Compact Electric CDMR-61 Operation & User’s Manual
Text of the manual
DIGITAL LINE MONITORING RELAY
CDMR-61
User Manual
Specifications ..................................................... 2-3
Terminals and Wiring-Diagram (Fig.1) ............... 3
Configuration of the CDMR-61 and
information about monitoring function details ....
4-5
Change of setting values ................................... 6
Assignment and negation of
Line Monitoring Relay CDMR-61 / User Manual
Page 2
Specifications
(other specifications on request)
Line Voltage Inputs:
Rated voltage Un ..................
: a) 3x 400V/230VAC b) 3x 100-110V / 58-64VAC
Measuring range ...................... :
1,3 Un
Overload capability ...............
:
2 Un (100% d
Line Monitoring Relay CDMR-61 / User Manual
Page 3
L1
L2
L3
N
L1 L2 L3 N B HP HN
Star-type system (4-wire mains) connecting diagram
EMC-Note: Wire length from terminal "B" to relay contact shall be less than 3m.
CDMR-61
L1
L2
L3
L1 L2 L3 N B HP HN
Delta system (3-wire mains) connecting diagram
CDMR-61
C
Line Monitoring Relay CDMR-61 / User Manual
Page 4
Introduction:
The CDMR-61 is a digital line monitoring relay based on a new generation microcontroller. It provides 13 monitoring
functions listed below with identification symbols.
U< ... undervoltage stage 1
f< ...
underfrequency stage 1
Vs> ...vector surge
U<< ... undervoltage stage 2
Line Monitoring Relay CDMR-61 / User Manual
Page 5
Attention: Operating in parallel with system requires undervoltage limits >= 70% Un (rated voltage) of at least
one undervoltage function, because frequency and vector surge functions are inhibited,
if all 3 voltages drop below 70% of Un.
Trip logic selection
Line Monitoring Relay CDMR-61 / User Manual
Page 6
Refer to fig.3 and fig.4 for additional information.
Undervoltage U<
Stufe1 K_2___<-
1. Starting from the standard line measuring values menue step through the main-menue
level with the keys ↓ or ↑ to the main menue of the desired function (e.g. U<).
2. Branch to the detailed-menue chain with
Line Monitoring Relay CDMR-61 / User Manual
Page 7
access to the change mode. The security code can be modified in the menue "General Settings \ Security code". Subse-
quent changing of the code is possible, but also in this case the active code has to be entered to get the permission for
changing.
Supply voltage
Usually a buffered DC voltage is use
Line Monitoring Relay CDMR-61 / User Manual
Page 8
2 ............
Blocking of all 13 monitoring functions. If blocking is released and a line fault present, tripping
is performed after the time delay programmed for the corresponding monitoring function.
.
Self-monitoring
The relay has a self-monitoring program for error detection in the data memory (