Altronix SMP10 Installation Manual
Text of Altronix SMP10 Installation Manual
* Specified at 25˚C ambient.
Voltage Output/Transformer Selection Table:
Voltage
Switch Position
Transformer
12VDC @ 10A
ON
24VAC or 28VAC / 175VA (Altronix model T2428175)
24VDC @ 6A
OFF
28VAC / 175VA (Altronix model T2428175)
24VDC @ 10A
OFF
28VAC / 300VA (Altronix model T2428300)
Installation Instructions:
SMP10 should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount SMP10 in the desired locati
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery is supplying power.
OFF
ON
No DC output. Short circuit or thermal overload condition.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
Terminal
Function/Description
AC/AC
Low voltage AC input (Voltage Output/Transformer Selection Table).
For 12VDC output use 28VAC or higher with 175VA po