M-system R9EWTU Instruction Manual
Read Online
Read the M-system R9EWTU Instruction Manual online using the built-in PDF viewer.
Text of the manual
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 1 / 21
INSTRUCTION MANUAL
MULTI POWER MONITORING UNIT
(clamp-on current sensor CLSE, Modbus/TCP)
MODEL R9EWTU
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Multi power monitoring unit...............................................(1)
Upper mounting adaptor.....................................................(2)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
This unit is programmable by using the PC Configurator
Software. For detailed information on the PC configuration,
refer to the PMCFG users manual. The PMCFG PC Con-
figurator Software is downloadable at M-System’s web site:
http://www.m-system.co.jp
POINTS OF CAUTION
■AUXILIARY POWER INPUT RATING & OPERATIONAL RANGE
• Locate the auxiliary power input rating marked on the
product and confirm its operational range as indicated
below:
100 – 240V AC rating: 85 – 264V, 50/60 Hz, < 9VA
110 – 240V DC rating: 99 – 264V, < 3W
■GENERAL PRECAUTIONS
• Before you remove or mount the unit, turn off the power
supply and input signal for safety.
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ENVIRONMENT
• Indoor use.
• Do not install the unit where it is directly exposed to rain,
water droplets or sunlight.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Wiring to the unit must be conducted by qualified service
personnel.
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 2 / 21
COMPONENT IDENTIFICATION
Terminal Block, Current Input 2
SD Card Slot
PC Configurator Connection Jack
RUN
LINK
LK100
COL
Status Indicator LED
Terminal Block, Current Input 1
RJ-45 Connector for
Modbus/TCP (Ethernet)
TOP VIEW
FRONT VIEW
Operating Mode Setting DIP SW (SW1)
Terminal Block,
Voltage Input / Auxiliary Power Supply
T1
3K
T2
3L
17
18
8
9
1K
3K
1L
3L
15
16
6
7
1K
3K
1L
3L
13
14
4
5
1K
3K
1L
3L
11
12
2
3
1K
1L
10
1
8ch
7ch
8ch
6ch
7ch
5ch
6ch
5ch
8ch
7ch
8ch
6ch
7ch
5ch
6ch
5ch
NC 1L
NC
1K
2
1
11
10
3L
1L
3K
1K
4
3
13
12
3L
1L
3K
1K
6
5
15
14
3L
1L
3K
1K
8
7
17
16
3L
3K
9
18
P1
4
U(+) V(−)
P2
P3
2
1
6
5
FE1
N
3
7
1ch
2ch
1ch
3ch
2ch
4ch
3ch
4ch
1ch
2ch
1ch
3ch
2ch
4ch
3ch
4ch
Unused
■STATUS INDICATOR LED
ID
COLOR
STATE
FUNCTION
SDCard
Red
Blinking
approx. 1 Hz
The unit is preparing to write.
The LED starts blinking 30 seconds before the unit starts writing in the SD card on
the hour every hour.
DO NOT extract the card while the LED shows the blinking pattern until the writing
is complete.
2 sec.
SD card access error.
The unit is unable to normally write in the card because it is full or its data contents
are damaged.
2 sec.
SD card partial access error.
The unit was unable to write in the card for unknown reason but now is recovered. A
part of the data contents is missing.
OFF
SD card not inserted.
ON
SD card inserted.
Blinking
approx. 2 Hz
The unit is writing in the SD card.
DO NOT extract the card.
Power
Red
ON
Normal
Blinking
approx. 0.5 Hz
Input overload or no input
Blinking
approx. 2 Hz
Setting error or device error
2 sec.
Internal calendar error or calendar backup battery life expired.
Re-set the calendar with the PC Configurator.
The LED blinks in the designated pattern every time when the power is turned on
after the battery life has been expired.
OFF
Device error
RUN
Red
ON
Normal communication
LINK
Red
ON
10BASE or 100BASE LINK
LK100
Red
Blinking
100BASE transmitting/receiving
COL
Red
Blinking
Collision
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 3 / 21
■OPERATING MODE SETTING
(*) Factory setting
• System Configuration (SW1-1, 2)
SW1-1
SW1-2
SYSTEM CONFIGURATION
OFF
OFF
Three-phase / 3-wire (*)
ON
OFF
Single-phase / 2-wire
OFF
ON
Single-phase / 3-wire
ON
ON
---
• Balanced or Unbalanced Load (SW1-3)
SW1-3
BALANCED / UNBALANCED
OFF
Unbalanced (*)
ON
Balanced
• Clamp Sensor Type (SW1-4, 5, 6)
SW1-4
SW1-5
SW1-6
CLAMP SENSOR TYPE
OFF
OFF
OFF
CLSE-R5 (5A) (*)
ON
OFF
OFF
CLSE-05 (50A)
OFF
ON
OFF
CLSE-10 (100A)
OFF
OFF
ON
CLSE-20 (200A)
ON
ON
OFF
CLSE-40 (400A)
OFF
ON
ON
CLSE-60 (600A)
• Configuration Mode (SW1-8)
SW1-8
CONFIGURATION MODE
OFF
DIP switch setting (*)
(PC Configurator setting is invalid.)
ON
PC Configurator and communication
(DIP switch setting is invalid.)
Note 1: Turn on the power supply to the unit after setting
operating mode.
Note 2: Be sure to set unused SW1-7 to OFF.
Note 3: Clamp sensor type setting is common to all circuits.
Note 4: The sensor type and other settings for individual
circuit can be performed on the PC Configurator or via
Ethernet.
■TERMINAL ASSIGNMENTS
5
14
13
1L
1K
3K
4
3L
3
2
1
12
11
10
1L
3L
1L
1K
3K
9
18
17
T2
T1
3K
8
3L
7
6
16
15
6ch
6ch
7ch
5ch
5ch
8ch
7ch
8ch
6ch
6ch
7ch
5ch
5ch
8ch
7ch
8ch
1L
3L
1K
3K
1K
1
5ch 1L Ch.5, Current input 1L
10
5ch 1K Ch.5, Current input 1K
2
5ch 3L Ch.5, Current input 3L
11
5ch 3K Ch.5, Current input 3K
3
6ch 1L Ch.6, Current input 1L
12
6ch 1K Ch.6, Current input 1K
4
6ch 3L Ch.6, Current input 3L
13
6ch 3K Ch.6, Current input 3K
5
7ch 1L Ch.7, Current input 1L
14
7ch 1K Ch.7, Current input 1K
6
7ch 3L Ch.7, Current input 3L
15
7ch 3K Ch.7, Current input 3K
7
8ch 1L Ch.8, Current input 1L
16
8ch 1K Ch.8, Current input 1K
8
8ch 3L Ch.8, Current input 3L
17
8ch 3K Ch.8, Current input 3K
9
T2
Unused
18
T1
Unused
1
NC
Unused
10
NC
Unused
2
1ch 1L Ch.1, Current input 1L
11
1ch 1K Ch.1, Current input 1K
3
1ch 3L Ch.1, Current input 3L
12
1ch 3K Ch.1, Current input 3K
4
2ch 1L Ch.2, Current input 1L
13
2ch 1K Ch.2, Current input 1K
5
2ch 3L Ch.2, Current input 3L
14
2ch 3K Ch.2, Current input 3K
6
3ch 1L Ch.3, Current input 1L
15
3ch 1K Ch.3, Current input 1K
7
3ch 3L Ch.3, Current input 3L
16
3ch 3K Ch.3, Current input 3K
8
4ch 1L Ch.4, Current input 1L
17
4ch 1K Ch.4, Current input 1K
9
4ch 3L Ch.4, Current input 3L
18
4ch 3K Ch.4, Current input 3K
14
5
6
3K
3L
1L
15
1K
16
17
18
7
8
9
3K
1K
3K
3L
1L
10
1
2
NC
NC
1L
11
1K
12
13
3
4
3ch
3ch
2ch
4ch
4ch
1ch
2ch
1ch
3ch
3ch
2ch
4ch
4ch
1ch
2ch
1ch
3K
1K
3L
1L
3L
• Current Input 2
4
1
P1
U(+)
5
P2
6
2
3
P3
V(−)
FE1
7
N
No.
ID
FUNCTION
1
U(+)
Auxiliary power (+)
2
V(−)
Auxiliary power (−)
3
FE1
Power ground
4
P1
Voltage input P1
5
P2
Voltage input P2
6
P3
Voltage input P3
7
N
Voltage input N
• Auxiliary Power Supply, Voltage Input
• Current Input 1
No.
ID
FUNCTION
No. ID
FUNCTION
No. ID
FUNCTION
No. ID
FUNCTION
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 4 / 21
INSTALLATION
■WALL MOUNTING
Attach the upper mounting adaptors to the upper side of
the unit, and pull out the lower mounting adaptors from the
lower side. Fasten a M4 screw through the mounting hole
(4.5 mm dia.) of each adaptor. (torque 1.4 N∙m)
To remove the upper mounting adaptor from the unit, pull
it out while squeezing the latches as shown in the figure
below.
push
push
■DIN RAIL MOUNTING
Set the unit so that the lower mounting adaptors are at the
bottom. Hook the upper hook at the rear side of the unit
onto the DIN rail and push in the lower part of the unit.
When removing the unit, pull out the unit while pushing
down the adaptors using a minus screwdriver.
DIN Rail (35 mm wide)
Mounting Adaptor
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■EXTERNAL DIMENSIONS unit: mm (inch)
6 (.24)
36−M3 SCREW TERMINAL
126 (4.96)
122 (DIN RAIL MOUNT)
115 (4.53)
140 (5.51)
DIN RAIL
35 mm wide
[4 (.16)]
6.5 (.25)
80 (3.15)
75 (2.95)
125 (4.92)
7.3 (.29)
7−M3.5 SCREW TERMINALS
4 − 4.5 (.18) dia. MTG HOLE
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 5 / 21
■CONNECTION DIAGRAM
5
6
4
7
8
9
1L
4
P1
5
6
7
P2
P3
N
11
1K
13
14
12
3K
15
16
17
18
2
3L
1
2
U(+)
V(−)
3
FE1
3
VOLTAGE
AUX. POWER SUPPLY
VOLTAGE INPUT
CURRENT INPUT 1
Ch. 1
CURRENT
1L
1K
3K
3L
Ch. 2
CURRENT
1L
1K
3K
3L
Ch. 3
CURRENT
1L
1K
3K
3L
1L
1K
3K
3L
1L
1K
3K
3L
1L
1K
3K
3L
1L
1K
3K
3L
Ch. 4
CURRENT
Ch. 5
CURRENT
Ch. 6
CURRENT
Ch. 7
CURRENT
Ch. 8
CURRENT
CURRENT INPUT 2
4
5
3
6
7
8
10
12
13
11
14
15
16
17
1
2
AUXILIARY
POWER SUPPLY
Modbus/TCP (Ethernet)
RJ-45 CONNECTOR
EXTENSION CONNECTOR
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 6 / 21
■INPUT WIRING
Use the model CLSE clamp sensor for current inputs.
The figure below shows only one circuit.
A maximum of eight (8) current sensor inputs can be connected (Ch. 1 through Ch. 8).
Grounding is not required for low voltage circuits.
N
1K 1L 3K 3L
L1
source
load
N
L2
u
v
v
u
U
V
V
U
k
l
K
L k
l
K
L
N
1K 1L 3K 3L
L1
source
load
N
L2
k
l
K
L k
l
K
L
1K 1L
L1
source
load
L2
L3
u
v
v
u
U
V
V
U
k
l
K
L
1K 1L
L1
source
load
L2
L3
k
l
K
L
N
1K 1L
L1
source
load
N
k
l
K
L
u
v
U
V
N
1K 1L
L1
source
load
N
k
l
K
L
System /
Application
Single-phase
/ 2-wire
Three-phase
/ 3-wire
balanced
load
Single-phase
/ 3-wire
1K 1L 3K 3L
L1
source
load
L2
L3
u
v
v
u
U
V
V
U
k
l
K
L k
l
K
L
1K 1L 3K 3L
L1
source
load
L2
L3
k
l
K
L k
l
K
L
Three-phase
/ 3-wire
unbalanced
load
Terminal
System /
Application
Terminal
P1
P1
P1 P2 P3
P1 P2 P3
P1 P2 P3
P1 P2
P1
P3
P1
P3
P3
MOUNTING REQUIREMENTS unit: mm (inch)
Pitch 130 (5.12) min.
126 (4.96)
75 (2.95)
4–M4
■ SINGLE MOUNTING
■ BASIC + EXTENSION UNIT
Pitch 223 (8.78) min.
126 (4.96)
75 (2.95)
70.5 (2.78)
6–M4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 7 / 21
WIRING INSTRUCTIONS
■SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue terminal size. Spade tongue type is also applicable.
• M3 Screw (current input)
Applicable wire size: 0.25 to 1.65 mm2 (AWG22 to 16)
Torque: 0.5 N∙m
3.3 max. (.13)
6 max.
(.24)
mm (inch)
• M3.5 Screw (auxiliary power and voltage input)
Applicable wire size: 1.04 to 2.63 mm2 (AWG16 to 14)
Torque: 0.8 N∙m
3.8 max. (.15)
7 max.
(.28)
mm (inch)
CHECKING ETHERNET CONNECTION
■IP ADDRESS
The R9EWTU does not support BootP Table Software. The IP Address and Subnet Mask can be configured using the PMCFG
Configurator Software.
The Modbus/TCP Port No. is fixed at 502.
■NODE ADDRESS
The R9EWTU firmware sets its Node Address to “01.”
The Node Address (ID) is sent via Modbus together with data. Set “01” with the application software of the user.
■CHECK WIRING
Connect an Ethernet cable to the RJ-45 connector.
■CHECK LED
When wiring is correct, LINK LED is turned on with 10BASE or 100BASE link.
When the module is receiving data with 100BASE, LK100 LED blinks.
■CHECK R9EWTU CONNECTION
Enter “ping command” on the Windows MS-DOS as follows:
C:¥WINDOWS>ping ***.***.***.***
(***.***.***.***: Enter IP address in decimal.)
ping ***.***.***.*** with 32 bytes of data:
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Ping statistics for ***.***.***.***
Packets:Sent=4,Received=4,Lost=0(0% loss)
Replies in case of normal connection are as shown above. If the connection cannot be established normally due to e.g. wrong
IP address, other replies such as ‘time out’ will be received.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 8 / 21
MODBUS - OPERATIONS
All registers are assigned to Holding Registers, which can be read out with Read Holding Registers or Read Input Registers
command. If reading an address with no assigned register is attempted, ‘0’ is given.
Write Multiple Registers command is used to write in registers. If writing an address with no assigned register is attempted,
‘Exception’ is given.
FUNCTION
COMMAND
EXPLANATION
RECOMMENDED TIME OUT VALUE
03
Read Holding Registers
Used to read registers
0.5 seconds
04
Read Input Registers
Used to read registers
0.5 seconds
16
Write Multiple Registers
Used to write in registers
2 seconds
These commands enable reading measured values and writing configurations.
One (1) word registers are represented in 16-bit integers, while two (2) word registers are in 32-bit. All registers are in the
form of signed integer unless specifically given in the explanations.
The lower digit word in a 32-bit register is assigned to the lower address (n), while the upper digit word is assigned to the
higher address (n+1).
Address
n
n + 1
Contents
Lower digit word
Upper digit word
The 32-bit register (2 words) must be read out and written in single command sequence.
It is recommended to wait for a time period indicated under ‘recommended time out value’ in the above table to receive a
response for a command. If no response is received for these time periods, take appropriate error processing such as retrying.
■MODBUS REGISTER ACCESS SETTING
ADDR.
WORD
PARAMETER
8977
2
Passcode entry for deactivating Modbus register write protection
Write a preset passcode in this register to deactivate the write protection via Modbus.
When the value set in this register matches the preset passcode, ‘1’ is set in the register address 8979 to en-
able writing in Modbus registers.
The value set in this register cannot be read out. It reads always ‘-1’ regardless of the set value.
When writing in the Modbus registers for setting change is complete, be sure to set a value (‘0’ is recom-
mended) other than the passcode to activate the write protection again.
8979
1
Modbus register access setting
0 : Write disable (*)
1 : Write enable
Other : Write disable
This setting is cleared when the power supply to the unit is removed. It always starts with ‘0’ (Write dis-
able) when the power supply is turned on. Set ‘1’ before writing in other registers.
Note that ‘1’ (Write enable) cannot be written in this register when the Modbus register write protection
passcode is preset and the write protection is enabled.
Be sure to write the correct passcode in the register address 8977 before changing the register setting from
‘0’ (Write disable) to ‘1’ (Write enable).
(*) Factory setting
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 9 / 21
■SYSTEM OPERATIONS
System operations include resetting accumulated values and rebooting.
ADDR.
WORD
PARAMETER
8993
1
Reboot system
Write ‘10001’ to reboot the system. (Any other values can be written but invalid.)
8994
2
Setting Modbus register write protection passcode
Set a passcode for enabling/disabling writing in registers via Modbus.
0 : Cancel write protection (*)
1 to 999 999 999: The set value is used as the passcode
Write the passcode in the register address 8977 before setting ‘1’ in the address 8979 to deactivate the write
protection.
The value in this register is encrypted when it is read out. Only ‘0’ (Cancel write protection) is read out as it
is.
When a new passcode is written, the register address 8979 is immediately reset to ‘0’ so as to limit the next
write command in access.
8996
1
Ch. 1 Reset count
Resetting specific count values among the channel 1 counts by writing a bit pattern as shown below.
Resetting is not executed for the bits set to ‘0.’
15
Bit
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Current harmonic distortion, max.
Voltage harmonic distortion, max. *
Average power, max. / min.
Average current, max. / min.
Frequency, max. / min.
Power factor, max. / min.
Power, max. / min.
Current, max. / min.
Voltage, max. / min.
Average power
Average current
Energy count per time unit
Totalized energy
*Resetting voltage related values is available only at Ch. 1.
8997
1
Ch. 2 Reset count
8998
1
Ch. 3 Reset count
:
:
:
9003
1
Ch. 8 Reset count
9004
1
Ch. 9 Reset count (DI 1 Reset count)
With the R9WTU-ED16 module, resetting specific count values among the DI 1 counts by writing a bit pat-
tern as shown below.
Resetting is not executed for the bits set to ‘0.’
15
Bit
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Pulse count per time unit
Totalized pulse count
With the R9WTU-EP8 module, Ch. 9 bit pattern is identical to that for Ch. 1.
9005
1
Ch. 10 Reset count (DI 2 Reset count)
9006
1
Ch. 11 Reset count (DI 3 Reset count)
:
:
:
9011
1
Ch. 16 Reset count (DI 8 Reset count)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 10 / 21
MODBUS - SETTING
■SYSTEM SETTING
ADDR.
WORD
PARAMETER
UNIT
9041
1
System configuration
0 : Single-phase / 2-wire (1CT)
1 : Single-phase / 3-wire (2CT)
2 : Three-phase / 3-wire, balanced load (1CT)
3 : Three-phase / 3-wire, unbalanced load (2CT) (*)
---
9042
1
Reserved
9043
1
Reserved
9044
2
VT rating, Primary
0 to 400 000 : Voltage (V)
Factory setting : 110
V
9046
1
VT rating, Secondary
50 to 500 : Voltage (V)
Factory setting : 110
The secondary can be set up to 500V. However, this does not mean the unit accepts 500V for
input. Do not use with the condition exceeding input rating written in the specification sheet
of the unit.
V
9047
1
Reserved
9048
1
Reserved
9049
1
Low-end cutout, Voltage
0 to 999 : Rated voltage × 0.001 × Specified value
Factory setting : 10
%/10
(*) Factory setting
■DEMAND SETTING
ADDR.
WORD
PARAMETER
UNIT
9057
1
Average (demand) current update interval
1 to 30 : Minutes
Factory setting : 30
Data updated at the integral multiple minutes of the setting
(e.g. Setting = 15 minutes, Updated at 0, 15, 30, and 45 minutes every hour)
Minutes
9058
1
Average (demand) power update interval
1 to 30 : Minutes
Factory setting : 30
Data updated at the integral multiple minute of the setting
Minutes
■STYLE SETTING
ADDR.
WORD
PARAMETER
9073
1
Power factor (PF1 through PF3, PF) sign
0 : Standard (IEC), Identical to the active energy (*)
1 : Special type 1 (IEEE), Positive in LAG, Negative in LEAD
9074
1
Reactive power (Q1 through Q3, Q) sign
0 : Standard (IEC), Positive from PF = 1.0 to 180° in LAG direction; Negative for the other direction (*)
1 : Special type 1, Positive in LAG, Negative in LEAD
9075
1
Reactive power (Q1 through Q3) calculation (Q = Q1 + Q2 + Q3)
0 : Standard (*)
Qn = √Sn2 – Pn2
1 : Reactive power meter method
Qn =
1
Nsmp
Nsmp
(Uni – Nui) Ii + (Nsmp / 4)
∑
i = 1
9076
1
Apparent power (S) calculation
0 : Standard (*)
S = √P2 + Q2
1 : Sum
S = S1 + S2 + S3
Note: ‘1,’ ‘2,’ ‘3’ in expressions like Q1, Q2, Q3 indicate ‘R,’ ‘S,’ ‘T phases’ respectively.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 11 / 21
■MODBUS SETTING
The device must be turned off and on in order to enable the Modbus setting.
ADDR.
WORD
PARAMETER
UNIT
9096
1
RUN LED time out
RUN LED turns off if the unit receives no Modbus command for the specified time peri-
od.
0 to 32 000 : Specified value × 0.1 seconds
Factory setting : 10
Sec./10
9121
2
Modbus/TCP IP address
IP address is stored in the form of ‘A.B.C.D’ in the following address:
Address
Upper Byte
Lower Byte
9121
A
B
9122
C
D
Factory setting : 192.168.0.1
---
9123
2
Modbus/TCP subnet mask
Subnet mask is stored in the form of ‘A.B.C.D’ in the following address:
Address
Upper Byte
Lower Byte
9123
A
B
9124
C
D
Factory setting : 255.255.255.0
---
9125
2
Modbus/TCP default gateway
Default gateway is stored in the form of ‘A.B.C.D’ in the following address:
Address
Upper Byte
Lower Byte
9125
A
B
9126
C
D
Factory setting : 0.0.0.0
---
9127
1
Modbus/TCP port No.
0 to 65535
Factory setting : 502
---
9128
1
Modbus/TCP connection time out
Connection is severed if no communication is established for the specified time period.
0 to 32 000 : Specified value × 0.1 seconds
Factory setting : 600
Sec./10
■DATE/TIME SETTING
The three registers must be written at once.
ADDR.
WORD
PARAMETER
9105
3
Current date/time setting
Reading/writing the current date and time.
Data/time is stored in BCD format in the following address:
Address
b15
b8
b7
b0
9105
BCD Year
(00 to 99)
BCD Month
(01 to 12)
9106
BCD Day
(01 to 31)
BCD Hour
(00 to 23)
9107
BCD Minute
(00 to 59)
BCD Second
(00 to 59)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 12 / 21
■SENSOR SETTING
ADDR.
WORD
PARAMETER
UNIT
9393
1
Ch. 1 CT rating, Primary
1 to 20 000 : Current (A)
Factory setting : 5
Valid only for the sensor type CLSE-R5. Selected sensor’s rating is automatically set for
other types of sensors.
A
9394
1
Ch. 1 Clamp sensor type
0 : CLSE-R5 (*)
1 : CLSE-05
2 : CLSE-10
3 : CLSE-20
4 : CLSE-40
5 : CLSE-60
6 : Reserved
7 : Reserved
---
9395
1
Low-end cutout, Current Ch. 1
0 to 999 : Rated current × 0.001 × Specified value
Factory setting : 10
%/10
9396
1
Reserved
9397
:
9400
4
Ch. 2 setting
Same as with the address 9393 through 9396
---
:
:
:
9543
:
9456
1
Ch. 16 setting
Same as with the address 9393 through 9396
Ch. 9 through 16 are valid only when the R9WTU-EP8 is used.
---
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 13 / 21
■DEVICE STATUS
ADDR.
WORD
PARAMETER
9537
1
Ch. 1 and Ch. 2 System error
Bit assignment as shown below.
15
Bit
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
STAT AVG ENE SET FDT PRG
PRG
: Control software error
FDT
: Factory calibration data error
SET
: User setting data error
ENE
: Energy data error
AVG
: Average data error
STAT : Maximum / minimum data error
‘1’ is placed when the respective errors are detected. All measuring operations stop while one or more sys-
tem errors are detected.
9538
1
Ch. 3 and Ch. 4 System error
Same as with the address 9537
:
:
:
9544
1
Ch. 15 and Ch. 16 System error
Same as with the address 9537
Ch. 9 through 16 are valid only when the R9WTU-EP8 is used.
9545
1
Ch. 1 Input overload
Bit assignment as shown below.
15
Bit
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
U31
F
U23
U12
U3N U2N U1N
I3
I2
I1
F
: Frequency
I1
: Line 1 current
I2
: Line 2 current
I3
: Line 3 current
U1N : Phase 1 voltage
U2N : Phase 2 voltage
U3N : Phase 3 voltage
U12
: Line 1 - 2 voltage
U23
: Line 2 - 3 voltage
U31
: Line 3 - 1 voltage
‘1’ is placed at the bit where an overload is detected.
9546
1
Ch. 2 Input overload
Same as with the address 9545
:
:
:
9560
1
Ch. 16 Input overload
Same as with the address 9545
Ch. 9 through 16 are valid only when the R9WTU-EP8 is used.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 14 / 21
■DEVICE INFORMATION
ADDR.
WORD
PARAMETER
9601
1
Device ID
9901 : R9xWTU
9602
1
Device version
Version number × 100 (e.g. Version 1.00 = 100)
9603
4
Serial No.
Each character is stored in the following address:
Address
Upper Byte
Lower Byte
9603
2nd
1st
9604
4th
3rd
9605
6th
5th
9606
8th
7th
9607
8
Tag name
This register is writable.
Each character is stored in the following address:
Address
Upper Byte
Lower Byte
9607
2nd
1st
9608
4th
3rd
9609
6th
5th
9610
8th
7th
9611
10th
9th
9612
12th
11th
9613
14th
13th
9614
16th
15th
9623
1
Extension function flag
Reading the following values depending upon the function:
0002H : RS-485 (Modbus RTU)
0080H : LONWORKS
0100H : CC-Link
2000H : Modbus/TCP
9624
1
Number of discrete input
0 : None
8 : 8 points (with the R9WTU-ED16)
9625
1
Number of discrete output
0 : None
8 : 8 points (with the R9WTU-ED16)
9626
1
Reserved
9627
1
Number of circuits
8 : 8 circuits
16 : 16 circuits (with the R9WTU-EP8)
9628
1
Number of counters
0 : None
8 : 8 points (with the R9WTU-ED16)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 15 / 21
MODBUS - MAPPING
■PARAMETER TYPES
TYPE
WORD
UNIT
RANGE
Current
2
mA
0 to 2 000 000 000 mA
Voltage
2
V/100
0 to 20 000 000.00 V
Active power
2
W
-2 000 000 000 to 2 000 000 000 W
Reactive power
2
var
-2 000 000 000 to 2 000 000 000 var
Apparent power
2
VA
0 to 2 000 000 000 VA
Power factor
2
cos φ
-1.0000 to 1.0000
Frequency
2
Hz/100
0 or 40.00 to 70.00 Hz
Active energy
2
kWh/10
0 to 99 999 999.9 kWh *1
Reactive energy
2
kvarh/10
0 to 99 999 999.9 kvarh *1
Harmonic distortion
1
%/10
0 to 999.9 %
Date/time
3
---
Each value is in BCD format.
Year value represented in the offset from 2000.
e.g. 100817160752h = Year 2010, August 17, 16:07:52
b48 b40 b39 b32 b31 b24 b23 b16 b15 b8 b7 b0
Year
Month
Day
Hour
Minute
Second
*1. Reset to 0 at overflow
■ADDRESS
If base address and offset is given separately in the following tables, add both values to determine the address for a particular
parameter.
[Example]
Ch. 1, Line 1 current, Present value = 65 + 0 = 65
Ch. 1, Line 1 current, Max. value = 65 + 10 = 75
• Voltage and Frequency
PARAMETER
PRESENT
MAX
MIN
Delta voltage, 1 – 2
1
17
33
Delta voltage, 2 – 3
3
19
35
Delta voltage, 3 – 1
5
21
37
Phase voltage, Phase 1
7
23
39
Phase voltage, Phase 2
9
25
41
Phase voltage, Phase 3
11
27
43
Total voltage *2
13
29
45
Frequency
15
31
47
*2. Total voltage
Single-phase/2-wire: Phase 1 voltage
Single-phase/3-wire: (Phase 1 + 3) / 2
Three-phase/3-wire: {Delta (1 – 2) + (2 – 3) + (3 – 1)} / 3
• Current
PARAMETER
BASE ADDRESS
BASIC UNIT
Ch. 1 Current
65
Ch. 2 Current
97
Ch. 3 Current
129
Ch. 4 Current
161
Ch. 5 Current
193
Ch. 6 Current
225
Ch. 7 Current
257
Ch. 8 Current
289
R9WTU-EP8
Ch. 9 Current
321
Ch. 10 Current
353
Ch. 11 Current
385
Ch. 12 Current
417
Ch. 13 Current
449
Ch. 14 Current
481
Ch. 15 Current
513
Ch. 16 Current
545
PARAMETER
OFFSET
PRESENT
MAX
MIN
Current, Line 1
+0
+10
+20
Current, Line 2
+2
+12
+22
Current, Line 3
+4
+14
+24
Neutral current
+6
+16
+26
Total current *3
+8
+18
+28
*3. Total current
Single-phase/2-wire: Line 1 current
Single-phase/3-wire: (Line 1 + 3) / 2
Three-phase/3-wire: (Line 1 + 2 + 3) / 3
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 16 / 21
• Power and Power Factor
PARAMETER
BASE ADDRESS
BASIC UNIT
Ch. 1 Power, Power factor
577
Ch. 2 Power, Power factor
673
Ch. 3 Power, Power factor
769
Ch. 4 Power, Power factor
865
Ch. 5 Power, Power factor
961
Ch. 6 Power, Power factor
1057
Ch. 7 Power, Power factor
1153
Ch. 8 Power, Power factor
1249
R9WTU-EP8
Ch. 9 Power, Power factor
1345
Ch. 10 Power, Power factor
1441
Ch. 11 Power, Power factor
1537
Ch. 12 Power, Power factor
1633
Ch. 13 Power, Power factor
1729
Ch. 14 Power, Power factor
1825
Ch. 15 Power, Power factor
1921
Ch. 16 Power, Power factor
2017
PARAMETER
OFFSET
PRESENT
MAX
MIN
Active power, Phase 1
+0
+32
+64
Active power, Phase 2
+2
+34
+66
Active power, Phase 3
+4
+36
+68
Active power
+6
+38
+70
Reactive power, Phase 1
+8
+40
+72
Reactive power, Phase 2
+10
+42
+74
Reactive power, Phase 3
+12
+44
+76
Reactive power
+14
+46
+78
Apparent power, Phase 1
+16
+48
+80
Apparent power, Phase 2
+18
+50
+82
Apparent power, Phase 3
+20
+52
+84
Apparent power
+22
+54
+86
Power factor, Phase 1
+24
+56
+88
Power factor, Phase 2
+26
+58
+90
Power factor, Phase 3
+28
+60
+92
Power factor
+30
+62
+94
• Average (demand) (AVG)
PARAMETER
BASE ADDRESS
BASIC UNIT
Ch. 1 Average
2113
Ch. 2 Average
2257
Ch. 3 Average
2401
Ch. 4 Average
2545
Ch. 5 Average
2689
Ch. 6 Average
2833
Ch. 7 Average
2977
Ch. 8 Average
3121
R9WTU-EP8
Ch. 9 Average
3265
Ch. 10 Average
3409
Ch. 11 Average
3553
Ch. 12 Average
3697
Ch. 13 Average
3841
Ch. 14 Average
3985
Ch. 15 Average
4129
Ch. 16 Average
4273
PARAMETER
OFFSET
LATEST
MAX
MAX
DATE/
TIME
MIN
MIN
DATE/
TIME
Current AVG date/time
+0
Current AVG
+3
+28
+30
+83
+85
Current AVG, Line 1
+5
+33
+35
+88
+90
Current AVG, Line 2
+7
+38
+40
+93
+95
Current AVG, Line 3
+9
+43
+45
+98
+100
Neutral current AVG
+11
+48
+50
+103
+105
Power AVG date/time
+13
Active power AVG
+16
+53
+55
+108
+110
Reactive power AVG
+18
+58
+60
+113
+115
Apparent power AVG
+20
+63
+65
+118
+120
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 17 / 21
• Energy / Pulse Count
PARAMETER
BASE ADDRESS
BASIC UNIT
Ch. 1 Energy
4417
Ch. 2 Energy
4481
Ch. 3 Energy
4673
Ch. 4 Energy
4737
Ch. 5 Energy
4929
Ch. 6 Energy
4993
Ch. 7 Energy
5185
Ch. 8 Energy
5249
EXTENSION UNIT
R9WTU-EP8
R9WTU-ED16
BASE ADDRESS
Ch. 9 Energy
DI 1 Pulse count
5441
Ch. 10 Energy
DI 2 Pulse count
5505
Ch. 11 Energy
DI 3 Pulse count
5697
Ch. 12 Energy
DI 4 Pulse count
5761
Ch. 13 Energy
DI 5 Pulse count
5953
Ch. 14 Energy
DI 6 Pulse count
6017
Ch. 15 Energy
DI 7 Pulse count
6209
Ch. 16 Energy
DI 8 Pulse count
6273
PARAMETER
OFFSET
BASIC UNIT
R9WTU-EP8
R9WTU-ED16
Totalized energy
Totalized pulse count
+0
Totalized reactive
energy (LAG)
Reserved
+2
Energy, last 1 hour
Pulse count, last 1 hour
+6
Energy, last 1 minute
Pulse count, last 1 minute
+8
Energy, 0 to 1
(o’clock)
Pulse count, 0 to 1
(o’clock)
+10
Energy, 1 to 2
Pulse count, 1 to 2
+12
Energy, 2 to 3
Pulse count, 2 to 3
+14
Energy, 3 to 4
Pulse count, 3 to 4
+16
Energy, 4 to 5
Pulse count, 4 to 5
+18
Energy, 5 to 6
Pulse count, 5 to 6
+20
Energy, 6 to 7
Pulse count, 6 to 7
+22
Energy, 7 to 8
Pulse count, 7 to 8
+24
Energy, 8 to 9
Pulse count, 8 to 9
+26
Energy, 9 to 10
Pulse count, 9 to 10
+28
Energy, 10 to 11
Pulse count, 10 to 11
+30
Energy, 11 to 12
Pulse count, 11 to 12
+32
Energy, 12 to 13
Pulse count, 12 to 13
+34
Energy, 13 to 14
Pulse count, 13 to 14
+36
Energy, 14 to 15
Pulse count, 14 to 15
+38
Energy, 15 to 16
Pulse count, 15 to 16
+40
Energy, 16 to 17
Pulse count, 16 to 17
+42
Energy, 17 to 18
Pulse count, 17 to 18
+44
Energy, 18 to 19
Pulse count, 18 to 19
+46
Energy, 19 to 20
Pulse count, 19 to 20
+48
Energy, 20 to 21
Pulse count, 20 to 21
+50
Energy, 21 to 22
Pulse count, 21 to 22
+5
Energy, 22 to 23
Pulse count, 22 to 23
+54
Energy, 23 to 24
Pulse count, 23 to 24
+56
Max. energy
Max. pulse count
+58
Max. energy data/time
Max. pulse count date/time
+60
• Voltage Harmonic Distortion (HD)
PARAMETER
PRESENT
MAX
Delta voltage HD, 1 – 2
6465
6473
Delta voltage HD, 2 – 3
6466
6474
Delta voltage HD, 3 – 1
6467
6475
Phase voltage HD, Phase 1
6468
6476
Phase voltage HD, Phase 2
6469
6477
Phase voltage HD, Phase 3
6470
6478
• Current Harmonic Distortion (HD)
PARAMETER
BASE ADDRESS
BASIC UNIT
Ch. 1 Current HD
6481
Ch. 2 Current HD
6489
Ch. 3 Current HD
6497
Ch. 4 Current HD
6505
Ch. 5 Current HD
6513
Ch. 6 Current HD
6521
Ch. 7 Current HD
6529
Ch. 8 Current HD
6537
R9WTU-EP8
Ch. 9 Current HD
6545
Ch. 10 Current HD
6553
Ch. 11 Current HD
6561
Ch. 12 Current HD
6569
Ch. 13 Current HD
6577
Ch. 14 Current HD
6585
Ch. 15 Current HD
6593
Ch. 16 Current HD
6601
PARAMETER
OFFSET
PRESENT
MAX
Current HD, Line 1
+0
+4
Current HD, Line 2
+1
+5
Current HD, Line 3
+2
+6
Neutral current HD
+3
+7
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 18 / 21
• Voltage Harmonic Content (HC)
PARAMETER
3rd
5th
...
29th
31st
Delta voltage HC, 1 – 2
6609
6610
...
6622
6623
Delta voltage HC, 2 – 3
6625
6626
...
6638
6639
Delta voltage HC, 3 – 1
6641
6642
...
6654
6655
Phase voltage HC, Phase 1
6657
6658
...
6670
6671
Phase voltage HC, Phase 2
6673
6674
...
6686
6687
Phase voltage HC, Phase 3
6689
6690
...
6702
6703
• Current Harmonic Content (HC)
PARAMETER
BASE ADDRESS
BASIC UNIT
Ch. 1 Current HC
6705
Ch. 2 Current HC
6769
Ch. 3 Current HC
6833
Ch. 4 Current HC
6897
Ch. 5 Current HC
6961
Ch. 6 Current HC
7025
Ch. 7 Current HC
7089
Ch. 8 Current HC
7153
R9WTU-EP8
Ch. 9 Current HC
7217
Ch. 10 Current HC
7281
Ch. 11 Current HC
7345
Ch. 12 Current HC
7409
Ch. 13 Current HC
7473
Ch. 14 Current HC
7537
Ch. 15 Current HC
7601
Ch. 16 Current HC
7665
PARAMETER
OFFSET
3rd
5th
...
29th
31st
Current HC, Line 1
+0
+1
...
+13
+14
Current HC, Line 2
+16
+17
...
+29
+30
Current HC, Line 3
+32
+33
...
+45
+46
Neutral current HC
+48
+49
...
+61
+62
• Discrete Input (DI)
‘0’ is read if the R9WTU-ED16 is not used.
ADDR.
WORD LENGTH
PARAMETER
7745
1
DI 1 Status
0 : OFF
1 : ON
7746
1
DI 2 Status
0 : OFF
1 : ON
7747
1
DI 3 Status
0 : OFF
1 : ON
7748
1
DI 4 Status
0 : OFF
1 : ON
7749
1
DI 5 Status
0 : OFF
1 : ON
7750
1
DI 6 Status
0 : OFF
1 : ON
7751
1
DI 7 Status
0 : OFF
1 : ON
7752
1
DI 8 status
0 : OFF
1 : ON
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 19 / 21
• Pulse Count
‘0’ is read if the R9WTU-ED16 is not used.
ADDR.
WORD LENGTH
PARAMETER
7777
2
DI 1 Pulse count
Pulse train input at DI 1 is counted. The counter resets to 0 when a pulse is added at 999
999 999 counts.
7779
2
DI 2 Pulse count
Pulse train input at DI 2 is counted. The counter resets to 0 when a pulse is added at 999
999 999 counts.
7781
2
DI 3 Pulse count
Pulse train input at DI 3 is counted. The counter resets to 0 when a pulse is added at 999
999 999 counts.
7783
2
DI 4 Pulse count
Pulse train input at DI 4 is counted. The counter resets to 0 when a pulse is added at 999
999 999 counts.
7785
2
DI 5 Pulse count
Pulse train input at DI 5 is counted. The counter resets to 0 when a pulse is added at 999
999 999 counts.
7787
2
DI 6 Pulse count
Pulse train input at DI 6 is counted. The counter resets to 0 when a pulse is added at 999
999 999 counts.
7789
2
DI 7 Pulse count
Pulse train input at DI 7 is counted. The counter resets to 0 when a pulse is added at 999
999 999 counts.
7791
2
DI 8 Pulse count
Pulse train input at DI 8 is counted. The counter resets to 0 when a pulse is added at 999
999 999 counts.
• Discrete Output (DO)
‘Exception’ is given if the R9WTU-ED16 is not used.
ADDR.
WORD LENGTH
PARAMETER
7841
1
DO 1
Output contact at the Extension Unit is turned on/off by writing in the address.
0 : OFF / 1 : ON
7842
1
DO 2
Output contact at the Extension Unit is turned on/off by writing in the address.
0 : OFF / 1 : ON
7843
1
DO 3
Output contact at the Extension Unit is turned on/off by writing in the address.
0 : OFF / 1 : ON
7844
1
DO 4
Output contact at the Extension Unit is turned on/off by writing in the address.
0 : OFF / 1 : ON
7845
1
DO 5
Output contact at the Extension Unit is turned on/off by writing in the address.
0 : OFF / 1 : ON
7846
1
DO 6
Output contact at the Extension Unit is turned on/off by writing in the address.
0 : OFF / 1 : ON
7847
1
DO 7
Output contact at the Extension Unit is turned on/off by writing in the address.
0 : OFF / 1 : ON
7848
1
DO 8
Output contact at the Extension Unit is turned on/off by writing in the address.
0 : OFF / 1 : ON
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 20 / 21
DATA LOGGING IN SD CARD
■GENERAL DESCRIPTION
The R9EWTU is equipped with a SD card slot.
The unit transfers to the card at 0 minute every hour its in-
ternal memory data: energy per hour; and voltage, current,
power and energy per minute.
A 4-GB SD card can store information of 8 channels for ap-
prox. 16 years.
■TIMING
Data recording is started from 0 minute of the hour when
the card is inserted.
For example, if it is inserted at 9:50, data from 9:00 to 10:00
is transferred to the card at 10:00, and later data is added
every hour until the card is extracted. (If the unit has been
started later than 9:00, data before the startup is not avail-
able.)
If the card is not in the unit on the hour, data transfer is not
executed and the internal data is automatically erased until
one is inserted to the unit again.
The SDCard LED starts blinking 30 seconds before the
hour every hour for noticing start of writing operation.
DO NOT extract the card while the LED is blinking until
the writing is complete.
If the card is extracted or the power supply to the unit is
turned off while it is writing, stored data may be destroyed
and inaccessible.
■SD CARD
Prepare one of the following types of memory card:
• Manufacturer: Hagiwara Solutions
Model: NSD6-004GH(A00SDI (discontinued),
NSDA-004GT (discontinued),
NSDA-004GL (discontinued),
NSD6-004GH(B21SEI
• Manufacturer: Apacer Technology
Model: AP-ISD04GIS4B-T, AP-ISD04GIS4B-3T
M-SYSTEM IS NOT LIABLE FOR ANY LOSS OF DATA.
Data may be lost in but not limited to the following cases:
• Wrong handling of the card
• Static or electric noise interference
• When the card is extracted or when the power supply to
the unit is turned off while it is accessed.
• When formatting SD card, use a dedicated software “SD
Card Formatter”.
“SD Card Formatter” is downloadable at SD Association’s
web site.
https://www.sdcard.org
■CALENDAR
The incorporated calendar IC is backed up with a battery
which enables the calendar backup for 2 years with no ex-
ternal power supply.
We recommend that the power supply is maintained as long
as possible while the SD card is used.
The battery does not wear while the external power is sup-
plied, however, the calendar cannot be backed up after the
total elapsed time without power supply exceeds 2 years.
The unit indicates a calendar error with POWER LED, and
resets the date and time to Year 2000, January 1, 00:00:00.
Refer to “COMPONENT IDENTIFICATION” section. Set
the date and time again in such a case.
Once the backup battery life is expired, the unit indicates
the same error every time the power supply to it is turned
on.
■DIRECTORY
XXXXXXXX
Device
201004
201004.csv
201005
Month
Month
20100401.csv
20100430.csv
Log file, 1 hour interval
Log file, 1 minute interval
Log file, 1 minute interval
・
・
・
• Device Folder
A data folder inherent to the device is automatically cre-
ated, and monthly folders are created in it.
Device folder is identified with the device’s serial number
(8 characters).
• Monthly Folder
Monthly folders are identified with year (4 characters) and
month (2 characters). All log files for the designated month
are stored in it.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 21 / 21
• Log File, 1 Hour Interval
Energy (watthour) and pulse counts per hour for each channel is stored on the hour every hour.
Each data storage cycle takes 1 row, and at the maximum of 1 month data is stored in a CSV (divided with comma) format
file. The first row of the file contains the data contents descriptions and the second contains the engineering unit descriptions.
PARAMETER
DATE
TIME
Ch. 1
Energy
Ch. 2
Energy
....
Ch. 8
Energy*1
DI 1 Pulse
Count*2
DI 2 Pulse
Count*2
....
DI 8 Pulse
Count*2
Row 1 Comment
Date
Time
1ch-EP
2ch-EP
8ch-EP
DI1-count
DI2-count
DI8-count
Row 2 Unit
kWh
kWh
kWh
pulse
pulse
pulse
Example
2010/08/25
10:00
123.4
123.4
123.4
4567
4567
4567
2010/08/25
11:00
123.4
123.4
123.4
4567
4567
4567
• Log File, 1 Minute Interval
Voltage, current, power, energy (watthour), and pulse counts per minute for each channel is stored.
Data transfer for the whole hour to the SD card is executed only at the same moment as for the hourly data.
Each data storage cycle takes 1 row, and at the maximum of 1 day data is stored in a CSV (divided with comma) format file.
The first row of the file contains the data contents descriptions and the second contains the engineering unit descriptions.
PARAMETER
DATE
TIME
Voltage
1
Voltage
2
Voltage
3
Ch.1
Current 1
Ch. 1
Current 2
Ch. 1
Current 3
Ch. 2
Current 1
....
Row 1 Comment
Date
Time
U1
U2
U3
1ch-I1
1ch-I2
1ch-I3
2ch-I1
Row 2 Unit
V
V
V
A
A
A
A
Example
2010/08/25
10:00
110.00
110.00
110.00
5.000
5.000
5.000
5.000
2010/08/25
10:01
110.00
110.00
110.00
5.000
5.000
5.000
5.000
....
Ch. 8
Current 3*1
Ch. 1
Power
Ch. 2
Power
....
Ch. 8
Power*1
Ch. 1
Energy
Ch. 2
Energy
....
Ch. 8
Energy*1
DI 1 Pulse
Count*2
DI 2 Pulse
Count*2
....
DI 8 Pulse
Count*2
8ch-I3
1ch-P
2ch-P
8ch-P
1ch-EP
2ch-EP
8ch-EP
DI1-count
DI2-count
DI8-count
A
kW
kW
kW
kWh
kWh
kWh
pulse
pulse
pulse
5.000
1.650
1.650
1.650
12.3
12.3
12.3
456
456
456
5.000
1.650
1.650
1.650
12.3
12.3
12.3
456
456
456
*1. Up to 16 channels with the R9WTU-EP8
*2. DI pulse counts are recorded only with the R9WTU-ED16
Voltage and current data are assigned as in the following table.
Three-
phase /
3-wire
Voltage 1
Delta voltage, 1 – 2
Single-
phase /
3-wire
Voltage 1
Phase voltage, Phase 1
Single-
phase /
2-wire
Voltage 1
Phase voltage, Phase 1
Voltage 2
Delta voltage, 2 – 3
Voltage 2
Phase voltage, Phase 3
Voltage 2
0
Voltage 3
Delta voltage, 3 – 1
Voltage 3
Delta voltage, 3 – 1
Voltage 3
0
Current 1
Current, Line 1
Current 1
Current, Line 1
Current 1
Current, Line 1
Current 2
Current, Line 2
Current 2
Current, Line 3
Current 2
0
Current 3
Current, Line 3
Current 3
Neutral current
Current 3
0
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.