Elcomponent AEM33 P 485 Instructions
Text of the manual
AEM33 P 485
INSTRUCTIONS
This instrument is manufactured in compliance with EN61010-1
Cat III for nominal operating voltages of 400V L-L and 230V L-N,
to ensure safe operation the user must comply with the
following instructions:
Ensure that the supply voltage is correct.
The auxiliary mains supply is internally fused at 250V,
100mA Type 2. External
The AEM33 is suitable for use with current transformers (CTs)
with 5A secondary output. Metering quality CTs of Class 1
accuracy with a minimum rating of 2.5VA are recommended.
Connections should be made according to the diagrams above.
CAUTION:
The pulse output contacts are rated at 100mA AC/DC, 100V
max. Under no circumstances should this rating be excee
to select from the following displays:
CURRENT DISPLAYS
Press
to select from the following displays:
POWER DISPLAYS
Press
to select from the following displays:
NOTE: The
symbol following the VAr value = capacitive
load. A negative indicator before the VAr value indicates
exported reactive power.
NOTE: The
symbol following the PF
symbol following the Cos value =
capacitive load.
INSTRUMENT SET-UP
To enter programming mode press
and
simultaneously
for 5 seconds. The display shows the CT settings screen. The
instrument settings are entered from this point, starting with
the CT values.
CT SET-UP
The CT primary value may then be set from the following
nominal values (secon
button to stop the test.
Press
and
simultaneously to reset the counter.
Press the
key to advance the page.
RS485 SET-UP
This allows the baud rate and MODBUS address to be set. Use
the and buttons to set the desired baud rate. Press the
key to store the value and advance the page.
Use the and buttons to set the unit addre