Dimplex DHW 300D Installation And Operating Instructions Manual
Read Online
Read the Dimplex DHW 300D Installation And Operating Instructions Manual online using the built-in PDF viewer.
Text of the manual
Bestell-Nr. | Order no. | No de commande: 451905.66.02
DE | EN | FR · FD 9912
DHW 300D
DHW 300D+
Montage- und
Gebrauchsanweisung
WarmWasser-
Wärmepumpe
für Innenaufstellung
Installation and
Operating Instruction
Hot Water
Heat Pump for
Indoor Installation
Instuctions d‘installation
et d‘utilisation
Chauffee-eau
thermodynamique
d‘intérieur
Glen
Dimplex
Thermal
Solutions
Dimplex
451905.66.02 · FD 9912
DE-1
DHW 300D - DHW 300D+
Deutsch
Inhaltsverzeichnis
1
Bitte sofort lesen .........................................................................................................................................DE-2
1.1
Wichtige Hinweise ...........................................................................................................................................................DE-2
1.2
Bestimmungsgemäßer Gebrauch..............................................................................................................................DE-2
1.3
Vorschriften / Sicherheitshinweise............................................................................................................................DE-2
2
Beschreibung ...............................................................................................................................................DE-3
2.1
Allgemein............................................................................................................................................................................DE-3
2.2
Kältemittelkreislauf (Funktionsprinzip der Wärmepumpe) ................................................................................DE-3
2.3
Sicherheits- und Regeleinrichtungen .......................................................................................................................DE-4
2.4
Temperaturfühler.............................................................................................................................................................DE-4
3
Lagerung und Transport............................................................................................................................DE-5
3.1
Allgemein............................................................................................................................................................................DE-5
3.2
Transport mit Gabelstapler (oder Hubwagen)........................................................................................................DE-5
3.3
Transport von Hand (Auslieferungszustand) ..........................................................................................................DE-5
3.4
Transport im Tragesack (Zubehör mit Sicherungsblech) ...................................................................................DE-5
3.5
Öffnen des Gerätes .........................................................................................................................................................DE-6
4
Aufstellung....................................................................................................................................................DE-6
4.1
Aufstellungsort..................................................................................................................................................................DE-6
4.2
Aufstellung .........................................................................................................................................................................DE-6
5
Montage.........................................................................................................................................................DE-7
5.1
Anschluss der Wasserleitungen..................................................................................................................................DE-7
5.2
Anschluss der Kondensatleitung................................................................................................................................DE-7
5.3
Elektrischer Anschluss ...................................................................................................................................................DE-7
5.4
Anschluss Luftkanal (optional).....................................................................................................................................DE-7
6
Inbetriebnahme ...........................................................................................................................................DE-8
6.1
Warmwasserkreislauf......................................................................................................................................................DE-8
7
Bedienung und Funktion der Warmwasser-Wärmepumpe..............................................................DE-8
7.1
Bedienung und Display..................................................................................................................................................DE-8
7.2
Menüstruktur.....................................................................................................................................................................DE-9
7.3
Funktionen ......................................................................................................................................................................DE-12
8
Wartung / Instandhaltung...................................................................................................................... DE-13
8.1
Wasserkreislauf / Kondensatablauf........................................................................................................................DE-13
8.2
Luftkreisversorgung .....................................................................................................................................................DE-13
8.3
Korrosionsschutzanode..............................................................................................................................................DE-14
9
Störungen / Fehlersuche (für den Nutzer)......................................................................................... DE-14
10 Außerbetriebnahme ................................................................................................................................ DE-14
11 Umweltrelevante Anforderungen ........................................................................................................ DE-14
12 Geräteinformation.................................................................................................................................... DE-15
13 Garantieurkunde....................................................................................................................................... DE-17
Anhang · Appendix · Annexes............................................................................................................................. A-I
Maßbild / Dimension drawing / Schéma coté ......................................................................................................... A-II
Einbindungsschemen / Integration diagram / Schéma d'intégration.............................................................. A-III
Elektroschema / Electrical circuit diagram / Schéma électrique ....................................................................... A-V
Konformitätserklärung / Declaration of Conformity / Déclaration de conformité .......................................A-VI
451905.66.02 · FD 9912
www.gdts.one
Deutsch
DHW 300D - DHW 300D+
1
Bitte sofort lesen
1.1
Wichtige Hinweise
ACHTUNG!
!
Vor
Inbetriebnahmen
ist
diese
Montage-
und
Gebrauchsanweisung zu lesen!
ACHTUNG!
!
Arbeiten an der Warmwasser-Wärmepumpe dürfen nur von
fachkundigen
Personen
ausgeführt
werden!
Unfallverhütungsvorschriften sind zu beachten!
ACHTUNG!
!
Die Gerätehaube ist nicht für den Tragevorgang nutzbar (die
Haube kann keine größeren Kräfte aufnehmen!)
ACHTUNG!
!
Nach
dem
Aufstellen
der
Wärmepumpe
muss
das
Sicherungsblech entfernt werden!
ACHTUNG!
!
Die Wärmepumpe darf nicht Überkopf transportiert werden.
ACHTUNG!
!
Bei
Erstellung
der
bauseitigen
Verrohrung
sind
Verschmutzungen im Leitungssystem zu vermeiden (evtl. vor
Anschluss der Warmwasser-Wärmepumpe Leitungen spülen)!
ACHTUNG!
!
Die Warmwasser-Wärmepumpe darf nur im mit Wasser
befüllten Zustand betrieben werden!
ACHTUNG!
!
Für den Kollektorfühler muss ein Temperaturfühler mit der
Widerstandskennlinie eines PT1000 (siehe Kap. 2.4.2 auf S. 4)
verwendet werden.
ACHTUNG!
!
Vor dem Öffnen der Warmwasser-Wärmepumpe ist diese
spannungsfrei zu schalten, auf nachlaufenden Ventilator ist
zu achten!
ACHTUNG!
!
Verletzungsgefahr durch scharfkantige Lamellen. Lamellen
dürfen nicht deformiert oder beschädigt werden!
ACHTUNG!
!
Vor öffnen des Gerätes ist dieses Spannungsfrei zu schalten.
ACHTUNG!
!
Die Klemme X8 kann auch in ausgeschalteten Zustand der
Wärmepumpe unter Spannung stehen
ACHTUNG!
!
Bei Einstellungen zur Nutzung von Photovoltaikenergie,
Solarthermie
oder
einem
externen
Kessel
sind
Warmwassertemperaturen >60°C möglich und deshalb ist ein
externer Verbrühschutz vorzusehen.
1.2
Bestimmungsgemäßer
Gebrauch
Dieses Gerät ist nur für den vom Hersteller vorgesehenen Ver-
wendungszweck freigegeben. Ein anderer oder darüber hinaus
gehender Gebrauch gilt als nicht bestimmungsgemäß. Dazu
zählt auch die Beachtung der zugehörigen Projektierungsunter-
lagen. Änderungen oder Umbauten am Gerät sind zu unterlas-
sen.
1.3
Vorschriften /
Sicherheitshinweise
ACHTUNG!
!
Vor
Inbetriebnahmen
ist
diese
Montage-
und
Gebrauchsanweisung zu lesen!
Die Warmwasser-Wärmepumpe dient ausschließlich zur
Erwärmung von Brauch- bzw. Trinkwasser in den angege-
benen Temperatureinsatzgrenzen! Die Erwärmung anderer
Flüssigkeiten als Trinkwasser ist nicht zulässig. Die techni-
schen Regeln für die Trinkwasserinstallation sind zu beach-
ten. Die Leitungsnennweiten für die bauseitige Sanitärins-
tallation
sind
unter
Berücksichtigung
der
gebäudespezifischen Anforderungen festzulegen und gel-
tenden Richtlinien und Vorschriften auszuführen. Gegebe-
nenfalls erforderliche Sicherheitseinrichtungen wie Druck-
minderventile sind spezifisch zu installieren.
Nicht erlaubt ist:
Die Aufstellung des Gerätes darf nicht erfolgen:
Unzulässig ist der Betrieb des Gerätes:
Bei der Konstruktion und Ausführung der Warmwasser-
Wärmepumpe wurden die relevanten EU-Richtlinien ein-
gehalten. (Siehe auch CE-Konformitätserklärung.)
Der Sachkundige hat dafür zu sorgen, dass vor Beginn von
Instandhaltungs-/Instandsetzungsarbeiten an kältemittel-
führenden Teilen, das Kältemittel soweit entfernt wird, wie
dies für die gefahrlose Durchführung der Arbeiten notwen-
dig ist. Kältemittel ist vorschriftsmäßig zu handhaben bzw.
zu entsorgen, es darf nicht in die Umwelt gelangen!
Der Kältekreis ist „hermetisch geschlossen“ und enthält
das vom Kyoto-Protokoll erfasste fluorierte Kältemittel
R134a. Angaben zum GWP-Wert und CO2-Äquivalent des
- der Betrieb mit lösemittelhaltiger oder explosiver Abluft
- Nutzung fetthaltiger, staubbelasteter oder mit klebender
Aerosole belasteter Abluft
- der Anschluss von Dunstabzugshauben an das
Lüftungssystem
- im Freien
- in frostgefährdeten Räumen
- in Nassräumen (z.B. Badezimmer)
- in Räumen die durch Gase, Dämpfe oder Staub
explosionsgefährdet sind
- mit leerem Speicherbehälter
- in der Bauphase des Gebäudes
451905.66.02 · FD 9912
DE-3
DHW 300D - DHW 300D+
Deutsch
Kältemittels finden sich im Kapitel Geräteinformation. Es ist
FCKW-frei, baut kein Ozon ab und ist nicht brennbar.
Nähere Angaben dazu finden sich im beiliegenden Log-
buch.
Bei Arbeiten an der Warmwasser-Wärmepumpe ist diese
immer spannungsfrei zu schalten.
Bei dem elektrischen Anschluss der Warmwasser-Wärme-
pumpe sind die entsprechenden VDE-, EN- bzw. IEC-Nor-
men einzuhalten. Darüber hinaus sind die technischen An-
schlussbedingungen
der
Energie-
Versorgungsunternehmen zu beachten.
Diese Wärmepumpe ist gemäß Artikel 1, Abschnitt 2 k) der
EU-Richtlinie 2006/42/EG (Maschinenrichtlinie) für den
Gebrauch im häuslichen Umfeld bestimmt und unterliegt
damit den Anforderungen der EU-Richtlinie 2014/35/EU
(Niederspannungsrichtlinie). Sie ist damit ebenfalls für die
Benutzung durch Laien zur Bereitung von Brauchwasser
für Läden, Büros und anderen ähnlichen Arbeitsumgebun-
gen, von landwirtschaftlichen Betrieben und Hotels, Pensi-
onen und ähnlichen oder anderen Wohneinrichtungen vor-
gesehen.
ACHTUNG!
!
Arbeiten an der Warmwasser-Wärmepumpe dürfen nur von
fachkundigen Personen ausgeführt werden!
Unfallverhütungsvorschriften sind zu beachten!
2
Beschreibung
2.1
Allgemein
Die Warmwasser-Wärmepumpe ist ein anschlussfertiges Heiz-
gerät und besteht im Wesentlichen aus dem Warmwasserspei-
cher, den Komponenten des Kältemittel-, Luft- und Wasser-
kreislaufes sowie allen für den automatischen Betrieb
erforderlichen Steuer-, Regel- und Überwachungseinrichtun-
gen.
Die Warmwasser-Wärmepumpe nutzt, unter Zuführung elektri-
scher Energie, die Wärme der angesaugten Luft für die Warm-
wasserbereitung. Der innere optionale Wärmetauscher ist für
den Anschluss an einen zusätzlichen Wärmeerzeuger geeignet,
wie Heizkessel oder Solaranlage. Die Geräte sind serienmäßig
mit einer Elektroheizung (1,5 kW) ausgerüstet.
Maßgebend für den Energiebedarf und die Aufheizdauer für die
Warmwasserbereitung ist die Temperatur der angesaugten Luft
der Wärmequelle und die Warmwassertemperatur.
Aus diesem Grunde kann zur gezielten Abwärmenutzung an
den serienmäßigen Stutzen der Warmwasser-Wärmepumpe
ein Luftkanalsystem (DN 160, max. Länge 10 m) angeschlossen
werden. Grundsätzlich muss für einen effektiven Wärmepum-
penbetrieb, ein Luftkurzschluss zwischen angesaugter und
ausgeblasener Luft vermieden werden. Eine mögliche Variante
ist z.B. der Einsatz eines Bogens auf der Ansaug- und Aus-
blasseite.
Mit fallender Ablufttemperatur sinkt die Wärmepumpenheiz-
leistung und es verlängert sich die Aufheizdauer. Für einen wirt-
schaftlichen Betrieb sollte die Luftansaugtemperatur 15 °C
nicht dauerhaft unterschreiten.
Die Elektroheizung erfüllt folgende Funktionen:
Zusatzheizung
Mit der Taste "Boost" kann für eine einstellbare Dauer die
Warmwasserbereitung mit Unterstützung der Elektrohei-
zung erfolgen.
Einsatzgrenze
Sinkt die Lufteintrittstemperatur unter -7 ±1,0 °C, schaltet
sich die Elektroheizung automatisch ein und erwärmt das
Wasser (nominal) bis zur eingestellten Sollwert-Warmwas-
sertemperatur.
Notheizung
Bei einer Störung der Wärmepumpe kann durch die Elekt-
roheizung die Warmwasserversorgung aufrecht erhalten
werden.
Vorbeugende thermische Desinfektion
An der Bedienfeldtastatur können im Menüpunkt thermi-
sche Desinfektion Wassertemperaturen über 60 °C (bis
85 °C) programmiert werden.
Nacherwärmung
Wassertemperaturen über 60 °C werden mit der Elektro-
heizung erreicht.
HINWEIS
�
Bei Warmwassertemperaturen > 60 °C wird die Wärmepumpe
abgeschaltet, und die Warmwasserbereitung erfolgt nur über
die Elektroheizung. Werkseitig ist der Heizstabregler auf 65 °C
eingestellt.
2.2
Kältemittelkreislauf
(Funktionsprinzip der
Wärmepumpe)
Der Kältemittelkreislauf ist ein geschlossenes System in dem
das Kältemittel R134a als Arbeitsmittel fungiert. Im Lamel-
lentauscher wird der angesaugten Luft bei niedriger Verdamp-
fungstemperatur die Wärme entzogen und an das Kältemittel
übertragen. Das dampfförmige Kältemittel wird von einem Ver-
dichter angesaugt und auf ein höheres Druck-/Temperaturni-
veau verdichtet und zum Verflüssiger transportiert, wo die im
Verdampfer aufgenommene Wärme und ein Teil der aufge-
nommenen Verdichterenergie an das Wasser abgegeben wird.
Anschließend wird der hohe Verflüssigungsdruck mittels eines
Drosselorgans (Expansionsventil) bis auf den Verdampfungs-
druck entspannt und das Kältemittel kann im Verdampfer wie-
der Wärme aus der angesaugten Luft aufnehmen.
451905.66.02 · FD 9912
www.gdts.one
Deutsch
DHW 300D - DHW 300D+
2.3
Sicherheits- und
Regeleinrichtungen
Die Warmwasser-Wärmepumpe ist mit folgenden Sicherheits-
einrichtungen ausgerüstet:
Hochdruckpressostat (HD)
Der Hochdruckpressostat schützt die Wärmepumpe vor unzu-
lässig hohem Betriebsdruck im Kältemittelkreislauf. Im Störfall
schaltet der Pressostat die Wärmepumpe ab. Die Wiederein-
schaltung der Wärmepumpe erfolgt zeitverzögert nach Druck-
absenkung im Kältemittelkreislauf.
Sicherheitstemperaturbegrenzer für Elektroheizung
(STB)
Der STB verhindert die Erzeugung unzulässig hoher Tempera-
turen im Warmwasserspeicher.
Bei Überschreitung des eingestellten Schaltwertes (99 °C) wird
die Elektroheizung abgeschaltet.
Eine Wiedereinschaltung der Elektroheizung ist erst möglich,
wenn die Warmwassertemperatur auf 90 °C abgesunken ist
und danach der Rückstellknopf (siehe Bild) am STB (unter Flan-
schabdeckung) gedrückt wird (darf nur von fachkundigen Per-
sonen erfolgen!).
Die Warmwasser-Wärmepumpe ist weiter mit folgenden Regel-
und Steuerungseinrichtungen ausgerüstet:
Temperaturregelung-Wärmepumpe
Die Temperaturkontrolle im Warmwasserspeicher und die Re-
gelung für den Verdichterbetrieb übernimmt die Steuerelektro-
nik. Elektronische Fühler erfassen die Wassertemperatur, diese
wird in Abhängigkeit vom eingestellten Sollwert geregelt. Die
Einstellung des gewünschten Temperaturniveaus (Sollwert) er-
folgt über die Tastatur an der Bedienblende.
Lufteintrittstemperatur
Der an die Regelung angeschlossene Fühler erfasst die Tempe-
ratur in der Warmwasser-Wärmepumpe direkt vor dem Ver-
dampfer (Luftansaugtemperatur). Bei einer Unterschreitung
des fest eingestellten Schaltwertes (-7 ±1 °C, Rückschaltwert 2
K,
Verzögerung 30 min) wird die Warmwasserbereitung automa-
tisch vom Wärmepumpenbetrieb auf Heizstabbetrieb umge-
schaltet.
2.4
Temperaturfühler
2.4.1 Einbaulage Temperaturfühler
R1
Fühler Lufteintritt
R3 Fühler Warmwasser
R5 Fühler Warmwasser regenerativ (optional)
R12
Fühler Abtauende
R13 Fühler Regenerativ (optional)
2.4.2 Messwerte Temperaturfühler
Messwerte NTC 10 Fühler (R1, R3, R5, R12)
Messwerte PT 1000 Fühler (R13)
85°
30°
F17
STB
Rückstellknopf
Temperatur in °C
-20
-15
-10
-5
0
5
10
NTC-10 in k
67,7
53,4
42,3
33,9
27,3
22,1
18,0
15
20
25
30
35
40
45
50
55
60
14,9
12,1
10,0
8,4
7,0
5,9
5,0
4,2
3,6
3,1
Temperatur in °C -30 -20 -10
0
10
20
30
40
50
PT 1000 in k
0,88
2
0,02
2
0,96
1
1,00
1,03
9
1,07
8
1,11
7
1,15
5
1,19
4
60
70
80
90 100 110 120 130 140 150 160
1,23
2
1,27
1
1,30
9
1,34
7
1,38
5
1,42
3
1,46
1
1,49
8
1,53
6
1,57
3
1,61
1
451905.66.02 · FD 9912
DE-5
DHW 300D - DHW 300D+
Deutsch
3
Lagerung und Transport
3.1
Allgemein
Grundsätzlich ist die Warmwasser-Wärmepumpe verpackt und
stehend ohne Wasserfüllung zu lagern bzw. zu transportieren.
Für kurze Wege ist eine Schräglage bis 45° bei vorsichtigem
Transport erlaubt. Sowohl beim Transportieren als auch bei der
Lagerung sind Umgebungstemperaturen von -20 bis +60 °C
zulässig.
3.2
Transport mit Gabelstapler
(oder Hubwagen)
Für den Transport mit Gabelstaplern muss die Warmwasser-
Wärmepumpe auf der Palette montiert bleiben. Die Hubge-
schwindigkeit ist klein zu halten. Bedingt durch die Kopflastig-
keit muss die Warmwasser-Wärmepumpe gegen Umfallen ge-
sichert werden. Um Schaden zu vermeiden, hat das Absetzen
der Warmwasser-Wärmepumpe auf einer ebenen Fläche zu er-
folgen.
3.3
Transport von Hand
(Auslieferungszustand)
Für den Transport von Hand kann im unteren Bereich die Holz-
palette verwendet werden. Mit der Zuhilfenahme von Seilen
oder Tragegurten (diese können um den Speichermantel gelegt
und an den Wasserrohrnippeln fixiert werden) kann eine zweite
oder dritte Trageposition bestimmt werden. Bei diesem Trans-
portvorgang (auch bei Transport mit Sackkarre) ist darauf zu
achten die max. zulässige Schräglage von 45° nicht zu über-
schreiten (siehe Bild).
ACHTUNG!
!
Die Gerätehaube ist nicht für den Tragevorgang nutzbar (die
Haube kann keine größeren Kräfte aufnehmen!)
3.4
Transport im Tragesack
(Zubehör mit Sicherungsblech)
Unter Zuhilfenahme des Zubehörs Tragesack ist es möglich, die
Wärmepumpe liegend innerhalb des Gebäudes zu transportie-
ren. Dazu ist die Haube abzunehmen und das dem Tragesack
beiliegende Sicherungsblech zu montieren. Dieses wird zwi-
schen der Transportöse des Verdichters und der Trennwand
mit dem mitgelieferten Montagematerial befestigt.
ACHTUNG!
!
Nach
dem
Aufstellen
der
Wärmepumpe
muss
das
Sicherungsblech entfernt werden!
Es ist darauf zu achten, dass das Gerät während des gesamten
Tragevorgangs nicht Überkopf transportiert wird.
ACHTUNG!
!
Die Wärmepumpe darf nicht Überkopf transportiert werden.
45°
Sicherungsblech an
Trennwand befestigt
Sicherungsblech
Sicherungsblech am
Verdichter befestigt
Auflagefläche
Wärmepumpe
im Tragesack
451905.66.02 · FD 9912
www.gdts.one
Deutsch
DHW 300D - DHW 300D+
3.5
Öffnen des Gerätes
Die Gerätehaube ist zweigeteilt. Um an das Geräteinnere zu ge-
langen oder zur Erleichterung des Transports (Vermeidung von
Schäden) ist es möglich, beide Haubenteile abzunehmen. Dazu
sind die vier Verriegelungen mit Viertelverdrehungen gegen
den Uhrzeigersinn zu öffnen (das nach vorne gerichtete
Schloss-Symbol zeigt den Zustand der Verriegelung an).
Danach kann die Fronthaube nach vorne abgenommen wer-
den.
Um die Luftführungshaube abzunehmen, sind die beiden Ver-
schlussschrauben zu entfernen. Danach kann die Haube nach
hinten abgenommen werden.
4
Aufstellung
4.1
Aufstellungsort
Für die Wahl des Gerätestandortes gilt:
Die Warmwasser-Wärmepumpe muss in einem frostfreien
und trockenen Raum aufgestellt werden.
Die Aufstellung und die Luftansaugung darf ferner nicht in
Räumen erfolgen, die durch Gase, Dämpfe oder Staub ex-
plosionsgefährdet sind.
Zur Vermeidung von Feuchteschäden an Innenwänden ist
eine gute Wärmeisolierung des Raumes in den die Aus-
blasluft eingeleitet wird zu angrenzenden Wohnräumen
empfehlenswert.
Ein Wasserablauf (mit Siphon) für das anfallende Konden-
sat muss vorhanden sein.
Die angesaugte Luft darf nicht übermäßig verunreinigt
bzw. stark staubbelastet sein.
Der Untergrund muss eine ausreichende Tragfähigkeit auf-
weisen (Gewicht Warmwasser-Wärmepumpe befüllt ca.
420 kg!).
Für einen störungsfreien Betrieb, sowie für Wartungs- und Re-
paraturarbeiten sind Mindestabstände von 0,6 m links und
rechts vom Gerät erforderlich (siehe Bild). Die Verbindung zur
Warmwasser-Wärmepumpe erfolgt (optional) mit EPP-Luftlei-
tungen NW 160 mm innen, 190 mm außen, die eine Länge von
insgesamt 10 m nicht überschreiten dürfen
Bei nicht eingesetzten Luftleitungen kann für einen schallopti-
mierten Betreib ausblasseitig ein nach unten gerichteter 90°
EPP-Bogen eingesetzt werden (siehe Bild)
4.2
Aufstellung
Die drei Transportsicherungsschrauben (M12 – verbinden
Palette mit Gerät) von der Palettenunterseite her entfer-
nen.
Palette entfernen und die drei Stellfüße (M12 – im Poly-
beutel am Speicherrohrnippel fixiert) montieren.
Warmwasser-Wärmepumpe platzieren und durch Verstel-
len der Gerätefüße Warmwasser-Wärmepumpe lotrecht
ausrichten! Anschließend die Kontermuttern an Gerätefü-
ßen festziehen.
min. 0,6 m
min. 0,6 m
90° EPP-Bogen
(Zubehör)
Bedienseite
min. 0,3 m
451905.66.02 · FD 9912
DE-7
DHW 300D - DHW 300D+
Deutsch
5
Montage
5.1
Anschluss der Wasserleitungen
Die Wasseranschlüsse siehe Maßbild (Kap. 1 auf S. II) befinden
sich an der Geräterückseite.
HINWEIS
�
Zirkulationsleitung
Aus energetischer Sicht sollte möglichst auf die Ausführung
einer Zirkulationsleitung verzichtet werden. Bei Anschluss
einer Zirkulationsleitung für das Warmwasserverteilsystem
muss diese, um unnötige Energieverluste zu vermeiden,
durch ein Ventil oder eine ähnliche Einrichtung absperrbar
ausgeführt werden. Die Freischaltung der Zirkulation erfolgt
nutzungsabhängig (Zeit- oder Bedarfsteuerung).
Die Leitungsnennweiten für die bauseitige Sanitärinstallation
sind unter Berücksichtigung des verfügbaren Wasserdruckes
und der zu erwartenden Druckverluste im Rohrleitungssystem
festzulegen.
Die technischen Regeln für die Trinkwasserinstallation sind zu
beachten. Die Leitungsnennweiten für die bauseitige Sani-
tärinstallation sind unter Berücksichtigung der gebäudespezifi-
schen Anforderungen festzulegen und geltenden Richtlinien
und Vorschriften auszuführen. Gegebenenfalls erforderliche Si-
cherheitseinrichtungen wie Druckminderventile sind spezifisch
zu installieren.
Die Wasserleitungen können in fester oder flexibler Bauart aus-
geführt werden. Das Korrosionsverhalten der verwendeten Ma-
terialien im Rohrleitungssystem ist zu beachten, um Schäden
durch Korrosion zu vermeiden (siehe Abschnitt Inbetrieb-
nahme).
HINWEIS
�
Anschlüsse Warmwasser, Kaltwasser, Zirkulation:
In diesen Rohrnippeln befinden sich Kunststoffeinsätze, die
dem Korrosionsschutz (speziell der Rohrnippelstirnflächen)
dienen. Diese Kunststoffeinsätze verbleiben nach der
Montage der Wasserleitungen in ihrer Position.
ACHTUNG!
!
Bei
Erstellung
der
bauseitigen
Verrohrung
sind
Verschmutzungen im Leitungssystem zu vermeiden (evtl. vor
Anschluss der Warmwasser-Wärmepumpe Leitungen spülen)!
5.2
Anschluss der
Kondensatleitung
Der Kondensatschlauch ist an der Geräterückseite durch den
Mantel geführt. Der Kondensatschlauch ist so zu verlegen, dass
das (im Wärmepumpenbetrieb) anfallende Kondensat ohne Be-
hinderung abfließen kann.
Am Kondensatschlauchende befindet sich ein drucklos öffnen-
des Dichtlippenventil, das bei Kürzung des Kondensatschlau-
ches mit versetzt werden muss (Ventil lässt sich leicht entfer-
nen und wieder einfügen). Das Kondensat ist in einen Siphon
abzuleiten (siehe hierzu auch Wartungshinweis unter 8.1).
HINWEIS
�
Das Dichtlippenventil muss eingesetzt sein, um Schäden
durch Kondensat zu vermeiden.
5.3
Elektrischer Anschluss
Die Warmwasser-Wärmepumpe ist anschlussfertig vorverdrah-
tet. Die Stromversorgung erfolgt über die Netzanschlussleitung
zu einer Schutzkontaktsteckdose (~230 V, 50 Hz). Auch nach
der Installation muss diese Steckdose zugänglich sein. Für die
Ansteuerung externer Geräte, z.B. für den zweiten Wärmeer-
zeuger, die Solarumwälzpumpe oder den Temperaturfühler
vom Kollektor, muss eine separate Leitung in das Gerät, durch
eine freie Kabelverschraubung, eingeführt und zugentlastet
werden. Dazu ist die Gerätehaube wie in Kap. 3.5 auf S. 6 be-
schrieben zu öffnen. Die jeweiligen Anschusspunkte der Kom-
ponenten sind dem Elektroschema Kap. 3 auf S. V und der
Elektrodokumentation zu entnehmen.
5.4
Anschluss Luftkanal (optional)
Das Gerät ist für den Anschluss eines EPP-Luftkanals (Einzel-
teile als Zubehör erhältlich DN 160 innen) ausgelegt. Durch die
90°-Stellung der beiden Anschlussstutzen sind die verschie-
densten Kanalführungen möglich.
451905.66.02 · FD 9912
www.gdts.one
Deutsch
DHW 300D - DHW 300D+
6
Inbetriebnahme
6.1
Warmwasserkreislauf
ACHTUNG!
!
Die Warmwasser-Wärmepumpe darf nur im mit Wasser
befüllten Zustand betrieben werden!
Anforderungen an den Warmwasserkreislauf
Verbraucherseitig können folgende Materialien im Warmwas-
serkreislauf eingebaut sein:
Kupfer
Edelstahl
Messing
Kunststoff
Abhängig von den eingesetzten Materialien des Warmwasser-
kreislaufes (kundenseitige Installation), können Materialunver-
träglichkeiten zu Korrosionsschäden führen. Dies ist besonders
bei Verwendung von verzinkten und aluminiumhaltigen Werk-
stoffen zu beachten. Besteht während des Betriebes die Ge-
fahr, dass das Wasser Verschmutzung beinhaltet, ist gegebe-
nenfalls ein Filter vorzusehen.
Inbetriebnahme der Warmwasseranlage
Alle Installationen am Wasser- und Luftkreis sowie alle
Elektroinstallationen müssen ordnungsgemäß und voll-
ständig ausgeführt worden sein
Warmwasserkreislauf über externen Anschluss befüllen.
Warmwasserkreislauf entlüften (Warmwasserhähne an den
obersten Entnahmestellen öffnen, bis keine Luft mehr fest-
zustellen ist).
Gesamten Warmwasserkreislauf auf Dichtheit prüfen.
Spannungsversorgung herstellen.
„Wärmepumpe“ einschalten.
Die gewünschte Warmwassertemperatur (z.B. 45 °C) wird
an der Tastatur eingestellt (Kap. 7 auf S. 8). Bis zum Errei-
chen des gewählten Temperaturniveaus ist immer eine
entsprechende Aufladezeit erforderlich.
7
Bedienung und Funktion der
Warmwasser-Wärmepumpe
7.1
Bedienung und Display
7.1.1 Beschreibung Tastenfunktion
7.1.2 Beschreibung Bereitschaftsanzeige
Taste
Name
Beschreibung
Menü
Wechsel in das Hauptmenü, hier können detail-
lierte Einstellungen für die Wärmepumpe vor-
genommen werden.
Boost
Schnellheizen
Heizstab wird aktiviert und arbeitet bis zum ein-
gestellten Warmwassersollwert für maximal
4 Stunden
Esc
ESC
Rücksprung in die nächsthöher gelegene
Menüebene
OK
Beginn und Abschluss der Änderung eines
Parameters bzw. Auswahl des gewünschten
Menüpunktes
AUF
Wertänderung nach oben, bzw. Auswahl Menü
und Parameter
Sonderfunktion in der Startmaske: Erhöhung
Warmwassersollwert
AB
Wertänderung nach unten, bzw. Auswahl Menü
und Parameter
Sonderfunktion in der Startmaske: Verringe-
rung Warmwassersollwert
Kopfzeile:
Gerätetyp, Wochentag, Uhrzeit
Hauptfeld:
Informationsübersicht in Klartext
451905.66.02 · FD 9912
DE-9
DHW 300D - DHW 300D+
Deutsch
7.2
Menüstruktur
Parameteränderung: Mit der Taste „Menü“ gelangt man ins
Menü. Hier können Änderungen an Parametern vorgenommen
werden. Mit den Pfeiltasten „AUF“ „AB“ wird der gewünschte
Menüpunkt ausgewählt. Mit der Taste „OK“ gelangt man dann
in das Untermenü.
Hier kann ebenfalls über die Pfeiltasten der zu verstellende Pa-
rameter ausgewählt werden. Mit der Taste „OK“ wird der mar-
kierte Wert ausgewählt und dann über die Pfeiltasten geändert.
Durch erneutes Drücken der Taste „OK“ wird die Eingabe ab-
geschlossen.
Menüblock
Menüpunkt
Parameter
Wert
Beschreibung
Einstellungen
Uhrzeit
00:00
Einstellung Zeit (24h Zeitform)
Datum
TT:MM:JJJJ
Einstellung Datum (Tag:Monat:Jahr)
Sprache
DEUTSCH
ENGLISCH
FRANCAIS
ITALIANO
POLSKI
Sprachauswahl
Signalton
Ein
Aus
Einstellung Tasten-Ton an / aus
Hintergrundbel.
0 % ... 50 % ...100 %
Einstellung Hintergrundbeleuchtung Display
Werkseinstellung
Zurücksetzen der Werkseinstellung
Typ
DHW 300
DHW 300+
DHW 300D
DHW 300D+
Brauchwasserwärmepumpe DHW 300
Brauchwasserwärmepumpe DHW 300+
mit Zusatz-Wärmetauscher
Brauchwasserwärmepumpe DHW 300D
mit Abtaufunktion
Brauchwasserwärmepumpe DHW 300D+
mit Abtaufunktion und Zusatz-Wärmetauscher
Warmwasser
Solltemperatur
25 °C ... 45 °C ... 85 °C
Einstellung der gewünschten Warmwasser-Solltemperatur
Absenkung
15 °C ... 25 °C ... 40 °C
Einstellung der minimalen Warmwasser-Temperatur, die
auch während einer programmierten Absenkung nicht unter-
schritten werden soll
Hysterese
2 K ... 3 K ... 10 K
Einstellung der Schalt-Hysterese
Elektroheizung
Modus
Verzögerung
Boost Dauer
Boost Solltemp.
ECO
AUTO
2 h ... 8 h...16 h
1 h ... 4 h ... 8 h
25 °C ... 60 °C ... 85 °C
ECO: Schaltet nur im Fehlerfall sowie bei PV u./o,. thermi-
scher Desinfektion ein
Die Elektroheizung wird anutomatisch eingeschaltet, wenn
die Warmwassersolltemperatur im Wärmepumpenbetrieb
nicht erreicht wird.
Boost: einstellbare Zeit (einmalig, unabhängig von der Ein-
stellung Auto/Eco)
Boost: einstellbare Solltemperatur
Zeitprogramme
Therm. Desinfektion
Thermische Desinfektion
Start
00:00 ... 23:59
Einstellung der Startzeit für eine thermische Desinfektion
(24h Zeitformat)
Tage
Mo ... So
Einstellung an welchem Tag die thermische Desinfektion
aktiviert werden soll
Sollwert
60 °C ... 65 °C ... 85 °C
Einstellung der Solltemperatur für eine thermische Desinfek-
tion
1. Absenkung
Start
00:00 ... 23:59
Einstellung der Startzeit für eine Absenkung der Warmwas-
ser-Solltemperatur
Ende
00:00 ... 23:59
Einstellung der Endezeit für eine Absenkung der Warmwas-
ser-Solltemperatur
Tage
So ... Mo
Mo - Fr
Sa - So
Mo - So
Einstellung an welchem Wochentag / Tagblock die Absen-
kung aktiviert sein soll
2.Absenkung
451905.66.02 · FD 9912
www.gdts.one
Deutsch
DHW 300D - DHW 300D+
Start
00:00 ... 23:59
Einstellung der Startzeit für eine Absenkung der Warmwas-
ser-Solltemperatur
Ende
00:00 ... 23:59
Einstellung der Endezeit für eine Absenkung der Warmwas-
ser-Solltemperatur
Tage
So ... Mo
Mo - Fr
Sa - So
Mo - So
Einstellung an welchem Wochentag / Tagblock die Absen-
kung aktiviert sein soll
(nur sichtbar bei Geräten mit Zusatzwärmetauscher und Auswahl AUS oder Sol
Solar
Auswahl
Aus
Bivalent
Sol
Auswahl der zusätzlichen Wärmequelle
Aus: (keine zus. Wärmequelle)
Bivalent: 2. Wärmeerzeuger, z. B. Öl, Gas- oder Holzkessel
Sol: Thermische Solaranlage
Einschaltdifferenz
6 K ... 8 K ... 10 K
Einstellung der Temperaturdifferenz zwischen Kollektor und
Speichertemperatur, bei der die Solarpumpe eingeschaltet
werden soll
Ausschaltdifferenz
2 K ... 4 K ... 6 K
Einstellung der Temperaturdifferenz zwischen Kollektor und
Speichertemperatur, bei der die Solarpumpe ausgeschaltet
werden soll
max. Speichertemp.
60 °C ... 65 °C ... 85 °C
Einstellung der maximal zulässigen Speichertemperatur,
wenn solarer Ertrag vorhanden ist
max. Kollektortemp.
125 °C ... 130 °C ... 135 °C Einstellung der maximal zulässigen Temperatur am Kollektor
(nur sichbar bei Geräten mit Zusatzwärmetauscher und Auswahl AUS oder Bivalent)
2. Wärmeerzeuger
Auswahl
Aus
Bivalent
Sol
Auswahl der zusätzlichen Wärmequelle
Aus: (keine zus. Wärmequelle)
Bivalent: 2. Wärmeerzeuger, z. B. Öl, Gas- oder Holzkessel
Sol: Thermische Solaranlage
Bivalenztemperatur
-8 °C ... 10 °C ... 15 °C
Grenztemperatur für den 2. Wärmeerzeuger. Unterhalb die-
ser Temperatur ist die Wärmepumpe gesperrt
Photovoltaik
Elektroheizung
Ja
Nein
Aktivierung der Elektroheizung (parallel zur Wärmepumpe) im
Photovoltaikbetrieb
Solltemperatur
35 °C ... 45 °C ... 60 °C
Eingabe des Warmwasser-Sollwertes, die bei Beschaltung
des Photovoltaikeingangs aktiv ist. Der erhöhte Sollwert ist
auch aktiv, wenn die Luftansaugtemperatur den Betrieb der
Wärmepumpe nicht erlaubt. Die Anforderung wird in dem
Fall mit dem elektrischen Heizstab oder, sofern vorhanden,
mit dem 2. Wärmeerzeuger abgearbeitet.
Information
Betriebsstatus
Speicher oben
Anzeige der Speichertemperatur oben (R3)
Speicher unten
Anzeige der Speichertemperatur unten (R5)
Lufteintritt
Anzeige der Lufttemperatur (R1)
Kollektortemp.
Anzeige der Kollektortemperatur ( R13 nur bei Modellen mit
Zusatzwärmetauscher und Auswahl Sol als 2. Wärmeerzeu-
ger)
Sollwert aktuell
Anzeige des aktuellen Warmwasser-Sollwertes
Abtaufühler
Anzeige der (nur bei Modellen mit Abtauung)
Ventilator
Anzeige des Schaltzustandes des Ventilators
Verdichter
Anzeige des Schaltzustandes des Verdichters
Elektroheizung
Anzeige des Schaltzustandes der Elektroheizung
Leistung
Anzeige der berechneten Leistungsaufnahme des Gerätes
Betriebsart
Anzeige der aktuellen Betriebsart
Laufzeiten
Gerät
Anzeige der Betriebsstunden
Ventilator
Anzeige der Laufzeit vom Ventilator
Menüblock
Menüpunkt
Parameter
Wert
Beschreibung
451905.66.02 · FD 9912
DE-11
DHW 300D - DHW 300D+
Deutsch
Verdichter
Anzeige der Laufzeit vom Verdichter
Elektroheizung
Anzeige der Laufzeit der Elektroheizung
Soft. Vers.
Anzeige der Software-Version
Hardware
Anzeige der Hardware-Version
Seriennummer
Anzeige der Seriennummer
Service
Passwort eingeben
Passwortgeschützter Bereich für den Kundendienst
Meldungen
Alarme
Anzeige der Alarme, Häufigkeit und Art
(Startbildschirm bei Erstinbetriebnahme)
Grundeinstellungen
Sprache
Einstellung der Sprache
Datum
Einstellung des aktuellen Datums
Uhrzeit
Einstellung der aktuellen Uhrzeit
Solltemperatur
Einstellung der gewünschten Warmwassertemperatur
Absenkung
Einstellung der reduzierten Warmwassertemperatur
Menüblock
Menüpunkt
Parameter
Wert
Beschreibung
451905.66.02 · FD 9912
www.gdts.one
Deutsch
DHW 300D - DHW 300D+
7.3
Funktionen
7.3.1 Zeitprogramme
Absenkung
Durch das Einstellen von Absenkzeiten, kann der Betrieb der
Brauchwasserwärmepumpe gesperrt werden. Es sind zwei un-
abhängige Absenkzeiten programmierbar. Die einzelnen Ab-
senkzeiten werden aktiviert, sobald der Stunden- oder Minu-
tenwert ungleich Null ist. Während der Absenkzeiten wird der
Speicher auf die Absenktemperatur gehalten. Die Funktionen
Solarthermie, Nutzung von Strom aus Photovoltaikanlagen und
Boost (Schnellheizen) sind während einer Sperrzeit möglich.
Vorbeugende thermische Desinfektion
Die Startzeit der vorbeugenden thermischen Desinfektion und
der gewünschte Sollwert müssen eingestellt werden. Die Funk-
tion wird aktiviert, sobald der Stunden- oder Minutenwert un-
gleich Null ist.
Zum Erreichen der eingestellten Solltemperatur wird sowohl die
Wärmepumpe als auch die Elektroheizung von Beginn an ein-
geschaltet. Damit wird sichergestellt, dass der geforderte Soll-
wert möglichst schnell erreicht werden kann.
HINWEIS
�
Ist nach 4 Stunden die Solltemperatur nicht erreicht, wird die
vorbeugende thermische Desinfektion abgebrochen. Die
eingestellte Startzeit kann an jedem Wochentag aktiviert
werden. Die vorbeugende thermische Desinfektion sollte
nicht nach 20 Uhr gestartet werden, damit die 4 Stunden zur
Verfügung stehen.
7.3.2 Elektroheizung
Die integrierte Elektroheizung kann zur Unterstützung des
Wärmepumpenbetriebs verwendet werden. Die Elektroheizung
wird automatisch eingeschaltet, wenn die Warmwasser-
Solltemperatur im Wärmepumpenbetrieb innerhalb der einge-
stellten Verzögerungszeit nicht erreicht wird. Im ECO Modus
wird die Elektroheizung nur angefordert, wenn die Einsatzberei-
che der Wärmepumpe verlassen werden und kein 2. Wärmeer-
zeuger vorhanden ist. Dies ist z.B. der Fall, wenn die Lufteintritt-
stemperatur unter-/überschritten wird. Über die Taste "Boost"
kann für eine einstellbare Dauer die Warmwasserbereitung mit
Unterstützung der Elektroheizung erfolgen.
Ist die Lufttemperatur größer als -7 °C, ist die Elektroheizung
gesperrt. Nur für die Boost-Funktion (Schnellheizen) kann sie
auch oberhalb der -7 °C-Grenze manuell eingeschaltet werden.
7.3.3 Zweiter Wärmeerzeuger (nur bei
DHW 300D+)
Mit Hilfe des integrierten Rohrwärmetauschers (1 m²) kann ein
vorhandener Wärmeerzeuger zur Aufheizung des Speichers ge-
nutzt werden. Die Nutzung eines 2.Wärmerzeugers muss im
Menü aktiviert werden. Er wird dann angefordert, wenn die Ein-
satzbereiche der Wärmepumpe verlassen werden. Dies ist der
Fall wenn die untere oder obere Lufteintrittsgrenze oder der
Warmwasser-Sollwert über der erreichbaren Temperatur im
Wärmepumpenbetrieb liegt (z.B. vorbeugende thermische Des-
infektion). Der 2.Wärmeerzeuger hat in diesem Fall Vorrang vor
der Elektroheizung in der Wärmepumpe. Beim Aktivieren des 2.
Wärmeerzeugers kann abweichend von der unteren Einsatz-
grenze der Lufttemperatur zusätzlich eine Bivalenztemperatur
gewählt werden. Wird diese Temperatur unterschritten, so wird
der Wärmepumpenbetrieb bereits ab der eingestellten Tempe-
ratur gesperrt und der 2. Wärmeerzeuger genutzt.
Für die Beladung des Speichers über den Zusatzwärmetau-
scher ist eine Umwälzpumpe erforderlich, die bei Bedarf betrie-
ben werden soll. Dazu sind zwei Lösungen möglich:
Ansteuerung einer Umwälzpumpe zur Nutzung des
Wärmetauschers durch vorhandene Warmwasser-
Wärmepumpen-Regelung
Diese Variante empfehlen wir beim Vorhandensein einer steti-
gen Wärmequelle z.B. Pufferspeicher einer Holzheizung wäh-
rend der Nutzung des 2.Wärmeerzeugers.
Der Anschluss der Umwälzpumpe erfolgt an der Klemme X4.
Ansteuerung einer Umwälzpumpe zur Nutzung des
Wärmetauschers durch vorhandene Kesselregelung
Diese Variante empfehlen wir, wenn neben der Umwälzpumpe
auch ein Kessel für die Erzeugung der Wärme eingeschaltet
werden muss. In diesem Fall ist in der Regel ein Fühler der vor-
handenen Kesselregelung im Speicher der Wärmepumpe erfor-
derlich. Der vorhandene Fühler muss elektrisch angeklemmt
und physisch im Gerät verbleiben. Hierzu innerhalb der Däm-
mung im Bereich der Elektroheizung aufgerollt verstauen und
ggf. die Sollwerte im Menü verringern. Bild unten zeigt die Posi-
tion des auszutauschenden Fühlers R5, der elektrisch an die ex-
terne Kesselregelung angeschlossen wird. Empfohlene Tiefe
des Fühlers im Rohr: ca. 550 mm.
Einbauposition externer Temperaturfühler für
bivalenten Betrieb
(Darstellung mit demontierter Gerätehaube)
451905.66.02 · FD 9912
DE-13
DHW 300D - DHW 300D+
Deutsch
7.3.4 Solarthermiefunktion
Alternativ zur Nutzung eines 2.Wärmeerzeugers kann die
Warmwasser-Wärmepumpen in Kombination mit einer thermi-
sche Solaranlage betrieben werden. Sobald ausreichender So-
larertrag erkannt wird, wird dieser zur Warmwasserbereitung
genutzt und die Wärmepumpe gesperrt. Die Schalthysteresen
können im Menü eingestellt werden. Die Umwälzpumpe wird
wieder ausgeschaltet, wenn kein Ertrag mehr vorhanden ist,
oder ein Temperaturgrenzwert, entweder am Kollektor, oder im
Speicher, überschritten wird. Die Solarthermiefunktion hat Vor-
rang vor dem Wärmepumpenbetrieb und der Elektroheizung..
ACHTUNG!
!
Für den Kollektorfühler muss ein Temperaturfühler mit der
Widerstandskennlinie eines PT1000 (siehe Kap. 2.4.2 auf S. 4)
verwendet werden.
7.3.5 Photovoltaikfunktion
Für die Photovoltaik-Funktion ist die Klemme X8 mit 230 V
50 Hz zu beschalten. Eine Auswerteeinheit (z.B. Wechselrichter)
ermittelt die aktuelle zur Verfügung stehende Leistung. Wenn
der Photovoltaik-Eingang aktiv ist, regelt die Wärmepumpe auf
den Sollwert für den PV-Betrieb. Als Einstellungsrichtwert für
die Leistungsschwelle im Wechselrichter der Photovoltik-An-
lage kann bei PV-Betrieb ohne Elektroheizung 1kW verwendet
werden (700 W Leistungsaufnahme Wärmepumpe zuzüglich
Grundlast des Haushaltes). Soll das Gerät immer mit Elektrohei-
zung im PV-Betrieb arbeiten, empfiehlt sich ein Einstellungs-
richtwert von 2,5 kW (2200 W Leistungsaufnahme Wärme-
pumpe inkl. Elektroheizung zuzüglich Grundlast des Hauses).
Die Solarthermiefunktion hat Vorrang gegenüber der Photovol-
taikfunktion. Der Betrieb der Wärmepumpe mit Strom aus der
Photovoltaikanlage wird im Display angezeigt.
HINWEIS
�
Die Warmwassersolltemperatur im Photovoltaikbetrieb sollte
auf max. 55 °C eingestellt werden, um einen effizienten
Betrieb der Wärmepumpe zu gewährleisten.
8
Wartung / Instandhaltung
ACHTUNG!
!
Vor dem Öffnen der Warmwasser-Wärmepumpe ist diese
spannungsfrei zu schalten, auf nachlaufenden Ventilator ist
zu achten!
Allgemeines
Die Warmwasserwärmepumpe ist sehr wartungsarm. Einmalig
nach der Inbetriebnahme im Abstand von einigen Tagen ist
eine Sichtkontrolle auf eventuelle Undichtigkeiten im Wasser-
system oder Verstopfung des Kondensatablaufes durchzufüh-
ren.
Am Kältekreis der Wärmepumpe sind keine Wartungsarbeiten
auszuführen.
Für eine Reinigung der Warmwasser-Wärmepumpe ist lediglich
ein feuchtes Tuch mit etwas Seifenlösung zu verwenden.
8.1
Wasserkreislauf /
Kondensatablauf
Die Überprüfung des Wasserkreislaufes beschränkt sich auf
eventuell bauseitig installierte Filter und etwaige Undichtigkei-
ten. Verschmutzte Wasserfilter sind zu reinigen und ggf. zu er-
neuern. Das Dichtlippenventil im Kondensatschlauchende ist
gelegentlich auf Verschmutzung zu prüfen und ggf. zu reinigen.
8.2
Luftkreisversorgung
Die Wartungsarbeiten beschränken sich auf das bedarfsabhän-
gige bzw. turnusmäßige Reinigen des Verdampfers.
ACHTUNG!
!
Verletzungsgefahr durch scharfkantige Lamellen. Lamellen
dürfen nicht deformiert oder beschädigt werden!
Bei der etwaigen Verwendung von Luftfiltern sind diese regel-
mäßig auf Verschmutzung zu prüfen und ggf. zu reinigen oder
zu erneuern.
ACHTUNG!
!
Vor öffnen des Gerätes ist dieses Spannungsfrei zu schalten.
ACHTUNG!
!
Die Klemme X8 kann auch in ausgeschalteten Zustand der
Wärmepumpe unter Spannung stehen
451905.66.02 · FD 9912
www.gdts.one
Deutsch
DHW 300D - DHW 300D+
8.3
Korrosionsschutzanode
Die im Warmwasserspeicher eingebaute Korrosionsschutzan-
ode (Abb. 8.1) ist regelmäßig mindestens alle zwei Jahre nach
der Inbetriebnahme elektrisch zu überprüfen und, falls erfor-
derlich, zu erneuern. Die elektrische Überprüfung erfolgt mit-
tels geeignetem Strommessgerät, ohne das Wasser im Spei-
cher abzulassen.
Vorgehensweise:
1)
PE-Leitung von Steckzunge der Schutzanode abziehen.
2)
Amperemeter (0...50 mA) zwischen PE-Leitung und Steck-
zunge schalten.
3)
Bewertung der Schutzanodenabnutzung:
Messwert > 1 mA Schutzanode ist in Ordnung.
Messwert < 1 mA Schutzanode muss geprüft bzw. aus-
getauscht werden.
Ist eine eindeutige elektrische Überprüfung nicht möglich, wird
eine visuelle Kontrolle der Schutzanode durch den Fachmann
empfohlen.
(Für einen evtl. erforderlichen Austausch der Schutzanode
[durch den Fachmann] muss das Wasser über das vorgesehene
Entleerungsventil (bei Installation vorzusehen - siehe Anhang)
aus dem Speicher abgelassen werden.
HINWEIS
�
Funktionsgeminderte
Schutzanoden
verringern
die
Gerätelebensdauer!
(Opferanode: elektrisch Isolierte Magnesiumanode mit Selen
nach DIN 4753 Teil 6)
Abb. 8.1:Anode Elektroheizung
9
Störungen / Fehlersuche
(für den Nutzer)
ACHTUNG!
!
Arbeiten an der Warmwasser-Wärmepumpe dürfen nur von
fachkundigen Personen ausgeführt werden!
Unfallverhütungsvorschriften sind zu beachten!
Die Wärmepumpe läuft nicht!
Bitte überprüfen Sie ob
der Stecker eingesteckt ist
an der Tastatur der Stand-By Modus gewählt wurde
an der Steckdose Spannung anliegt
die Luftansaug- bzw. Umgebungstemperatur -7 °C ist
die Warmwassertemperatur mehr als 60 °C beträgt
Die Wärmepumpe schaltet sich vorzeitig ab
(Solltemperatur ist noch nicht erreicht)
Bitte überprüfen Sie ob
Lüftungsleitungen abgeknickt oder deren Öffnungen ver-
schlossen sind oder evtl. vorhandene Luftfilter stark verun-
reinigt (zugesetzt) sind.
Kondensat läuft nicht ab (Wasser unter dem Gerät)
Bitte überprüfen Sie ob
das Dichtlippenventil am Kondensatschlauchende verun-
reinigt oder verstopft ist, reinigen Sie es ggf., das Ventil
lässt sich leicht entfernen und wieder einsetzen.
die Luftzufuhr / Luftabführung stark vermindert ist (abge-
knickte Luftleitung / zugesetzter Luftfilter).
Wenn die oben genannten Fragen nicht der Fehlerbehebung
dienen, wenden Sie sich an Ihren Installateur oder an den Kun-
dendienstservice.
10 Außerbetriebnahme
Auszuführende Tätigkeiten:
Warmwasser-Wärmepumpe spannungsfrei schalten.
Wasserkreislauf komplett absperren (Warmwasser-, Kalt-
wasser- und Zirkulationsleitung) und den Warmwasser-
speicher entleeren.
11 Umweltrelevante
Anforderungen
Bei Instandsetzung oder Außerbetriebsetzung der Warmwas-
ser-Wärmepumpe sind die umweltrelevanten Anforderungen in
Bezug auf Rückgewinnung, Wiederverwendung und Entsor-
gung von Betriebsstoffen und Bauteilen gemäß DIN EN 378
einzuhalten.
451905.66.02 · FD 9912
DE-15
DHW 300D - DHW 300D+
Deutsch
12 Geräteinformation
1
Typ- und Verkaufsbezeichnung
DHW 300D
DHW 300D+
2
Bauform
2.1
Anzahl Einheiten
1
1
2.2
Wärmequelle
Luft
Luft
2.3
Abtauung
ja
ja
2.4
Speicher-Nennvolumen
Liter
285
280
2.5
Wärmetauscher innen liegend - Übertragungsfläche
m2
-
1,0
2.6
Fühlerrohr ø innen für externen Fühler
mm
9
9
2.7
Aufstellort
frostfrei
frostfrei
2.8
Speicherwerkstoff
Stahl emailliert nach DIN 4753
Stahl emailliert nach DIN 4753
2.9
Speicher-Dämmung
PU mit PS-Mantel
PU mit PS-Mantel
2.10 Speicher-Nenndruck
bar
6
6
3
Einsatzgrenzen
3.1
Einsatzgrenze Wärmequelle1
°C
-7 bis 35
-7 bis 35
3.2
Einstellbereich Warmwasser im Wärmepumpenbetrieb
°C
20 bis 60 ± 1,0 K
20 bis 60 ± 1,0 K
4
Durchfluss / Schall
4.1
Luftstrom
m3/h
325
325
4.2
Externe Pressung max.
Pa
80
80
4.3
Luftkanalanschlußlänge max.
m
10
10
4.4
Schallleistungspegel
dB(A)
60
60
4.5
Schalldruckpegel 2
dB(A)
50
50
5
Abmessung / Gewicht und Füllmengen
5.1
Abmessungen Höhe (min) x Breite x Tiefe
mm
1867 x 740 x 776
1867 x 740 x 776
5.2
Luftkanalanschluss Durchmesser /
Nennweite mit EPP-Lüftungsrohr
mm
190 / DN 160
190 / DN 160
5.3
Gewicht (unbefüllt)
kg
108
123
5.4
Kältemittel R 134a/ Füllmenge
kg
0,95
0,95
5.5
GWP-Wert / CO2 Äquivalent
1430 / 1
1430 / 1
5.6
Kältkreis hermetisch geschlossen
ja
ja
6
Elektrischer Anschluss
6.1
Schutzart
IP 21
IP 21
6.2
Anschlussspannung
1/N/PE~230 V, 50 Hz
1/N/PE~230 V, 50 Hz
6.3
Anschlussleitung ca. 2,7 m - 1,5 mm2
mit Stecker
mit Stecker
6.4
Absicherung max.
A
C16
C16
6.5
Stromaunahme Wärmepumpe cos
0,8
0,8
6.6
Stromaufnahme elektr. Zusatzheizung
A
6,5
6,5
6.7
Stromaufnahme max.
A
9,5
9,5
6.8
Einschaltstrom max.
A
13,5
13,5
6.9
Nennaufnahme Wärmepumpe bei 60 °C3
W
528
528
6.10 Leistungsaufnahme elektr. Zusatzheizung
W
1500
1500
6.11 Leistungsaufnahme Ventilator
W
58
58
6.12 Gesamtleistungsaufnahme max.
W
2200
2200
7
Hydraulischer Anschluss
7.1
Anschluss Zirkulationsleitung
Außengewinde
R 3/4"
R 3/4"
7.2
Anschluss Warmwasser-Auslauf
Außengewinde
R1"
R1"
7.3
Anschluss Kaltwasser-Zulauf
Außengewinde
R1"
R1"
7.4
Anschluss innerer Wärmetauscher
Außengewinde
-
Rp 1"
8
Leistungswerte
8.1
Aufheizzeit 3 4
h:min
09:22
09:22
451905.66.02 · FD 9912
www.gdts.one
Deutsch
DHW 300D - DHW 300D+
8.2
Energieaufnahme während der Aufheizzeit 3 4
kWh
4,25
4,25
8.3
Leistungsaufnahme während Bereitschaftsperiode 4 5
W
29
29
8.4
Elektrischer Energieverbrauch
WEL-TC nach EN 16147 Zyklus XL 4 5
kWh
5,78
5,78
8.5
COP nach EN 16147 Zyklus XL 4 5
3,3
3,3
8.6
Bezugswarmwassertemperatur 4 5
°C
55,9
55,9
8.7
Maximal nutzbare Warmwassermenge 4 5
Liter
421
421
8.8
Lastprofil 4 5
XL
XL
8.9
Warmwasserbereitungs-Energieeffizienz ŋwh
4
5
%
137
137
1. Bei Temperaturen unter 7 °C ± 1 °C schaltet sich automatisch der Heizstab ein und das Wärmepumpenmodul aus.
2. In 1m Abstand (bei Freiaufstellung bzw. bei Aufstellung ohne Ablustkanal oder 90°-Rohrbogen abluftseitig).
3. Aufheizvorgang des Nenninhaltes von 10 °C auf 55 °C bei Luftansaugtemperatur von 15 °C und relat. Feuchte von 70 %
4. Die Angaben gelten für ein neues Gerät mit sauberen Wärmetauschern
5. Bei Luftansaugtemperatur von 15 °C und relat. Feuchte von 70 %
451905.66.07 · FD 9912
DE-17
DHW 300VD+
Deutsch
13 Garantieurkunde
Glen Dimplex Thermal Solutions
Garantieurkunde GDTS
(Warmwasser-Wärmepumpen, Dezentrale Wohnungslüftungsge-
räte mit Wärmerückgewinnung)
gültig für Deutschland und Österreich
(Ausgabestand 11/2019)
Die nachstehenden Bedingungen, die die Voraussetzungen und
den Umfang unserer Garantieleistung umschreiben, lassen die Ge-
währleistungsverpflichtungen des Verkäufers aus dem Kaufvertrag
mit dem Endabnehmer unberührt. Für die Geräte leisten wir Garan-
tie gemäß nachstehenden Bedingungen:
Wir beheben unentgeltlich nach Maßgabe der folgenden Bedin-
gungen Mängel am Gerät, die auf einem Material und/oder Herstel-
lungsfehler beruhen, wenn sie uns unverzüglich nach Feststellung
und innerhalb von 24 Monaten nach Lieferung an den Ers-
tendabnehmer gemeldet werden. Bei Ersatzteilen und bei gewerb-
lichem Gebrauch innerhalb von 12 Monaten.
Dieses Gerät fällt nur dann unter diese Garantie, wenn es von einem
Kunden in einem der Mitgliedstaaten der Europäischen Union ge-
kauft wurde, es bei Auftreten des Mangels in Deutschland oder Ös-
terreich betrieben wird und Garantieleistungen auch in Deutsch-
land oder Österreich erbracht werden können.
Die Behebung der von uns als garantiepflichtig anerkannten Män-
gel geschieht dadurch, dass die mangelhaften Teile unentgeltlich
nach unserer Wahl instandgesetzt oder durch einwandfreie Teile
ersetzt werden. Durch Art oder Ort des Einsatzes des Gerätes oder
schlechte Zugänglichkeit des Gerätes bedingte außergewöhnliche
Kosten der Nachbesserung werden nicht übernommen. Der freie
Gerätezugang muss durch den Kunden gestellt werden. Ausge-
baute Teile, die wir zurücknehmen, gehen in unser Eigentum über.
Die Garantiezeit für Nachbesserungen und Ersatzteile endet mit
dem Ablauf der ursprünglichen Garantiezeit für das Gerät. Die Ga-
rantie erstreckt sich nicht auf leicht zerbrechliche Teile, die den
Wert oder die Gebrauchstauglichkeit des Gerätes nur unwesentlich
beeinträchtigen. Es ist jeweils der Original-Kaufbeleg mit Kauf-
und/oder Lieferdatum vorzulegen.
Eine Garantieleistung entfällt, wenn vom Kunden oder einem Drit-
ten die entsprechenden VDE-Vorschriften, die Bestimmungen der
örtlichen Versorgungsunternehmen oder unsere Montage- und Ge-
brauchsanweisung sowie die in den Projektierungsunterlagen ent-
haltenen Hinweise zu Wartungsarbeiten oder Einbindungsschemen
nicht beachtet worden sind oder wenn unser funktionsnotwendi-
ges Zubehör nicht eingesetzt wurde. Durch etwa seitens des Kun-
den oder Dritter unsachgemäß vorgenommenen Änderungen und
Arbeiten, wird die Haftung für die daraus entstehenden Folgen auf-
gehoben. Die Garantie erstreckt sich auf das Gerät und vom Lieferer
bezogene Teile. Nicht vom Lieferer bezogene Teile und Geräte-/An-
lagenmängel, die auf nicht vom Lieferer bezogene Teile zurückzu-
führen sind, fallen nicht unter den Garantieanspruch.
Bei endgültig fehlgeschlagener Nachbesserung wird der Hersteller
entweder kostenfreien Ersatz liefern oder den Minderwert vergü-
ten. Im Falle einer Ersatzlieferung behalten wir uns die Geltendma-
chung einer angemessenen Nutzungsanrechnung für die bisherige
Nutzungszeit vor. Weitergehende oder andere Ansprüche, insbe-
sondere solche auf Ersatz außerhalb des Gerätes entstandenen
Schäden, sind ausgeschlossen.
Für bestimmte Geräte bietet der Hersteller freibleibend eine optio-
nale, kostenpflichtige Verlängerung der Garantie auf 60 Monate ab
Lieferung an den Erstendabnehmer. Diese ist ausschließlich Online
unter www.dimplex.de/garantieverlaengerung zu beauftragen und
muss vom Hersteller bestätigt werden. Die Garantie endet spätes-
tens 72 Monate ab Auslieferung Werk bzw. 78 Monate ab Ferti-
gungsdatum.
Es wird keine Haftung für die ordnungsgemäße Planung, Dimensio-
nierung und Ausführung der Gesamtanlage übernommen. Die Be-
hebung von Anlagenmängeln und Wartezeiten sind Sonderleistun-
gen.
Glen Dimplex Thermal Solutions
Glen Dimplex Deutschland GmbH
Abteilung: Service
Am Goldenen Feld 18
95326 Kulmbach
Für die Auftragsbearbeitung werden der Typ, die Seriennummer S/
N, das Fertigungsdatum FD und falls angegeben der Kundendiens-
tindex KI des Gerätes benötigt.
Diese Angaben befinden sich auf dem Typschild des Gerätes.
Kundendienstadresse:
Tel.-Nr.:
Fax.-Nr.:
E-Mail-Adresse:
Internet:
+49 (0) 9221 709 545
+49 (0) 9221 709 924545
[email protected]
www.gdts.one
www.dimplex.de/garantieverlaengerung
www.dimplex.de/seviceauftrag
451905.66.02 · FD 9912
EN-1
DHW 300D - DHW 300D+
English
Table of contents
1
Please read immediately............................................................................................................................EN-2
1.1
Important notes................................................................................................................................................................EN-2
1.2
Intended use......................................................................................................................................................................EN-2
1.3
Regulations / safety information................................................................................................................................EN-2
2
Description....................................................................................................................................................EN-3
2.1
General.................................................................................................................................................................................EN-3
2.2
Refrigerant circuit (heat pump operating principle).............................................................................................EN-3
2.3
Safety and control devices ...........................................................................................................................................EN-4
2.4
Temperature sensor........................................................................................................................................................EN-4
3
Storage and transport ................................................................................................................................EN-5
3.1
General.................................................................................................................................................................................EN-5
3.2
Fork lift (or lift truck) transport.....................................................................................................................................EN-5
3.3
Manual transport
(factory default).................................................................................................................................................................EN-5
3.4
Transport in carrier (accessory with locking plate) ...............................................................................................EN-5
3.5
Opening the device.........................................................................................................................................................EN-6
4
Installation ....................................................................................................................................................EN-6
4.1
Installation location .........................................................................................................................................................EN-6
4.2
Installation ..........................................................................................................................................................................EN-6
5
Assembly.......................................................................................................................................................EN-7
5.1
Connecting the water pipes.........................................................................................................................................EN-7
5.2
Connecting the condensate pipe...............................................................................................................................EN-7
5.3
Electrical connection ......................................................................................................................................................EN-7
5.4
Air duct connection (optional) .....................................................................................................................................EN-7
6
Commissioning............................................................................................................................................EN-8
6.1
Domestic hot water system..........................................................................................................................................EN-8
7
Operation and function of the domestic hot water heat pump.......................................................EN-8
7.1
Operation and display ....................................................................................................................................................EN-8
7.2
Menu structure .................................................................................................................................................................EN-9
7.3
Functions .........................................................................................................................................................................EN-12
8
Maintenance / repair............................................................................................................................... EN-13
8.1
Water circuit / condensate drain.............................................................................................................................EN-13
8.2
Air circuit supply............................................................................................................................................................EN-13
8.3
Corrosion protection anode ......................................................................................................................................EN-14
9
Faults / troubleshooting (for the user)................................................................................................ EN-14
10 Decommissioning .................................................................................................................................... EN-14
11 Environmental requirements................................................................................................................. EN-14
12 Device information .................................................................................................................................. EN-15
Anhang · Appendix · Annexes............................................................................................................................. A-I
Maßbild / Dimension drawing / Schéma coté ......................................................................................................... A-II
Einbindungsschemen / Integration diagram / Schéma d'intégration.............................................................. A-III
Elektroschema / Electrical circuit diagram / Schéma électrique ....................................................................... A-V
Konformitätserklärung / Declaration of Conformity / Déclaration de conformité .......................................A-VI
451905.66.02 · FD 9912
www.gdts.one
English
DHW 300D - DHW 300D+
1
Please read immediately
1.1
Important notes
ATTENTION!
!
Read these installation and operating instructions before
commissioning!
ATTENTION!
!
Work on the domestic hot water heat pump is to be performed
by qualified personnel only! Observe accident prevention
regulations!
ATTENTION!
!
The device cover cannot be used for carrying (the cover
cannot withstand significant forces).
ATTENTION!
!
Once the heat pump has been set up, the guard plate must be
removed!
ATTENTION!
!
The heat pump must not be transported overhead.
ATTENTION!
!
When installing the on-site pipework, ensure that the pipes
are not contaminated (flush pipes before connecting the
domestic hot water heat pump if necessary).
ATTENTION!
!
The domestic hot water heat pump must only be operated
when filled with water.
ATTENTION!
!
The domestic hot water heat pump must only be operated
when filled with water.
ATTENTION!
!
The collector sensor must be a temperature sensor with the
resistance characteristic curve of a PT1000 (see Cap. 2.4.2 on
pag. 4).
ATTENTION!
!
Disconnect the power supply before opening the domestic
hot water heat pump; possible fan coasting must be
considered.
ATTENTION!
!
Risk of injury caused by sharp-edged fins. Fins must not be
deformed or damaged!
ATTENTION!
!
The device must be de-energised before it can be opened.
ATTENTION!
!
The terminal X8 can also be energized when the heat pump is
in switched-off state
ATTENTION!
!
For settings for using photovoltaic energy. a solar thermal
system or an external boiler, domestic hot water temperatures
of >60°C are possible and an external scald protection must
therefore be in place.
1.2
Intended use
This device is only intended for use as specified by the manu-
facturer. Any other use beyond that intended by the manufac-
turer is prohibited. This requires the user to abide by the rele-
vant project planning documents. Please refrain from
tampering with or altering the device.
1.3
Regulations / safety
information
ATTENTION!
!
Read these installation and operating instructions before
commissioning!
The domestic hot water heat pump is used exclusively to
heat water for domestic use and drinking water within the
specified operating temperature limits. The heating of flu-
ids other than domestic water is not permitted. Technical
regulations for domestic water installation are to be ob-
served. The nominal pipe widths for the on-site sanitary in-
stallation must be determined taking into account the
building-specific requirements and the valid directives and
regulations. Any necessary safety devices, such as pres-
sure reducing valves, must be installed according to the
specific requirements.
The following are not permitted:
It is not permissible to install the device:
It is not permissible to operate the device:
The construction and design of the domestic hot water
heat pump complies with the relevant EU directives. (See
also CE declaration of conformity).
The technician must ensure that the refrigerant is flushed
adequately to allow maintenance and repair work to be car-
ried out on refrigerant circuit components without risk. Re-
frigerant must be properly handled and disposed of; it
must not be released into the environment!
The refrigeration circuit is "hermetically sealed" and con-
tains the fluorinated refrigerant R134a included in the
Kyoto protocol. Information on the GWP value and CO2
equivalent of the refrigerant can be found in the chapter
- Operating the pump with solvent-based or explosive ex-
haust air
- The use of exhaust air containing grease, dust or aero-
sols
containing adhesive substances
- The connection of extractor hoods to the
ventilation system
- Outdoors
- In rooms which are exposed to frost
- In rooms subject to high humidity (e.g. bathrooms)
- In rooms with air which is potentially explosive
due to gases, vapours or dust
- With an empty cylinder
- During the construction phase of the building
451905.66.02 · FD 9912
EN-3
DHW 300D - DHW 300D+
English
Device information. The refrigerant is CFC-free, non-ozone
depleting and non-combustible.
More information can be found in the accompanying log
book.
Always disconnect the power supply before carrying out
any work on the domestic hot water heat pump.
When connecting the domestic hot water heat pump to
the power supply, the relevant VDE, EN and IEC standards
must be complied with. Also observe the technical connec-
tion requirements of the electrical utility companies.
This heat pump is designed for use in a domestic environ-
ment according to Article 1, Paragraph 2 k) of EU directive
2006/42/EG (machinery directive) and is thus subject to
the requirements of EU directive 2014/35/EU (low-voltage
directive). It is therefore also intended for use by non-pro-
fessionals for domestic water preparation for shops, of-
fices and other similar working environments, agricultural
establishments and hotels, guesthouses and other resi-
dential buildings.
ATTENTION!
!
Work on the domestic hot water heat pump is to be performed
by qualified personnel only!
Observe accident prevention regulations!
2
Description
2.1
General
The domestic hot water heat pump is a ready-to-use heating
device whose main components are a domestic hot water cyl-
inder, the components of the refrigerant, air and water circuits
and the control, regulation and monitoring devices required for
automatic operation.
With the help of electrical energy, the domestic hot water heat
pump uses the heat stored in the drawn-in air for domestic hot
water preparation. The optional internal heat exchanger can be
connected to additional heat generators such as boilers and
solar energy systems. The units are equipped with an electric
heater (1.5 kW) as standard.
The temperature of the drawn-in air (the heat source) serves as
the reference value for the energy consumption, the domestic
hot water preparation heat-up time and domestic hot water
temperature.
For this reason, an air duct system (DN 160, max. length 10 m)
can be connected to the standard spigot of the domestic hot
water heat pump for targeted waste heat recovery. For the heat
pump to be operated effectively, air short-circuits between the
drawn-in air and the blown-out air must always be avoided. This
can, for example, be achieved through the use of a bend on the
intake and outlet side.
Falling outlet air temperatures reduce the heat pump's heat
output and increase the heat-up time. In order for the heat
pump to be operated economically, the air intake temperature
should not fall below 15 °C for an extended period.
The electric heater fulfils the following functions:
Supplementary heating
With the "Boost" key, the domestic hot water preparation
can be supported with the electric heater for an adjustable
period of time.
Operating limit
If the air intake temperature falls below 7 ±1.0 °C, the elec-
tric heater switches on automatically and (nominally) heats
the water up to the domestic hot water set temperature.
Emergency heating
In the event of a heat pump fault, the domestic hot water
supply is maintained by the electric heater.
Preventative thermal disinfection
Using the operator panel keypad, domestic hot water tem-
peratures above 60 °C (up to 85 °C) can be programmed
via the "thermal disinfection" menu item.
Reheating
Water temperatures over 60 °C are achieved with the elec-
tric heater.
� NOTE
When the domestic hot water temperature reaches > 60 °C,
the heat pump switches off and the domestic hot water
preparation takes place solely by the electric heater. The
factory setting for the heating element controller is 65 °C.
2.2
Refrigerant circuit (heat pump
operating principle)
The refrigerant circuit is a closed system in which the R134a re-
frigerant is the work material. The finned heat exchanger ex-
tracts heat from the drawn-in air at a low evaporation tempera-
ture, and transfers it to the refrigerant. The vaporous refrigerant
is taken in by a compressor, where it is compressed to a higher
pressure and temperature level before being transported to the
liquefier, where the heat absorbed in the evaporator and part of
the compressing energy is transferred to the water. Subse-
quently, the high condensation pressure is lowered to the evap-
oration pressure by a throttle mechanism (expansion valve), and
the refrigerant can again extract heat from the intake air in the
evaporator.
451905.66.02 · FD 9912
www.gdts.one
English
DHW 300D - DHW 300D+
2.3
Safety and control devices
The domestic hot water heat pump is equipped with the follow-
ing safety devices:
High pressure switch (HP)
The high pressure switch protects the heat pump against unac-
ceptably high operating pressure in the refrigerant circuit and
switches the heat pump off in the event of a fault. The heat
pump restarts with a time delay when the pressure in the refrig-
erant circuit has dropped again.
Safety temperature limiter for electric heater (STL)
The STL prevents impermissibly high temperatures from devel-
oping in the domestic hot water cylinder.
The electric heater switches off if the set switching value
(99 °C) is exceeded.
The electric heater cannot be switched on again until the do-
mestic hot water temperature has decreased to 90 °C and the
reset button (see illustration) on the STL (under flange cover) is
pressed (this must only be done by qualified personnel).
The domestic hot water heat pump is also equipped with the
following regulation and control devices:
Heat pump temperature controller
Temperature control in the domestic hot water cylinder and the
regulation for compressor operation is carried out by the con-
trol electronics. Electronic sensors measure the water tempera-
ture, which is regulated based on the setpoint. The desired tem-
perature level (setpoint) is set via the keypad on the control
panel.
Air intake temperature
The sensor connected to the controller measures the tempera-
ture in the domestic hot water heat pump directly in front of the
evaporator (air intake temperature). If the set switching value is
not reached (-7 ±1 °C, reset value 2 K,
delay 30 min), the domestic hot water preparation is switched
automatically from heat pump operation to heating element
operation.
2.4
Temperature sensor
2.4.1 Temperature sensor installation
position
R1
Air inlet sensor
R3 Domestic hot water sensor
R5 Domestic hot water renewable sensor (optional)
R12
Defrost end sensor
R13 Renewable sensor (optional)
2.4.2 Measured values temperature sensor
Measured values NTC 10 sensor (R1, R3, R5, R12)
Measured values PT 1000 sensor (R13)
85°
30°
F17
STB
Rückstellknopf
Temperature in °C
-20
-15
-10
-5
0
5
10
NTC-10 in k
67.7
53.4
42.3
33.9
27.3
22.1
18.0
15
20
25
30
35
40
45
50
55
60
14.9
12.1
10.0
8.4
7.0
5.9
5.0
4.2
3.6
3.1
Temperature
in °C
-30 -20 -10
0
10
20
30
40
50
PT 1000 in k
0.88
2
0.02
2
0.96
1
1.00
1.03
9
1.07
8
1.11
7
1.15
5
1.19
4
60
70
80
90 100 110 120 130 140 150 160
1.23
2
1.27
1
1.30
9
1.34
7
1.38
5
1.42
3
1.46
1
1.49
8
1.53
6
1.57
3
1.61
1
451905.66.02 · FD 9912
EN-5
DHW 300D - DHW 300D+
English
3
Storage and transport
3.1
General
The domestic hot water heat pump should always be stored
and transported packaged in an upright position, without being
filled with water. If handled carefully, the device can be trans-
ported over short distances with a maximum tilt angle of 45°.
Ambient temperatures between -20 and +60 °C are permissible
during transport and storage.
3.2
Fork lift (or lift truck) transport
The domestic hot water heat pump must remain mounted on
the pallet when being transported with a fork lift. The pump
should be lifted slowly. Because of its high centre of mass, the
domestic hot water heat pump must be secured against top-
pling. To prevent damage, the domestic hot water heat pump
must be lowered onto a level surface.
3.3
Manual transport
(factory default)
The wooden pallet can be used underneath the device for the
purpose of manual transportation. A second or third carrying
position can be created with the help of ropes or carrying slings
(these may be wrapped around the cylinder casing and at-
tached to the water pipe nipples). When transporting the heat
pump in this manner (or with a hand truck), do not, under any
circumstances, exceed the max. tilt angle of 45° (see illustra-
tion).
ATTENTION!
!
The device cover cannot be used for carrying (the cover
cannot withstand significant forces).
3.4
Transport in carrier (accessory
with locking plate)
The carrying bag accessory can be used to transport the heat
pump horizontally within the building. For this, the cover must
be removed and the guard plate supplied with the carrying bag
must be mounted. The guard plate is fixed in place between the
transport lug of the compressor and the dividing wall using the
mounting material provided.
ATTENTION!
!
Once the heat pump has been set up, the guard plate must be
removed!
It is important to ensure that the device is not transported over-
head during the entire transport process.
ATTENTION!
!
The heat pump must not be transported overhead.
45°
guard plate
Fix the guard plate
on the compressor
Contact surface
heat pump in
the carrying bag
Fix the guard plate
on the dividing wall
451905.66.02 · FD 9912
www.gdts.one
English
DHW 300D - DHW 300D+
3.5
Opening the device
The device cover is divided in two. To access the inside of the
device or to make transport easier (prevent damage), both
cover parts can be removed. To do this, the four locks must be
opened with quarter-turns in anti-clockwise direction (the lock
symbol pointing towards the front shows the status of the lock).
The cover can then be removed to the front.
To remove the air circuit cover, the two locking screws must be
removed. The cover can then be removed to the rear.
4
Installation
4.1
Installation location
Installation location criteria:
The domestic hot water heat pump must be installed in a
dry and frost-free room.
Furthermore, installation and air intake is not permitted in
rooms with air which is potentially explosive because of
gases, vapours or dust.
In order to prevent damage to interior walls caused by hu-
midity, good thermal insulation between the room into
which the exhaust air is released and the neighbouring
rooms is recommended.
Condensate drainage (with a siphon) must be provided.
The air taken in may not be excessively contaminated or
contain large amounts of dust.
The load-bearing capacity of the foundation must be suffi-
cient (the weight of the filled domestic hot water heat
pump is approx. 420 kg).
For fault-free operation and for any maintenance and repair
work, minimum clearances of 0.6 m are required on the left and
right of the device (see illustration). The domestic hot water
heat pump can be connected (optionally) using EPP air ducts
NW 160 mm internal, 190 mm external, which must not exceed
a total length of 10 m.
If air ducts are not used, a 90° EPP pipe bend pointing down-
wards on the outlet side can be used for sound optimised oper-
ation (see illustration)
4.2
Installation
Remove the three transport restraint screws (M12 - fixing
the device to the pallet) from the bottom of the pallet.
Remove the pallet and mount the three M12 supporting
feet (in the plastic bag attached to the nipple of the cylin-
der pipe).
Position the domestic hot water heat pump and align it ver-
tically by adjusting the device feet. Then tighten the coun-
ter nuts on the device feet.
Lock
open
min. 0,6 m
min. 0,6 m
min. 0,3 m
90° EPP-pipe bend
(accessories)
Operator side
451905.66.02 · FD 9912
EN-7
DHW 300D - DHW 300D+
English
5
Assembly
5.1
Connecting the water pipes
The water connections (see scaled diagram (Cap. 1 on pag. II))
are located at the rear of the unit.
� NOTE
Circulation pipe
For energy efficiency reasons, a circulation pipe should not be
used if this can be avoided. If a circulation pipe is installed in
the domestic hot water distribution system, a valve or a similar
device must be provided as shut-off facility to avoid
unnecessary energy losses. Circulation is enabled according
to use (time or requirement control).
The nominal pipe widths for the on-site sanitary installation
must be determined by taking into account the available water
pressure and any pressure drops expected to occur in the pipe-
work.
Technical regulations for domestic water installation are to be
observed. The nominal pipe widths for the on-site sanitary in-
stallation must be determined taking into account the building-
specific requirements and the valid directives and regulations.
Any necessary safety devices, such as pressure reducing
valves, must be installed according to the specific require-
ments.
Both rigid and flexible water pipes may be used. Observe the
corrosion behaviour of the pipework materials used in order to
avoid corrosion damage (see section Commissioning).
� NOTE
Domestic hot water, cold water and circulation connections:
These pipe nipples contain plastic inserts, the purpose of
which is to protect against corrosion (in particular to the pipe
nipple flange surfaces). These plastic inserts remain in their
positions after installation.
ATTENTION!
!
When installing the on-site pipework, ensure that the pipes
are not contaminated (flush pipes before connecting the
domestic hot water heat pump if necessary).
5.2
Connecting the condensate
pipe
The condensate hose is routed through the cladding at the rear
of the device. It should be routed in such a way that the con-
densate produced (during heat pump operation) can flow away
freely.
There is a pressureless seal valve at the end of the condensate
hose, which must be relocated accordingly if the condensate
hose is shortened (the valve can be easily removed and re-in-
serted). The condensate should be drained into a siphon (also
refer to the maintenance information in section 8.1).
� NOTE
The sealing lip valve must be used to prevent damage from
condensate.
5.3
Electrical connection
The domestic hot water heat pump is wired ready for use;
power is supplied via the power supply, which is plugged into
an earthed wall socket (~230 V, 50 Hz). This socket must remain
accessible after installation. In order to control external devices,
e.g. the 2nd heat generator, solar circulating pump or collector
temperature sensor, a separate cable must be connected to the
device via an available cable gland and strain relieved. Do this
by opening the device cover as described in Cap. 3.5 on pag. 6.
The relevant connection points of the components can be
found in the electrical circuit diagram Cap. 3 on pag. V and the
electrical documentation.
5.4
Air duct connection (optional)
The device is designed for connecting an EPP air duct (individ-
ual components available as accessories DN 160 inside). The
90° position of the two connecting stubs means that a wide
range of ducts are possible.
Air outlet
Air inlet
451905.66.02 · FD 9912
www.gdts.one
English
DHW 300D - DHW 300D+
6
Commissioning
6.1
Domestic hot water system
ATTENTION!
!
The domestic hot water heat pump must only be operated
when filled with water.
Domestic hot water system requirements
The following materials can be used in the consumer's domes-
tic hot water system:
Copper
Stainless steel
Brass
Plastic
Depending on the materials used in the domestic hot water
system (customer installation), material incompatibility may
lead to corrosion damage. This especially applies to zinc-plated
materials and materials containing aluminium. If there is a risk
of water contamination during operation, it may be necessary
to install a filter.
Commissioning the domestic hot water system
All installations for the water circuit and air circuit, as well
as all electrical installations, must have been carried out
correctly and fully completed.
Fill the domestic hot water circuit via an external connec-
tion.
Purge the domestic hot water circuit (open domestic hot
water taps at the highest extraction points until there are
no more traces of air).
Check the entire domestic hot water system for leaks.
Establish the power supply.
Switch on the heat pump.
The desired domestic hot water temperature (e.g. 45 °C) is
shown on the keypad (Cap. 7 on pag. 8). A corresponding
heat-up time is necessary before the selected temperature
level is reached.
7
Operation and function of
the domestic hot water heat
pump
7.1
Operation and display
7.1.1 Description of the key functions
7.1.2 Description ready display
Key
Name
Description
Menu
Switches to the main menu, where detailed set-
tings for the heat pump can be made.
Boost
Quick heating
Heating element is activated and works for a
maximum of 4 hours to the domestic hot water
set temperature
Esc
ESC
Return to the previous menu level
OK
Beginning and completion of a parameter
change / selection of a desired menu item
UP
Value change upwards, or selection menu and
parameters
DOWN
Value change downwards, or selection menu
and parameters
Header:
Unit type, weekday, time
Main field:
Information overview in plain text
451905.66.02 · FD 9912
EN-9
DHW 300D - DHW 300D+
English
7.2
Menu structure
Parameter change: The menu is accessed using the "Menu"
key. In this menu, changes can be made to parameters. The de-
sired menu item is selected with the arrow keys "UP" "DOWN".
The submenu is accessed using the "OK" key.
In this submenu, the parameter that is to be changed can be se-
lected (also using the arrow keys). The "OK" key is used to se-
lect the marked value, which can then be changed via the arrow
keys. The entry is completed by pressing the "OK" key again.
w
Menu block
Menu item
Parameter
Value
Description
Settings
Time
00:00
Time setting (24 hour time display)
Date
DD:MM:YYYY
Date setting (Day:Month:Year)
Language
DEUTSCH
ENGLISH
FRANCAIS
ITALIANO
POLSKI
Language selection
Signal tone
On
Off
Setting key tone on / off
Backlight
0 % ... 50 % ...100 %
Setting display backlight
Factory setting
Factory setting reset
Type
DHW 300
DHW 300+
DHW 300D
DHW 300D+
Domestic water heat pump DHW 300
Domestic water heat pump DHW 300+
with additional heat exchanger
Domestic water heat pump DHW 300D
with defrost function
Domestic water heat pump DHW 300D+
with defrost function and additional heat exchanger
Domestic hot
water
Set temperature
25 °C ... 45 °C ... 85 °C
Sets the desired domestic hot water set temperature
Lower
15 °C ... 25 °C ... 40 °C
Sets the minimum hot water temperature, which should also not be
undershot for the duration of a programmed lower process.
Hysteresis
2 K ... 3 K ... 10 K
Sets the switching hysteresis
Electric heater
Mode
Delay
Boost period
Boost set temp.
ECO
AUTO
2 h ... 8 h...16 h
1 h ... 4 h ... 8 h
25 °C ... 60 °C ... 85 °C
ECO: Only switches in the event of an error and with PV b./t., ther-
mal disinfection on
The electric heater is automatically switched on if the domestic hot
water set temperature is not reached within the set delay time in
heat pump operation.
Boost: adjustable time (once, regardless of the Auto/Eco setting)
Boost: adjustable set temperature
Time programs
Therm. disinfection
Thermal disinfection
Start
00:00 ... 23:59
Sets the start time for thermal disinfection (24 hour time display)
Days
Mo ... Su
Sets the day on which thermal disinfection should be activated
Set value
60 °C ... 65 °C ... 85 °C
Sets the set temperature for thermal disinfection.
1st lower
Start
00:00 ... 23:59
Sets the start time for lowering the domestic hot water set temper-
ature
End
00:00 ... 23:59
Sets the end time for lowering the domestic hot water set tempera-
ture
Days
Su ... Mo
Mo - Fr
Sa - Su
Mo - Su
Sets the weekday / block of days on which the lower should be acti-
vated
2nd lower
Start
00:00 ... 23:59
Sets the start time for lowering the domestic hot water set temper-
ature
End
00:00 ... 23:59
Sets the end time for lowering the domestic hot water set tempera-
ture
Days
Su ... Mo
Mo - Fr
Sa - Su
Mo - Su
Sets the weekday / block of days on which the lower should be acti-
vated
(only visible for devices with additional heat exchanger and OFF or Sol selected)
451905.66.02 · FD 9912
www.gdts.one
English
DHW 300D - DHW 300D+
Solar
Selection
Off
Bivalent
Sol
Choice of additional heat source
Off: (no add. heat source)
Bivalent: 2nd heat generator, e.g. oil, gas or wood boiler
Sol: Thermal solar energy system
Switch-on difference
6 K ... 8 K ... 10 K
Sets the temperature difference between the collector and cylinder
temperature at which the solar pump should be switched on
Switch-off difference
2 K ... 4 K ... 6 K
Sets the temperature difference between the collector and cylinder
temperature at which the solar pump should be switched off
Max. cylinder temp.
60 °C ... 65 °C ... 85 °C
Sets the maximum cylinder temperature that is permissible when
solar gain is available
Max. collector temp.
125 °C ... 130 °C ... 135 °C
Sets the maximum permissible temperature on the collector
(only visible for devices with additional heat exchanger and OFF or Bivalent selected)
2nd heat genera-
tor
Selection
Off
Bivalent
Sol
Choice of additional heat source
Off: (no add. heat source)
Bivalent: 2nd heat generator, e.g. oil, gas or wood boiler
Sol: Thermal solar energy system
Bivalence temperature
-8 °C ... 10 °C ... 15 °C
Limit temperature for the 2nd heat generator. The heat pump is
blocked below this temperature
Photovoltaic
Electric heater
Yes
No
Activates the electric heater (parallel to the heat pump) in photovol-
taic mode
Set temperature
35 °C ... 45 °C ... 60 °C
Entry of the domestic hot water setpoint, which is active when pho-
tovoltaic inlet is connected. The increased setpoint is also active if
the air intake temperature does not allow the heat pump to operate.
In this case, the request is processed with the electric heating ele-
ment or, where present, the 2nd heat generator.
Information
Operating status
Cylinder top
Display of the cylinder temperature top (R3)
Cylinder bottom
Display of the cylinder temperature bottom (R5)
Air inlet
Display of the air temperature (R1)
Collector temp.
Display of the collector temperature (R13 only on models with addi-
tional heat exchanger and Sol selected as 2nd heat generator)
Current setpoint
Displays the current domestic hot water setpoint
Defrost sensor
Display the defrost (only on models with defrost)
Fan
Shows the switching status of the fan
Compressor
Shows the switching status of the compressor
Electric heater
Shows the switching status of the electric heater
Power
Shows the calculated power consumption of the device
Operating mode
Displays the current operating mode
Runtimes
Unit
Displays the operating hours
Fan
Shows the runtime of the fan
Compressor
Shows the runtime of the compressor
Electric heater
Shows the runtime of the electric heater
Soft. vers.
Shows the software version
Hardware
Shows the hardware version
Serial number
Shows the serial number
Service
Enter password
Password-protected area for after-sales service
Messages
Alarms
Displays the alarms, frequency and type
Menu block
Menu item
Parameter
Value
Description
451905.66.02 · FD 9912
EN-11
DHW 300D - DHW 300D+
English
(start screen during first commissioning)
Basic settings
Language
Sets the language
Date
Sets the current date
Time
Sets the current time
Set temperature
Sets the desired domestic hot water temperature
Lower
Sets the reduced domestic hot water temperature
Menu block
Menu item
Parameter
Value
Description
451905.66.02 · FD 9912
www.gdts.one
English
DHW 300D - DHW 300D+
7.3
Functions
7.3.1 Time programs
Lower
It is possible to block the operation of the domestic water heat
pump by setting lower times. Two independent lower times can
be programmed. The individual lower times are activated as
soon as the hour or minute value is not equal to zero. During the
lower times, the cylinder is kept at the lower temperature. The
solar thermal and rapid heating functions, and the function for
using electricity from PV systems and boost (quick heating) are
possible during shut-off times.
Preventative thermal disinfection
The start time for preventative thermal disinfection and the de-
sired setpoint must be set. The function is activated as soon as
the hour or minute value is not equal to zero.
Both the heat pump and the electric heater are switched on
from the start to achieve the set temperature. This ensures that
the required setpoint can be reached as quickly as possible.
� NOTE
If the set temperature is not reached within 4 hours, the
preventative thermal disinfection is terminated. The set start
time can be activated every weekday. Preventative thermal
disinfection should not be started after 8pm to ensure that
the four hours required are available.
7.3.2 Electric heater
The integrated electric heater can be used to supplement heat
pump operation. The electric heater is automatically switched
on if the domestic hot water set temperature is not reached
within the set delay time in heat pump operation. In ECO mode,
the electric heater is only requested if the operating ranges of
the heat pump are left and no 2nd heat generator is present.
This is the case, for example, when the air intake temperature is
undershot/exceeded. With the "Boost" key, the domestic hot
water preparation can be supported with the electric heater for
an adjustable period of time.
If the air temperature is above -7 °C, the electric heater is
blocked. It can only be switched on manually above the -7 °C
limit for the boost (rapid heating) function.
7.3.3 Second heat generator (only with
DHW 300D+)
An existing heat generator can be used to heat the cylinder
using the integrated tube heat exchanger (1 m²) . The use of a
2nd heat generator must be activated in the menu. It is re-
quested if the heat pump's operating limits are exceeded. This
is the case when the bottom or top air intake limit or the domes-
tic hot water setpoint lies above the achievable temperature
during heat pump operation (e.g. preventative thermal disinfec-
tion). In this case, the 2nd heat generator has priority over the
electric heater in the heat pump.When the 2nd heat generator
is activated, it is additionally possible to select a bivalence tem-
perature which deviates from the lower operating limit (air tem-
perature). If this temperature is undershot, heat pump opera-
tion is blocked as soon as the set temperature is reached, and
the 2nd heat generator is then used.
A circulating pump is required for charging the cylinder via the
additional heat exchanger, which should be operated where
necessary. There are two possible solutions for this:
Activating a circulating pump for using the heat
exchanger through existing domestic hot water heat
pump regulation
This version is recommended if a constant heat source is pres-
ent, e.g. wood heating buffer tank when using the 2nd heat
generator.
The circulating pump is connected on terminal X4:
Activating a circulating pump for using the heat
exchanger through existing boiler controller
We recommend this version if, in addition to the circulating
pump, a boiler also has to be switched on to generate the heat.
In this case, a sensor of the existing boiler controller is usually
required in the heat pump cylinder. The existing sensor must be
connected electrically and remain physically in the unit. To do
this, stow it rolled up in the insulation in the electric heater area
and reduce the setpoints in the menu where necessary. The fig-
ure below shows the position of the sensor R5 to be replaced,
which is connected electrically to the external boiler controller.
Recommended depth of the sensor in the pipe approx. 550
mm.
Installation position of the external temperature
sensor for bivalent operation
(device cover removed in illustration)
451905.66.02 · FD 9912
EN-13
DHW 300D - DHW 300D+
English
7.3.4 Solar thermal function
As an alternative to using a 2nd heat generator, the domestic
hot water heat pump can be operated in combination with a
thermal solar installation. As soon as a sufficient solar yield is
detected, it is used for domestic hot water preparation and the
heat pump is blocked. The hystereses can be set in the menu.
The circulating pump is switched off again when a solar gain is
no longer available or when a temperature limit value is ex-
ceeded, either on the collector or in the cylinder. The solar ther-
mal function has priority over heat pump operation and the
electric heater.
ATTENTION!
!
The collector sensor must be a temperature sensor with the
resistance characteristic curve of a PT1000 (see Cap. 2.4.2 on
pag. 4).
7.3.5 Photovoltaic function
For the photovoltaic function, the terminal X8 must be fed with
230 V 50 Hz. The evaluation unit (e.g. inverter checker) meas-
ures the output that is currently available. If the photovoltaic
input is active, the heat pump controls to the setpoint for the PV
mode. 1 kW can be used as a setting reference point for the
power threshold in the inverter checker of the photovoltaic
plants during PV operation without electric heater (700 W
power consumption heat pump plus base load of the house-
hold). If the device is to work permanently with the electric
heater in PV operation, a setting reference point of 2.5 kW is ad-
visable (2200 W power consumption heat pump incl. electric
heater, plus base load of the building). The solar thermal func-
tion has priority over the photovoltaic function. The display
shows that the heat pump is being operated using electricity
from the photovoltaic installation.
� NOTE
The domestic hot water set temperature in photovoltaic mode
should be set to max. 55 °C to guarantee efficient operation of
the heat pump.
8
Maintenance / repair
ATTENTION!
!
Disconnect the power supply before opening the domestic
hot water heat pump; possible fan coasting must be
considered.
General
The domestic hot water heat pump is extremely low mainte-
nance. Furthermore, a one-off visual inspection for possible
leaks in the water system and clogging of the condensate drain
must be carried out a few days after commissioning.
The refrigeration circuit of the heat pump does not require
maintenance.
Only use a damp cloth with a little soap solution to clean the do-
mestic hot water heat pump.
8.1
Water circuit / condensate drain
The water circuit check is limited to filters that may have been
installed on site and possible leakages. Dirty water filters should
be cleaned and, if necessary, replaced. The seal valve in the end
of the condensate hose must only be checked for contamina-
tion, and cleaned if necessary.
8.2
Air circuit supply
Maintenance work is limited to cleaning the evaporator on a
regular basis and as required.
ATTENTION!
!
Risk of injury caused by sharp-edged fins. Fins must not be
deformed or damaged!
If air filters are used, they should be regularly checked for con-
tamination and be cleaned and replaced if required.
ATTENTION!
!
The device must be de-energised before it can be opened.
ATTENTION!
!
The terminal X8 can also be energized when the heat pump is
in switched-off state
451905.66.02 · FD 9912
www.gdts.one
English
DHW 300D - DHW 300D+
8.3
Corrosion protection anode
The corrosion protection anode (Fig. 8.1) installed in the do-
mestic hot water cylinder should be electrically checked on a
regular basis, at least every two years after commissioning, and
be replaced if necessary. Electrical checking is carried out by
means of a suitable ammeter, without draining the cylinder.
Procedure:
1)
Unplug the PE cable from the protection anode tab.
2)
Connect the ammeter (0 to 50 mA) between the PE cable
and the tab.
3)
Evaluation of wear on the protection anode:
Measured value > 1 mA protection anode is in working
order.
Measured value < 1 mA protection anode must be
tested and/or replaced.
If electrical testing does not provide any clear results, a visual
inspection of the protection anode by a technician is recom-
mended.
Should replacement of the protection anode [by a technician]
be necessary, the cylinder must be drained via the drain valve
provided (to be fitted during installation - see Appendix).
� NOTE
Malfunctioning protection anodes reduce the service life of
the device!
(Electrically insulated magnesium anode with selenium
complying with DIN 4753 part 6)
Fig. 8.1:Anode electric heater
9
Faults / troubleshooting (for
the user)
ATTENTION!
!
Work on the domestic hot water heat pump is to be performed
by qualified personnel only!
Observe accident prevention regulations!
The heat pump will not operate!
Check the following:
the plug is plugged in
stand-by mode has been selected on the keyboard
the socket is supplied with voltage
the air inlet temperature or ambient temperature is -7 °C
the domestic hot water temperature is over 60 °C
The heat pump switches off prematurely (set
temperature has not yet been reached)
Check the following:
air ducts have been bent or their openings have been
sealed, or whether any air filters are heavily contaminated
(clogged).
Condensate cannot drain properly (there is water
under the device)
Check the following:
The seal valve in the end of the condensate hose is con-
taminated or clogged, and clean if necessary; the valve can
be easily removed and replaced.
the inflow and outflow of air is significantly reduced (bent
air duct / clogged air filter).
If the above suggestions cannot help you eliminate these faults,
please contact your technician or after-sales service partner.
10 Decommissioning
Tasks to be carried out:
Disconnect the domestic hot water heat pump from the
power supply.
Completely shut off the water circuit (domestic hot water,
cold water and circulation pipe) and drain the domestic hot
water cylinder.
11 Environmental
requirements
During maintenance or decommissioning of the domestic hot
water heat pump, all environmental requirements regarding re-
covery, recycling and disposal of materials and components
must be observed in compliance with DIN EN 378.
451905.66.02 · FD 9912
EN-15
DHW 300D - DHW 300D+
English
12 Device information
1
Type and order code
DHW 300D
DHW 300D+
2
Design
2.1
Number of units
1
1
2.2
Heat source
Air
Air
2.3
Defrosting
yes
yes
2.4
Nominal cylinder volume
litre
285
280
2.5
Transfer area of the internal heat exchanger
m2
-
1.0
2.6
Sensor pipe ø internal for external sensors
mm
9
9
2.7
Installation location
Frost-free
Frost-free
2.8
Cylinder material
Enamelled steel complying with
DIN 4753
Enamelled steel complying with
DIN 4753
2.9
Cylinder insulation
PU with PS cladding
PU with PS cladding
2.10 Nominal cylinder pressure
bar
6
6
3
Operating limits
3.1
Heat source operating limit1
°C
-7 to 35
-7 to 35
3.2
Domestic hot water setting range in heat pump operation
°C
20 to 60 ± 1.0 K
20 to 60 ± 1.0 K
4
Flow / sound
4.1
Air flow
m3/h
325
325
4.2
External compression max.
Pa
80
80
4.3
Air duct connection length max.
m
10
10
4.4
Sound power level
dB(A)
60
60
4.5
Sound pressure level 2
dB(A)
50
50
5
Dimension/weight and filling quantities
5.1
Dimensions height (min.) x Width x Depth
mm
1867 x 740 x 776
1867 x 740 x 776
5.2
Air duct connection diameter
normial width with EPP-ventilating pipe
mm
190 / DN 160
160 / DN 160
5.3
Weight (empty)
kg
107
122
5.4
Refrigerant R 134a/total filling weight
kg
0.95
0.95
5.5
GWP value / CO2 equivalent
--- / t
1430 / 1
1430 / 1
5.6
Refrigeration circuit hermetically sealed
yes
yes
6
Electrical connection
6.1
Degree of protection
IP 21
IP 21
6.2
Connection voltage
1/N/PE~230 V, 50 Hz
1/N/PE~230 V, 50 Hz
6.3
Connecting cable approx. 2.7 m - 1.5 mm2
With plug
With plug
6.4
Fuse max.
A
C16
C16
6.5
Power consumption heat pump cos
0.8
0.8
6.6
Supplementary electrical heating power consumption
A
6.5
6.5
6.7
Power consumption max.
A
9.5
9.5
6.8
Switch-on current max.
A
13.5
13.5
6.9
Heat pump nominal power consumption at 60 °C3
W
528
528
6.10 Supplementary electrical heating power consumption
W
1500
1500
6.11 Power consumption of fan
W
58
58
6.12 Total power consumption max.
W
2200
2200
7
Hydraulic connection
7.1
Circulation pipe connection
external thread
R 3/4"
R 3/4"
7.2
Domestic hot water outlet connection
external thread
R1"
R1"
7.3
Cold water inlet connection
external thread
R1"
R1"
7.4
Internal heat exchanger connection
external thread
-
Rp 1"
8
Performance values
8.1
Heat-up time 3 4
h:min
09:22
09:22
451905.66.02 · FD 9912
www.gdts.one
English
DHW 300D - DHW 300D+
8.2
Energy consumption during heat-up time 3 4
kWh
4.25
4.25
8.3
Power consumption during stand-by period 4 5
W
29
29
8.4
Electric energy consumption
WEL-TC according to EN 16147 cycle XL 4 5
kWh
5.78
5.78
8.5
COP according to EN 16147 cycle XL 4 5
3.3
3.3
8.6
Reference domestic hot water temperature 4 5
°C
55.9
55.9
8.7
Maximum usable domestic hot water quantity 4 5
litres
421
421
8.8
Load profile 4 5
XL
XL
8.9
Water heating energy efficiency ŋwh 4 5
%
137
137
1. At temperatures below 7 °C ± 1 °C, the heating element switches on automatically and the heat pump module switches off.
2. At a distance of 1m (free-standing installation or installation without exhaust air duct or 90° pipe bends on outlet side).
3. Heating up of nominal volume from 10 °C to 55 °C at air intake temperature of 15 °C and humidity of 70 %
4. The information is valid for a new device with clean heat exchangers
5. At an air intake temperature of 15 °C and 70 % relative humidity.
451905.66.02 · FD 9912
FR-1
DHW 300D - DHW 300D+
Français
Table des matières
1
À lire immédiatement.................................................................................................................................FR-2
1.1
Remarques importantes................................................................................................................................................FR-2
1.2
Utilisation conforme........................................................................................................................................................FR-2
1.3
Prescriptions / consignes de sécurité ......................................................................................................................FR-2
2
Description....................................................................................................................................................FR-3
2.1
Généralités..........................................................................................................................................................................FR-3
2.2
Circuit frigorifique (principe de fonctionnement de la pompe à chaleur) ....................................................FR-3
2.3
Dispositifs de sécurité et de régulation....................................................................................................................FR-4
2.4
Sonde de température ...................................................................................................................................................FR-4
3
Stockage et transport.................................................................................................................................FR-5
3.1
Généralités..........................................................................................................................................................................FR-5
3.2
Transport avec chariot élévateur à fourche (ou chariot élévateur) .................................................................FR-5
3.3
Transport manuel
(état à la livraison).............................................................................................................................................................FR-5
3.4
Transport dans sac de portage (accessoires avec tôle de sécurisation).......................................................FR-5
3.5
Ouverture de l’appareil...................................................................................................................................................FR-6
4
Installation ....................................................................................................................................................FR-6
4.1
Emplacement ....................................................................................................................................................................FR-6
4.2
Installation ..........................................................................................................................................................................FR-6
5
Montage.........................................................................................................................................................FR-7
5.1
Raccordement des conduites d’eau..........................................................................................................................FR-7
5.2
Raccordement de la conduite d’écoulement des condensats ........................................................................FR-7
5.3
Branchements électriques............................................................................................................................................FR-7
5.4
Raccordement de la gaine d’air (en option) ............................................................................................................FR-7
6
Mise en service.............................................................................................................................................FR-8
6.1
Circuit d’eau chaude.......................................................................................................................................................FR-8
7
Commande et fonctions du chauffe-eau thermodynamique ..........................................................FR-8
7.1
Commande et affichage................................................................................................................................................FR-8
7.2
Structure du menu...........................................................................................................................................................FR-9
7.3
Fonctions ......................................................................................................................................................................... FR-12
8
Entretien / maintenance......................................................................................................................... FR-13
8.1
Circuit d’eau / écoulement des condensats........................................................................................................ FR-13
8.2
Circuit d’alimentation en air....................................................................................................................................... FR-13
8.3
Anode anticorrosion..................................................................................................................................................... FR-14
9
Défauts / recherche de pannes (pour l’utilisateur) .......................................................................... FR-14
10 Mise hors service...................................................................................................................................... FR-14
11 Exigences en matière de protection de l’environnement .............................................................. FR-14
12 Informations sur les appareils ............................................................................................................... FR-15
Anhang · Appendix · Annexes............................................................................................................................. A-I
Maßbild / Dimension drawing / Schéma coté ......................................................................................................... A-II
Einbindungsschemen / Integration diagram / Schéma d'intégration.............................................................. A-III
Elektroschema / Electrical circuit diagram / Schéma électrique ....................................................................... A-V
Konformitätserklärung / Declaration of Conformity / Déclaration de conformité .......................................A-VI
451905.66.02 · FD 9912
www.gdts.one
Français
DHW 300D - DHW 300D+
1
À lire immédiatement
1.1
Remarques importantes
ATTENTION !
!
Avant la mise en service, lire ces instructions de montage et
d’utilisation!
ATTENTION !
!
Tout travail sur le chauffe-eau thermodynamique ne devra
être réalisé que par un personnel qualifié! Respecter les
consignes de sécurité de prévention des accidents!
ATTENTION !
!
Ne pas utiliser le capot de l’appareil pour le transport (le capot
n’a pas été conçu pour supporter de fortes sollicitations!)
ATTENTION !
!
Ne pas oublier de retirer la tôle de blocage après l'installation
de la pompe à chaleur !
ATTENTION !
!
La pompe à chaleur ne doit pas être transportée tête penchée
vers le bas.
ATTENTION !
!
Lors du raccordement aux tuyauteries du client, éviter la
pénétration
d’impuretés
dans
le
circuit
(rincer
éventuellement les conduites avant de raccorder le chauffe-
eau thermodynamique)!
ATTENTION !
!
Le chauffe-eau thermodynamique ne peut fonctionner que
rempli d’eau!
ATTENTION !
!
Il convient d’utiliser une sonde de température ayant les
caractéristiques de résistance d’une PT1000 pour le capteur
(voir Chap. 2.4.2 à la page 4).
ATTENTION !
!
Mettre le chauffe-eau thermodynamique hors tension avant
de l’ouvrir. Tenir compte du fait que le ventilateur continue à
tourner!
ATTENTION !
!
Lamelles à arêtes vives : risque de blessures. Ne pas déformer
ni endommager les lamelles!
ATTENTION !
!
Avant d’ouvrir l’appareil, assurez-vous qu’il est bien hors
tension.
ATTENTION !
!
La borne X8 peut aussi être sous tension pendant l'arrêt de la
pompe à chaleur
ATTENTION !
!
Dans le cas des réglages requis pour l'utilisation de l'énergie
photovoltaïque, de la thermie solaire ou d'une chaudière
externe, des températures de l'eau chaude sanitaire >60°C
sont possibles. Par conséquent, une protection anti-brûlure
externe doit donc être prévue.
1.2
Utilisation conforme
Cet appareil ne doit être employé que pour l’affectation prévue
par le fabricant. Toute autre utilisation est considérée comme
non conforme. La documentation accompagnant les projets
doit également être prise en compte. Toute modification ou
transformation sur l’appareil est à proscrire.
1.3
Prescriptions / consignes de
sécurité
ATTENTION !
!
Avant la mise en service, lire ces instructions de montage et
d’utilisation!
Le chauffe-eau thermodynamique sert exclusivement à
chauffer l’eau sanitaire et/ou l’eau potable dans les limites
de température spécifiées! Le chauffage de liquides autres
que l’eau potable n’est pas autorisé. Il est impératif de res-
pecter les normes techniques relatives à l’installation d’eau
chaude potable. Les diamètres nominaux pour le raccorde-
ment aux conduites de l’installation sanitaire doivent être
déterminés en fonction des spécificités du bâtiment ainsi
que des normes et des prescriptions en vigueur. Ne pas ou-
blier de monter les éventuels dispositifs de sécurité néces-
saires, comme les manodétendeurs.
Il est interdit:
Ne pas installer l’appareil:
Le fonctionnement de l’appareil est interdit:
Lors de la conception et de la fabrication du chauffe-eau
thermodynamique, les directives UE applicables ont été
respectées. (Voir aussi déclaration de conformité CE.)
La personne qualifiée doit veiller, avant les travaux d’entre-
tien et de remise en état sur les parties contenant du fluide
frigorigène, à éliminer ce fluide autant que nécessaire pour
permettre une exécution des travaux sans danger. Manipu-
ler et éliminer le fluide frigorigène conformément aux pres-
criptions; le fluide frigorigène ne doit pas parvenir directe-
ment dans l’environnement!
Le circuit frigorifique est « hermétiquement fermé » et
contient le fluide frigorigène fluoré R134a répertorié dans
le protocole de Kyoto. Vous trouverez la valeur PRG (poten-
- d’utiliser l’appareil avec de l’air évacué contenant des
solvants ou des matières explosives
- d’utiliser de l’air évacué contenant des graisses ou
chargé de poussières
ou d’aérosols collants
- de raccorder des hottes d’évacuation de la vapeur
au système de ventilation
- à l’extérieur
- dans des locaux exposés au gel
- dans des locaux humides (salles de bains par ex.)
- dans des locaux présentant un danger d’explosion
(car contenant des gaz, des émanations ou des pous-
sières)
- avec un ballon vide
- tant que le bâtiment est en travaux
451905.66.02 · FD 9912
FR-3
DHW 300D - DHW 300D+
Français
tiel de réchauffement global) et l'équivalent CO2 du fluide
frigorigène au chapitre Informations sur les appareils. Il est
sans HCFC, non inflammable et ne détruit pas la couche
d’ozone.
Vous trouverez plus d'informations à ce sujet dans le jour-
nal de bord ci-joint.
Tout travail sur le chauffe-eau thermodynamique devra
être effectué hors tension.
Les normes VDE, EN ou CEI correspondantes doivent être
respectées lors des branchements électriques du chauffe-
eau thermodynamique. En outre, il convient de respecter
les conditions de branchement des sociétés d’électricité.
Cette pompe à chaleur est conçue pour une utilisation
dans un environnement domestique selon l’article1 (para-
graphe 2k) de la directive UE 2006/42/CE (directive rela-
tive aux machines) et est ainsi soumise aux exigences de la
directive UE 2014/35/UE (directive basse tension). Elle est
donc également prévue pour l’utilisation par des per-
sonnes non initiées à des fins de production d'eau sanitaire
pour les boutiques, bureaux, autres environnements de tra-
vail équivalents et entreprises agricoles, ainsi que les hô-
tels, pensions et autres lieux résidentiels.
ATTENTION !
!
Tout travail sur le chauffe-eau thermodynamique ne devra
être réalisé que par un personnel qualifié!
Respecter les consignes de sécurité de prévention des
accidents!
2
Description
2.1
Généralités
Le chauffe-eau thermodynamique est un appareil de chauffage
prêt à brancher. Il est pour l’essentiel composé du ballon d’eau
chaude sanitaire, des composants du circuit de fluide frigori-
gène, du circuit d’air et du circuit d’eau, ainsi que de tous les
dispositifs de commande, de régulation et de surveillance des-
tinés au fonctionnement automatique.
Le chauffe-eau thermodynamique utilise, s’il est alimenté en
énergie électrique, la chaleur de l’air aspiré pour la production
d’eau chaude sanitaire. L’échangeur thermique optionnel inté-
gré est destiné à être raccordé à un générateur de chaleur sup-
plémentaire tel que chaudière ou installation solaire. Les appa-
reils sont équipés de série d’une résistance électrique (1,5 kW).
Ce sont les températures de l’air aspiré (source de chaleur) et de
l’eau chaude qui déterminent le besoin en énergie et la durée
de chauffage de la production d’eau chaude sanitaire.
Pour cette raison, et afin de permettre une récupération ciblée
de la chaleur perdue, un système de gaines d’air (DN 160, lon-
gueur max. 10 m) peut être relié à la tubulure installée de série
sur le chauffe-eau thermodynamique. Pour assurer un fonc-
tionnement efficace de la pompe à chaleur, il convient d’une
manière générale d’éviter un court-circuit d’air entre aspiration
et échappement de l’air. On peut envisager, par ex., d’installer
un coude côté aspiration et côté échappement.
Une chute de la température de l’air évacué provoque une dimi-
nution de la puissance calorifique de la pompe à chaleur et une
prolongation de la durée de montée en température. Un fonc-
tionnement rentable de la pompe à chaleur n’est assuré que si
la température de l’air aspiré ne descend pas en dessous de
15 °C de façon prolongée.
La résistance électrique remplit les fonctions
suivantes:
Chauffage d’appoint
La touche «Boost permet de préparer l'eau chaude sani-
taire au moyen de la résistance électrique pour une durée
qui peut être paramétrée.
Limite d’utilisation
Si la température d’entrée de l’air descend en dessous de
7±1,0 °C, la résistance électrique se met automatiquement
en route et chauffe l’eau à la température de consigne qui
a été paramétrée (température nominale).
Chauffage de secours
En cas de défaut de la pompe à chaleur, la résistance élec-
trique assure le maintien de la production d’eau chaude sa-
nitaire.
Désinfection thermique préventive
Des températures d’eau supérieures à 60 °C (85 °C max.)
peuvent être programmées dans l'option de menu Désin-
fection thermique préventive via le clavier du panneau de
commande.
Réchauffement d'appoint
La résistance électrique permet d'obtenir des tempéra-
tures de l'eau supérieures à 60 °C.
REMARQUE
�
Lorsque la température de l’eau est > 60 °C, la pompe à
chaleur s’arrête et la production d’eau chaude sanitaire est
assurée uniquement par la résistance électrique. Le
régulateur de la résistance électrique est préréglé sur 65 °C
2.2
Circuit frigorifique (principe de
fonctionnement de la pompe à
chaleur)
Le circuit frigorifique est un système fermé dans lequel le fluide
frigorigène R134a sert de vecteur d’énergie. L’échangeur à la-
melles extrait la chaleur de l’air aspiré à basse température
d’évaporation et la transmet au fluide frigorigène. Le fluide fri-
gorigène est aspiré sous forme de vapeur par un compresseur
qui le porte à une pression et une température plus élevées et
l’envoie au condenseur, dans lequel la chaleur recueillie par
l’évaporateur et une partie de l’énergie absorbée par le com-
presseur sont transmises à l’eau. Puis, la pression élevée de
condensation est ramenée par un organe de décompression
(détendeur) au niveau de la pression d’évaporation, et le fluide
frigorigène peut à nouveau extraire, dans l’évaporateur, la cha-
leur contenue dans l’air aspiré.
451905.66.02 · FD 9912
www.gdts.one
Français
DHW 300D - DHW 300D+
2.3
Dispositifs de sécurité et de
régulation
Le chauffe-eau thermodynamique est équipé des dispositifs de
sécurité suivants:
Pressostat haute pression (PHP)
Le pressostat haute pression protège la pompe à chaleur d’une
pression trop importante au niveau du circuit frigorifique. En
cas de défaut, le pressostat arrête la pompe à chaleur. Le redé-
marrage de la pompe à chaleur est impossible tant que la pres-
sion du circuit frigorifique n’est pas retombée.
Limiteur de température de sécurité (LTS) de la
résistance électrique
Le LTS évite que l’eau ne monte trop en température dans le
ballon d’eau chaude sanitaire.
Un dépassement du seuil de température paramétré (99 °C) dé-
clenche l’arrêt de la résistance électrique.
Le réenclenchement de la résistance électrique n’est possible
que lorsque la température de l’eau chaude sanitaire est retom-
bée à 90 °C et après que quelqu’un (personnes qualifiées uni-
quement) a appuyé sur le bouton de redémarrage (voir figure)
du LTS (sous le couvre-bride).
Le chauffe-eau thermodynamique est équipé des dispositifs de
régulation et de commande suivants:
Pompe à chaleur - réglage de la température
L’électronique de commande contrôle la température dans le
ballon d’eau chaude sanitaire et régule le fonctionnement du
compresseur. Les sondes électroniques mesurent la tempéra-
ture de l’eau, laquelle est réglée en fonction de la valeur de
consigne définie. Le niveau de température souhaité (valeur de
consigne) est réglé via le clavier du tableau de commande.
Température d’entrée de l’air
La sonde raccordée à la régulation mesure la température dans
le chauffe-eau thermodynamique directement en amont de
l’évaporateur (température de l’air aspiré). Si la température est
inférieure au seuil de commutation fixe (-7 ±1 °C, hystérésis de
2K,
temporisation de 30min), la production d’eau chaude sanitaire
passe automatiquement du mode pompe à chaleur au mode
résistance électrique.
2.4
Sonde de température
2.4.1 Position de montage de la sonde de
température
R1
Sonde d’entrée d’air
R3 Sonde d’eau chaude sanitaire
R5 Sonde d’eau chaude sanitaire régénérative (en option)
R12
Sonde fin de dégivrage
R13 Sonde régénérative (en option)
2.4.2 Valeurs de mesure de la sonde de
température
Valeurs de mesure de la sondeNTC10 (R1, R3, R5,
R12)
Valeurs de mesure de la sonde PT1000 (R13)
85°
30°
F17
STB
Rückstellknopf
Température en °C
-20
-15
-10
-5
0
5
10
NTC-10 en k
67,7
53,4
42,3
33,9
27,3
22,1
18,0
15
20
25
30
35
40
45
50
55
60
14,9
12,1
10,0
8,4
7,0
5,9
5,0
4,2
3,6
3,1
Température
en °C
-30 -20 -10
0
10
20
30
40
50
PT 1000 en k
0,88
2
0,02
2
0,96
1
1,00
1,03
9
1,07
8
1,11
7
1,15
5
1,19
4
60
70
80
90 100 110 120 130 140 150 160
1,23
2
1,27
1
1,30
9
1,34
7
1,38
5
1,42
3
1,46
1
1,49
8
1,53
6
1,57
3
1,61
1
451905.66.02 · FD 9912
FR-5
DHW 300D - DHW 300D+
Français
3
Stockage et transport
3.1
Généralités
D’une manière générale, le chauffe-eau thermodynamique doit
être stocké et transporté emballé, à la verticale et vide d’eau.
Sur de petits trajets, une inclinaison de 45° est autorisée à
condition de transporter l’appareil avec précaution. Les tempé-
ratures ambiantes de transport et de stockage admises vont de
-20 à +60 °C.
3.2
Transport avec chariot
élévateur à fourche (ou chariot
élévateur)
Lors du transport avec un chariot élévateur à fourche, le
chauffe-eau thermodynamique doit rester sur une palette. Le
levage doit s’effectuer à une faible vitesse d’élévation! Le
chauffe-eau thermodynamique présentant un équilibre ins-
table, il convient de l’arrimer pour éviter qu’il ne bascule. Afin
d’éviter tout dommage, poser le chauffe-eau thermodyna-
mique sur une surface plane.
3.3
Transport manuel
(état à la livraison)
Pour le transport manuel, la palette en bois peut être utilisée
comme socle. Une deuxième ou troisième personne peut aider
au transport au moyen d’élingues ou de sangles (ces dernières
peuvent être mises autour de l’enveloppe du ballon et fixées
aux embouts des tuyaux). Dans ce type de transport (y compris
par diable), veiller à ne pas dépasser l’inclinaison max. admis-
sible de 45° (voir figure).
ATTENTION !
!
Ne pas utiliser le capot de l’appareil pour le transport (le capot
n’a pas été conçu pour supporter de fortes sollicitations!)
3.4
Transport dans sac de portage
(accessoires avec tôle de
sécurisation)
Le sac de transport proposé comme accessoire permet de dé-
placer la pompe à chaleur à l'horizontale à l'intérieur du bâti-
ment. Pour cela, retirer le capot et installer la tôle de blocage
fournie avec le sac de transport. À l'aide du matériel de mon-
tage fourni, fixer la tôle entre l'œillet de transport du compres-
seur et la paroi de séparation.
ATTENTION !
!
Ne pas oublier de retirer la tôle de blocage après l'installation
de la pompe à chaleur !
Pendant toute la durée de la manutention, veiller à ne pas trans-
porter l'appareil tête penchée vers le bas.
ATTENTION !
!
La pompe à chaleur ne doit pas être transportée tête penchée
vers le bas.
45°
Surface de soutien de
la pompe à chaleur dans
le sac de transport
Tôle de blocage
Fixer la tôle de blocage
sur le compresseur
Fixer la tôle de blocage sur
la paroi de séparation
451905.66.02 · FD 9912
www.gdts.one
Français
DHW 300D - DHW 300D+
3.5
Ouverture de l’appareil
Le capot de l’appareil est en deux parties. Il est possible de reti-
rer les deux parties du capot pour accéder à l’intérieur de l’ap-
pareil ou faciliter le transport (prévention des dommages). Pour
cela, il suffit de tourner les quatre loquets d’un quart de tour
dans le sens antihoraire (le symbole en forme de cadenas sur la
face avant indique si le loquet est verrouillé ou non).
Ensuite, il suffit de tirer le capot avant vers l’avant pour le retirer.
Pour retirer le capot de canalisation d’air, il faut retirer les deux
vis de fixation. Ensuite, il suffit de tirer le capot vers l’arrière pour
le retirer.
4
Installation
4.1
Emplacement
À considérer pour le choix de l’emplacement:
Le chauffe-eau thermodynamique doit être installé dans
un local sec à l’abri du gel.
L’installation et l’aspiration d’air sont également interdites
dans des locaux présentant un danger d’explosion lié aux
gaz, émanations ou poussières qu’ils contiennent.
Pour éviter tout dommage dû à l’humidité des murs inté-
rieurs, il est recommandé de prévoir une bonne isolation
thermique entre la pièce vers laquelle l’air évacué est dirigé
et les pièces d’habitation avoisinantes.
Prévoir un écoulement des condensats (avec siphon).
L’air aspiré ne doit pas contenir trop d’impuretés et ne doit
pas être fortement chargé en poussières.
Le sol doit présenter une force portante suffisante (le poids
approximatif du chauffe-eau thermodynamique plein est
de 420 kg!).
Il faut prévoir un dégagement d’au moins 0,6 m à gauche
comme à droite de l’appareil (voir figure) pour qu’il puisse fonc-
tionner correctement, mais aussi pour effectuer les interven-
tions d’entretien et de réparation. Le raccordement au chauffe-
eau thermodynamique peut être effectué (en option) au moyen
de gaines d’air en EPP de diamètre intérieur DN 160 mm et dia-
mètre extérieur 190 mm et d’une longueur max. totale de 10 m.
En l’absence de gaines d’air, il est possible de réduire le niveau
sonore d’échappement au moyen d’un coude à 90° en EPP
orienté vers le bas (voir figure).
4.2
Installation
Retirer les trois vis de fixation pour le transport (M12 -
fixent l’appareil à la palette) en les dévissant de la face infé-
rieure de la palette.
Enlever la palette et monter les trois pieds de réglage (M12
dans la poche en plastique fixée sur l’embout du ballon).
Positionner le chauffe-eau thermodynamique et vérifier
qu’il est bien d’aplomb en réglant les pieds! Serrer alors les
contre-écrous des pieds de l’appareil.
Loquet
ouvert
min. 0,6 m
min. 0,6 m
min. 0,3 m
Coude à 90° en EPP
(accessoire)
Vue de face
451905.66.02 · FD 9912
FR-7
DHW 300D - DHW 300D+
Français
5
Montage
5.1
Raccordement des conduites
d’eau
Les raccordements d’eau (voir schéma coté, Chap. 1 à la page
II) se trouvent à l’arrière de l’appareil.
REMARQUE
�
Conduite de circulation
Afin d’économiser de l’énergie, il est recommandé de se
dispenser de conduite de circulation (bouclage). En cas de
raccordement d’une conduite de circulation au système de
distribution d’eau chaude, prévoir une possibilité de
fermeture (vanne ou autre élément d’arrêt) afin de limiter les
pertes d’énergie inutiles. Le circulateur de bouclage ECS doit
être activé en fonction des besoins (commande par minuterie
ou en cas de besoin).
Les diamètres nominaux pour le raccordement aux conduites
de l’installation sanitaire du client doivent être déterminés en
fonction de la pression d’eau disponible et des pertes de pres-
sion prévisibles du circuit de tuyauteries.
Il est impératif de respecter les normes techniques relatives à
l’installation d’eau chaude potable. Les diamètres nominaux
pour le raccordement aux conduites de l’installation sanitaire
doivent être déterminés en fonction des spécificités du bâti-
ment ainsi que des normes et des prescriptions en vigueur. Ne
pas oublier de monter les éventuels dispositifs de sécurité né-
cessaires, comme les manodétendeurs.
Les conduites d’eau peuvent être de type rigide ou flexible.
Tenir compte du comportement à la corrosion des matériaux
utilisés pour le circuit de tuyauteries afin d’éviter les dégâts dus
à la rouille (voir section Mise en service).
REMARQUE
�
Raccordements eau chaude sanitaire, eau froide, circulation :
Les nipples comportent des inserts en plastique qui les
protègent de la corrosion (en particulier au niveau des bords).
Ces inserts en plastique restent en place après l’installation
des conduites d’eau.
ATTENTION !
!
Lors du raccordement aux tuyauteries du client, éviter la
pénétration
d’impuretés
dans
le
circuit
(rincer
éventuellement les conduites avant de raccorder le chauffe-
eau thermodynamique)!
5.2
Raccordement de la conduite
d’écoulement des condensats
Le flexible d’écoulement des condensats passe à travers l’enve-
loppe sur la paroi arrière de l’appareil. Il doit être monté de telle
sorte que les condensats (produits par le fonctionnement de la
pompe à chaleur) puissent s’écouler librement.
Le bout du flexible est muni d’une vanne d’étanchéité à ouver-
ture sans pression, qui doit être replacée sur le flexible d’éva-
cuation des condensats si celui-ci est raccourci (la vanne peut
être aisément démontée puis remontée). Faire déboucher les
condensats dans un siphon (voir aussi les consignes de mainte-
nance au point 8.1).
REMARQUE
�
La vanne à lèvre d'étanchéité doit être utilisée afin de prévenir
tout dommage dû aux condensats.
5.3
Branchements électriques
Le chauffe-eau thermodynamique est précâblé et prêt à être
branché. L’alimentation électrique s’effectue par un câble de
raccordement secteur branché sur une prise de terre (~230 V,
50 Hz). Cette prise de courant doit rester accessible après le
montage. Pour la commande d’appareils externes, tels que le
deuxième générateur de chaleur, le circulateur solaire ou la
sonde de température du capteur, il convient de passer un
câble séparé avec décharge de traction dans l’appareil au tra-
vers d’un presse-étoupe libre. Pour ce faire, ouvrir le capot de
l’appareil comme décrit au Chap. 3.5 à la page 6. Les divers
points de raccordement des composants figurent dans le ta-
bleau suivant ainsi que dans la documentation électrique.
5.4
Raccordement de la gaine d’air
(en option)
Cet appareil a été spécialement conçu pour le raccordement
d’une gaine d’air en EPP (éléments constitutifs disponibles
dans la gamme des accessoires, diamètre intérieur DN 160).
Les deux tubulures de raccordement à 90° se prêtent aux confi-
gurations de raccordement les plus variées.
Sortie d‘air
Entrée d‘air
451905.66.02 · FD 9912
www.gdts.one
Français
DHW 300D - DHW 300D+
6
Mise en service
6.1
Circuit d’eau chaude
ATTENTION !
!
Le chauffe-eau thermodynamique ne peut fonctionner que
rempli d’eau!
Conditions à remplir par le circuit d’eau chaude
sanitaire
Pour son circuit d’eau chaude sanitaire, le client peut utiliser les
matériaux suivants:
Cuivre
Acier inoxydable
Laiton
Matière plastique
Les incompatibilités avec les matériaux utilisés dans le circuit
d’eau chaude sanitaire (côté client) peuvent provoquer un phé-
nomène de corrosion et donc des dommages. C’est notam-
ment le cas en cas d’association de matériaux zingués et de
matériaux contenant de l’aluminium. Prévoir éventuellement un
filtre si l’eau utilisée pour le fonctionnement de la pompe risque
de contenir des impuretés.
Mise en service de l’installation d’eau chaude
sanitaire
Toutes les installations effectuées sur les circuits d’eau et
d’air ainsi que toutes les installations électriques doivent
être exécutées intégralement et selon les réglementations.
Remplir le circuit d’eau chaude par le biais du raccorde-
ment externe.
Purger le circuit d’eau chaude (ouvrir les robinets d’eau
chaude aux points de prise supérieurs jusqu’à purge com-
plète de l’air).
Vérifier l’étanchéité du circuit d’eau chaude dans son en-
semble.
Établir l’alimentation électrique.
Mettre en marche la «pompe à chaleur».
La température souhaitée pour l’eau chaude sanitaire (par
ex. 45 °C) se règle au clavier (Chap. 7 à la page 8). Un temps
de montée en charge est systématiquement nécessaire
pour atteindre le niveau de température sélectionné.
7
Commande et fonctions du
chauffe-eau
thermodynamique
7.1
Commande et affichage
7.1.1 Touches de commande
7.1.2 Description de l’affichage d’état
opérationnel
Touch
e
Nom
Description
Menu
Permet de passer au menu principal, où il est
possible d’effectuer des réglages détaillés pour
la pompe à chaleur.
Boost
Chauffage rapide
La résistance électrique se met en marche et
fonctionne jusqu’à ce que la température de
consigne de l’eau chaude sanitaire soit atteinte,
à raison toutefois d’une durée de 4 heures
maximum.
Esc
ESC
Retour au niveau de menu immédiatement
supérieur
OK
Début et fin de la modification d’un paramètre
ou sélection de l’option de menu souhaitée;
HAUT
Augmentation de la valeur ou sélection de
menu et de paramètre
BAS
Diminution de la valeur ou sélection de menu et
de paramètre
Ligne d’en-tête :
Type d'appareil, jour de la semaine, heure
Main field:
Information overview in plain text
451905.66.02 · FD 9912
FR-9
DHW 300D - DHW 300D+
Français
7.2
Structure du menu
Modification des paramètres: La touche « Menu » sert à accé-
der au menu. C’est ici que vous pouvez modifier des para-
mètres. Les touches flèches « HAUT » / « BAS » servent à sé-
lectionner l’option de menu souhaitée. La touche « OK »
permet d’accéder au sous-menu.
Les touches flèches servent également à sélectionner les para-
mètres à modifier. La touche « OK » sert à sélectionner la va-
leur en surbrillance pour la modifier à l’aide des touches flèches.
Le paramètre spécifié est validé en appuyant une nouvelle fois
sur la touche « OK ».
w
Groupe de menus
Option de
menu
Paramètre
Valeur
Description
Réglages
Heure
00:00
Réglage de l’heure (format 24 h)
Date
JJ:MM:AAAA
Réglage de la date (jour:mois:année)
Langue
DEUTSCH
ENGLISCH
FRANÇAIS
ITALIANO
POLSKI
Sélection de la langue
Signal sonore
Marche
Arrêt
Paramètre d’activation / désactivation des signaux sonores
Rétro-éclairage
0 % ... 50 % ...100 %
Réglage du rétro-éclairage de l’écran
Réglages usine
Restauration des paramétrages d'usine
Type
DHW300
DHW300+
DHW300D
DHW300D+
Ballon thermodynamique DHW 300
Ballon thermodynamique DHW 300+
avec échangeur thermique supplémentaire
Ballon thermodynamique DHW 300D
avec fonction de dégivrage
Ballon thermodynamique DHW 300D+
avec fonction de dégivrage et échangeur the5rmique supplémen-
taire
Eau chaude sani-
taire
Température de consi-
gne
25 °C ... 45 °C ... 85 °C
Réglage de la température de consigne de l’eau chaude sanitaire
Abaissement
15 °C ... 25 °C ... 40 °C
Réglage de la température minimale de l’eau chaude sanitaire,
c’est-à-dire du seuil en dessous duquel elle ne doit pas descendre,
y compris pendant une durée d'abaissement programmée
Hystérésis
2 K ... 3 K ... 10 K
Réglage de l’hystérésis de commutation
Chauffage électrique
Mode
Temporisation
Durée boost
Temp. consigne
boost
ECO
AUTO
2 h ... 8 h...16 h
1 h ... 4 h ... 8 h
25 °C ... 60 °C ... 85 °C
ECO : n'est activé qu'en cas de défaut, ainsi que pour la PV et/ou la
désinfection thermique
La résistance électrique se met automatiquement en marche si la
température de consigne de l'eau chaude sanitaire n'est pas
atteinte dans le délai de temporisation paramétré en mode pompe
à chaleur.
Boost: durée paramétrable (une seule fois, indépendamment du
réglage Auto/Eco)
Boost: température de consigne paramétrable
Programm. horai-
res
Désinfection thermique
Désinfection thermique
Début
00:00 ... 23:59
Réglage de l’heure de démarrage de la désinfection thermique (for-
mat 24 h)
Jours
Lu ... Di
Réglage du jour de déclenchement de la désinfection thermique
Val. consigne
60 °C ... 65 °C ... 85 °C
Réglage de la température de consigne pour la désinfection ther-
mique
1er abaissement
Début
00:00 ... 23:59
Réglage de l’heure de démarrage de l’abaissement de la tempéra-
ture de consigne de l'eau chaude sanitaire
Fin
00:00 ... 23:59
Réglage de l’heure de fin de l’abaissement de la température de
consigne de l'eau chaude sanitaire
Jours
Di ... Lu
Lu - Ve
Sa - Di
Lu - Di
Réglage du jour de la semaine / bloc de jours durant lequel l’abais-
sement doit être activé
2e abaissement
Début
00:00 ... 23:59
Réglage de l’heure de démarrage de l’abaissement de la tempéra-
ture de consigne de l'eau chaude sanitaire
451905.66.02 · FD 9912
www.gdts.one
Français
DHW 300D - DHW 300D+
Fin
00:00 ... 23:59
Réglage de l’heure de fin de l’abaissement de la température de
consigne de l'eau chaude sanitaire
Jours
Di ... Lu
Lu - Ve
Sa - Di
Lu - Di
Réglage du jour de la semaine / bloc de jours durant lequel l’abais-
sement doit être activé
(s’affiche uniquement sur les appareils avec échangeur thermique supplémentaire et sélection Arrêt ou Sol)
Solaire
Sélection
Arrêt
Bivalent
Sol
Choix de la source de chaleur supplémentaire
Arrêt : (pas de source de chaleur supplémentaire)
Bivalent : 2e générateur de chaleur, par ex. chaudière au fioul, au
gaz ou au bois
Sol. : système solaire thermique
Différence enclenche-
ment
6 K ... 8 K ... 10 K
Réglage de la différence de température entre le capteur et le bal-
lon à partir de laquelle la pompe solaire doit être activée
Différence coupure
2 K ... 4 K ... 6 K
Réglage de la différence de température entre le capteur et le bal-
lon à partir de laquelle la pompe solaire doit être désactivée
Temp. max. ballon
60 °C ... 65 °C ... 85 °C
Réglage de la température maximale admissible du ballon en cas de
production solaire
Temp. max. capteur
125 °C ... 130 °C ... 135 °C
Réglage de la température maximale admissible au niveau du cap-
teur
(s’affiche uniquement sur les appareils avec échangeur thermique supplémentaire et sélection Arrêt ou Bivalent)
2e générateur de
chaleur
Sélection
Arrêt
Bivalent
Sol
Choix de la source de chaleur supplémentaire
Arrêt : (pas de source de chaleur supplémentaire)
Bivalent : 2e générateur de chaleur, par ex. chaudière au fioul, au
gaz ou au bois
Sol. : système solaire thermique
Temp. bivalence
-8 °C ... 10 °C ... 15 °C
Température limite pour le 2e générateur de chaleur. La pompe à
chaleur est bloquée en dessous de cette température
Photovoltaïque
Chauffage électrique
Oui
Non
Activation de la résistance électrique (parallèlement à la pompe à
chaleur) en mode de fonctionnement photovoltaïque
Température de consi-
gne
35 °C ... 45 °C ... 60 °C
Entrée de la valeur de consigne de l’eau chaude sanitaire activée en
cas de commutation de l’entrée photovoltaïque. La valeur de
consigne majorée est également active si la température de l’air
aspiré n’autorise pas le fonctionnement de la pompe à chaleur.
Dans ce cas, la demande est prise en charge par la résistance élec-
trique, ou le cas échéant, par le 2e générateur de chaleur.
Informations
État de service
Haut de ballon
Affichage de la température en haut de ballon (R3)
Bas de ballon
Affichage de la température en bas de ballon (R5)
Entrée d’air
Affichage de la température d’air (R1)
Temp. capteur
Affichage de la température du capteur (R 13 uniquement sur les
modèles avec échangeur thermique supplémentaire et paramètre
Sol. sélectionné pour le 2e générateur de chaleur)
Val. consigne actu.
Affichage de la valeur de consigne actuelle pour l’eau chaude sani-
taire
Sonde dégivr.
Affichage de la sonde dégivrage (uniquement sur les modèles avec
dégivrage)
Ventilateur
Affichage de l’état de commutation du ventilateur
Compresseur
Affichage de l’état de commutation du compresseur
Chauffage élec-
trique
Affichage de l’état de commutation de la résistance électrique
Puissance
Affichage de la puissance absorbée de l’appareil (calculée)
Mode de fonct.
Affichage du mode de fonctionnement actuel
Durées de fonct.
Appareil
Affichage des heures de fonctionnement
Ventilateur
Affichage de la durée de fonctionnement du ventilateur
Compresseur
Affichage de la durée de fonctionnement du compresseur
Groupe de menus
Option de
menu
Paramètre
Valeur
Description
451905.66.02 · FD 9912
FR-11
DHW 300D - DHW 300D+
Français
Chauffage élec-
trique
Affichage de la durée de fonctionnement de la résistance électrique
Vers. logiciel
Affichage de la version logicielle
Matériel
Affichage de la version matérielle
Numéro de série
Affichage du numéro de série
Service
Saisir mot de passe
Rubrique réservée au SAV, accès protégé par mot de passe
Messages
Alarmes
Affichage des alertes, de leurs types et de leurs fréquences
(écran d’accueil lors de la mise en service initiale)
Réglages de base
Langue
Réglage de la langue
Date
Réglage de la date actuelle
Heure
Réglage de l’heure actuelle
Température de consi-
gne
Réglage de la température d’eau chaude sanitaire souhaitée
Abaissement
Réglage de la température d’eau chaude sanitaire abaissée
Groupe de menus
Option de
menu
Paramètre
Valeur
Description
451905.66.02 · FD 9912
www.gdts.one
Français
DHW 300D - DHW 300D+
7.3
Fonctions
7.3.1 Programmations horaires
Abaissement
Le réglage de durées d’abaissement permet de bloquer le fonc-
tionnement du ballon thermodynamique. Deux durées d’abais-
sement peuvent être programmées séparément. Les durées
d’abaissement sont activées séparément dès que la valeur des
heures ou des minutes est différente de zéro. Le ballon est
maintenu à la température d’abaissement au cours des phases
d’abaissement. Les fonctions Solaire thermique, Utilisation du
courant des installations photovoltaïques et Boost (chauffage
rapide) sont disponibles pendant une durée de blocage.
Désinfection thermique préventive
Il est nécessaire de régler l’heure du début de la désinfection
thermique préventive ainsi que la valeur de consigne souhaitée.
La fonction est activée dès que la valeur des heures ou des mi-
nutes est différente de zéro.
Pour atteindre la température de consigne réglée, la pompe à
chaleur et la résistance électrique sont mises en marche dès le
début. Cela garantit que la valeur de consigne exigée sera at-
teinte le plus rapidement possible.
REMARQUE
�
La désinfection thermique préventive est interrompue si, au
bout de 4heures, la température de consigne n’est toujours
pas atteinte. L’heure de début réglée peut être activée tous les
jours de la semaine. La désinfection thermique préventive ne
doit pas être démarrée après 20heures, de manière à pouvoir
disposer des 4heures requises.
7.3.2 Chauffage électrique
La résistance électrique intégrée peut servir d’appoint au mode
pompe à chaleur. Elle se met automatiquement en marche si la
température de consigne de l’eau chaude sanitaire n’est pas at-
teinte dans le délai paramétré en mode pompe à chaleur. En
mode ECO, la résistance électrique n'est sollicitée que lorsque
les plages d'utilisation de la pompe à chaleur sont abandonnées
et qu'aucun 2e générateur de chaleur n'est disponible. C’est le
cas, p. ex., lorsque la température d’entrée de l’air est dépassée
ou n’est pas atteinte. La touche «Boost» permet de préparer
l'eau chaude sanitaire au moyen de la résistance électrique
pour une durée qui peut être paramétrée.
La résistance électrique est bloquée si la température de l’air
est supérieure à -7 °C. Elle peut également être mise en marche
manuellement au-dessus de la limite de -7 °C uniquement pour
la fonction Boost (chauffage rapide).
7.3.3 Deuxième générateur de chaleur
(modèle DHW 300D+ uniquement)
L’échangeur thermique à tubes intégré (1 m²) permet d’utiliser
un générateur de chaleur déjà installé pour le chauffage du bal-
lon. Il convient d’activer l’utilisation d’un deuxième générateur
de chaleur dans le menu. Il est alors sollicité en dehors des
plages d’exploitation de la pompe à chaleur. C’est le cas lorsque
la température d’entrée d’air se situe en dehors des limites
d’utilisation inférieure et supérieure, mais aussi si la tempéra-
ture de consigne de l'eau chaude sanitaire ne peut être atteinte
en mode pompe à chaleur (par ex. désinfection thermique pré-
ventive). Dans ce cas, le deuxième générateur de chaleur est
prioritaire sur la résistance électrique de la pompe à chaleur. En
cas d’activation du 2e générateur de chaleur, on peut sélection-
ner également une température de bivalence, différente de la li-
mite d’utilisation inférieure constituée par la température de
l’air. Si la température n’atteint pas cette limite inférieure, le
fonctionnement de la pompe à chaleur est bloqué à partir de la
température réglée et le 2e générateur de chaleur est utilisé.
Pour recharger le ballon à l’aide de l’échangeur thermique sup-
plémentaire, il faut un circulateur commandé selon les besoins.
Pour cela, deux solutions sont envisageables :
Commande d’un circulateur pour utiliser
l’échangeur thermique via la régulation du chauffe-
eau thermodynamique existante
Nous recommandons cette solution en présence d’une source
de chaleur continue, par ex. ballon tampon d’un chauffage au
bois pendant l’utilisation du 2e générateur de chaleur.
Le branchement du circulateur s’effectue au niveau de la borne
X4.
Commande d’un circulateur pour utiliser
l’échangeur thermique via la régulation existante
d’une chaudière
Nous recommandons cette solution si, parallèlement au circu-
lateur, une chaudière doit également être mise en marche pour
produire de la chaleur. Dans ce cas, une sonde de la régulation
de la chaudière présente est nécessaire, en règle générale, dans
le ballon de la pompe à chaleur. La sonde disponible doit rester
raccordée électriquement et physiquement dans l'appareil.
Dans ce but, la ranger enroulée à l'intérieur de l'isolation dans la
zone de la résistance électrique et réduire au besoin les
consignes dans le menu. La figure ci-dessous montre la posi-
tion de la sonde R5 à échanger, qui doit être raccordée électri-
quement à la régulation externe de la chaudière. La profondeur
conseillée de la sonde dans le tube est d’env.550mm.
Position de montage de la sonde de température
externe pour le mode de fonctionnement bivalent
(illustration avec le capot de l’appareil démonté)
451905.66.02 · FD 9912
FR-13
DHW 300D - DHW 300D+
Français
7.3.4 Fonction solaire thermique
Au lieu d’avoir recours à un deuxième générateur de chaleur, le
chauffe-eau thermodynamique peut également fonctionner en
association avec une installation solaire thermique. Dès que la
production solaire détectée est suffisante, l’énergie générée
sert à produire de l’eau chaude sanitaire et la pompe à chaleur
s’arrête. Les hystérésis de commutation peuvent être réglées
dans le menu. Le circulateur s’arrête de nouveau en l’absence
de production ou en cas de dépassement d'une température li-
mite, que ce soit au niveau du capteur ou dans le ballon. La
fonction solaire thermique a priorité sur le fonctionnement de la
pompe à chaleur et la résistance électrique.
ATTENTION !
!
Il convient d’utiliser une sonde de température ayant les
caractéristiques de résistance d’une PT1000 pour le capteur
(voir Chap. 2.4.2 à la page 4).
7.3.5 Fonction photovoltaïque
Pour utiliser la fonction photovoltaïque, il faut alimenter la
borne X8 avec une tension de 230 V 50 Hz. L’unité d’évaluation
(par ex. contrôleur d’inverseur) détermine la puissance couram-
ment disponible. Lorsque l’entrée photovoltaïque est active, la
pompe à chaleur se base sur la valeur de consigne spécifiée
pour le mode PV. En mode PV sans résistance électrique, la va-
leur de 1kW peut être utilisée comme réglage conseillé du seuil
de puissance dans le contrôleur d'inverseur des installations
photovoltaïques (puissance absorbée de la pompe à chaleur de
700 W plus la charge de base du foyer). Si l'appareil doit tou-
jours fonctionner avec résistance électrique en mode PV, une
valeur de 2,5kW est recommandée pour le réglage (puissance
absorbée de la pompe à chaleur de 2200W, résistance élec-
trique y compris, plus la charge de base du foyer). La fonction
solaire thermique est prioritaire sur la fonction photovoltaïque.
Le fonctionnement de la pompe à chaleur avec du courant pro-
venant de l’installation photovoltaïque est signalé à l’écran.
REMARQUE
�
La température de consigne de l’eau chaude sanitaire en
mode photovoltaïque doit être réglée sur 55 °C max. pour
garantir un fonctionnement efficace de la pompe à chaleur.
8
Entretien / maintenance
ATTENTION !
!
Mettre le chauffe-eau thermodynamique hors tension avant
de l’ouvrir. Tenir compte du fait que le ventilateur continue à
tourner!
Généralités
Le chauffe-eau thermodynamique nécessite peu d’entretien. Il
convient, une fois après la mise en service et à plusieurs jours
d’intervalle, de s’assurer par contrôle visuel que le circuit d’eau
ne présente pas de fuite et que l’écoulement des condensats
n’est pas bouché.
Ne pas effectuer de travaux de maintenance sur le circuit frigo-
rifique de la pompe à chaleur.
Pour nettoyer le chauffe-eau thermodynamique, utiliser uni-
quement un chiffon humecté d’eau savonneuse.
8.1
Circuit d’eau / écoulement des
condensats
Le contrôle du circuit d’eau se limite à la surveillance des filtres
que le client peut avoir installés et aux fuites éventuelles. Net-
toyer ou remplacer les filtres à eau encrassés. Vérifier occasion-
nellement que la vanne d’étanchéité au bout du flexible d’écou-
lement des condensats est bien propre, la nettoyer si
nécessaire.
8.2
Circuit d’alimentation en air
Les travaux de maintenance se limitent au nettoyage de l’éva-
porateur (en fonction des besoins ou à intervalles réguliers).
ATTENTION !
!
Lamelles à arêtes vives : risque de blessures. Ne pas déformer
ni endommager les lamelles!
En présence de filtres à air, vérifier régulièrement qu’ils ne sont
pas sales. Les nettoyer ou les remplacer si nécessaire.
ATTENTION !
!
Avant d’ouvrir l’appareil, assurez-vous qu’il est bien hors
tension.
ATTENTION !
!
La borne X8 peut aussi être sous tension pendant l'arrêt de la
pompe à chaleur
451905.66.02 · FD 9912
www.gdts.one
Français
DHW 300D - DHW 300D+
8.3
Anode anticorrosion
L’anode anticorrosion (Fig. 8.1) montée dans le ballon d’eau
chaude sanitaire doit être contrôlée électriquement à inter-
valles réguliers et tous les deux ans au minimum après la mise
en service. La remplacer si nécessaire. Le contrôle électrique
s’effectue au moyen d’un ampèremètre approprié, sans vidan-
ger le ballon.
Procédure à suivre:
1)
Retirer la gaine PE de la languette de l’anode anticorrosion.
2)
Brancher l’ampèremètre (0 à 50 mA) entre la gaine PE et la
languette.
3)
Évaluation du degré d’usure de l’anode anticorrosion :
Valeur mesurée > 1 mA anode en bon état.
Valeur mesurée < 1 mA anode à contrôler ou à rempla-
cer
S’il est impossible d’effectuer un contrôle électrique fiable de
l’anode anticorrosion, un contrôle visuel par une personne qua-
lifiée est recommandé.
Lorsqu’un remplacement de l’anode anticorrosion [par un spé-
cialiste] se révèle nécessaire, vider le ballon en utilisant le robi-
net de purge prévu à cet effet (y penser lors du montage - voir
annexe).
REMARQUE
�
Une anode anticorrosion en mauvais état de marche abrège la
durée de service de l’appareil !
(Anode
sacrificielle :
anode
en
magnésium
isolée
électriquement suivant DIN 4753 Partie 6)
Fig. 8.1:Anode de la chauffage électrique
9
Défauts / recherche de
pannes (pour l’utilisateur)
ATTENTION !
!
Tout travail sur le chauffe-eau thermodynamique ne devra
être réalisé que par un personnel qualifié!
Respecter les consignes de sécurité de prévention des
accidents!
La pompe à chaleur ne fonctionne pas.
Veuillez vérifier que
le connecteur est bien dans la prise,
le mode Veille n’a pas été sélectionné au clavier,
la prise de courant est alimentée,
la température de l’air aspiré ou la température ambiante
est -7 °C,
la température de l'eau chaude sanitaire est inférieure à
60 °C
La pompe à chaleur s’arrête prématurément (la
température de consigne n’est pas encore atteinte)
Veuillez vérifier que
les gaines de ventilation ne sont pas pliées ou que leurs ou-
vertures ne sont pas bouchées, et que les éventuels filtres
à air ne sont pas fortement encrassés (bouchés).
Les condensats ne s’écoulent pas (eau sous
l’appareil)
Veuillez vérifier que
la vanne d’étanchéité au bout du flexible d’écoulement des
condensats n’est pas encrassée ou bouchée; la nettoyer si
nécessaire; la vanne peut être démontée et remontée faci-
lement.
rien n’entrave l’alimentation en air et l’évacuation de l’air
(gaine d’air pliée / filtre à air bouché).
Si les questions mentionnées ci-dessus ne vous permettent pas
de remédier à la défaillance, veuillez vous adresser à votre
chauffagiste ou à votre service après-vente.
10 Mise hors service
Tâches à accomplir:
Mettre le chauffe-eau thermodynamique hors tension.
Fermer complètement le circuit d’eau (eau chaude sani-
taire, eau froide et conduite de circulation) et vidanger le
ballon d’eau chaude sanitaire.
11 Exigences en matière de
protection de
l’environnement
En cas de maintenance ou de mise hors service du chauffe-eau
thermodynamique, respecter les consignes de protection de
l’environnement en matière de récupération, de recyclage et
d’élimination des consommables et des composants suivant la
norme DIN EN 378.
451905.66.02 · FD 9912
FR-15
DHW 300D - DHW 300D+
Français
12 Informations sur les
appareils
1
Désignation technique et référence de commande
DHW 300D
DHW 300D+
2
Design
2.1
Nombre d’unités
1
1
2.2
Source de chaleur
Air
Air
2.3
Dégivrage
Oiu
Oiu
2.4
Volume nominal du ballon
litres
285
280
2.5
Échangeur thermique interne – surface de transfert
m2
-
1,0
2.6
Tuyau de sonde, ø intérieur, pour sonde externe
mm
9
9
2.7
Emplacement
À l’abri du gel
À l’abri du gel
2.8
Matériau du ballon
Acier; émaillé selon DIN 4753
Acier; émaillé selon DIN 4753
2.9
Isolation du ballon
PU avec enveloppe PS
PU avec enveloppe PS
2.10 Pression nominale du ballon
bars
6
6
3
Plages d’utilisation
3.1
Plage d’utilisation de la source de chaleur1
°C
-7 à 35
-7 à 35
3.2
Plage de réglage de l’eau chaude sanitaire en mode pompe à chaleur
°C
20 à 60 ± 1,0 K
20 à 60 ± 1,0 K
4
Débit / bruit
4.1
Flux d’air
m3/h
325
325
4.2
Compression externe max.
Pa
80
80
4.3
Longueur max. du raccordement à la gaine d’air
m
10
10
4.4
Niveau de puissance acoustique
dB(A)
60
60
4.5
Niveau de pression sonore 2
dB(A)
50
50
5
Dimensions / poids et capacités
5.1
Dimensions hauteur (min.) x largeur x profondeur
mm
1867x740x776
1867x740x776
5.2
Diamètre de raccordement à la gaine d’air
diamètre norminal avec EPP-tuyau d’aération
mm
190 / DN 160
190 / DN 160
5.3
Poids (à vide)
kg
107
122
5.4
Fluide frigorigène R134a / capacité
kg
0,95
0,95
5.5
Valeur PRG / équivalent CO2
--- / t
1430 / 1
1430 / 1
5.6
Circuit frigorifique hermétiquement fermé
oui
oui
6
Branchements électriques
6.1
Degré de protection
IP21
IP21
6.2
Tension de raccordement
1/N/PE~230 V, 50 Hz
1/N/PE~230 V, 50 Hz
6.3
Câble de raccordement env. 2,7 m - 1,5 mm2
Avec connecteur
Avec connecteur
6.4
Fusible max.
A
C16
C16
6.5
Consommation de courant de la pompe à chaleur cos
0,8
0,8
6.6
Consommation de courant du chauffage électrique d’appoint
A
6,5
6,5
6.7
Consommation de courant max.
A
9,5
9,5
6.8
Courant de démarrage
A
13,5
13,5
6.9
Puissance nominale absorbée de la pompe à chaleur à 60 °C3
W
528
528
6.10 Puissance absorbée du chauffage électrique d’appoint
W
1 500
1 500
6.11 Puissance absorbée du ventilateur
W
58
58
6.12 Puissance totale absorbée max.
W
2 200
2 200
7
Raccordement hydraulique
7.1
Raccordement conduite de circulation
filet. ext.
R 3/4"
R 3/4"
7.2
Raccordement sortie d’eau chaude sanitaire
filet. ext.
R1"
R1"
7.3
Raccordement alimentation en eau froide
filet. ext.
R1"
R1"
7.4
Raccordement échangeur thermique interne
filet. ext.
-
Rp 1’’
8
Données de puissance
451905.66.02 · FD 9912
www.gdts.one
Français
DHW 300D - DHW 300D+
8.1
Durée de chauffe 3 4
h:min
09:22
09:22
8.2
Consommation d’énergie au cours de la chauffe 3 4
kWh
4,25
4,25
8.3
Consommation d’énergie en veille 4
5
W
29
29
8.4
Consommation d’énergie électrique
WEL-TC selon la norme EN 16147 cycle XL 4 5
kWh
5,78
5,78
8.5
COP selon la norme EN16147, cycleXL 4 5
3,3
3,3
8.6
Température d’eau chaude sanitaire de référence 4 5
°C
55,9
55,9
8.7
Quantité d’eau chaude sanitaire maximale disponible 4 5
litres
421
421
8.8
Profil de soutirage 4 5
XL
XL
8.9
Efficacité énergétique pour le chauffage de l’eau ŋwh 4 5
%
137
137
1. À une température inférieure à 7 °C ± 1 C, la résistance électrique se met automatiquement en marche et le module de pompe à chaleur s’arrête
2. À une distance de 1m (pour un emplacement dégagé ou pour une installation sans conduite ou coude à 90° pour l’air évacué côté évacuation d’air).
3. Procédure de réchauffement du contenu nominal avec passage de 10 °C à 55 °C pour une température d’air aspiré de 15 °C et une humidité relative de 70 %
4. Ces données renvoient à un appareil neuf avec échangeur thermique non encrassé
5. À une température de l’air aspiré de 15 °C et une humidité relative de 70 %.
451905.66.02 · FD 9912
A-I
DHW 300D - DHW 300D+
Anhang · Appendix · Annexes
Anhang · Appendix · Annexes
1
Maßbild / Dimension drawing / Schéma coté........................................................................................ A-II
2
Einbindungsschemen / Integration diagram / Schéma d'intégration ............................................A-III
2.1
Hydraulisches Einbindungsschema / Hydraulic Block Diagram / Schéma d’intégration hydraulique A-III
2.2
Legende / Legend / Légende........................................................................................................................................A-III
2.3
Einbindungsschema Wärmetauscher an thermische Solaranlage / Heat Exchanger Integration Diagram
for Thermal Solar Installation / Schéma d’intégration échangeur therm. à installation solaire therm. A-IV
3
Elektroschema / Electrical circuit diagram / Schéma électrique......................................................A-V
3.1
Anschluss der externen Komponenten / Connecting the external components / Branchement de la
composants externe ..........................................................................................................................................................A-V
3.2
Legende / Legend / Légende.........................................................................................................................................A-V
4
Konformitätserklärung / Declaration of Conformity / Déclaration de conformité......................A-VI
451905.66.02 · FD 9912
www.gdts.one
Anhang · Appendix · Annexes
DHW 300D - DHW 300D+
1
Maßbild / Dimension drawing / Schéma coté
* nur Variante
mit 2. Wärmeerzeuger
* only version with
2nd heat generator
* Modèle avec 2e générateur
de chaleur uniquement
elektrische Leitungseinführungen
Warmwasserausgang R1
Kondensatschlauch
Korrosionsschutzanode
Zirkulationsleitung
Elektrischer Heizstab
Wärmetauscher Eingang
Rp1
Wärmetauscher Ausgang
Rp1
Kaltwasserzulauf R1
Electric cable entries
Domestic hot water outlet R1
Condensate hose
Corrosion protection anode
Circulation pipe
Electric heating element
Heat exchanger input
Rp1
Heat exchanger output
Rp1
Cold water inlet R1
Entrée des câbles électriques
Évacuation d’eau chaude R1
Flexible d’écoulement
des condensats
Anode anticorrosion
Conduite de circulation
Cartouche électrique chauffante
Entrée échangeur thermique
Rp1
Sortie échangeur thermique
Rp1
Alimentation en eau froide R1
1
2
3
4
5
6
7 *
8 *
9
Lufteintritt
Luftaustritt
Air inlet
Air outlet
Sortie d’air
Entrée d’air
10
11
Max. Kippmaß ohne Haube
Max. tilied dimension
without cover
Valeur de basculement
max. sans capot
12
1627
451905.66.02 · FD 9912
A-III
DHW 300D - DHW 300D+
Anhang · Appendix · Annexes
2
Einbindungsschemen / Integration diagram / Schéma
d'intégration
2.1
Hydraulisches Einbindungsschema / Hydraulic Block Diagram / Schéma
d’intégration hydraulique
2.2
Legende / Legend / Légende
1
Absperrventil
Shutoff valve
Robinet d’arrêt
2
Druckminderventil
Pressure reducing valve
Réducteur de pression
3
Prüfventil
Test valve
Soupape de contrôle
4
Rückflussverhinderer
Return flow inhibitor
Clapet anti-reflux
5
Manometeranschlussstutzen
Pressure gauge connecting stubs
Tubulures de raccordement manomètre
6
Entleerungsventil
Drain valve
Vanne de vidange
7
Membran-Sicherheitsventil
Diaphragm safety valve
Soupape de sécurité à membrane
8
Zirkulationspumpe
Circulation pump
Pompe de circulation
9
Abfluss
Outlet
Ecoulement
Warmwasser / Domestic hot water / Eau chaude sanitaire
Zirkulation (wenn erforderlich) /
Circulation (if necessary) /
Circulation (si nécessaire)
Anschluß Wärmetauscher /
Heat exchanger connection /
Raccordement échangeur thermique
Kaltwasseranschluß nach DIN 1988 /
Cold water connection according to DIN 1988 /
Raccordement eau froide selon DIN 1988
451905.66.02 · FD 9912
www.gdts.one
Anhang · Appendix · Annexes
DHW 300D - DHW 300D+
2.3
Einbindungsschema Wärmetauscher an thermische Solaranlage / Heat
Exchanger Integration Diagram for Thermal Solar Installation / Schéma
d’intégration échangeur therm. à installation solaire therm.
Wärmetauscher
Heat exchanger
Echangeur thermique
Wärmetauscher
Heat exchanger
Echangeur thermique
Vorlauf
Flow
Départ
Rücklauf
Return flow
Retour
Rückschlagklappe
Check valve
Clapet anti-retour
Hahn
Tap
Robinet
Thermometer
Thermometer
Thermomètre
vom Kollektor
From the collector
en provenance du collecteur
Sicherheitsventil
Safety valve
Soupape de sécurité
Entlüftung / De-aeration / Purge
Manometer
Pressure gauge
Manomètre
Auffangbehälter
Catchment tank
Puisard
Durchflussmesser
Flow meter
Débitmètre
Rückschlagklappe
Check valve
Clapet anti-retour
Hähne
Taps
Robinets
Hahn
Tap
Robinet
Ausdehnungsgefäß
Expansion vessel
Vase d´expansion
Umwälzpumpe
Circulating pump
Circulateur
Füllpumpe
Filling pump
Pompe de remplissage
zum Kollektor
To the collector
vers le collecteur
451905.66.02 · FD 9912
A-V
DHW 300D - DHW 300D+
Anhang · Appendix · Annexes
3
Elektroschema / Electrical circuit diagram / Schéma électrique
3.1
Anschluss der externen Komponenten / Connecting the external
components / Branchement de la composants externe
3.2
Legende / Legend / Légende
Klemme /
Terminal /
Borne
Externe Komponente
External component
Composant externe
X4 / M16
Umwälzpumpe (2. WE)
Circulating pump (HG 2)
Circulateur (2e GDC)
X7 / K23
Externe Sperre
External block
Blocage externe
X8 / N27
Photovoltaik
Photovoltaic
Photovoltaique
X15 / R13
Kollektorfühler
Collector sensor
Sonde de capteur
451905.66.02 · FD 9912
www.gdts.one
Anhang · Appendix · Annexes
DHW 300D - DHW 300D+
4
Konformitätserklärung / Declaration of Conformity / Déclaration
de conformité
Die aktuelle CE-Konformitätserklärung finden sie als Download unter:
You can find and download the current CE conformity declaration at:
Vous pouvez télécharger la déclaration de conformité CE actuelle sous :
https://gdts.one/dhw300D
https://gdts.one/dhw300Dplus
Glen Dimplex Deutschland GmbH
Geschäftsbereich GDTS
Am Goldenen Feld 18
D-95326 Kulmbach
Irrtümer und Änderungen vorbehalten.
Subject to alterations and errors.
Sous réserve d’erreurs et modifications.
+49 (0) 9221 709 924545