Bürkert Werke GmbH & Co. KG, 2020 - 2021 Operating Instructions 2110/03_EU-EN_00815301 / Original DE ...
9.3.2 Changing user password.............................................................................................19 9.3.3 Disabling user password............ ...
at the operation site. Important safety information! ▶ ▶Carefully read these instructions. ▶ ▶Observe in particular the safety instructions, intended use and operating conditions. ▶ ▶Persons who work on the device must read and understand these instructions. 1.1 Symbols Warnin ...
from external sensors and transfers this data to external actuators or büS participants via the büS interface. ▶ ▶Use the device only as intended. Non-intended use of the device may be dangerous to people, nearby equipment and the environment. ▶ ▶Use the device only in conjunction with third-party devices and com ...
Type ME64 3 Basic safety instructions These safety instructions do not take into account any unforeseen circumstances and events which occur during installation, operation and maintenance. The operator is responsible for observing the location-spe- cific safety regulations, also with reference to personnel. General hazardous situations. To prevent injuries, observe the following: ▶ ▶Use the device only when it is in perfect ...
Sales Center Christian-Bürkert-Str. 13-17 D-74653 Ingelfingen Phone + 49 (0) 7940 - 10-91 111 Fax + 49 (0) 7940 - 10-91 448 E-mail: [email protected] International You can find the international contact addresses on the Internet at: country.burkert.com 4.2 Warranty A precondition for the warranty is that the device is used as intended in consideration o ...
external sensors and transfers this data to external actuators or büS participants via the büS interface. The module is designed for decentralised use in the process environment. It is easy to install and increases process reliability due to integrated monitoring and diagnostic functions. It can be use ...
Underneath the light blue side panel there is a switch for changing over the supply voltage from connection X03 to connection X01. Connection X03 is activated upon delivery. If the modules are only supplied by connection X01, the switch must be changed over. For further information, see section “7.3.2 Supply voltage” on page 15. English ...
6.2 Standards The applied standards, which are used to demonstrate conformity with the directives, are listed in the EU type examination certificate and/or the EU Declaration of Conformity (if applicable). 6.3 Operating conditions Note Malfunction due to heat and heavy frost ▶ ▶Do not use the devi ...
4 Frequency Max. 2.5 kHz Switching threshold VON = 10…30 V, VOFF = 0…5 V 6.6 Diagnostics Possible data 3-wire sensors 2-wire sensors Mech. limit switches Short circuit X – – Wire break – X – 6.7 Dimensions 210 65 R7 5,3 200,5 4,3 9 Langloch 7,4 18 5,3 4,3 5,8 7,4 R7,5 Figure 2: Dimensions of I/O module Type ME64 FieldConnect English ...
▶ ▶Only trained technicians may perform installation work. ▶ ▶Perform installation work using suitable tools only. 7.1 Installing the device The device will be delivered fully installed. Modifications to the device are only permitted to be carried out by Bürkert. → →Install the device on a level surface using 2 screws (M4) and 2 flat washers (accordin ...
Requirements for UL certified devices: ▶ ▶Connect devices only with a UL certified (CYJV or PVVA) cable with suitable ratings. ▶ ▶Maximum permissible temperature of the cable is 105 °C. ▶ ▶Do not lay Ethernet cables used for communication outdoors. ▶ ▶Provide galvanic isolation to separate external circuits connected to the ports from main circuits to protect against insulati ...
Function: Digital inputs A/B, supply voltage 24 V View Pin Assignment Function 3 5 1 2 4 1 24 V Supply 2 IN B Digital input channel B 3 GND Supply 4 IN A Digital input channel A 5 FE Shielding Table 3: Connections X1 to X8 7.3.2 Supply voltage Supply via A-coded connection, max. 4 A. Switch underneath the side panel needs to be changed over. Return flow is prevented by the switch underneath the side panel. T ...
Notes on planning büS networks can be found in the Guide for planning of büS networks. 7.3.5 Circuit diagram GND DI X 24 V 3 wire 2 wire Switch ME 64 ME 63 ME 63 Passiv 4 5 2 1 3 4 2 3 1 1 3 2 4 3 5 1 2 4 3 5 1 2 4 3 5 1 2 4 X01 X03 X04 CAN-H CAN-L X1 X2 X3-X8 GND FE 24V IN A IN A IN B IN B X02 24V 4 2 3 1 3 2 2 3 4 1 1 4 1 ...
Type ME64 8 Start-up with an external controller The I/O module Type ME64 FieldConnect can be used in büS networks or CANopen networks. Information on CANopen can be found at: country.burkert.com → ME64 → Downloads “User Manuals” → CANopen Network configuration In conjunction with the following Bürkert devices, the I/O module can be integrated into existing control systems: •• Fieldbus gateway Type M ...
Type ME64 9 Start-up with Bürkert Communicator The Bürkert Communicator software can be downloaded free of charge from the Bürkert website. In addition to the software, the USB-büS interface kit, available as an accessory, is required. The USB-büS interface kit can be ordered from Bürkert as an accessory (see Page 33). This chapter only describes basic use of the Bürkert Communicator. Detailed information on us ...
Type ME64 9.2 Connecting the device to the “Bürkert Communicator” The Bürkert Communicator can be connected to the device via a büS network or with the büS stick. → →Install the Bürkert Communicator on the PC. → →Use the USB-büS-interface to establish the connection between the device and the PC. Not required for the devices in a büS network. → →Start the Bürkert Communicator. → →In the men ...
Type ME64 9.3.3 Disabling user password Required user level: “Installer” Options > Password manager ... → →If necessary, enter the installer password. The Change user password window appears. → →Disable the password at the desired user level. User password Active user level during program start No user password disabled User “Advanced user” disabled Advanced user “Installer” disabled Installer 9.4 ...