MTS Systems MAXPLUS 231 Manual
Text of MTS Systems MAXPLUS 231 Manual
M AX P L U S 2 3 1 O P T I O N S P I N D L E AM P L I F I E R
Application
This manual is designed to help you install the MaxPlus™ 231 Option Spindle amplifier.
Unpacking and Inspection
Carefully unpack the amplifier and inspect it for visible damage. Check items against the
packing list. Report any missing or damaged items to your supplier.
Warranty and Service
The amplifier is warranted to be free from defects in workmanship and materials for a p
Warranty and Service (continued)
Service Under Warranty
•
Return your defective unit, freight prepaid, and it will be repaired and returned within two weeks of
receipt via regular UPS, freight prepaid.
•
Upon request, a factory-repaired replacement unit will be sent via regular prepaid UPS, within 4
working days. Next day shipment for overnight delivery, freight collect, is available at an expediting
charge of $100. The defective unit is to be return
The 231 Spindle Amplifier was designed to be used with the MPM1094R-1092 spindle motor.
This motor is wound in a WYE configuration with four windings in each leg of the WYE that are
connected with a system of relay switches mounted on the side of the motor that change the
motor KE and KT. This allows up to 20 horsepower in four speed ranges, eliminating the need
for any complex mechanical gear reductions.
The TAC output of the amplifier is s
0 to 45°C (32 to 113°F) Maximum, Ambient
0 to 95% noncondensing
Input/Output Interface: Analog Signals
Velocity Command Input
Velocity Output
Current Output
Differential input 0 to ±10 Vdc(15 Vdc Max)
1 volt per 1000 rpm
10 volts = Rated Current
24 Volt Logic:
Enable
Speed
Shift
Ramps
Orient
Slow Output (open collector)
Fault Output (open collector)
Note: +30 volts op
MPA-80-231-SPINDLE Mechanical Footprint
.5 RECOMMENDED
D
SIDE VIEW
C
B
A
1.0"
.31
NOTE
13.6
14.6
FRONT VIEW
Summary of Amplifier Dimensions
MODEL
A in.
B in.
C in.
D in.
MPA-80-231
8.5
6.5
1.3
10.63
NOTE
If front cover is attached, additional
clearance of .2 should be allowed.
2KHZ 20-25 VP-P
SIN/COS 0-5V MAX RMS
FEEDBACK
SHLD
SHLD
GND
GND
GND
GND
REF
COS
TS
SIN
CONTINUOUS
LIMIT
RESET
HI-BUS
MOTOR
FEEDBACK
AMPLIFIER
SHORTS
CURRENT
MARK
SIN
REF
MOTOR
J2
120 VAC
L1
L2
LOW SPD 1
SPD 2
SPD 3
HIGH SPD 4
J1
REF
REF GND
COS
COS GND
SIN
SIN GND
THERM
THERM
SHIELD
R
E
S
O
L
V
E
R
MOTOR PC CARD
S
P
E
E
D
S
E
L
NOTE
100% shielded cable is foil and
This is an output that comes ON at the resolver zero
position and can be used in conjunction with alignment
procedures. The zero position is about .5 degrees.
CURRENT(BI-COLOR)
This is a bi-colored LED that produces either red or
green as a function of load. The intensity increases with
load. Red indicates positive torque and green indicates
negative torque.
There are seven faults that will reduce amplif
Simulated Encoder Signals
For external counting or position control, a 9-pin D type female connector that has TTL
differential outputs is provided. This simulates quadrature encoder channel A and channel B
signals. A differential mark signal is also available.
1
6
2
7
3
8
4
9
5
A\
A
B
B\
M
M\
GND
EXTERNAL CONTROLLER
SIGNALS AND GND
ENCODER
SIMULATION CONNECTOR
P1
TYPICAL ENCODER CABLE
COMMENTS:
1) THE AMPLIFIER OUTPUTS ARE RS422 DIFFERENTIAL LINE DRIVE
I/O Wiring and Descriptions
The amplifier has five inputs and two outputs. These inputs and outputs are designed to
interface to a 24 volt logic system. The amplifier is shipped so that the operation of the inputs
is as follows.
With no wires connected to ENB, SPD, or SHFT, the amplifier is not enabled and normal
operation will not occur. The inputs are activated by connecting them with a switch closure to
any of the provided GND terminals.
J2
120 VA
Ramps are enabled by default. Grounding PIN 12 (ramps) disables ramping. Grounding PIN
13 (orient) causes the motor shaft to rotate at 1 rps.
There is a connector for control purposes inside the motor. The four possible speed ranges
are identified as LOW 1, 2, 3, and HI 4. The user has to devise the logic as to how to operate
the relays based on the amplifier control inputs.
There are two outputs, Fault and Slow. These are open collector (NPN 2N7053)
Analog Inputs, Outputs, and Adjustments
Inputs
There is one analog input channel for the command input. This is a differential input and it is
summed with a TAC feedback amplifier that controls velocity.
AUX
SIG
RESP
CUR
BAL
RESET
ENCODER
I/O
GND
ORIENT
RAMPS
GND
-COM
+COM
CUR
TAC
GND
FLT
SHFT
SLOW
SPD
ENB
}
ANALOG INPUT
WIRING EXAMPLE
GND
–COMMAND SIGNAL
+COMMAND SIGNAL
CURRENT
TAC
GND
Normal operation of the command signal is to apply a + voltage
The location of these adjustments is directly below the I/O wiring.
NOTE
The pot labeled AUX controls the speed of
the spindle orient feature and need not be
adjusted by the user.
FEEDBACK AND I/O CONTROL ASSEMBLY
AUX
SIG
RESP
CUR
BAL
RESET
ENCODER
I/O
GND
ORIENT
RAMPS
GND
-COM
+COM
CUR
TAC
GND
FLT
SHFT
SLOW
SPD
ENB
Outputs
Two diagnostic outputs are the dc voltage proportional to velocity and the dc output
proportional to current/torque. The nominal T
Analog Inputs (Specific Interface Requirements)
The analog input channel is a differential input amplifier to allow controllers that have
differential output drivers a three wire connection that excludes potential ground loops. When
differential modes of operation are used, the command input is based on 5 volts equaling
maximum input and the analog ground from the external controller must be connected to the
MPA drives GND connection. A +5 volt connec
1 2 3 4
JP4
JP9
JP11
JP3
JP19
JP3
BI-POLAR
ABSOLUTE (STANDARD)
The position of this jumper determines the kind of dc voltage proportional to current that is a
diagnostic signal at the (CUR) output of the I/O connector. With the shorting pin in the bipolar
position, the output CUR signal is plus for positive current and minus for negative current. The
voltage range is pl
SPINDLE ORIENT ENABLE
disabled
enabled
(STANDARD)
The position of this jumper determines whether the shaft will turn at 1 rps when PIN 13 is
grounded.
JP11
ORIENT DIRECTION
CW (viewed from shaft end)
CCW
(STANDARD)
The position of this jumper determines which direction the motor will turn when the orient
feature is enabled.
JP9
RESETABLE
FAULTS
(STANDARD)
NON
RESETABLE
FAULTS
When JP9 is in the left position (default) the amplifier must be power cy
AC Input and Internal Protection
A branch circuit disconnect must be provided in front of the amplifier.
Model
Three Phase Power
MPA-80-231
60 amps
80-260 Vac
AC power wiring must be consistent with any local codes, national electric codes, and be able
to withstand the voltage current ratings applied.
A
(ground) terminal is supplied and should be connected to earth ground.
Internal Protection
These amplifiers have internal AC Input fuses and a shunt f
The ac supply source for the amplifier is supposed to be bonded to earth ground.
Typical WYE Secondary
L1 (HOT)
L2 (HOT)
L3 (HOT)
GND
EARTH
GROUND
Typical Delta Secondary
EARTH
GROUND
L2 (HOT)
GND
L1 (HOT)
L3 (HOT)
These are the two most typical transformer configurations and failure to ground these properly
could void warranty. These are 230 Vac.
There are too many transformers to depict all combinations. The MPA amplifier does not care
where the earth ground is. This example is a delta secondary.
Delta Secondary
L2 (NEUTRAL)
GND
L1 (HOT)
L3 (HOT)
EARTH
GROUND
In this example, L2 became ground.