ABB DATUM L150 Operating Manual

Brand: ABB
Category: Measuring Instruments
Model: DATUM L150 (Operating Manual)
File Type: PDF
File Size: —
Pages: 24
Text of ABB DATUM L150 Operating Manual

ABB DATUM L150 8 8 8 8 8 8

A1 A2 A3 888888 DATUM L160

Further reference for more detailed

information or technical details. Use of Instructions Although Warning hazards are related to personal injury, and Caution hazards are associated with equipment or property damage, it must be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process system performance leading to perso

INTRODUCTION ........................................................................................... 2

2 ELECTRICAL INSTALLATION .................................................................... 3 2.1 Host Computer Serial Communications ............................................... 3 2.2 OPTO22 Boards for use with Personal Computers ............................. 3 2.3 Two-wire and Four-wire Connection .................................

ABB DATUM L150 This Operating Guide describes the DATUM L150/L160 MODBUS serial data

communications option and must be used in conjunction with the standard User Guide (IM/L150 or IM/L160) supplied with the instrument. Information. The MODBUS option provides the following facilities: • Standard RS422/485 communications. • MODBUS RTU protocol – for master (host computer) to slave (DATUM L150/L160) system. • 500V d.c. isolation from external connec

This section describes the connection of serial data transmission cables between

the master (host computer) and slave DATUM L150/L160 instruments on a MODBUS serial link. All connections other than those used for serial communication are shown in Section 5 of the relevant User Guide. 2.1 Host Computer Serial Communications An RS422/485 communications driver must be fitted to the host computer. It is strongly recommended that the

Pull-up and Pull-down Resistors – Figs. 2.1 and 2.2

To prevent false triggering of slaves when the master (host computer) is inactive, pull-up and pull-down resistors must be fitted to the RS422/485 interface in the host computer – see Figs. 2.1 and 2.2. +5V 0V 1.8kΩ Pull-up Resistor 1.8kΩ Pull-down Resistor Host Computer Rx– Rx+ Tx– Tx+ 'A' 'A 'B' 'B GND 20 21 22 23 24 Tx+/Rx+ Tx–/Rx– GND +5V 0V 1.8kΩ P

Pull-up and Pull-down Resistors

Host Computer +5V 0V 'A 'B 1.8kΩ Pull-down Resistor 1.8kΩ Pull-up Resistor 0V +5V 0V 'A 'B 1.8kΩ Pull-down Resistor 1.8kΩ Pull-up Resistor Rx+ Rx– Tx– Tx+ GND 20 21 22 23 24 Fig. 2.2a Four-wire Operation – L150 Fig. 2.2b Four-wire Operation – L160 Host Computer +5V 0V 'A 'B 1.8kΩ Pull-down Resistor 1.8kΩ Pull-up Resistor 0V +5V 0V 'A 'B 1.8kΩ Pull-down Resistor 1.8k

ABB DATUM L150 Termination Resistor – Fig. 2.3

For long transmission lines, a 120Ω termination resistor must be fitted to the last slave in the chain – see Fig. 2.3. First Slave Last Slave Tx+ Tx- Rx+ Rx- GND 120Ω Termination Resistor (External) Master Rx+ Rx– Tx+ Tx– GND Tx+ Tx– Rx+ Rx– GND Host Computer Fig. 2.3 Connecting Multiple Slaves 2.6 Serial Connections – Figs. 2.1 to 2.4 Information. • Up to 10 slaves can

ABB DATUM L150 Serial Connections – Figs. 2.1 to 2.4

Rx+ Rx– Tx+ GND Rx+ Rx– Tx+ Tx– GND OPTO22 Adaptor Board Connections Screen Tx– 8 9 4 5 3 Fig. 2.4 OPTO22 Board Connections

ABB Measuring Instruments Owners Instructions: