MTS Systems MAXPLUS 231 Manual 

Text of MTS Systems MAXPLUS 231 Manual 

M AX P L U S 2 3 1 O P T I O N S P I N D L E AM P L I F I E R

Application This manual is designed to help you install the MaxPlus™ 231 Option Spindle amplifier. Unpacking and Inspection Carefully unpack the amplifier and inspect it for visible damage. Check items against the packing list. Report any missing or damaged items to your supplier. Warranty and Service The amplifier is warranted to be free from defects in workmanship and materials for a p

Warranty and Service (continued)

Service Under Warranty • Return your defective unit, freight prepaid, and it will be repaired and returned within two weeks of receipt via regular UPS, freight prepaid. • Upon request, a factory-repaired replacement unit will be sent via regular prepaid UPS, within 4 working days. Next day shipment for overnight delivery, freight collect, is available at an expediting charge of $100. The defective unit is to be return

The 231 Spindle Amplifier was designed to be used with the MPM1094R-1092 spindle motor.

This motor is wound in a WYE configuration with four windings in each leg of the WYE that are connected with a system of relay switches mounted on the side of the motor that change the motor KE and KT. This allows up to 20 horsepower in four speed ranges, eliminating the need for any complex mechanical gear reductions. The TAC output of the amplifier is s

0 to 45°C (32 to 113°F) Maximum, Ambient

0 to 95% noncondensing Input/Output Interface: Analog Signals Velocity Command Input Velocity Output Current Output Differential input 0 to ±10 Vdc(15 Vdc Max) 1 volt per 1000 rpm 10 volts = Rated Current 24 Volt Logic: Enable Speed Shift Ramps Orient Slow Output (open collector) Fault Output (open collector) Note: +30 volts op

MPA-80-231-SPINDLE Mechanical Footprint

.5 RECOMMENDED D SIDE VIEW C B A 1.0" .31 NOTE 13.6 14.6 FRONT VIEW Summary of Amplifier Dimensions MODEL A in. B in. C in. D in. MPA-80-231 8.5 6.5 1.3 10.63 NOTE If front cover is attached, additional clearance of .2 should be allowed.

6 Signal/Wiring Overview AUX SIG RESP CUR BAL RESET FEEDBACK SHLD SHLD GND GND GND GND REF COS TS SIN CONTINUOUS LIMIT RESET HI-BUS MOTOR FEEDBACK AMPLIFIER SHORTS CURRENT MARK ENCODER POWER I/O GND ORIENT RAMPS GND -COM +COM CUR TAC GND FLT SHFT SLOW SPD ENB

2KHZ 20-25 VP-P

SIN/COS 0-5V MAX RMS FEEDBACK SHLD SHLD GND GND GND GND REF COS TS SIN CONTINUOUS LIMIT RESET HI-BUS MOTOR FEEDBACK AMPLIFIER SHORTS CURRENT MARK SIN REF MOTOR J2 120 VAC L1 L2 LOW SPD 1 SPD 2 SPD 3 HIGH SPD 4 J1 REF REF GND COS COS GND SIN SIN GND THERM THERM SHIELD R E S O L V E R MOTOR PC CARD S P E E D S E L NOTE 100% shielded cable is foil and

This is an output that comes ON at the resolver zero

position and can be used in conjunction with alignment procedures. The zero position is about .5 degrees. CURRENT(BI-COLOR) This is a bi-colored LED that produces either red or green as a function of load. The intensity increases with load. Red indicates positive torque and green indicates negative torque. There are seven faults that will reduce amplif

Simulated Encoder Signals

For external counting or position control, a 9-pin D type female connector that has TTL differential outputs is provided. This simulates quadrature encoder channel A and channel B signals. A differential mark signal is also available. 1 6 2 7 3 8 4 9 5 A\ A B B\ M M\ GND EXTERNAL CONTROLLER SIGNALS AND GND ENCODER SIMULATION CONNECTOR P1 TYPICAL ENCODER CABLE COMMENTS: 1) THE AMPLIFIER OUTPUTS ARE RS422 DIFFERENTIAL LINE DRIVE

I/O Wiring and Descriptions

The amplifier has five inputs and two outputs. These inputs and outputs are designed to interface to a 24 volt logic system. The amplifier is shipped so that the operation of the inputs is as follows. With no wires connected to ENB, SPD, or SHFT, the amplifier is not enabled and normal operation will not occur. The inputs are activated by connecting them with a switch closure to any of the provided GND terminals. J2 120 VA

Ramps are enabled by default. Grounding PIN 12 (ramps) disables ramping. Grounding PIN

13 (orient) causes the motor shaft to rotate at 1 rps. There is a connector for control purposes inside the motor. The four possible speed ranges are identified as LOW 1, 2, 3, and HI 4. The user has to devise the logic as to how to operate the relays based on the amplifier control inputs. There are two outputs, Fault and Slow. These are open collector (NPN 2N7053)

Analog Inputs, Outputs, and Adjustments

Inputs There is one analog input channel for the command input. This is a differential input and it is summed with a TAC feedback amplifier that controls velocity. AUX SIG RESP CUR BAL RESET ENCODER I/O GND ORIENT RAMPS GND -COM +COM CUR TAC GND FLT SHFT SLOW SPD ENB } ANALOG INPUT WIRING EXAMPLE GND –COMMAND SIGNAL +COMMAND SIGNAL CURRENT TAC GND Normal operation of the command signal is to apply a + voltage

The location of these adjustments is directly below the I/O wiring.

NOTE The pot labeled AUX controls the speed of the spindle orient feature and need not be adjusted by the user. FEEDBACK AND I/O CONTROL ASSEMBLY AUX SIG RESP CUR BAL RESET ENCODER I/O GND ORIENT RAMPS GND -COM +COM CUR TAC GND FLT SHFT SLOW SPD ENB Outputs Two diagnostic outputs are the dc voltage proportional to velocity and the dc output proportional to current/torque. The nominal T

Analog Inputs (Specific Interface Requirements)

The analog input channel is a differential input amplifier to allow controllers that have differential output drivers a three wire connection that excludes potential ground loops. When differential modes of operation are used, the command input is based on 5 volts equaling maximum input and the analog ground from the external controller must be connected to the MPA drives GND connection. A +5 volt connec

1 2 3 4

JP4 JP9 JP11 JP3 JP19 JP3 BI-POLAR ABSOLUTE (STANDARD) The position of this jumper determines the kind of dc voltage proportional to current that is a diagnostic signal at the (CUR) output of the I/O connector. With the shorting pin in the bipolar position, the output CUR signal is plus for positive current and minus for negative current. The voltage range is pl

SPINDLE ORIENT ENABLE

disabled enabled (STANDARD) The position of this jumper determines whether the shaft will turn at 1 rps when PIN 13 is grounded. JP11 ORIENT DIRECTION CW (viewed from shaft end) CCW (STANDARD) The position of this jumper determines which direction the motor will turn when the orient feature is enabled. JP9 RESETABLE FAULTS (STANDARD) NON RESETABLE FAULTS When JP9 is in the left position (default) the amplifier must be power cy

AC Input and Internal Protection

A branch circuit disconnect must be provided in front of the amplifier. Model Three Phase Power MPA-80-231 60 amps 80-260 Vac AC power wiring must be consistent with any local codes, national electric codes, and be able to withstand the voltage current ratings applied. A (ground) terminal is supplied and should be connected to earth ground. Internal Protection These amplifiers have internal AC Input fuses and a shunt f

The ac supply source for the amplifier is supposed to be bonded to earth ground.

Typical WYE Secondary L1 (HOT) L2 (HOT) L3 (HOT) GND EARTH GROUND Typical Delta Secondary EARTH GROUND L2 (HOT) GND L1 (HOT) L3 (HOT) These are the two most typical transformer configurations and failure to ground these properly could void warranty. These are 230 Vac.

There are too many transformers to depict all combinations. The MPA amplifier does not care

where the earth ground is. This example is a delta secondary. Delta Secondary L2 (NEUTRAL) GND L1 (HOT) L3 (HOT) EARTH GROUND In this example, L2 became ground.

MTS Systems Amplifier Owners Instructions: