COMEM DTI Instruction Manual
Text of COMEM DTI Instruction Manual
COMEM DTI TEMPERATURE MONITORING UNIT DTI AND EDTI
2
Content index
Safety..................................................4
DTI and eDTI........................................5
Electrical diagram................................7
Front panel description........................8
Programming of the device.................9
Modality of tripping and restore........15
Diagnostic.........................................16
Visualization of the maximum
measured temperature
COMEM DTI Make sure that any person installing, taking into operation and operating the
“temperature monitoring unit DTI/eDTI”:
• is technically qualified and competent.
• fully comply with these assembling instructions.
Improper operations or misuse could cause danger to:
• life and limb
• to the equipment and other assets of the operator
• to the equipment proper function
Opening of the device will void your warranty
TEMPERATURE MONITORING UNIT DTI AND EDTI 4
DTI and eDTI
Product description
The Temperature monitoring device DTI/eDTI is used in resin or dry type transfor-
mers and can also be easily adapted for use in oil transformers.
The DTI/eDTI uses PT100 temperature probes for a constant monitoring of tran-
sformer temperatures. The device generates two intervention levels of electric
signals (alarm and trip).
Safety notes on the equipment operation
The electrical
COMEM DTI DTI and eDTI
Connection of the temperature sensors
For the connection of the sensor RTD PT100 it’s necessary to follow the indica-
tion of the wiring diagram of this manual: pay attention to not invert the position
between the conductors with red insulator and the conductor with white insulator.
The probes type PT100 with three wires use the third wire to compensate the
resistance of the conductors (max 20 Ω).
If the sensor has two wires (normally wh
TEMPERATURE MONITORING UNIT DTI AND EDTI 6
Electrical diagram
View rear panel of the instrument with terminals for the connections
Modbus RTU / 4-20mA
1
2
3
4
HOLD
FAN
SET
TRIP
HOT
T.
MAX
ENTER
RESET
°C
T3
T4
1
2
3
4
FAULT
HOLD
FAN
SET
ALARM
TRIP
T1
T2
HOT
T.
MAX
ENTER
RESET
°C
DTI
033
048
°C
T3
T4
1
2
3
4
FAULT
HOLD
FAN
SET
ALARM
TRIP
T1
T2
HOT
T.
MAX
ENTER
RESET
°C
eDTI
Modbus RTU / 4-20mA
033
048
Front panel description
1
2
3
4
8
9
10
10
11
7
6
5
Legend:
1. LEDs T1-T2-T3-T4 for the on-measuring channel displayed
2. T1-T2 and
TEMPERATURE MONITORING UNIT DTI AND EDTI 8
Programming of the device
When the device is switched on, on the display will flash the index of the internal
software: later the device starts to display the temperature read on the measured
input.
To enter in the programming mode, press the button SET for some second up to
light the relative SET LED.
The settings appear in the sequence showed after. To go out of the programming
mode without changing the preset v
Selection of the number of active inputs
It is possible to select the number of activated inputs. It’s possible to choose
between 3 and 4 inputs enabled; if there are 3 inputs enabled the T4 display
remain off.
Select 3 or 4 inputs with ← and → keys.
Confirm with ENTER.
Control ventilation
The FAN led will switch on indicating the programming of the ventilation control.
If 3 inputs are selected the following setting are available:
• ventilation
TEMPERATURE MONITORING UNIT DTI AND EDTI 10
Programming of the device
Selection of the threshold of switch-on and switch-off ventilation
It is possible to program the threshold for enabling and disabling the ventilation.
• Selection the threshold for disabling ventilation
The FAN LED is on, with fixed light indicates this phase of programming.
With ← and → keys select the value of temperature indicated on display.
Interval of programming: from
Selection of the baud rate
This setting is indicated on displays with:
• BDR on T1-T2 display
• value to set on T3-T4 display.
With ← and → keys select the baud rate
It’s possible to choose between the following values: 2,4 - 4,8 - 9,6 - 19,2 kbps.
Confirm with ENTER.
Selection data bit and stop bit
This setting is indicated on displays with:
• the type of parity on T1-T2 display
• the number of data bit and stop bit on T3-T4 display.
TEMPERATURE MONITORING UNIT DTI AND EDTI 12
Selection of the linked channel with the analogue output
This setting is indicated on displays with:
• AN on T1-T2 display
• the linked measure channel on T3-T4 display: CH 1/2/3/4 for the 1/2/3/4
measure channel, ALL to link the measure channel with the higher temperature.
With ← and → keys to select the options.
Confirm with ENTER.
Configuration output signal
In this phase it’s possible to define
Programming of the device
Configuration diagnostic probes
This function allows to enable or to disable the control on the probes. This fun-
ctionality controls the variation of the temperature in a defined time. A flag raise
if this variation is higher than a set value.
Exit from the programming phase
Press the SET key or wait for about 8 seconds without to press any key to come
out of the programming phase.
It’s necessary to indicate the maximum vari
TEMPERATURE MONITORING UNIT DTI AND EDTI 14
Modality of tripping and restore
Alarm
On the relative channel, if the threshold value set is exceeded of +1°C, after 5
seconds the ALARM relay is energized and the ALARM led is.
The alarm rearm (relay de-energized and the involved LED off) occurs when the
temperature goes down of 2°C respect at the threshold value set.
Trip
On the relative channel, if the threshold value set is exceeded of +1°, after 5
second
The device is provided of the thermic probes diagnostic function.
The condition controlled on the measured input are:
• Probe PT100 interrupted: signalling on the display the message O P E (open).
• Probe in short circuit: signalling on the display the message S H R
(short circuit).
• Probe out of order for wrong read temperature: signalling on the display the
message F D C.
When the device switches on the auto-diagnostic, FAULT
TEMPERATURE MONITORING UNIT DTI AND EDTI 16
Visualization of the channels with the higher temperature
Test of the light signaling
Exclusion of the input probes not used
Visualization of the maximum measured temperature
Pressing the HOT key for some seconds till switching to the HOT led.
On the T1-T2 display, the hotter temperature among the inputs 1 and 2 will
appear.
On the T3-T4 display, the hotter temperature among the inputs 3 and 4 will
appear.
To com
Modality of tripping and restore
Auxiliary power supply
24/230 V dc/ac ±15% 50-60 Hz
Maximum consumption
4 VA
Measured inputs
3 - 4 inputs by RTD PT100 (max wire resistance 20 Ω)
Interval of measure
-30°C up to +200°C / precision ± 2°C
Interval of visualization
-30°C up to +220°C
Tripped delay-hysteresis
5 seconds – 2°C
Measured visualization
2 displays with led 7 segments, 3-digits
Outputs
DTI: 4 relay NO-C-NC (250 V 5
TEMPERATURE MONITORING UNIT DTI AND EDTI 18
Appendix A: MODBUS Address
Register address Operations
Description
Notes
Operation for monitoring
0x280
R
CH1 Instantaneous Temperature [°C]
0x281
R
CH2 Instantaneous Temperature [°C]
0x282
R
CH3 Instantaneous Temperature [°C]
0x283
R
CH4 Instantaneous Temperature [°C]
0x288
R
CH1 Maximum Temperature [°C]
0x289
R
CH2 Maximum Temperature [°C]
0x28A
R
CH3 Maximum Temperature [°C]
0x28B
R
CH4 Maximum Temperat
Modbus RTU / 4-20mA °C
T3
T4
1
2
3
4
FAULT
HOLD
FAN
SET
ALARM
TRIP
T1
T2
HOT
T.
MAX
ENTER
RESET
°C
DTI
°C
T3
T4
1
2
3
4
FAULT
HOLD
FAN
SET
ALARM
TRIP
T1
T2
HOT
T.
MAX
ENTER
RESET
°C
DTI
033
048
°C
T3
T4
1
2
3
4
FAULT
HOLD
FAN
SET
ALARM
TRIP
T1
T2
HOT
T.
MAX
ENTER
RESET
°C
eDTI
Modbus RTU / 4-20mA
033
048