Thermia WT-C Installation Manual

File Specifications

Brand: Thermia
Category: Water Heater
Model: WT-C (Installation Manual), prhIpqC1AgjzA
File Type: PDF
File Size: —
Pages: 16 pages

Download Document

Get a high-quality, printable PDF version of this manual for offline use.

Download PDF Manual (16 pages)

⚠️ Download Safety: This PDF is completely safe to download (last scan date: 29/05/2026).

Read Online

Read the Thermia WT-C Installation Manual online using the built-in PDF viewer.

Key Pages of Document

Thermia AB is not liable or bound by warranty if these instructions

are not adhered to during installation or service. The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive 2006/42/EC) © Copyright Thermia AB ...

Table of Contents

1 Getting started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.1 Getting started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2 Model specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

The accumulator tank should stand on a solid surface and be leveled with assistance from the setscrews underneath the tank (not fitted

on all models). The tank models that come without setscrews can be leveled with assistance of a shim. This must be done before the tank is connected to the pipes and filled with water. See picture below for adjusting the setscrews. Connections not in use must be plugged app ...

Corrosion protection, coil

- copper copper Storage volume V litres 473 721 Volume, coil litres 4x3,5 6x3,5 Length, coil litres 4x12 6x12 Max. pressure, hot water heater bar 3 Max. pressure, coil bar 10 Max. immersion heater length mm 670 850 Net weight kg 161 191 Immersion heater max. output kW 9 2x9 Standing loss S W 101 127 Energy efficiency class - C Dimensions WT-V Unit 500 750 Height (in ...

1 Expansion/venting (DN25)

2 Connections (DN50, x8) 3 Temperature sensor (DN20, x3) 4 Immersion heater (DN50) 5 Tap water coil (2x12m, Ø22mm) 6 Preheat coil/tap water (2x12m, Ø22mm) Technical data Storage volume V 473 litres Test pressure 4,3 bar Working pressure 3 bar Rated temperature 100 °C Weight 161 kg Standing loss S 101 W Energy efficiency class C Dimens ...

1 Expansion/Venting (DN25)

2 Heat source (DN50, x8) 3 Tap water coil (3x12m, Ø22) 4 Temperature sensor (DN20, x3) 5 Immersion heater (DN50) 6 Preheat coil/Tap water(3x12m, Ø22) Technical data Storage volume V 721 litres Test pressure 4,3 bar Working pressure 3 bar Rated temperature 100 °C Weight 191 kg Standing loss S 127 W Energy efficiency class C ...

WT-C FC (Front Connection)

Technical data WT-C FC Unit 500 FC (3Bar) 500 FC (6Bar) 750 FC (3Bar) 750 FC (6Bar) 1000 FC (3Bar) 1000 FC (6Bar) Total volume litres 477 503 721 676 971 907 Storage volume V litres 466 492 704,5 659,5 949 885 Total coil volume litres 11 11 16,5 16,5 22 22 Coil length m 4x12 4x12 6x12 6x12 8x12 8x12 Coil surface (per coil) m2 3 Working pressure Bar 3 6 3 6 3 6 Test pressure Bar 4,3 8,6 4,3 8,6 4,3 8,6 Max pressure, coil Bar 1 ...

WT-C 500 FC (3 bar)

Connections 1765 1738 1505 1400 1290 1005 905 525 410 285 205 175 1 2 5 4 3 ø840 ø640 0 865 805 8 6 7 1 Venting (DN32) 2 Heat source (DN50, x4) 3 Tap water coil (2x12m, Ø22mm) 4 Temperature sensor (DN20, x2) 5 Heat source (DN32) 6 Heat source/Immersion heater (DN50) 7 Preheat coil/Tap water (2x12m, Ø22mm) 8 Drain tap/Temperature sensor (DN20) Technical data Total volume 477 litres Storage volume V 466 litres Total coil volume ...

WT-C 500 FC (6 bar)

Connections 1 2 6 4 3 7 5 ø840 ø650 8 1 Venting (DN32) 2 Heat source (DN50, x4) 3 Tap water coil (2x12m, Ø22mm) 4 Temperature sensor (DN20, x2) 5 Heat source (DN32) 6 Heat source/Immersion heater (DN50) 7 Preheat coil/Tap water (2x12m, Ø22mm) 8 Drain tap/Temperature sensor (DN20) Technical data Total volume 503 litres Storage volume V 492 litres Total coil volume 11 litres Coil surface (per coil) 3 m2 Working pressure 6 bar Te ...

WT-C 750 FC (3 bar)

Connections 1830 1804 1535 1430 1320 1175 1035 685 440 315 235 205 1 2 5 4 3 6 7 8 Ø960 Ø780 0 935 835 1 Venting (DN32) 2 Heat source (DN50, x4) 3 Tap water coil (3x12m, Ø22mm) 4 Temperature sensor (DN20, x2) 5 Heat source (DN32) 6 Heat source/Immersion heater (DN50) 7 Preheat coil/Tap water (3x12m, Ø22mm) 8 Drain tap/Temperature sensor (DN20) Technical data Total volume 721 litres Storage volume V 704,5 litres Total coil volu ...

WT-C 750 FC (6 bar)

Connections 1837 1812 1531 1501 1396 1286 1184 1081 731 486 361 251 231 1 2 5 4 3 6 7 8 Ø950 Ø750 0 931 831 1 Venting (DN32) 2 Heat source (DN50, x4) 3 Tap water coil (3x12m, Ø22mm) 4 Temperature sensor (DN20, x2) 5 Heat source (DN32) 6 Heat source/Immersion heater (DN50) 7 Preheat coil/Tap water (3x12m, Ø22mm) 8 Drain tap/Temperature sensor (DN20) Technical data Total volume 676 litres Storage volume V 659,5 litres Total coil ...

WT-C 1000 FC (3 bar)

Connections 1927 1565 1065 715 470 345 235 265 0 2 4 5 6 8 3 1205 1350 1460 865 965 1 Ø890 Ø1090 7 1 Venting (DN32) 2 Heat source (DN50, x4) 3 Tap water coil (4x12m, Ø22mm) 4 Temperature sensor (DN20, x2) 5 Heat source (DN32) 6 Heat source/Immersion heater (DN50) 7 Preheat coil/Tap water (4x12m, Ø22mm) 8 Drain tap/Temperature sensor (DN20) Technical data Total volume 971 litres Storage volume V 949 litres Total coil volume 22 ...

WT-C 1000 FC (6 bar)

Connections 1900 1570 1875 1222 1120 770 525 400 270 290 0 2 4 5 6 8 3 1325 1435 1540 870 970 1 Ø850 Ø1050 7 1 Venting (DN32) 2 Heat source (DN50, x4) 3 Tap water coil (4x12m, Ø22mm) 4 Temperature sensor (DN20, x2) 5 Heat source (DN32) 6 Heat source/Immersion heater (DN50) 7 Preheat coil/Tap water (4x12m, Ø22mm) 8 Drain tap/Temperature sensor (DN20) Technical data Total volume 907 litres Storage volume V 885 litres Total coil ...

WT-C Accumulator tanks

Thermia AB Box 950 SE 671 29 ARVIKA Phone +46 570 81300 E-mail: [email protected] Internet: www.thermia.com Thermia can accept no responsibility for possible errors in catalogues, brochures and other printed material. Thermia reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary ...