The SP-300 control is a two stage, general pur-
pose, temperature control for use in HVAC, re-
frigeration, and industrial applications. The set-
point temperature range is user selectable from:
-30°F to +100°F or 70°F to 200°F
The control provides two staged isolated SPDT
relay contacts. The relays are controlled by com-
paring the thermistor temperature sensor to a
setpoint. The SP-300 allows the user to select
either “heat” mode (both relays operate on tem-
perature fall) or “cool” mode (both relays operate
on temperature rise) or “heat/cool” mode (output
1 relay operates on temperature fall and output 2
relay operates on temperature rise). The control
setpoint can be set using the internal setpoint dial
(factory setting) or a remote setpoint dial (see
Goldline RSP-30 remote setpoint on page 6). The
SP-300 also features a plug in connector for a TD-
30 Digital Display Monitor. The TD-30 snaps
into the cover for easy mounting and displays
both sensor and setpoint temperatures.
Power can be provided from a 24VDC, 24VAC,
115VAC or 240VAC power source. Each set of
relay contacts is completely isolated so the out-
puts can switch any voltage, regardless of the SP-
300 power source. Furthermore, one relay output
can switch high voltage, the other switch low
voltage. A movable divider is provided to sepa-
rate high and low voltage wiring compartments.
Specifications
Specifications
Specifications
Specifications
Specifications
Power:
Approx. 2VA required from any
power source:
21-27VDC
21-27VAC, 50/60Hz
105-130VAC, 50/60Hz
195-250VAC, 50/60Hz
Outputs:
SPDT isolated (dry)contacts,
1HP@115VAC, 2HP@240VAC
rating @ 240VAC:
20A on NO contacts
10A on NC contacts
Sensors:
Thermistor, 10K @ 25°C/77°F
Type SW supplied with control
Interchangeable with any IE
temperature sensor
1000 ft. maximum wire run
Setpoint:
Low -30 to +100°F
High 70 to 200°F
Differential 1:
1-25°F
Differential 2:
1-25°F
Stage Offset:
1-25°F
Accuracy:
+/- 1°F
Environment:
-30 to +130°F
0-95% rH, non-condensing
The SP-300 can be configured to operate in a
variety of applications using jumpers located on
the circuit board (see diagram below). Set these
jumpers based on your application, before at-
tempting to install or wire the control. The jumper
functions and appropriate positions are shown in
the diagram below.
SETPOINT
D IFF 1
D IFF 2
OFFSET
R
C
1
2
3
4
Setpoint
Selection
Anti-Cycle
Protection
Cool/Heat
Selection
Setpoint
Range
Connector
for TD-30
Power LED
O utput 1 LED
O utput 2 LED
Output 2 operates on te mperature ris
The SP-300 is designed for mounting indoors,
protected from the weather and with non-con-
densing humidity. For outdoor use or in moist
environments use a Goldline RE-1 raintight en-
closure. Use the mounting screws supplied or
optional mounting bracket (consult IE factory).
Sensor Mounting and Wiring
To maximize temperature measurement accuracy
securely mount the sensor and then insulate it to
protect it from the effects of ambient temperature.
18 AWG twisted pair wire should be used for
normal indoor wiring runs. Sensor wiring run
outdoors must be rated for outdoor use and ensure
that wire connections are protected from the
weather. For long runs or runs near other electri-
cal wiring use shielded cable (Belden 8760 for
indoor use or Belden 8428 for outdoor use). Ground
the shields to one of the SP-300 cover screws. If
the SW sensor supplied with the control does not
meet your needs, contact your distributor for
information on the wide range of interchangeable
Goldline temperature sensors.
The temperature sensor wires run back to the
control should be connected to the screw termi-
nals labeled "3" and "4".
Power input
The SP-300 control requires power to operate.
Either 24VDC, 24VAC, 115 or 208/240VAC can
be used. Be sure to only power the control with
ONE power input. Connect 24VAC to the “R”
and “C” terminals; 24VDC to the “R” (+) and “C”
(-); 115VAC to the terminals marked “115VAC”
or 208/240VAC to the terminals marked
“240VAC”. Connect grounds to the green screw
provided or use grounding clips (eg Steel City
“Gee clips” or Raco #975). Refer to wiring
diagram below.
{
{
Sensor
Sensor
Sensor
Sensor
The SP-300 outputs are isolated (dry) contacts
which are ideal for many control applications.
Because there is no output voltage, if you are
directly controlling a load (e.g. pump, blower,
valve, etc.) then you must connect a source of
power to the SP-300 output relay. “NO” are
normally open contacts which close when the
control output is on. “NC” are normally closed
contacts which open when the control output is
on. If wiring for a heat/cool application, be
sure to wire the heat load across the Output 1
relay and cool load across output 2 relay. Refer
to the diagram below for example wiring.
{
{
{
{
Sensor
Sensor
Sensor
Sensor
off when the sensor falls to the setpoint. Output 2
will turn on when the sensor temperature rises to
the setpoint plus the stage offset plus the differen-
tial-2. Output 2 turns off when the sensor falls to
the setpoint plus stage offset.
1 Stage Heat/1 Stage Cool mode
Output 1 is in "heat" mode and operates identi-
cally to Output 1 described in “heat” mode. Out-
put 2 is in “cool” mode and operates identically to
Output 2 described in “cool” mode above.
Refer to the diagrams below for control logic.
The SP-300 operation is straightforward.
2 Stage Heat mode
Output 1 will turn on when the sensor temperature
falls to the setpoint minus the differential-1 and
turn off when the sensor rises to the setpoint.
Output 2 will turn on when the sensor temperature
falls to the setpoint minus the stage offset minus
the differential-2. Output 2 turns off when the
sensor rises to the setpoint minus stage offset.
2 Stage Cool mode
Output 1 will turn on when the sensor temperature
rises to the setpoint plus the differential-1 and turn
Operation
Operation
Operation
Operation
Operation
The SP300 uses 3 LED indicators to display the
status of the control. The diagram on page 2 shows
the location of each LED. Refer to the chart below
for LED information.
Anti-Cycle
This feature is used to prevent an output from
turning on within 4 minutes of the output turning
off, regardless of temperature. Each output is
independent and has its own Anti-Cycle timer.
The internal timer starts counting immediately
after the control output "satisfies" (output relay
Operation
Operation
Operation
Operation
Operation(Continued)
(Continued)
(Continued)
(Continued)
(Continued)
turn off). The output relay is only allowed to
energize AFTER the timer has completed count-
ing. If the timer hasn't finished counting, the
corresponding Output LED will blink.
NOTE: When input power is first applied to the
control, the Anti-Cycle internal timer automati-
cally starts and will prevent the output relay(s)
from energizing until after the timer has finished
counting.
SP-300E.CDR
Using the optional RSP-30
The RSP-30 is a remote setpoint adjustment and
can be mounted up to 500 feet away from the SP-
300 control. Be sure to move the Setpoint Selec-
tion jumper to the "External" position and the
Setpoint Range to the desired temperature range,
when using the RSP-30. See included instruc-
tions for mounting information. The RSP-30
uses a 3 conductor connection to the SP-300
control. A 3 position screw terminal block on the
RSP-30 is labeled "1", "2", and "3", similar to the
screw terminal located under "R" and "C" on the
SP-300. Using 3 conductor wire, connect each
pair of similarly marked screw terminals. Refer to
the diagram below.
Adjustments
Adjust the setpoint, differential 1, differential 2
and stage offset to the desired settings.
Contact your Goldline Dealer for these accesso-
ries:
• TD-30 - digital display
• TDA-30 - digital display with alarm
• RSP-30 - remote setpoint
• full line of sensors
INDEPENDENT ENERGY INC.
42 Ladd Street,
East Greenwich, RI 02818
(401) 884-6990
(800) 343-0826
(401) 885-1500 fax
P/N 134009A
°F
OHM
°F
OHM
°F
OHM
°F
OHM
°F
OHM
°F
OHM
°F
OHM
-50
491,142
0
85,387
50
19,900
100
5,827
150
2,044
200
829
250
378
-49
472,642
1
82,719
51
19,377
101
5,697
151
2,005
201
815
251
373
-48
454,909
2
80,142
52
18,870
102
5,570
152
1,966
202
802
252
367
-47
437,907
3
77,656
53
18,377
103
5,446
153
1,929
203
788
253
362
-46
421,602
4
75,255
54
17,899
104
5,326
154
1,892
204
775
254
357
-45
405,965
5
72,937
55
17,435
105
5,208
155
1,856
205
763
255
352
-44
390,966
6
70,698
56
16,985
106
5,094
156
1,821
206
750
256
347
-43
376,577
7
68,535
57
16,548
107
4,982
157
1,787
207
738
257
342
-42
362,770
8
66,447
58
16,123
108
4,873
158
1,753
208
726
258
337
-41
349,522
9
64,428
59
15,711
109
4,767
159
1,720
209
714
259
332
-40
336,804
10
62,479
60
15,310
110
4,664
160
1,688
210
702
260
327
-39
324,597
11
60,595
61
14,921
111
4,563
161
1,657
211
691
261
323
-38
312,876
12
58,774
62
14,543
112
4,464
162
1,626
212
680
262
318
-37
301,622
13
57,014
63
14,176
113
4,368
163
1,596
213
669
263
314
-36
290,813
14
55,313
64
13,820
114
4,274
164
1,567
214
658
264
309
-35
280,433
15
53,669
65
13,473
115
4,183
165
1,538
215
648
265
305
-34
270,460
16
52,078
66
13,136
116
4,094
166
1509
216
637
266
301
-33
260,878
17
50,541
67
12,809
117
4,007
167
1,482
217
627
267
296
-32
251,670
18
49,054
68
12,491
118
3,922
168
1,455
218
617
268
292
-31
242,821
19
47,616
69
12,182
119
3,839
169
1,428
219
607
269
288
-30
234,316
20
46,225
70
11,882
120
3,758
170
1,402
220
598
270
284
-29
226,138
21
44,879
71
11,589
121
3,679
171
1,377
221
588
271
280
-28
218,276
22
43,577
72
11,305
122
3,602
172
1,352
222
579
272
276
-27
210,716
23
42,318
73
11,029
123
3,527
173
1,328
223
570
273
273
-26
203,445
24
41,099
74
10,761
124
3,454
174
1,304
224
561
274
269
-25
196,451
25
39,919
75
10,500
125
3,382
175
1,281
225
553
275
265
-24
189,722
26
38,777
76
10,246
126
3,312
176
1,258
226
544
276
262
-23
183,248
27
37,671
77
9,999
127
3,244
177
1,235
227
536
277
258
-22
177,019
28
36,601
78
9,758
128
3,177
178
1,213
228
527
278
255
-21
171,023
29
35,565
79
9,525
129
3,112
179
1,192
229
519
279
251
-20
165,251
30
34,561
80
9,297
130
3,049
180
1,171
230
511
280
248
-19
159,696
31
33,590
81
9,076
131
2,987
181
1,150
231
503
281
244
-18
154,347
32
32,648
82
8,861
132
2,926
182
1,130
232
496
282
241
-17
149,197
33
31,737
83
8,651
133
2,867
183
1,110
233
488
283
238
-16
144,236
34
30,853
84
8,447
134
2,809
184
1,091
234
481
284
235
-15
139,458
35
29,998
85
8,249
135
2,752
185
1,072
235
473
285
232
-14
134,855
36
29,169
86
8,056
136
2,697
186
1,054
236
466
286
229
-13
130,420
37
28,365
87
7,867
137
2,643
187
1,035
237
459
287
225
-12
126,147
38
27,587
88
7,684
138
2,591
188
1,017
238
452
288
223
-11
122,030
39
26,832
89
7,506
139
2,539
189
1,000
239
445
289
220
-10
118,061
40
26,100
90
7,333
140
2,489
190
983
240
439
290
217
-9
114,235
41
25,391
91
7,164
141
2,440
191
966
241
432
291
214
-8
110,547
42
24,704
92
6,999
142
2,392
192
950
242
426
292
211
-7
106,991
43
24,037
93
6,839
143
2,345
193
933
243
420
293
208
-6
103,561
44
23,391
94
6,683
144
2,299
194
918
244
413
294
206
-5
100,254
45
22,764
95
6,530
145
2,254
195
902
245
407
295
203
-4
97,063
46
22,156
96
6,382
146
2,210
196
887
246
401
296
200
-3
93,986
47
21,566
97
6,238
147
2,167
197
872
247
395
297
198
-2
91,017
48
20,993
98
6,097
148
2,125
198
857
248
390
298
195
-1
88,152
49
20,438
99
5,960
149
2,084
199
843
249
384
299
193
300
190
Technical Assistance
Technical Assistance
Technical Assistance
Technical Assistance
Technical Assistance
For help in installing, operating, or troubleshoot-
ing this control, you may call for technical assis-
tance at 800-343-0826. Independent Energy’s
technicians are available from 8:00AM to 5:00PM
Eastern Time, Monday through Friday. You may
call at other times and leave a message, and a
technician will call you back as soon as possible.
Temperature vs. Resistance Chart
Temperature vs. Resistance Chart
Temperature vs. Resistance Chart
Temperature vs. Resistance Chart
Temperature vs. Resistance Chart
All Goldline controls use 10K thermistor sensors.
When disconnected from the control, the sensor
will read 10K ohms at 25ºC/77 F. Refer to the
chart below for the resistance at other tempera-
tures. For a given temperature, the resistance is
accurate to +/- 1%. For a given resistance the
temperature is accurate to +/- 0.5ºF