Danfoss VLT HVAC Instruction Manual
Text of the manual
Danfoss FC Drive LCP Display Layout
Danfoss FC drives have a total of 5 possible variables that can be set up and displayed to the user.
There are also three status message fields at the bottom of the display. These three Drive Status
fields tell you the Type of Control and Reference Site currently in use,�
Available LCP Display Variables
Operating variable
Unit
Operating variable
Unit
[0] None (No display value)
P 16‐53 Digi Pot Reference
P 0‐15 Readout: actual setup
P 16‐54 Feedback 1
Unit
P 0‐37 Display Text 1
P 16‐55 Feedback 2
Unit
P 0‐38 Display Text 2
P 16‐56 Feedback 3
Unit
P 0‐39 Display Text 3
P 1
Danfoss FC Drive LCP Bottom Line Status Messages
GROUP 1 – First (left) word: Type of Control
Operating mode
Description
Hand
The navigation keys on the LCP can be used to control the drive. Stop commands, reset,
reversing, DC brake, and other signals applied to the control terminals override local control.
Off
T
GROUP 3 – Third (right) word: Operation Status
Operation status
Description
AC brake
AC brake was selected in parameter 2‐10 Brake Function. The AC brake over‐magnetizes the
motor to achieve a controlled slow down.
AMA finish OK
Automatic motor adaptation (AMA) was carried out successfully.
AMA ready
AMA is ready
GROUP 3 – Third (right) word: Operation Status
Operation status
Description
Freeze output
The remote reference is active, which holds the present speed.
• 20 Freeze Output was selected as a function for a digital input (parameter group 5–1*
Digital Inputs). The corresponding terminal is active. Speed control is
GROUP 3 – Third (right) word: Operation Status
Operation status
Description
Ramping
The motor is accelerating/decelerating using the active ramp up/down. The reference, a limit
value, or a standstill is not yet reached.
Ref. high
The sum of all active references is above the reference limit set in parameter 4‐55�