COMEM DTI TEMPERATURE MONITORING UNIT DTI AND EDTI

2 Content index Safety..................................................4 DTI and eDTI........................................5 Electrical diagram................................7 Front panel description........................8 Programming of the device.................9 Modality of tripping and restore........15 Diagnostic.........................................16 Visualization of the maximum measured temperature

COMEM DTI Make sure that any person installing, taking into operation and operating the

“temperature monitoring unit DTI/eDTI”: • is technically qualified and competent. • fully comply with these assembling instructions. Improper operations or misuse could cause danger to: • life and limb • to the equipment and other assets of the operator • to the equipment proper function Opening of the device will void your warranty
TEMPERATURE MONITORING UNIT DTI AND EDTI 4 DTI and eDTI Product description The Temperature monitoring device DTI/eDTI is used in resin or dry type transfor- mers and can also be easily adapted for use in oil transformers. The DTI/eDTI uses PT100 temperature probes for a constant monitoring of tran- sformer temperatures. The device generates two intervention levels of electric signals (alarm and trip). Safety notes on the equipment operation The electrical

COMEM DTI DTI and eDTI

Connection of the temperature sensors For the connection of the sensor RTD PT100 it’s necessary to follow the indica- tion of the wiring diagram of this manual: pay attention to not invert the position between the conductors with red insulator and the conductor with white insulator. The probes type PT100 with three wires use the third wire to compensate the resistance of the conductors (max 20 Ω). If the sensor has two wires (normally wh
TEMPERATURE MONITORING UNIT DTI AND EDTI 6 Electrical diagram View rear panel of the instrument with terminals for the connections

Modbus RTU / 4-20mA

1 2 3 4 HOLD FAN SET TRIP HOT T. MAX ENTER RESET °C T3 T4 1 2 3 4 FAULT HOLD FAN SET ALARM TRIP T1 T2 HOT T. MAX ENTER RESET °C DTI 033 048 °C T3 T4 1 2 3 4 FAULT HOLD FAN SET ALARM TRIP T1 T2 HOT T. MAX ENTER RESET °C eDTI Modbus RTU / 4-20mA 033 048 Front panel description 1 2 3 4 8 9 10 10 11 7 6 5 Legend: 1. LEDs T1-T2-T3-T4 for the on-measuring channel displayed 2. T1-T2 and
TEMPERATURE MONITORING UNIT DTI AND EDTI 8 Programming of the device When the device is switched on, on the display will flash the index of the internal software: later the device starts to display the temperature read on the measured input. To enter in the programming mode, press the button SET for some second up to light the relative SET LED. The settings appear in the sequence showed after. To go out of the programming mode without changing the preset v

Selection of the number of active inputs

It is possible to select the number of activated inputs. It’s possible to choose between 3 and 4 inputs enabled; if there are 3 inputs enabled the T4 display remain off. Select 3 or 4 inputs with ← and → keys. Confirm with ENTER. Control ventilation The FAN led will switch on indicating the programming of the ventilation control. If 3 inputs are selected the following setting are available: • ventilation
TEMPERATURE MONITORING UNIT DTI AND EDTI 10 Programming of the device Selection of the threshold of switch-on and switch-off ventilation It is possible to program the threshold for enabling and disabling the ventilation. • Selection the threshold for disabling ventilation The FAN LED is on, with fixed light indicates this phase of programming. With ← and → keys select the value of temperature indicated on display. Interval of programming: from

Selection of the baud rate

This setting is indicated on displays with: • BDR on T1-T2 display • value to set on T3-T4 display. With ← and → keys select the baud rate It’s possible to choose between the following values: 2,4 - 4,8 - 9,6 - 19,2 kbps. Confirm with ENTER. Selection data bit and stop bit This setting is indicated on displays with: • the type of parity on T1-T2 display • the number of data bit and stop bit on T3-T4 display.
TEMPERATURE MONITORING UNIT DTI AND EDTI 12 Selection of the linked channel with the analogue output This setting is indicated on displays with: • AN on T1-T2 display • the linked measure channel on T3-T4 display: CH 1/2/3/4 for the 1/2/3/4 measure channel, ALL to link the measure channel with the higher temperature. With ← and → keys to select the options. Confirm with ENTER. Configuration output signal In this phase it’s possible to define

Programming of the device

Configuration diagnostic probes This function allows to enable or to disable the control on the probes. This fun- ctionality controls the variation of the temperature in a defined time. A flag raise if this variation is higher than a set value. Exit from the programming phase Press the SET key or wait for about 8 seconds without to press any key to come out of the programming phase. It’s necessary to indicate the maximum vari
TEMPERATURE MONITORING UNIT DTI AND EDTI 14 Modality of tripping and restore Alarm On the relative channel, if the threshold value set is exceeded of +1°C, after 5 seconds the ALARM relay is energized and the ALARM led is. The alarm rearm (relay de-energized and the involved LED off) occurs when the temperature goes down of 2°C respect at the threshold value set. Trip On the relative channel, if the threshold value set is exceeded of +1°, after 5 second

The device is provided of the thermic probes diagnostic function.

The condition controlled on the measured input are: • Probe PT100 interrupted: signalling on the display the message O P E (open). • Probe in short circuit: signalling on the display the message S H R (short circuit). • Probe out of order for wrong read temperature: signalling on the display the message F D C. When the device switches on the auto-diagnostic, FAULT
TEMPERATURE MONITORING UNIT DTI AND EDTI 16 Visualization of the channels with the higher temperature Test of the light signaling Exclusion of the input probes not used Visualization of the maximum measured temperature Pressing the HOT key for some seconds till switching to the HOT led. On the T1-T2 display, the hotter temperature among the inputs 1 and 2 will appear. On the T3-T4 display, the hotter temperature among the inputs 3 and 4 will appear. To com

Modality of tripping and restore

Auxiliary power supply 24/230 V dc/ac ±15% 50-60 Hz Maximum consumption 4 VA Measured inputs 3 - 4 inputs by RTD PT100 (max wire resistance 20 Ω) Interval of measure -30°C up to +200°C / precision ± 2°C Interval of visualization -30°C up to +220°C Tripped delay-hysteresis 5 seconds – 2°C Measured visualization 2 displays with led 7 segments, 3-digits Outputs DTI: 4 relay NO-C-NC (250 V 5
TEMPERATURE MONITORING UNIT DTI AND EDTI 18 Appendix A: MODBUS Address Register address Operations Description Notes Operation for monitoring 0x280 R CH1 Instantaneous Temperature [°C] 0x281 R CH2 Instantaneous Temperature [°C] 0x282 R CH3 Instantaneous Temperature [°C] 0x283 R CH4 Instantaneous Temperature [°C] 0x288 R CH1 Maximum Temperature [°C] 0x289 R CH2 Maximum Temperature [°C] 0x28A R CH3 Maximum Temperature [°C] 0x28B R CH4 Maximum Temperat
Modbus RTU / 4-20mA °C T3 T4 1 2 3 4 FAULT HOLD FAN SET ALARM TRIP T1 T2 HOT T. MAX ENTER RESET °C DTI °C T3 T4 1 2 3 4 FAULT HOLD FAN SET ALARM TRIP T1 T2 HOT T. MAX ENTER RESET °C DTI 033 048 °C T3 T4 1 2 3 4 FAULT HOLD FAN SET ALARM TRIP T1 T2 HOT T. MAX ENTER RESET °C eDTI Modbus RTU / 4-20mA 033 048