AC CIRCUIT BREAKER TEST SET

OPERATOR’S MANUAL Version 3.1 MODEL HC-75C (480V) SERIAL NUMBER: Phenix Technologies, Inc. 75 Speicher Drive Accident, MD 21520 USA Copyright © Phenix Technologies, Inc. Rev 1/18/2018 jsh ...

AC CIRCUIT BREAKER TEST SET

Model Number HC 75C Serial Number Customer Customer's Purchase Order Number Manufacturing Date ...

TABLE OF CONTENTS

SECTION NUMBER TITLE PAGE DANGER / GENERAL SAFETY PRECAUTIONS 1 SPECIFICATIONS 2 INTRODUCTION 3 SAFETY 4 INSTALLATION INSTRUCTIONS 5 POWER ON / OFF PROCEDURE 6 POWER SECTION DESCRIPTION 7 TESTING PROCEDURE 8 TROUBLESHOOTING 9 SERVICE AND MAINTENANCE 10 CALIBRATION OF CIRCUIT BREAKER TEST SETS 11 WinHC PC SOFTWARE 12 ELECTRICAL SCHEMA ...

SECTION 1: DANGER / WARNINGS

WARNING !! Complete Grounding of this unit is necessary for the safe operation of this equipment. Disconnect inputs before ungrounding this equipment. ...

GENERAL SAFETY PRECAUTIONS

HIGH VOLTAGE / CURRENT This equipment is capable of providing POTENTIALLY LETHAL VOLTAGES! Improper operation or test practices may result in injury or death to the operator or surrounding personnel. The operation of High Voltage test equipment should only be performed by personnel familiar with HIGH VOLTAGE testing and ...

SECTION 2: SPECIFICATIONS

Input: 480 VAC, 60 Hz, 400 AAC (Note: The above current levels are based on the 30 minute duty cycle. To estimate the current draw on the facility power at different duty cycles, multiply the above currents by the ratio of the output currents. Ex.: An HC-75C will draw approximately 7.5 times the above current at the 1 se ...

0.1% of Full Scale

Ranges: 100/1000/10,000/100,000 Amps Accuracy: 0.8% rdg + 0.3% range ± 5% of Full Scale 0.02 – 0.10 Seconds Timer: Resolution: 0.002 Seconds 0.120 Cycles Ranges: 0 - 999.999 Seconds 0 - 99,999.990 Cycles Test durations of less than 10 cycles Timer Accuracy: ± 0.004 S ...

SECTION 3: INTRODUCTION

Phenix Technologies' High Current Test Sets represent a new era of electrical testing technology. This design is based on time-proven concepts and the power offered by an embedded 32-bit microcomputer. High reliability Semiconductor Controlled Rectifiers (SCRs) have been combined with a phase angle firing system to delive ...

SECTION 4: SAFETY

Several safeguards have been built into the Phenix Technologies high current test sets; however, these safeguards are only effective if safe work practices are also used. The test set and these procedures have been designed for use by knowledgeable electrical workers who have been properly trained in its use. Please note the fo ...

SECTION 5: INSTALLATION INSTRUCTIONS

1. Position the test set in the desired position. For 2-cabinet units, place the regulator cabinet on top of the transformer cabinet. The following procedure is only required for 2-cabinet units (HC-12C and HC-20C): a. Connect the interconnect ground cable from the regulator cabinet to the transformer cabinet. ...