ABB DATUM L150 8 8 8 8 8 8
A1
A2
A3
888888
DATUM
L160
Further reference for more detailed
information or technical details.
Use of Instructions
Although Warning hazards are related to personal injury, and Caution hazards are
associated with equipment or property damage, it must be understood that operation of
damaged equipment could, under certain operational conditions, result in degraded
process system performance leading to perso
INTRODUCTION ........................................................................................... 2
2
ELECTRICAL INSTALLATION .................................................................... 3
2.1
Host Computer Serial Communications ............................................... 3
2.2
OPTO22 Boards for use with Personal Computers ............................. 3
2.3
Two-wire and Four-wire Connection .................................
ABB DATUM L150 This Operating Guide describes the DATUM L150/L160 MODBUS serial data
communications option and must be used in conjunction with the standard User
Guide (IM/L150 or IM/L160) supplied with the instrument.
Information.
The MODBUS option provides the following facilities:
•
Standard RS422/485 communications.
•
MODBUS RTU protocol – for master (host computer) to slave
(DATUM L150/L160) system.
•
500V d.c. isolation from external connec
This section describes the connection of serial data transmission cables between
the master (host computer) and slave DATUM L150/L160 instruments on a
MODBUS serial link. All connections other than those used for serial
communication are shown in Section 5 of the relevant User Guide.
2.1
Host Computer Serial Communications
An RS422/485 communications driver must be fitted to the host computer. It is
strongly recommended that the
Pull-up and Pull-down Resistors – Figs. 2.1 and 2.2
To prevent false triggering of slaves when the master (host computer) is inactive,
pull-up and pull-down resistors must be fitted to the RS422/485 interface in the host
computer – see Figs. 2.1 and 2.2.
+5V
0V
1.8kΩ Pull-up
Resistor
1.8kΩ Pull-down
Resistor
Host Computer
Rx–
Rx+
Tx–
Tx+
'A'
'A
'B'
'B
GND
20
21
22
23
24
Tx+/Rx+
Tx–/Rx–
GND
+5V
0V
1.8kΩ P
Pull-up and Pull-down Resistors
Host Computer
+5V
0V
'A
'B
1.8kΩ
Pull-down
Resistor
1.8kΩ Pull-up
Resistor
0V
+5V
0V
'A
'B
1.8kΩ
Pull-down Resistor
1.8kΩ
Pull-up
Resistor
Rx+
Rx–
Tx–
Tx+
GND
20
21
22
23
24
Fig. 2.2a Four-wire Operation – L150
Fig. 2.2b Four-wire Operation – L160
Host Computer
+5V
0V
'A
'B
1.8kΩ
Pull-down
Resistor
1.8kΩ Pull-up
Resistor
0V
+5V
0V
'A
'B
1.8kΩ
Pull-down Resistor
1.8k
ABB DATUM L150 Termination Resistor – Fig. 2.3
For long transmission lines, a 120Ω termination resistor must be fitted to the last
slave in the chain – see Fig. 2.3.
First Slave
Last Slave
Tx+
Tx-
Rx+
Rx-
GND
120Ω
Termination Resistor
(External)
Master
Rx+
Rx–
Tx+
Tx–
GND
Tx+
Tx–
Rx+
Rx–
GND
Host
Computer
Fig. 2.3 Connecting Multiple Slaves
2.6
Serial Connections – Figs. 2.1 to 2.4
Information.
•
Up to 10 slaves can
ABB DATUM L150 Serial Connections – Figs. 2.1 to 2.4
Rx+
Rx–
Tx+
GND
Rx+
Rx–
Tx+
Tx–
GND
OPTO22 Adaptor
Board Connections
Screen
Tx–
8
9
4
5
3
Fig. 2.4 OPTO22 Board Connections