Arbiter Systems 931A Operation Manual
Read Online
Read the Arbiter Systems 931A Operation Manual online using the built-in PDF viewer.
Text of the manual
Power System Analyzer
Operation Manual
931A POWER SYSTEM ANALYZER
CURRENT
VOLTAGE
TRANSDUCER
TIMER
SETUP 1
SETUP 2
SETUP 3
SETUP 4
SETUP 5
SETUP 6
NARROW-BAND-WIDE
MEAS 3 PHASE CH1 RANGE
RESTART
CONFIG
SHIFT
HELP
REVIEW
PRINT LOG
STORE SETUP
SCALE
ESCAPE
ENTER
VOLTS
AMPS
PHASE
FREQUENCY
POWER
VARS
VA
PF
HARMONICS
WAVEFORM
CHANNEL 1
SELECT
CHANNEL 2
SELECT
MEASURE
HOLD
CH2 RANGE
MIN
MAX
TRANSDUCER
MENU
LOG DATA
PRINT
LAST SETUP
CH1 / CH2
ON/OFF
FUSE
1AF/250V
85-264 Vac
47-440 Hz
110-250 Vdc
RS-232
GROUND
BEFORE
USE
DISPLAY
CONFIG
ARM / RESET
A
B
C
N
750 Vrms / 1000 Vdc MAX
20 Arms MAX
10Vdc
MAX
100mAdc
MAX
A
B
300V
MAX
A
B
Arbiter Systems, Inc.
Paso Robles, CA 93446
U.S.A.
www.arbiter.com
This manual is issued for reference only, at the convenience of Arbiter
Systems.
Reasonable effort was made to verify that all contents were
accurate as of the time of publication. Check with Arbiter Systems at the
address below for any revisions made since the original date of publication.
Contact Information
Arbiter Systems, Inc.
1324 Vendels Circle, Suite 121
Paso Robles, CA 93446
(805) 237-3831
www.arbiter.com
[email protected]
[email protected]
Definition
This manual describes the Model 931A Power System Analyzer, and
accessories.
Firmware and Firmware Updates
This manual was created based on the following firmware:
Copyright Program: 10 February 2010
Help Version: 25 JUNE 1996
DSP Version: 093098
The firmware versions indicated above are displayed on the Model 931A
at startup.
To freeze the display during this screen, press and hold
the ESCAPE key until finished viewing. Also, the 931A will issue this
information from the serial port using the VER command. See the VER
command on page 124.
Firmware Updates are available as a ROM replacement from Arbiter
Systems by contacting technical support at the information above.
ii
Arbiter Systems makes no warranty, expressed or implied, on any
product manufactured or sold by Arbiter Systems except for the following
limited warranty against defects in materials and workmanship on products
manufactured by Arbiter Systems.
Products manufactured by Arbiter Systems are guaranteed against
defective materials and workmanship under normal use and service for
one year from the date of delivery. The responsibility of Arbiter Systems
under this warranty is limited to repair or replacement, at Arbiter Systems’
option, of any product found to be defective. Arbiter Systems shall have
no liability under this warranty unless it receives written notice of any
claimed defect, within the earlier of:
Thirty days of discovery by Buyer, or;
One year from the date of delivery.
For warranty service or repair, products must be returned to a service
facility designated by Arbiter Systems. Buyer shall prepay all shipping
charges, duties, and taxes to send the product to Arbiter Systems and
Buyer shall prepay shipping charges, duties, and taxes to return the
product to Buyer.
THE WARRANTY SET FORTH HEREIN CONSTITUTES THE
ONLY WARRANTY OBLIGATIONS OF ARBITER SYSTEMS, EX-
PRESSED OR IMPLIED, STATUTORY, BY OPERATION OF LAW,
OR OTHERWISE. ARBITER SYSTEMS DISCLAIMS ANY WAR-
RANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICU-
LAR PURPOSE, AND BUYER EXPRESSLY WAIVES ALL OTHER
WARRANTIES.
This limited warranty does not extend to any product, which has been
subject to:
1. Improper use or application, abuse, or operation beyond its rated
capacity, or contrary to the instructions in the operation and
maintenance manuals (if any);
2. Accident;
3. Repair or maintenance performed by Buyer, except in accordance
with the operation and maintenance manuals, if any, and any special
instructions of Arbiter Systems;
4. Modification without the prior written authorization of Arbiter
Systems (whether by the substitution of non-approved parts or
otherwise).
iii
The remedies provided herein are Buyer’s sole and exclusive remedies.
In no event shall Arbiter Systems be liable for direct, indirect, incidental
or consequential damages (including loss of profits), whether based on
contract, tort, or other legal theory.
FOR THE FASTEST POSSIBLE SERVICE, PLEASE PROCEED AS
FOLLOWS:
1. Notify Arbiter Systems, Inc., specifying the instrument model
number and serial number and giving full details of the difficulty.
Service data or instrument-return authorization will be provided
upon receipt of this information.
2. If instrument return is authorized, forward prepaid to the manufac-
turer. If it is determined that the instrument is not covered by this
warranty, an estimate will be made before the repair work begins, if
requested.
See Contact Information on page ii.
iv
Arbiter Systems, Inc.
Model 931A
Power System Analyzer
Operation Manual
Table of Contents
Chapter 1
General Information
Chapter 2
Functional Description
Chapter 3
Operation
Chapter 4
Specifications
Appendix A
RS-232 Commands
Appendix B
Optional Accessories
Appendix C
CE Mark Certification
Index
Copyright Arbiter Systems Incorporated September 2021 All rights re-
served. International copyright secured.
PD0017400T
Reorder Number: AS0094000
v
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
1.2
Supplied Equipment . . . . . . . . . . . . . . . . . . . . . .
1
1.3
Available Accessories . . . . . . . . . . . . . . . . . . . . . .
2
2
Functional Description
3
2.1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
2.2
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
2.2.1
Voltage
. . . . . . . . . . . . . . . . . . . . . . . . .
3
2.2.2
Current . . . . . . . . . . . . . . . . . . . . . . . . .
3
2.2.3
Transducer
. . . . . . . . . . . . . . . . . . . . . . .
5
2.2.4
Timer . . . . . . . . . . . . . . . . . . . . . . . . . .
5
2.3
Measurement Channels . . . . . . . . . . . . . . . . . . . . .
5
2.4
Measurement Method
. . . . . . . . . . . . . . . . . . . . .
6
2.4.1
Sampling and Filtering . . . . . . . . . . . . . . . . .
8
2.5
User Interface . . . . . . . . . . . . . . . . . . . . . . . . . .
8
2.5.1
Graphics Display . . . . . . . . . . . . . . . . . . . .
8
2.5.2
Keypad . . . . . . . . . . . . . . . . . . . . . . . . .
9
2.6
RS-232C Interface
. . . . . . . . . . . . . . . . . . . . . . .
9
2.7
Power Supply and Battery . . . . . . . . . . . . . . . . . . .
9
2.7.1
Battery Power
. . . . . . . . . . . . . . . . . . . . .
9
2.7.2
Line Power/Battery Charging . . . . . . . . . . . . .
10
2.7.3
Auto-Shutdown Mode . . . . . . . . . . . . . . . . .
11
2.8
Start-Up Sequence . . . . . . . . . . . . . . . . . . . . . . .
11
2.8.1
Holding the Start-Up Sequence . . . . . . . . . . . .
11
2.8.2
Reset – Instrument Default Setup
. . . . . . . . . .
11
3
Operation
13
3.1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
3.2
Front Panel Connections . . . . . . . . . . . . . . . . . . . .
13
vii
Chassis Ground . . . . . . . . . . . . . . . . . . . . .
13
3.2.2
Voltage Inputs
. . . . . . . . . . . . . . . . . . . . .
14
3.2.3
Current Inputs . . . . . . . . . . . . . . . . . . . . .
14
3.2.4
Transducer Inputs . . . . . . . . . . . . . . . . . . .
15
3.2.5
Timer Inputs . . . . . . . . . . . . . . . . . . . . . .
15
3.3
Front Panel Keys . . . . . . . . . . . . . . . . . . . . . . . .
15
3.3.1
Main Functions . . . . . . . . . . . . . . . . . . . . .
15
3.3.2
Secondary Functions . . . . . . . . . . . . . . . . . .
26
3.3.3
Data Entry Functions . . . . . . . . . . . . . . . . .
41
3.3.4
Timer Control Functions . . . . . . . . . . . . . . . .
42
3.4
Front Panel Display
. . . . . . . . . . . . . . . . . . . . . .
44
3.5
Direct Measurements . . . . . . . . . . . . . . . . . . . . . .
44
3.5.1
AC Voltage Measurement . . . . . . . . . . . . . . .
44
3.5.2
AC Current Measurement . . . . . . . . . . . . . . .
46
3.5.3
DC Voltage Measurement . . . . . . . . . . . . . . .
48
3.5.4
Frequency Measurement . . . . . . . . . . . . . . . .
49
3.5.5
Harmonic Measurement . . . . . . . . . . . . . . . .
50
3.6
Combined Measurements
. . . . . . . . . . . . . . . . . . .
52
3.6.1
Phase Angle Measurement . . . . . . . . . . . . . . .
52
3.6.2
Active Power – Reactive Power . . . . . . . . . . . .
54
3.6.3
Apparent Power – Power Factor
. . . . . . . . . . .
56
3.6.4
Waveform Display
. . . . . . . . . . . . . . . . . . .
58
3.7
Timer Measurements . . . . . . . . . . . . . . . . . . . . . .
58
3.7.1
Connecting the Inputs . . . . . . . . . . . . . . . . .
59
3.7.2
Configuring the Timer . . . . . . . . . . . . . . . . .
59
3.7.3
Timer Measurement Categories . . . . . . . . . . . .
62
3.8
Transducer Testing . . . . . . . . . . . . . . . . . . . . . . .
64
3.8.1
Configuring the Transducer . . . . . . . . . . . . . .
64
3.8.2
Connecting the Inputs . . . . . . . . . . . . . . . . .
70
3.8.3
Connecting the Outputs . . . . . . . . . . . . . . . .
75
3.8.4
Performing the Measurement . . . . . . . . . . . . .
75
3.8.5
Custom Pulse, or Contact Output Tests . . . . . . .
75
3.8.6
Performing a Test
. . . . . . . . . . . . . . . . . . .
80
3.9
Using External PT’s and CT’s
. . . . . . . . . . . . . . . .
84
3.10 Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . .
84
3.10.1 Capturing Data . . . . . . . . . . . . . . . . . . . . .
84
3.10.2 Reviewing Data . . . . . . . . . . . . . . . . . . . . .
85
3.10.3 Erasing Logged Data . . . . . . . . . . . . . . . . . .
86
3.11 Printing / Exporting Data . . . . . . . . . . . . . . . . . . .
86
3.11.1 Print / Data Export Setup
. . . . . . . . . . . . . .
86
3.11.2 ASCII Format
. . . . . . . . . . . . . . . . . . . . .
87
3.11.3 Graphics Format (FX-80) . . . . . . . . . . . . . . .
87
viii
. . . . . . . . . . . . . . . . . . . . . . . . .
87
3.11.5 Spreadsheet . . . . . . . . . . . . . . . . . . . . . . .
88
3.11.6 Initiating Printing / Exporting . . . . . . . . . . . .
97
4
Specifications
99
4.1
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
99
4.1.1
Voltage
. . . . . . . . . . . . . . . . . . . . . . . . .
99
4.1.2
Current . . . . . . . . . . . . . . . . . . . . . . . . .
99
4.1.3
Transducer
. . . . . . . . . . . . . . . . . . . . . . .
99
4.1.4
Timer . . . . . . . . . . . . . . . . . . . . . . . . . . 100
4.2
Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . 100
4.2.1
Voltage and Current . . . . . . . . . . . . . . . . . . 100
4.2.2
Phase Angle . . . . . . . . . . . . . . . . . . . . . . . 100
4.2.3
Frequency . . . . . . . . . . . . . . . . . . . . . . . . 101
4.2.4
Timer . . . . . . . . . . . . . . . . . . . . . . . . . . 101
4.2.5
Transducer
. . . . . . . . . . . . . . . . . . . . . . . 101
4.2.6
Harmonics . . . . . . . . . . . . . . . . . . . . . . . . 101
4.2.7
Power Quantities . . . . . . . . . . . . . . . . . . . . 101
4.3
General Specifications . . . . . . . . . . . . . . . . . . . . . 102
4.3.1
Measurement Bandwidth
. . . . . . . . . . . . . . . 102
4.3.2
Memory . . . . . . . . . . . . . . . . . . . . . . . . . 102
4.3.3
Display
. . . . . . . . . . . . . . . . . . . . . . . . . 102
4.3.4
Keypad . . . . . . . . . . . . . . . . . . . . . . . . . 102
4.3.5
Environment
. . . . . . . . . . . . . . . . . . . . . . 102
4.3.6
Input Power . . . . . . . . . . . . . . . . . . . . . . . 103
4.3.7
Serial Port
. . . . . . . . . . . . . . . . . . . . . . . 103
A RS-232C Commands
105
A.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
A.2 Serial Port Examples . . . . . . . . . . . . . . . . . . . . . . 106
A.3 Command Summary . . . . . . . . . . . . . . . . . . . . . . 107
A.3.1
Battery Charging Status (BAT)
. . . . . . . . . . . 107
A.3.2
Backlight Set (BLT) . . . . . . . . . . . . . . . . . . 107
A.3.3
Channel Calibrate (CCH) . . . . . . . . . . . . . . . 107
A.3.4
Ratio CH1/CH2 (CCR) . . . . . . . . . . . . . . . . 108
A.3.5
Channel Input Select (CHS) . . . . . . . . . . . . . . 108
A.3.6
Calibrate Input (CIN) . . . . . . . . . . . . . . . . . 109
A.3.7
Transducer Configuration (COT) . . . . . . . . . . . 109
A.3.8
Daylight Saving Time, Set (DAY)
. . . . . . . . . . 110
A.3.9
Display Dump, ASCII (DDA) . . . . . . . . . . . . . 110
A.3.10 Data Dump, Bitmapped (DDB)
. . . . . . . . . . . 111
A.3.11 Store Calibration Data in EEPROM (EEP) . . . . . 111
ix
A.3.12 DSP Frequency Calibrate (FRD) . . . . . . . . . . . 111
A.3.13 Frequency, Return (FRQ) . . . . . . . . . . . . . . . 111
A.3.14 Timer Calibrate (FTM) . . . . . . . . . . . . . . . . 112
A.3.15 Harmonics Display (HAR) . . . . . . . . . . . . . . . 112
A.3.16 Harmonic Magnitude, Return (HMA)
. . . . . . . . 112
A.3.17 Harmonic Phase Angle, Return (HPH) . . . . . . . . 113
A.3.18 Power Down (KIL) . . . . . . . . . . . . . . . . . . . 113
A.3.19 Log Data (LOG) . . . . . . . . . . . . . . . . . . . . 113
A.3.20 Last Setup (LSU)
. . . . . . . . . . . . . . . . . . . 113
A.3.21 Magnitude (Channel), Return (MAG) . . . . . . . . 114
A.3.22 Measure Hold (MHD) . . . . . . . . . . . . . . . . . 114
A.3.23 MIN/MAX, Display (MMN)
. . . . . . . . . . . . . 114
A.3.24 Bandwidth-Narrow, Set (NAB) . . . . . . . . . . . . 114
A.3.25 Overload Status (OVD) . . . . . . . . . . . . . . . . 115
A.3.26 Phase/Frequency Display (P F) . . . . . . . . . . . . 115
A.3.27 Power/Vars Display (P V) . . . . . . . . . . . . . . . 115
A.3.28 Power Factor, Return (PFA)
. . . . . . . . . . . . . 115
A.3.29 Phase Mode, Set (PHM) . . . . . . . . . . . . . . . . 116
A.3.30 Phase, Return (PHS)
. . . . . . . . . . . . . . . . . 116
A.3.31 Power, Return (PWR) . . . . . . . . . . . . . . . . . 116
A.3.32 Range Hold, Set (RHD) . . . . . . . . . . . . . . . . 117
A.3.33 Logged Data, Review (RLD)
. . . . . . . . . . . . . 117
A.3.34 Range Hold, Release (RRH) . . . . . . . . . . . . . . 117
A.3.35 MIN/MAX, Restart (RST) . . . . . . . . . . . . . . 117
A.3.36 Transducer Channel (SCC) . . . . . . . . . . . . . . 118
A.3.37 Serial Number (SER)
. . . . . . . . . . . . . . . . . 118
A.3.38 Flash Log (SLO) . . . . . . . . . . . . . . . . . . . . 118
A.3.39 Scale On/Off (SOO) . . . . . . . . . . . . . . . . . . 119
A.3.40 DSP Speed (SPD) . . . . . . . . . . . . . . . . . . . 119
A.3.41 Phase Preference, Set (SPH)
. . . . . . . . . . . . . 119
A.3.42 Range, Set (SRG)
. . . . . . . . . . . . . . . . . . . 120
A.3.43 Scale Factors, Set or Return (SSC) . . . . . . . . . . 120
A.3.44 Store Setup (SST) . . . . . . . . . . . . . . . . . . . 121
A.3.45 Setup, Recall (SUP) . . . . . . . . . . . . . . . . . . 121
A.3.46 Timer, Arm (TAM)
. . . . . . . . . . . . . . . . . . 121
A.3.47 Time, Return (TDR) . . . . . . . . . . . . . . . . . . 121
A.3.48 Time, Set (TDS) . . . . . . . . . . . . . . . . . . . . 121
A.3.49 Timer Configuration, Set or Return (TCF)
. . . . . 122
A.3.50 Transducer Display (TDU)
. . . . . . . . . . . . . . 122
A.3.51 Timer Display (TIM)
. . . . . . . . . . . . . . . . . 123
A.3.52 Timer Reading, Return (TMR) . . . . . . . . . . . . 123
A.3.53 Timer, Reset (TRS) . . . . . . . . . . . . . . . . . . 123
x
A.3.54 Timer, Stop (TSP) . . . . . . . . . . . . . . . . . . . 123
A.3.55 Timer, Start (TST)
. . . . . . . . . . . . . . . . . . 123
A.3.56 Volts/Amps Display (V A)
. . . . . . . . . . . . . . 123
A.3.57 VA/PF Display (V P) . . . . . . . . . . . . . . . . . 124
A.3.58 Volt-Amps, Return (VAM)
. . . . . . . . . . . . . . 124
A.3.59 VARS, Return (VAR) . . . . . . . . . . . . . . . . . 124
A.3.60 Version, Return (VER)
. . . . . . . . . . . . . . . . 124
A.3.61 Waveform Display (WAV) . . . . . . . . . . . . . . . 125
A.3.62 Bandwidth Wide, Set (WIB)
. . . . . . . . . . . . . 125
A.3.63 Transducer Input, Display (XDI) . . . . . . . . . . . 125
A.3.64 Transducer Output, Display (XDO)
. . . . . . . . . 125
B Optional Accessories
127
B.1
Precision Current Transformer
. . . . . . . . . . . . . . . . 127
B.1.1
Specifications . . . . . . . . . . . . . . . . . . . . . . 127
B.1.2
Input Connections . . . . . . . . . . . . . . . . . . . 127
B.1.3
Current Display
. . . . . . . . . . . . . . . . . . . . 128
B.2
Handle/Bail . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
B.2.1
Parts and Accessories
. . . . . . . . . . . . . . . . . 128
B.2.2
Required Tools . . . . . . . . . . . . . . . . . . . . . 128
B.2.3
Procedure . . . . . . . . . . . . . . . . . . . . . . . . 128
B.2.4
Operation . . . . . . . . . . . . . . . . . . . . . . . . 128
B.3
Extended Memory . . . . . . . . . . . . . . . . . . . . . . . 129
B.3.1
Data Organization . . . . . . . . . . . . . . . . . . . 130
B.3.2
Computing the Number of Files and Records . . . . 132
B.3.3
Log Data Triggering . . . . . . . . . . . . . . . . . . 133
B.3.4
Front Panel Operation . . . . . . . . . . . . . . . . . 134
B.3.5
Remote Operation . . . . . . . . . . . . . . . . . . . 135
B.3.6
Setup of Logged Data Operation . . . . . . . . . . . 135
B.3.7
Review of Logged Data
. . . . . . . . . . . . . . . . 137
B.3.8
Trigger Remote Data Logging . . . . . . . . . . . . . 138
C CE Mark Certification
139
xi
List of Figures
2.1
Model 931A Front Panel . . . . . . . . . . . . . . . . . . . .
4
2.2
Input Multiplexing . . . . . . . . . . . . . . . . . . . . . . .
5
3.1
Phase, Power Factor, and VAR Definitions . . . . . . . . . .
19
3.2
Phase, Power Factor, VAR Quadrants
. . . . . . . . . . . .
20
3.3
Three-Phase Measurement Selection
. . . . . . . . . . . . .
28
3.4
Three Phase Display Selection . . . . . . . . . . . . . . . . .
28
3.5
Three Phase Tabular Display . . . . . . . . . . . . . . . . .
28
3.6
Three-Phase Displays for an ABC System . . . . . . . . . .
32
3.7
Three-Phase Displays for a CBA System . . . . . . . . . . .
33
3.8
1-Phase, 2-Wire, 1-Element Connections . . . . . . . . . . .
34
3.9
1-Phase, 3-Wire, 2-Element Connections . . . . . . . . . . .
34
3.10 3-Phase, 3-Wire, 2-Element Connections . . . . . . . . . . .
35
3.11 3-Phase, 4-Wire, 2.5-Element Connections . . . . . . . . . .
35
3.12 3-Phase, 4-Wire, 3-Element Connections . . . . . . . . . . .
36
3.13 Phase Angle Example
. . . . . . . . . . . . . . . . . . . . .
54
3.14 1-Phase, 2-Wire, 1-Element Transducer Test . . . . . . . . .
71
3.15 1-Phase, 3-Wire, 2-Element Transducer Test . . . . . . . . .
72
3.16 3-Phase, 4-Wire, 2.5-Element Transducer Test . . . . . . . .
73
3.17 3-Phase, 4-Wire, 3-Element Transducer Test . . . . . . . . .
74
3.18 3-Phase, 4-Wire, 3-Element Custom Pulse Transducer Test
83
B.1
Model 931A Case with Handle/Bail
. . . . . . . . . . . . . 129
xiii
List of Tables
2.1
AC Measurement Configurations . . . . . . . . . . . . . . .
6
2.2
DC Measurement Configurations . . . . . . . . . . . . . . .
7
2.3
RS-232C Port Pinout / Signal Description . . . . . . . . . .
10
2.4
931A Reset Selection Screen . . . . . . . . . . . . . . . . . .
12
3.1
Phase Angle Preferences . . . . . . . . . . . . . . . . . . . .
20
3.2
Channel 2, AC Voltage Ranges, Vrms
. . . . . . . . . . . .
23
3.3
Channel 2, AC Current Ranges, Arms . . . . . . . . . . . .
23
3.4
Channel 2, DC Voltage Ranges, Vdc . . . . . . . . . . . . .
23
3.5
Channel 1, AC Voltage Ranges, Vrms
. . . . . . . . . . . .
37
3.6
Channel 1, AC Current Ranges, Arms . . . . . . . . . . . .
37
3.7
Channel 1, DC Voltage Ranges, Vdc . . . . . . . . . . . . .
37
3.8
Phase Convention . . . . . . . . . . . . . . . . . . . . . . . .
54
B.1
Custom Data Table . . . . . . . . . . . . . . . . . . . . . . . 132
xv
The Arbiter Systems Model 931A Power System Analyzer is a state-of-the-
art instrument offering unprecedented accuracy in the measurement of pa-
rameters related to AC Power Generation, Transmission, and Distribution.
Using Arbiter’s proprietary PowerDSA Digital Signal Processing (DSP)
circuitry, the Model 931A greatly enhances the precision measurement of
these AC parameters. Powered by either an internal rechargeable battery
or by AC line voltage, the Model 931A is truly portable. This manual is
divided into four chapters and two appendices as follows:
Chapter 1.
General Information
Chapter 2.
Functional Description
Chapter 3.
Operation
Chapter 4.
Specifications
Appendix A.
RS-232C Commands
Appendix B.
Optional Accessories
1.2
Supplied Equipment
The Model 931A is supplied with a standard AC Power Cord (P09R), RS-
232 Null-Modem Cable (P/N CA0019806), Safety Ground Lead (812HA-8)
and one Operations Manual (AS0094000).
1
The following accessories are available for use with the Model 931A:
Model Number
Description
931A/01
16-Megabyte internal memory
AS0060000
PowerCSV, Applications software (download only).
Requires Option 01
AS0035901
Adjustable handle/bail Assembly
09311A
400 Amp 20:1 precision CT, 0.1% accuracy.
Includes AS0036000 Mounting Bracket
AP0012800
1000:1 Clamp-on CT, 200 Amps
AP0012900
250:5, 500:5, 1000:5 Clamp-on CT, 1000 Amps
AP0001300
1000:1; 1000A, 600V, Cat. III, EN61010
811AT/CT*
3-Phase Universal Test Plug Current Lead Set
813AT/BT*
3-Phase Safety Voltage Lead Set
815AT/BT*
3-Phase Fused Voltage Lead Set
816AT/CT*
3-Phase Spade-lug Current Lead Set
817AT*
3-Phase CT Lead Set: red, yellow, blue
* This is a partial list. Other high-quality test leads and accessories are
also available. Contact Arbiter Systems for further information.
2
The following paragraphs provide a brief functional description of some
Model 931A components. Figure 2.1 illustrates the front panel.
2.2
Inputs
2.2.1
Voltage
Measure AC or DC voltages through four color-coded insulated banana
jacks on the front panel.
Labeled A, B, C, and N, each terminal can
accept input voltages of up to 750 Vrms or 1000 Vdc. Each input voltage
terminal is isolated from signal common with an impedance of 1 megohm,
and is physically isolated from the chassis.
2.2.2
Current
The 931A features three independent, transformer-coupled AC current
inputs, accessible via three pairs of front-panel binding posts, which are
color-coded for polarity and labeled A, B, and C.
Each terminal can accept an AC signal with a rms current value of up
to 20 amps. All current inputs are isolated to withstand a potential of
1000 Vpeak from chassis ground.
3
931A POWER SYSTEM ANALYZER
CURRENT
VOLTAGE
TRANSDUCER
TIMER
SETUP 1
SETUP 2
SETUP 3
SETUP 4
SETUP 5
SETUP 6
NARROW-BAND-WIDE
MEAS 3 PHASE CH1 RANGE
RESTART
CONFIG
SHIFT
HELP
REVIEW
PRINT LOG
STORE SETUP
SCALE
ESCAPE
ENTER
VOLTS
AMPS
PHASE
FREQUENCY
POWER
VARS
VA
PF
HARMONICS
WAVEFORM
CHANNEL 1
SELECT
CHANNEL 2
SELECT
MEASURE
HOLD
CH2 RANGE
MIN
MAX
TRANSDUCER
MENU
LOG DATA
PRINT
LAST SETUP
CH1 / CH2
ON/OFF
FUSE
1AF/250V
85-264 Vac
47-440 Hz
110-250 Vdc
RS-232
GROUND
BEFORE
USE
DISPLAY
CONFIG
ARM / RESET
A
B
C
N
750 Vrms / 1000 Vdc MAX
20 Arms MAX
10Vdc
MAX
100mAdc
MAX
A
B
300V
MAX
A
B
Figure 2.1: Model 931A Front Panel
4
Two front panel inputs accept voltage or current transducer output signals.
These inputs share a common return, and accept signals of up to 10 volts
DC, or 100 mA DC. The Model 931A can be configured to measure the
voltage or current directly, or convert the signals for display of either
measured input units or a percentage of full-scale or percent error.
2.2.4
Timer
Timer inputs “A” and “B” accept signals of up to 300 volts peak or
DC, without regard to polarity. The timer circuitry can be triggered by
application or removal of AC/DC voltage, or by contact closure/opening.
Display results of timer measurements in either seconds, or cycles.
2.3
Measurement Channels
The Model 931A incorporates two measurement channels, referred to as
Channel 1 and Channel 2. Multiplexing of the voltage and current inputs
makes it possible to connect them to one or both of these measurement
channels, in different configurations. Figure 2.2 illustrates multiplexing of
voltage and current inputs between the two measurement channels.
Figure 2.2: Input Multiplexing
Tables 2.1 and 2.2 list the possible input configurations for the two
measurement channels. Table 2.1 lists AC Measurement Configurations
and Table 2.2 lists DC Measurement Configurations.
Using the two
measurement channels individually allows concurrent measurements of
separate signals (voltage and/or current).
5
Compare the amplitudes and phase angles of two voltage signals by
connecting the first voltage (i.e.
Va-b) to Channel 1 and the second
voltage (i.e.
Vc-n) to Channel 2.
Likewise, analyze two currents by
referencing Channel 2 to Channel 1. For power quantities such as real
power (POWER), vars (VARS), Volt-amperes (VA), and power factor
(PF), connect the voltage to Channel 1 and current to Channel 2.
Since channel 1 is used as the internal reference, connect the lowest
distortion input signal to Channel 1. For most power systems the voltage
has lower distortion than the current. If analyzing only one signal, it must
be connected to Channel 1. If analyzing a single highly distorted waveform,
connect a reference signal of the same fundamental frequency to Channel
1 and the highly distorted waveform to Channel 2.
Configuration
Measured Input
Referenced To
Va-b
Voltage A
Voltage input B
Vb-c
Voltage B
Voltage input C
Vc-a
Voltage C
Voltage input A
Va-c
Voltage A
Voltage input C
Vc-b
Voltage C
Voltage input B
Vb-a
Voltage B
Voltage input A
Va-n
Voltage A
Voltage input N
Vb-n
Voltage B
Voltage input N
Vc-n
Voltage C
Voltage input N
Va-s
Voltage A
Synthesized neutral
Vb-s
Voltage B
Synthesized neutral
Vc-s
Voltage C
Synthesized neutral
Ia
Current A
Independent
Ib
Current B
Independent
Ic
Current C
Independent
In
- (Ia+Ib+Ic)
Channel 2 only
Table 2.1:
AC Measurement Configurations
2.4
Measurement Method
The fundamental frequency, of an input signal, is first analyzed by the
Model 931A digital signal processing (DSP) algorithms.
Using only
Channel 1, these measurements require a fairly ”clean” signal. To make
accurate measurement of the fundamental frequency, input signal must
have less than 30% total harmonic distortion (THD). A stable frequency
display indicates that the fundamental measurement was successful.
6
Voltage input B
Vb-c
Voltage B
Voltage input C
Vc-a
Voltage C
Voltage input A
Va-c
Voltage A
Voltage input C
Vc-b
Voltage C
Voltage input B
Vb-a
Voltage B
Voltage input A
Va-n
Voltage A
Voltage input N
Vb-n
Voltage B
Voltage input N
Vc-n
Voltage C
Voltage input N
Va-s
Voltage A
Synthesized neutral
Vb-s
Voltage B
Synthesized neutral
Vc-s
Voltage C
Synthesized neutral
Table 2.2:
DC Measurement Configurations
The Model 931A has two simultaneous measurement modes: wide-band
and narrow-band. Except for harmonics and waveform, all measurements
are made continuously, regardless of the measurement displayed. Changing
the display selection, other than for harmonics or waveform, does not affect
the measurement process. In contrast, the 931A measures harmonics and
waveform on-demand.
The Wide-Band Mode simulates the operation of an extremely accurate
analog rms detector or analog multiplier. Therefore, measurements made
in wide-band include the effect of harmonics within the instrument’s 3.05
kHz bandwidth.
The Narrow-Band Mode is a completely different measurement pro-
cess. Through proprietary DSP state-estimation algorithms, it accurately
estimates the parameters (viz. frequency, magnitude, and phase angle) of
the input waveform. This mode rejects the effects of noise, distortion, and
DC offsets, measuring the fundamental parameters with great precision.
Unlike an FFT, these algorithms are insensitive to the input frequency,
and will make accurate measurements for any frequency within the rated
range of 20-500 Hz.
For measuring a signal with more than 30% THD, or a signal that has
any harmonic with greater amplitude than the fundamental component,
apply the signal to be measured to CH2 and a clean synchronous signal
with the desired fundamental frequency to CH1. The Model 931A will
lock on to the CH1 signal and the CH2 signal can be analyzed.
7
Sampling and Filtering
The Model 931A normally samples input signals at approximately 62.5
thousand samples per second (kS/s) and employs a 15 kHz, two-pole
analog anti-alias filter. The signals are filtered again using a digital low-
pass filter to remove signals outside the measurement bandwidth (3.05
kHz). The digital filter provides greater accuracy and repeatability and
a better rejection rate than could be accomplished with analog filtering.
Measurements performed with this technique are essentially free of the
harmful effects of aliasing.
8,192 samples are taken from Channels 1 and 2 during each mea-
surement cycle.
This process requires approximately 131 milliseconds.
Depending on the exact measurements made, approximately three mea-
surement cycles are executed per second.
Since substantial dead time
between measurements occur, the Model 931A is not capable of performing
cycle-by-cycle, real-time monitoring.
For fundamental signals below approximately 40 Hz, the sampling rate
is automatically reduced to 12.5 Ks/s, allowing accurate measurements at
frequencies down to 5 Hz. The record length under these conditions is 655
ms.
The Model 931A completes a measurement cycle 2 to 3 times per
second.
The cycle includes collecting data, processing and displaying
results. A faster update rate of 4 to 5 times per second is achieved by
initiating the “Fast Mode.” Pressing the shift key twice, or issuing the SPD
RS-232 command, starts this mode. The speed increase is accomplished
by eliminating the computation of harmonic data. If the unit is in the Fast
Mode and the harmonics display is selected it will revert back to normal
operation.
Using the Fast Mode does not degrade the accuracy of the
Model 931A.
2.5
User Interface
The user interface for the Model 931A is designed to streamline overall
operation by making the most commonly used functions easily accessible.
The following paragraphs briefly describe the Model 931A user interface.
2.5.1
Graphics Display
A supertwist liquid crystal display (LCD) serves as the main display
and is capable of displaying both characters and graphics, including the
waveforms of the input signals. The display features a backlight that can
be enabled for operation in subdued lighting conditions.
8
The main keyboard consists of 18 multi-function keys whose primary
functions generally relate to the most commonly used features.
Access
secondary functions by first pressing the SHIFT key and then the sec-
ondary function key. When a menu operation requires cursor movement
or data entry, the top row of keys functions as such.
2.6
RS-232C Interface
The Model 931A includes an RS-232C communications port, which allows
remote control and command of the instrument using a PC, modem, or
terminal. When connecting the Model 931A to a PC, use the supplied
null-modem cable.
The RS-232C port may also be used to connect a
printer to the instrument. Serial port configuration information for the
RS-232C port is described in Section 4.3.7 and RS-232C commands are
listed in Appendix B. Refer to Section 3.11.6 for information on printing
and exporting data. Table 2.3 lists the connector types, pin locations and
signal descriptions for the RS-232C port of the Model 931A and other
devices.
Once properly set up, a host computer may assume total control. All
functions and data available from the front panel are also available to the
host computer. All commands consist of three letter commands preceded
in some cases by setup parameters separated by commas. The Model 931A
does not echo commands. Once a valid three-letter command has been
received, it will be acted upon immediately. The action taken depends
on the command given. “Display change,” “setup modification,” “data
output (or export),” and “data logging” are some examples. When the
Model 931A returns a “?” it signifies an unrecognizable command or an
out-of-bounds number.
2.7
Power Supply and Battery
The Model 931A can operate either from an internal, rechargeable battery,
or from an external AC/DC power source.
2.7.1
Battery Power
In normal operation, the battery will operate the Model 931A for eight
hours on a full charge.
Factors affecting the operating time include:
9
backlight control (the backlight adds approximately 50% to power drain),
use of the timer and transducer inputs, and the measurement function.
931A
PC
PC
Seiko
ATENS
EPSON
Seiko
DPU-411
XP-320
FX-80
DPU-414
DB9F
DB9F
DB25M
DB25M
DB25M
DB25M
DB9M
2 / RXD
3 / TXD
2 / TXD
N/C
3 / TXD
2 / TXD
2 / TXD
3 / TXD
2 / RXD
3 / RXD
2 / RXD
2 / RXD
3 / RXD
3 / RXD
4 / DTR
N/C
N/C
N/C
N/C
N/C
N/C
5 / GND
5 / GND
7 / GND
7 / GND
7 / GND
7 / GND
5 / GND
7 / RTS
6 / DSR
5 / CTS
N/C
4 / CTS
4 / CTS
N/C
N/C
8 / CTS
6 / DSR
N/C
20 / DSR
20 / DSR
N/C
8 / CTS
7 / RTS
4 / RTS
5 / Busy
5 / RTS
5 / RTS
8 / RTS
Table 2.3:
RS-232C Port Pinout / Signal Description
2.7.2
Line Power/Battery Charging
Battery charging occurs whenever power is applied to the Model 931A
main power inlet. The internal charger supplies a steady level of power
to the instrument, whether powered on or off.
If the 931A is powered
on, power is split between instrument operation and battery charging. If
using the back light, additional power is directed to the instrument, and
increases the time to charge the NiMH battery. To charge the battery
completely from a depleted state should take approximately 8 hours with
the Model 931A powered off. Charge only if ambient temperature is
in the range: 0 ◦C – 40 ◦C (32 ◦F – 104 ◦F).
NiMH battery charging in the Model 931A is monitored and controlled
using three factors: (1) ∆T/∆t, (2) ∆V/∆t, and (3) time.
∆T/∆t:
When the cell reaches full charge, most of the charging
energy is converted to heat. This increases the rate of change of battery
temperature, which can be detected by a sensor such as a thermistor.
∆V/∆t:
When the battery is fully charged the voltage across its
terminals drops slightly. The charger can detect this and stop charging.
Elapsed Time: Total charge time is monitored and battery charging
stops when the preprogrammed time interval has elapsed.
The low battery state is indicated on the main display by “LOW
BAT!!”, and flashes On and Off. The Model 931A will automatically shut
down if the low battery condition persists for longer than several minutes.
It is recommended that the unit be charged or shut off when it
indicates a low battery condition.
10
Auto-Shutdown Mode extends the battery-life by deactivating the instru-
ment power if no input signals are present and no keystrokes occur within
a period of approximately 10 minutes.
To return to normal operation,
simply press the ON/OFF key.
Activate the Auto-Shutdown Mode by
using the MENU key (see Section 3.3.1.13).
2.8
Start-Up Sequence
Several tasks are performed during the power-on initialization sequence.
First, the Model 931A reads calibration data from the EEPROM (installed
only in units with serial numbers greater than A0194). The initial sign-on
message reports any errors in the calibration data along with the cali-
bration date. These errors are corrected using a built-in Hamming Code
Algorithm.
If the number of reported errors increases with subsequent
start-ups it is an indication that the EEPROM should be replaced. The
calibration date is displayed as a decimal number with the format:
MMDDYY.
The second part of the sign-on display shows the ROM program
copyright date, the Help ROM version date and the DSP ROM version
date. The DSP ROM date is displayed as a decimal number in the format:
MMDDYY. As new features are added to the Model 931A these dates are
updated.
2.8.1
Holding the Start-Up Sequence
Holding the escape key during the startup sequence holds the startup
displays, including the two parts mentioned above.
Holding the enter
key during the startup sequence allows resetting the setup parameters of
calibration.
2.8.2
Reset – Instrument Default Setup
To reset the instrument to original default conditions when it shipped
from the factory, follow the resetting procedure listed below. Three menu
selections are available, shown in the simulated display below. Normally,
only the first or second items should be selected.
Selecting FULL will
completely reset the instrument and calibration constants will be lost. To
reset the 931 to factory defaults, select PARTIAL. To escape from this
menu, select EXIT and press the ENTER key.
11
INSTRUMENT DEFAULT SETUP
EXIT
(Nothing Disturbed)
PARTIAL
(Calibration Not Disturbed)
FULL
(All Values Set To Default)
Table 2.4:
931A Reset Selection Screen
2.8.2.1
Resetting Procedure
NOTE: DO NOT SELECT “FULL” UNLESS YOU INTEND TO
COMPLETELY ERASE THE INSTRUMENT CALIBRATION!
NOTE: Normally, select “PARTIAL” to restore the instrument
to original default conditions.
1. Press the ON/OFF button to start the unit.
2. Press and release the ENTER key when the first display screen
becomes visible.
3. Using the Cursor keys (up or down arrows) select “PARTIAL” from
the three options shown in Table 2.4.
4. Press ENTER and the instrument should ask, “ARE YOU SURE??
YES=UP NO=DOWN”. Press the UP arrow to complete the reset
procedure. Otherwise, press the DOWN arrow to escape.
5. The display should indicate the message, “PLEASE WAIT 10s TO
4m”. After a short time the display should return to the final VOLTS
AMPS display indication.
6. You may need to configure your settings under MENU and/or SHIFT
> SCALE.
12
This section describes how to operate the Model 931A, Power System
Analyzer. Topics discussed in this section include: Front panel connectors,
front panel controls and display, measurement configuration, taking mea-
surements, use of external PT’s and CT’s, data logging, and printing/data
exporting.
3.2
Front Panel Connections
There are a total of eighteen connectors on the front panel (excluding
the RS-232C and power inlet connectors), and all will accept a standard
banana plug.
Eleven of the front panel banana jacks are recessed and
insulated for safety at high voltages. The remaining seven jacks are of
a type suitable for high-current applications. The following paragraphs
describe the functions of each of these connectors.
3.2.1
Chassis Ground
A ground lug, located in the lower right-hand corner of the front panel,
is connected to the instrument chassis, and also to the safety ground lead
of the AC power connector. When the Model 931A is operated with the
power line cord connected, the chassis of the instrument will be connected
to the safety ground for the ac outlet.
However, when operated from
the internal battery with the power cord disconnected, the chassis will be
floating.
13
The purpose of the ground lug is to allow the
chassis to be tied to a safety ground, especially
during battery operation.
CAUTION: The front-panel ground terminal should always be
connected to the safety ground for the circuit under test.
This is especially critical for operation with the line cord
unplugged, since the AC line input safety ground will not be
connected.
3.2.2
Voltage Inputs
The Model 931A features four, front-panel inputs, which can be used for
measurement of AC or DC voltages. These inputs are labeled “A”, “B”,
“C”, and “N” (for phase A, phase B, phase C, and Neutral, respectively).
All four of the inputs utilize identical circuitry,
which allows for measurement of voltages up to 750
Vrms or 1000 Vdc between inputs. The 1 megohm
input voltage dividers are tied to a common point.
Any unused voltage inputs will float at the average
value of the used inputs. Safety-insulated banana jacks are used for the
connections. Measure voltage between any two of the inputs (e.g., “A”
and “N”). Also, the 931A will measure voltage between the input and a
synthesized neutral, which is the average of the voltages at inputs A, B,
and C.
3.2.3
Current Inputs
The Model 931A has three inputs for use in AC current measurement. Each
of the inputs uses a pair of five-way binding posts, and has a maximum
current capability of 20 amps rms. For each pair of terminals, the left-hand
side is positive, and the right-hand side is negative.
For measurement of 3-phase neutral current, the neutral signal (In) is
available on Channel 2.
(3.1)
In = −(Ia + Ib + Ic)
14
Measure transducers via two front-panel inputs
sharing a common return. One input permits mea-
suring a transducer voltage output and the other
permits measuring a transducer current output.
Make connections via insulated banana jacks. For
safety, the measurement-input section is electri-
cally isolated from the instrument chassis and all other inputs.
A transducer can be tested “live” in a circuit, or using an external
source. The transducer inputs are connected to the Model 931A voltage or
current measurement channels, and the transducer output is connected to
the Model 931A transducer measurement input, except for Custom Pulse,
which uses the Timer Input. For details on transducer testing, refer to
Section 3.8.
3.2.5
Timer Inputs
�������
������
���������
����
� ���
�
�
�����
Two timer inputs are provided via two pairs of insulated
banana jacks, with the inputs being independently and
optically coupled.
The timer is designed for testing of protective relays,
and other similar or related tasks.
3.3
Front Panel Keys
The following paragraphs describe the functions and features that can
be accessed via Front Panel Keys.
The functions of the keys in the
main keyboard are divided into three groups: Main Functions, Secondary
Functions, and Data Entry Functions. The Secondary and the Data Entry
Functions differ from the Main Functions in that they must be preceded by
another keystroke (either the shift key, or one invoking a selection menu).
There is also a separate group of three keys having functions associated
with the control of the internal timer. The functions of these keys are
referred to as Timer Control Functions.
3.3.1
Main Functions
The primary functions of the front panel keys are described below. The
text located directly below each key identifies its primary function. Press
the key once to access these primary functions.
15
Press the VOLTS/AMPS key to display the amplitude values for
the signals routed to Channels 1 and 2. The input multiplexing
circuitry determines which input signals are connected to the
measurement channels, according to selections made by the
operator (see Sections 3.5.1.2 and 3.5.2.2).
Press the VOLTS/AMPS key again to produce a tabular display
showing the signals routed to Channels 1 and 2. Also present is a graphical
display of the phase angle. Tabular values, including phase, Watts, VARs,
VA, Lead or Lag and frequency (Hz) are located on the right side of the
display.
Make amplitude measurements with the instrument in either the
narrow-band mode (fundamental only), or wide-band mode (true rms).
In wide-band mode, the square root of the average of the squared
instantaneous sampled values determines the true rms amplitude.
It
includes harmonics up to 3.05 kHz and removes DC prior to calculation.
In narrow-band mode, an extremely accurate, proprietary digital signal
processing (DSP) algorithm determines the fundamental amplitude. It also
excludes the effects of DC, harmonics and noise.
3.3.1.2
Phase/Frequency
������ �
�����
���������
Press the PHASE/FREQUENCY key to display the frequency
of the input signal routed to measurement Channel 1, and the
phase angle of the signal routed to Channel 2 (relative to the
signal on measurement Channel 1).
The input multiplexing
circuitry determines which input signals are connected to the
measurement channels, according to selections made by the
operator (see Sections 3.5.1.2 and 3.5.2.2).
Phase angle and frequency are always measured using narrow-band
fundamental DSP techniques, guaranteeing accurate measurements in the
presence of harmonics, noise, and DC offsets. The displayed phase angle
is that of the fundamental component only.
16
Display phase angle as 0◦C to 360◦C or as ±180◦C, and a lagging phase
angle may also be chosen to be positive or negative by convention. Select
your preferred phase convention as described in Section 3.3.1.13, under
Menu. See Figure 3.1 for Phase Angle definitions.
3.3.1.3
Power/Vars
������ �
�����
����
Press the POWER/VARS key to display active and reactive
power for the combination of signals routed to Channels 1 and
2.
The input multiplexing circuitry determines which input
signals are connected to the measurement channels, according
to selections made by the operator. (see Section 3.5.1.2).
To use the POWER/VARS function, Channel 1 must be set
to measure AC voltage, and Channel 2 must be set to measure AC current.
In wide-band mode, active power (watts) is measured by taking the
average of the products of the instantaneous values of voltage and current,
including the effects of harmonics.
Reactive power (Vars) is measured by taking the vector difference of the
wide-band apparent power less the active power (active power is described
above). The wide-band apparent power is the product of the wide-band
rms voltage and the wide-band rms current.
(3.2)
Wide − band V ARs =
�
V A2 + W 2
Mathematically, reactive power is defined as the square root of the
quantity apparent power squared minus active power squared. The sign of
the wide-band reactive power is determined from the sign of the narrow-
band reactive power.
In narrow-band mode, active power (Watts) is measured by multiplying
the fundamental voltage and current magnitude and the cosine of their
phase angle, all determined accurately by DSP. Harmonics are ignored.
Narrow-band reactive power (Vars) is measured by multiplying the funda-
mental voltage and current by the sine of negative of the fundamental phase
angle, all determined accurately by DSP. Again, harmonics are ignored.
(3.3)
Narrow − band V ars = Vfund × Ifund × Sin(−Θ)
Press the POWER/VARS key a second time to toggle the display
from Power to Energy. Both Watt-hours and VAR-hours are continuously
accumulated. Use the RESTART key to zero the Energy readings. Power
17
readings are summed once every second, using the real-time clock, to
produce Energy readings.
3.3.1.4
VA/PF
������ �
��
��
Press the VA/PF key to display the apparent power and
power factor for signals routed to Channels 1 and 2.
The
input multiplexing circuitry determines which input signals are
connected to the measurement channels, according to selections
made by the operator (refer to Section 3.5.1.2 and 3.5.2.2).
To use the VA/PF function, Channel 1 must be set to mea-
sure AC voltage, and Channel 2 set to measure AC current. Measurements
may be made in either wide-band or narrow-band mode. The power factor
range is between -1 and +1, leading or lagging (see Figure 3.1).
In wide-band mode, apparent power (volt-amps, or VA) is determined
by multiplying the wide-band rms voltage by the wide-band rms current.
Power factor is determined by dividing the wide-band active power by the
wide-band apparent power (refer to Section 3.3.1.3).
In narrow-band mode, apparent power is determined by multiplying the
fundamental amplitude of the voltage and the current (accurately by DSP).
Power factor is the cosine of the phase angle between the fundamentals of
the current and the voltage, ignoring harmonics. The Lead/Lag indication
for Power Factor may be disabled. Refer to Section 3.3.1.13, Menu - Phase
Preference.
Pressing the VA/PF key a second time toggles the display from Power
to Energy. VA-hours are continuously accumulated. Use the RESTART
key to zero the Energy readings. Power readings are summed once every
second, using the real-time clock, to produce Energy readings.
18
����� �� ��
�� �� ���
���� �� �
� �� ��
����� �� ����
��� �� ������ ���
���� � ������� � ��
�� � ������ �� ��
������ �� ����
��� �� � ���
����� �� ����� �� ��
�� �� �
������ �� �����
�� � ������ ���
����� � ������ � ��
�� � ������� � ��
����� �� ����
��� � �� ���
���� �� �
� �� � ��
����� �� �����
��� � ������ ����
���� �� ������� � ��
�� � ������ �� ��
����� �� ����
��� �� ������� ����
���� �� ������ � ��
� � ������ � ��
����� � ����
��� �� �� ����
���� � ����� � ��
�� � �
������� ���� �������
�������� ������ �������
����������� ����� �� ��� ����
������
��������� ���� ��� ��� �������� ���
���� �� �������
���� � �������
������������
����� ������ � ��� �
����� � ������ � ������ �� ���� ����
����� � ����� � ������ � ���� �
��� � ������ � �����
������ �������� � ����� ����� ������� �������
���� �������� �� �������� ������
��������� ���� ������� ��� �������
��������
����������
����� ������ � ��������
��� � ���� � ����
�
� �
���� �� ��� � � � �
��������
������ ������ �� ����
�
�
Figure 3.1: Phase, Power Factor, and VAR Definitions
19
������ ����� ��������
��������
������ ����� ���������
��������
������ ������ ���������
��������
������ ����� ��������
��������
� � �� �
��
������ �
� �� �
�
� �� � � � � ��
��� �
� � � �
��
�������� ��� � ����
� �
�
� � � � �� �
��
� � �� �
� �� �
�
������ �����
�������
��������
���
������ �����
�������
���������
���
�������� �����
������
��������
���
�������� �����
������
���������
���
����� ������
����
������ ������
����
����� ������
�����
����� ������
�����
Figure 3.2: Phase, Power Factor, VAR Quadrants
Phase Convention
Quadrant I
Quadrant II
Quadrant III
Quadrant IV
CH2 Lagging CH1
(-) for ±180◦
0◦ to -90◦
-90◦ to -180◦
+180◦ to +90◦
+90◦ to 0◦
(+) for ±180◦
0◦ to +90◦
+90◦ to +180◦
-180◦ to -90◦
-90◦ to 0◦
(-) for 0 - 360◦
360◦ to 270◦
270◦ to 180◦
180◦ to 90◦
90◦ to 0◦
(+) for 0 - 360◦
0◦ to 90◦
90◦ to 180◦
180◦ to 270◦
270◦ to 360◦
Table 3.1:
Phase Angle Preferences
Phase angle of Channel 2 (current) relative to Channel 1 (voltage)
Lagging Current – An alternating current which, in each half-cycle, reaches
it maximum value a fraction of a cycle later than the maximum value of
the voltage that produces it.
20
Press the HARMONICS key to view a graphic display of the
magnitude of individual harmonics for the signals routed to
Channels 1 or 2. The input multiplexing circuitry determines
which input signals are connected to the measurement chan-
nels, according to selections made by the operator (refer to
Sections 3.5.1.2 and 3.5.2.2).
Harmonics up to the 50th are shown for fundamentals of 50 or 60
Hz. At 400 Hz, only harmonics up to the 7th are displayed, due to the
instrument bandwidth limitation of 3.05 kHz.
Harmonics are measured by first determining the AC fundamental and
the DC components of the signal, and removing them algebraically from
the digitized waveform. For the spectral display, K-factor, and individual
harmonic measurements, Fast Fourier Transform analysis determines the
residual. Dividing the rms of the residual by the wide-band rms amplitude
determines the Total Harmonic Distortion (THD). With these techniques,
harmonic measurement accuracy is not dependent upon fundamental
frequency.
Select any harmonic with the movable cursor found in the graphic
display using the arrow keys.
The display also shows corresponding
numerical values of the amplitude and the phase angle of the harmonic
relative to fundamental. Press CHANNEL 1 SELECT or CHANNEL 2
SELECT to toggle the display between the signals applied to Channels 1
or 2.
Numerical display of THD and K-factor are always available. THD is
the rms of the residual, including noise and spurious signals, as a percent
of the wide-band rms. K-factor is the rms sum of the fundamental plus
the individual harmonics (each weighted by the square of the harmonic
number) expressed as a ratio to the fundamental. It is an estimate of the
heating effect of harmonic energy in magnetic materials. K-factor is used
to determine transformer de-rating. K-factor is 1.0 for a perfect sine wave
and greater than 1.0 with distortion.
3.3.1.6
Waveform
������ �
��������
�����
Press the WAVEFORM key to view a graphic display of the
waveforms for the signals, which are routed to Channels 1 and
2.
The input multiplexing circuitry determines which input
signals are connected to the measurement channels, according
to selections made by the operator.
21
Displayed waveforms correspond to the input signals after
they have been digitized and subjected to digital low-pass filtering. The
display includes all components of the signal up to 3.05 kHz.
The waveform display is normalized to positive going zero crossings of
Channel 1 signal fundamentals. To inspect the current waveform, reference
the current at Channel 2 to the voltage at Channel 1.
The displayed
waveform amplitude is relative to the displayed percentage of the selected
range.
View waveforms individually by pressing CHANNEL 1 SELECT, or
CHANNEL 2 SELECT, with the waveform display active.
3.3.1.7
Channel 1 Select
�������� �
������
�����������
Press the CHANNEL 1 SELECT key to view the input config-
uration menu for Channel 1.
Always connect the lowest distortion input signal to Channel
1 since it is used as the internal reference.
For most power
systems the voltage has lower distortion than the current. If
applying only one signal, it must be connected to Channel 1.
If analyzing a single highly distorted waveform connect a reference signal
of the same fundamental frequency to Channel 1 and the waveform to be
analyzed to Channel 2.
Combinations from the front panel inputs allow twenty-seven choices;
three AC currents (A, B, C); twelve AC voltages, and twelve DC voltages.
Each voltage terminal may be referenced to any other voltage terminal,
to the front-panel neutral, or (for AC) to a synthesized neutral, which is
the average of “Va”, “Vb” and “Vc”. Tables 2.1 and 2.2 list the possible
input combinations.
3.3.1.8
Channel 2 Select
�������� �
������
���������
Press the CHANNEL 2 SELECT key to select the input con-
figuration menu for Channel 2. Front panel input combinations
allow twenty-eight choices; four AC currents (A, B, C, N); twelve
AC voltages, and twelve DC voltages.
The Neutral Current
“N” is minus the vector sum of “Ia, Ib, and Ic”. Each voltage
terminal may be referenced to any other voltage terminal, to
the front-panel neutral, or (for AC) to a synthesized neutral, which is the
average of “Va”, “Vb” and “Vc”. Tables 2.1 and 2.2 list the possible input
combinations.
22
Press the MEASURE/HOLD key to stop the measurement
process and hold the instantaneous value of each measured
parameter. With the exceptions of harmonics, waveform and 3-
phase, any display function may be selected during the time that
the measurement hold mode is active, and the corresponding
values observed. Harmonics, waveform, or 3-phase information
may only be displayed if the instrument was in that respective mode when
the MEASURE/HOLD key was pressed. Press the MEASURE/HOLD key
again to leave the Measurement Hold mode and resume measurements.
The display indicates whenever the Measurement Hold mode is active.
Two other methods of activating the Measurement Hold mode is by
reviewing Logged Data, or by the Timer Stop Gate (see 3.7.2.5).
3.3.1.10
CH2 Range
��� �����
���� �����
Press the CH2 RANGE key to select the operating voltage or
current range for Channel 2. The ranges are only approximate
and vary from unit to unit.
Range values allow selection of
either auto range, or a fixed range made available from one of
the following groups (depending on the input mode selected):
0 – 3.5
12 – 28
96 – 224
3 – 7
24 – 56
192 – 448
6 – 14
48 – 112
384 – 750
Table 3.2:
Channel 2, AC Voltage Ranges, Vrms
0 – 0.09
0.32 – 0.75
2.56 – 5.97
0.08 – 0.18
0.64 – 1.49
5.12 – 11.9
0.16 – 0.37
1.28 – 2.98
10.24 – 20.0
Table 3.3:
Channel 2, AC Current Ranges, Arms
0 – 5
17 – 40
135.8 – 320
4.2 – 10
34 – 80
271.5 – 640
8.5 – 20
68 – 160
543 – 1000
Table 3.4:
Channel 2, DC Voltage Ranges, Vdc
23
Min / Max / Ave
���
���
�������
Press the MIN/MAX key to display the minimum, maximum
and average values for any and all measured parameters.
Accumulation of 3-phase minimum and maximum parame-
ters occur only while the 3-phase display is active.
The
MIN/MAX/AVERAGE feature continuously updates the mini-
mum, maximum and average values stored since initial power-on. During
display of a parameter, any new value exceeding the currently stored
minimum or maximum will overwrite it. Averaging is continually updated
during the measurement period.
Accumulation of data can also be re-
initiated, by pressing the SHIFT key, then the RESTART key.
Pressing the MIN/MAX key repeatedly scrolls between minimum,
maximum, average and present data.
3.3.1.12
Transducer
����������
������
Press the TRANSDUCER key to show measurements taken at
the front-panel transducer voltage and current inputs. Config-
ure the Model 931A to display the transducer-input magnitude
as either the actual measured quantity or as a percentage of full
scale. Likewise, display the transducer output level as either the measured
quantity or percentage of full scale, or as a percent error (based on the
input and output ranges). Prior to initiation of Transducer measurements,
the Model 931A automatically performs a self-calibration.
3.3.1.13
Menu
����
����
Press the MENU key to display a configuration menu used to
define configurable parameters within the Model 931A. The sub-
menus and functions available from the MENU key are defined
as follows:
RS-232 Port Setup: Used to set the baud rate, data bits, stop
bits, parity, and flow control for the RS-232C communications port.
Set Real-Time Clock: Set the Year, Month, Day, Hour, Minute,
Second, and also the Daylight Saving mode.
Backlight and Auto-Shutdown: Select the operating mode for
the display backlight and for the Auto-Shutdown function.
The
Auto-Shutdown function will turn the instrument off if there are
no input signals or keystrokes for approximately 10 minutes.
24
Phase Preference: Select the conventions to be used for phase
display. This includes whether phase angle is displayed as ±180◦ or
0−360◦ and (–) for Channel 2 lagging Channel 1 or (+) for Channel
2 lagging Channel 1. The Phase Preference selection only affects the
displayed phase angle and no other quantities. Section 3.6.1 describes
the phase convention selection. There is also a selection for enabling
or disabling the Power Factor “Lead/Lag” display.
Print Selections: Allows selection of the type of data to be printed
or exported when pressing the PRINT key. A complete description
of the printing function is contained in Section 3.11.
Print Broadcast Mode: Allows automatic output of the selected
print option at various time intervals.
Auto-Log Setup: Shows up only when 16-Mbyte memory card is
installed. See Section B.3.4 for details.
3.3.1.14
Log Data
���� ����
������
Press the LOG DATA key to store measurement data to non-
volatile memory. Stored data includes current time and date,
according to the built-in real-time clock. The memory location
in which data is stored will be indicated momentarily in the
lower right corner of the display.
Displays a diagnostic message if the
memory is full.
See Section 3.10 for details of data logging features
and controls.
For a Model 931A equipped with extended memory, see
Section B.3.
3.3.1.15
Print
�����
������ ���
Press the PRINT key to transmit the current measurement data
to a printer, modem, or computer connected to the RS-232 port.
See Section 3.11 for a complete description of printing functions.
25
Press the LAST SETUP key to restore the instrument-state to
what it was immediately prior to the last change. It may be
used to undo an unwanted change, or to toggle between two
different setups. When LAST SETUP is pressed, the current
state is also stored as the new LAST SETUP.
3.3.1.17
Ch1/Ch2
��� �� ���
�����
Press the CH1/CH2 key to display the magnitude and phase
of the signal at Channel 1 divided by the signal at Channel 2.
Depending on the input signals selected, the displayed units for
magnitude will be either ohms (Channel 1 voltage and Channel
2 current), mhos (Channel 1 current and Channel 2 voltage), or P/U (both
channels the same). The value shown for phase represents the phase angle
between the signal at Channel 1 and the signal at Channel 2. It is displayed
in accordance with the phase convention defined for the instrument (see
Section 3.6.1.3).
When using the CH1/CH2 function, any scaling factors for magnitude
and/or phase will apply to the displayed result (see Section 3.3.2.17 for a
discussion of scaling factors).
CH1/CH2 is useful for checking the amplitude and phase angle ac-
curacy of current transformers.
Connect the primary in series with a
Model 931A current input and set that input to Channel 1.
Connect
the transformer secondary to another current input and set that input to
Channel 2. Set the scale factor for the CT input (see Section 3.3.2.17) and
press CH1/CH2. Using an external source, supply the appropriate level
current.
3.3.2
Secondary Functions
The secondary functions of the front panel keys are shown below. They
are identified by the text located directly above each of the keys, and are
highlighted in gray. Access these functions by pressing SHIFT prior to
pressing the desired key.
3.3.2.1
Shift
Press the SHIFT key to access the functions in the shaded gray areas above
the keys. An indicator in the display shows when the SHIFT key has been
pressed. Press SHIFT a second time to prevent access to the secondary
functions.
26
Setup 1 – 6
Up to six different instrument configurations can be stored for future
measurements using STORE SETUP (see Section 3.3.2.16) and recalled by
first pressing SHIFT and then the applicable SETUP 1 through SETUP 6
front panel key. The stored setup information includes Channel Selection,
CT/PT Scale Factors, Transducer and Timer Configurations. Setup keys
do not enable SCALE factors, and are shown below.
������ �
�����
����
������
������ �
�����
���������
������ �
�����
����
������ �
��
��
������ �
���������
������ �
��������
�����
3.3.2.3
Narrow Band
�������� �
������
�����������
Press the NARROW-BAND key to change the measurement
mode for amplitude and power quantities to measure the fun-
damental frequency only. The system uses proprietary DSP algo-
rithms in which harmonics are ignored. Refer to the help screens
for each individual measurement for more detailed descriptions.
Channel 1 is used as the internal reference. Use Channel 1 if only one
signal is measured. If measuring both a current and a voltage, use Channel
1 for measuring the voltage and Channel 2 for the current.
3.3.2.4
Wide Band
�������� �
������
���������
Press the BAND-WIDE key to change the measurement mode to
wide-band for amplitude and power quantities; this includes all
frequencies up to 3.05 kHz. For more information, refer to the
help screens for each individual measurement.
3.3.2.5
Measure 3 Phase
�������
����
����� ������
Press SHIFT, then MEAS 3 PHASE to display the 3-phase mea-
surement selection window. MEAS 3 PHASE permits the Model
931A to make sequences of measurements on sets of voltage and
current inputs. The measured set of input combinations depends
on the 3-phase measurement selection chosen (see Figure 3.3).
27
Figure 3.3: Three-Phase Measurement Selection
To select the appropriate measurement mode, move the cursor to the
desired mode and press ENTER. The input pairs shown in parenthesis
are those used for the TABULAR display. The Model 931A displays the
following display selection menu when you press ENTER:
Figure 3.4: Three Phase Display Selection
3.3.2.6
Tabular Display
The 931A makes a sequence of measurements as shown in the 3-phase
Measurement Selection menu. Amplitude, power and phase quantities for
the individual phases are shown along with the totals for the system. In
the right column, the screen identifies totals by a “T”, energy readings by
“H” and as averages by a “*”. The sample Tabular display below identifies
the individual quantities.
Values for
Va and Ia
Values for
Vc and Ic
Combined
Values
Phase Sequence Indication
Average Voltage
Average Current
Average Phase
Total Active Power
Total Reactive Power
Total Apparent Power
Average Power Factor/lead/lag
Measurement Indicator
Mode Indicator
ABC
Figure 3.5: Three Phase Tabular Display
28
In 1-phase 3-wire, the instrument alternates between measurements of
“Van,Ia” and “Vcn,Ic”. This is useful for making measurements on split-
phase systems. The column on the far right shows the averages for voltage,
current, phase and the totals for power quantities. The columns for “A”
and “C” show the voltage; characters in the lower right-hand corner of the
display alternate between “VanIa” and “VcnIc”, indicating the current
measurement.
In 3-phase 3-wire 2-element mode, the instrument alternates between
measurements of “Vab,Ia”,“Vcb,Ic”,“Vac,Ib”, and “Vcb,Vab”.
It com-
putes “Vac” and includes it in the 3-phase average voltage.
While Ib
is measured, it is not included in the 3-phase results.
This procedure
yields accurate results for active power, but to estimate apparent power,
a correction of 0.866 must be arbitrarily applied since accuracy depends
on the symmetry of the phase voltages. “VcbVab” phase is measured to
determine phase rotation.
In 3-phase 3-wire 3-element mode, the instrument sequences between
measurements of “Vas,Ia”, “Vbs,Ib”; and “Vcs,Ic” (“s” denotes synthe-
sized neutral, which is the average of the signals present at voltage inputs
“a”, “b”, and “c”). Results are accurate for active power, but to estimate
apparent power synthesized neutral is used, and accuracy depends on
symmetry of the phase voltages. Reactive power, power factor, and phase
angle also are estimated. “VasVbs” phase is measured to determine phase
rotation.
In 3-phase 4-wire, 3-element mode, the instrument sequences between
measurements of “Van,Ia”, “Vbn,Ib”, and “Vcn,Ic”.
All results are
accurate.
This is the preferred mode for 3-phase measurements when
neutral is available. Phase rotation is determined by measuring “VanVcn”.
In 3-phase 4-wire 2.5 element mode, the instrument sequences between
measurements of “Van,Ia”, “Vb,Ib”, “Vcn,Ic”, and “VcnVan”.
NOTE: The “B” voltage input must be externally connected to
the “N” voltage input.
“Vb” is internally generated using the synthesized neutral circuit, and
the accuracy of all results depends on the symmetry of the phase voltages.
In all three-phase modes, the Model 931A also measures and displays
phase the sequence, “ABC” or “CBA”. (see Figures 3-2 and 3-3). A phase
measurement of “Vab to Vac” is made at the end of each sequence. If
the “Vab to Vac” phase is negative, the sequence is “ABC” otherwise it
is “CBA”. Phase Sequence may be checked using the waveform display.
29
With Channel 1 set to “Van” and Channel 2 set to “Vbn”, the waveform
display will show the peak of “Vbn” 120 degrees after the peak of “Van”
for an “ABC” Phase Sequence. The waveform display always begins at
the zero crossing of the Channel 1 signal. Dashes displayed for the phase
sequence indicate that the Model 931A could not measure a valid “Vab to
Vac” phase. Phase rotation is determined by measuring “VcnVan”.
The second tabular display (Watt/VAR/VA Hour) replaces the total
power quantities with accumulated energy readings. The energy readings
are set to zero by pressing the RESTART key.
3.3.2.7
Vector Diagram
The Vector Diagram consists of a table of the measured voltages, currents
and phase angles along with their vector representation. The “A” phase
voltage vector is fixed in the horizontal direction. Positions of all other
vectors rotate according to their phase angle with respect to the “A” phase
voltage.
Positive phase angle is denoted by counter-clockwise rotation.
The length of the vectors shows the relative amplitude of each phase. The
largest voltage and the largest current each have the longest vectors. A
vector with a length of less than one pixel is not displayed. All voltage
and current phases are made with respect to the “A” phase voltage. The
“A” phase voltage must be present for a proper Vector Diagram display.
3.3.2.8
Voltage and Current Sequence
The Voltage and Current Sequence display shows the measured voltages,
currents and phase angles in the top portion of the display. The bottom
half of the display shows the positive (V1, I1), negative (V2, I2) and zero
(V0,I0) sequence values. The Model 931A defines the positive sequence
as the values in the “ABC” direction and negative sequence as values in
the “CBA” direction. Also included is a computed value for the neutral
current amplitude and phase angle. All voltage and current phases are
made with respect to the “A” phase. The “A” phase must be present for
a proper Voltage and Current Sequence display.
Positive-Sequence Current (I1) and Voltage (V1) are the normal com-
ponents represented in balanced three-phase (3-wire and 4-wire) systems.
They are present in operating motor and generator windings.
Negative-Sequence Currents (I2) and Voltages (V2) are the components
in 3-phase systems that result from unbalanced phase-to-phase current and
voltage. They cause undesired heating in motor and generator windings.
Reversed phase sequence – ACB vs ABC – can be viewed as an extreme
negative sequence case.
30
Zero-Sequence Currents (I0) and Voltages (V0) are characteristic of
unbalanced 3-phase four-wire systems, and correlate to “neutral shift”,
where there is a current and potential difference in motor or generator
windings with respect to system ground. Zero-Sequence conditions result
from unequal phase-to-neutral parameters.
31
Tabular with Power
Vector Diagram
Voltage and Current Sequence
Waveform
Figure 3.6: Three-Phase Displays for an ABC System
32
Tabular with Power
Vector Diagram
Voltage and Current Sequence
Waveform
Figure 3.7: Three-Phase Displays for a CBA System
33
Figure 3.8: 1-Phase, 2-Wire, 1-Element Connections
������
����
�
��
��
Figure 3.9: 1-Phase, 3-Wire, 2-Element Connections
34
Figure 3.10: 3-Phase, 3-Wire, 2-Element Connections
������
����
�
��
�
�
Figure 3.11: 3-Phase, 4-Wire, 2.5-Element Connections
35
Figure 3.12: 3-Phase, 4-Wire, 3-Element Connections
36
Press the CH1 RANGE key to select the operating voltage or
current range for Channel 1. The ranges are only approximate
and vary from unit to unit. Press SHIFT then the CH1 RANGE
key to view a menu showing a selection of auto range or a fixed
range. The following fixed range groups are available:
0 – 3.5
12 – 28
96 – 224
3 – 7
24 – 56
192 – 448
6 – 14
48 – 112
384 – 750
Table 3.5:
Channel 1, AC Voltage Ranges, Vrms
0 – 0.09
0.32 – 0.75
2.56 – 5.97
0.08 – 0.18
0.64 – 1.49
5.12 – 11.9
0.16 – 0.37
1.28 – 2.98
10.24 – 20.0
Table 3.6:
Channel 1, AC Current Ranges, Arms
0 – 5
17 – 40
135.8 – 320
4.2 – 10
34 – 80
271.5 – 640
8.5 – 20
68 – 160
543 – 1000
Table 3.7:
Channel 1, DC Voltage Ranges, Vdc
When an input signal exceeds the upper limit of a range which is
held, the numbers in the display will change to dashes, and the message
”Channel 1 Overload” will appear.
3.3.2.11
Restart
���
���
�������
Press the RESTART key to erase minimum, maximum and
average values previously stored and begin recording new ones.
Pressing RESTART will also reset Energy values to zero.
37
Press SHIFT then the CONFIG key to set the transducer input
and output ranges; it affects the testing of transducers. The
Model 931A can be set to automatically calculate and display
transducer error as percent of full scale, when the same input
signal is applied to the transducer under test and the Model 931A. Any
calibrator or load box with source may be used, or transducers may be
calibrated in-circuit.
Press the CONFIG key to view the following menu:
Use the arrow keys to select a menu item, then press ENTER. Selections
made from this menu will activate other sub-menus, which allow for various
transducer-test configurations. Once all parameters have been set, press
ESCAPE and Transducer Operation will begin. See Section 3.8 for further
information on transducer testing.
3.3.2.13
Help
����
����
Press SHIFT then the HELP key to find reference information
about the functions of the Model 931A. To get help for a specific
function, press SHIFT, then HELP, followed by the key for the
desired function.
Use the up and down arrow keys to page
through the help message; press the ESCAPE key to return to normal
operation. Display a menu featuring help topics for general operation by
pressing SHIFT then HELP twice (i.e. SHIFT/HELP/SHIFT/HELP).
3.3.2.14
Review
��� ����
������
Press SHIFT then REVIEW to view a menu of stored records.
An example display is shown below:
38
1. Use the up and down arrow keys to select a record to be cleared or
reviewed
2. Press ENTER to view the highlighted record.
After pressing
ENTER, the unit goes into measurement hold mode and the stored
record overwrites the current data. See Section 3.10 for further in-
formation on data logging and reviewing. Press MEASURE/HOLD
to release the instrument from the measurement hold mode.
3. When in the selection menu display, press the left arrow key to clear
the highlighted record from memory.
4. To remove all data records from memory, press ENTER when Clear
All Entries is highlighted.
5. Press escape to return the instrument to normal operation with out
any modification of stored data.
3.3.2.15
Print Log
�����
������ ���
Press SHIFT then PRINT LOG to print to a list of the stored
records to printer or computer connected to the serial interface
(RS-232 port).
3.3.2.16
Store Setup
���� �����
������ �����
Use the STORE SETUP key to save the current instrument-
state in one of six memory registers: SETUP 1 through SETUP
6. Press SHIFT then STORE SETUP to produce the following
prompt on the display:
Press SHIFT and desired SETUP key to store current instrument-state.
Press SHIFT, followed by one of the six SETUP keys (highlighted in
gray across the top row) to store the current instrument setup into the
corresponding register (SETUP 1 through SETUP 6). All setups are stored
in non-volatile memory. For instructions on recalling instrument setups,
see Section 3.3.2.2.
3.3.2.17
Scale
��� � ���
�����
Use the SCALE key to apply individual Scale Factors to each AC
measurement input function. Scale Factor corrections can adapt
the Model 931A for use with current or potential transformers.
39
These adjustments can compensate for phase or amplitude error,
and account for the ratio of a CT or PT.
Amplitude and phase scale factors may be entered for:
Each of the three current inputs;
Each of the three voltage inputs relative to neutral;
The three voltage inputs relative to each other.
Use the store SETUP FUNCTION described in Section 3.3.2.16 to
store global PT and CT scale factors (not individual) for later retrieval.
The following assignments are made:
Set Scale:
Auto Sets:
Set Scale
Auto Sets:
Van
Vas, Vb
Vbc
Vcb
Vbn
Vbs
Vca
Vac
Vcn
Vcs
Ia
In
Vba
Vab
SCALE does not allow scale factors to be entered for DC
measurements.
Press SHIFT > SCALE to view Scale Factor Gain and Phase Selections.
The display then shows the magnitude and phase scale factors for each of
the input functions as seen below.
For magnitude, the factor represents the number by which a measured
value is multiplied during the measurement process.
For example, a
magnitude scale factor of 100, with 10 volts applied to the Model 931A
input, displays 1000 volts.
Therefore, if the Model 931A was used to
measure the voltage at the output of a 100:1 PT, and the magnitude scale
factor was set to 100, the display would show the actual voltage value
present at the PT input (compensating for the 100:1 reduction of the PT).
Valid range for Scale Factors is 999999 to 0.0001.
Apply global PT and CT scale factors and simplify operation when
desiring to use a PT or CT on any input. For example, press SHIFT >
SCALE, then select PT with the cursor, then press ENTER. Using the
cursor, select the appropriate digit, or decimal point, using the right and
40
left arrow keys. Finally, use the up and down arrow keys to change the
numerical digit, or decimal point, and press ENTER. After the changing
the PT and CT values, move the cursor to PT/CT ON, and press ENTER.
When done, this applies the new scale factors for PT and CT to every
input, and blocks out the individual scale factors shown for Vxy and Ix.
Phase angle scale factors indicate the offset, in degrees, that will be
added to the input signal before it is displayed. Additionally, these offsets
apply only at the fundamental frequency of the signal. In the harmonic
display mode, phase offsets equal the offset at the fundamental frequency
multiplied by the chosen harmonic number.
Enable or disable individual scale corrections globally using the SCALE
menu (see Scale Factor Screen above), bottom line.
Measurements made in wide-band mode use digital true-rms detection.
Phase corrections are applied for power quantities by using complex
multiplication. The accuracy of this method depends on the absence of
significant harmonic power and the size of the phase offset.
3.3.3
Data Entry Functions
When performing operations, which require modification of parameters
or making selections from menus, the arrow keys in the top row of the
keyboard are used for cursor movement as described in the following
paragraphs.
The general procedure for selecting items from a menu is to use the
arrow keys to move the cursor (arrow symbol) to the desired selection and
press the ENTER key. If the menu selection was a number to be modified,
the cursor (flashing underline) will appear under the digit to be modified.
Use the right/left arrow keys to select the digit to be modified. Use the
up/down arrow keys to cycle the digit (+, ,., 0, 1, 2, 3, 4, 5, 6, 7, 8, 9).
Press ENTER when the number is correct. The plus, minus and decimal
point will only be included in the cycle where appropriate.
3.3.3.1
Nomenclature
������ �
�����
���������
������ �
�����
����
������ �
��
��
������ �
���������
������ �
��������
�����
������ �
�����
����
������
41
Use the left arrow key to move the display cursor to the left. The cursor
movement function associated with this key is automatically enabled when
required. After making a menu selection, this key will return to its primary
function.
3.3.3.3
Down Arrow
Use the down arrow key to move the display cursor down. The cursor
function associated with this key is automatically enabled as required.
After making a menu selection, this key will return to its primary function.
3.3.3.4
Up Arrow
Use the up arrow key to move the display cursor up. The cursor movement
function associated with this key is automatically enabled when required.
After making a menu selection, this key will return to its primary function.
3.3.3.5
Right Arrow
Use the right arrow key to move the display cursor right.
The cursor
movement function associated with this key is automatically enabled as
required. After making a menu selection, this key will return to its primary
function.
3.3.3.6
Enter
Press the ENTER key to make menu selections and accept modified
numbers.
3.3.3.7
Escape
Press the ESCAPE key to back-out of menus or selections.
While not
necessary to precede ESCAPE with SHIFT, ESCAPE is automatically
available when applicable. Also, use ESCAPE to terminate the display
of waveforms, 3-phase, harmonics, or XMODEM file transfers. To view
the sign-on message, press and hold the ESCAPE key while the Sign-On
message is being displayed; release to continue.
3.3.4
Timer Control Functions
Three keys, located left of the timer connection terminals, control opera-
tion of the internal timer. The functions of these keys are described below.
42
Use the DISPLAY key to view the main display for the timer; this includes
the time measurement, the timer function and trigger modes. An example
is shown below.
In the main timer display, FUNCTION shows the parameter that the
timer is configured to measure. TRIGGER A and TRIGGER B describe
the actions, which will constitute valid triggers for the “A” and “B” inputs.
3.3.4.2
Config
Press the CONFIG key to display the timer configuration menu, which
appears as follows:
One or more sub-menus follow each of the menu selections, which allow
configuration of the specific functions.
Section 3.7 provides more detailed information about the timer sub-
menus and their functions.
3.3.4.3
Arm/Reset
Use the ARM/RESET key to arm and reset the active timer.
Once
stopped, pressing the ARM/RESET key will reset the timer. Pressing it
a second time arms the timer for next cycle. The ARM/RESET function
may also be used to manually stop the timer during a measurement cycle.
43
Front Panel Display
The Model 931A uses a supertwist liquid-crystal display with a resolution
of 240 horizontal pixels by 64 vertical pixels. In most cases, both mea-
surement channels simultaneously display information from measurements
and some instrument configuration.
The display has a bright CCFL backlight available for low ambient
light situations. See Section 3.3.1.13 Menu, Backlight and Auto-shutdown
control, for directions on using the backlight.
Use of the backlight
significantly increases the battery drain.
Display changes in response to keystrokes allow selections from multiple
menu levels, resulting in a self-prompting interface.
3.5
Direct Measurements
For measurement of certain parameters, the Model 931A computes results
from one or both channels individually.
Always use Channel 1 if only
one input signal is present. These measurement parameters include the
following:
AC Voltage
AC Current
DC Voltage
Frequency
Harmonics
Waveform
The following sections provide instructions for performing measure-
ments of parameters within this group.
3.5.1
AC Voltage Measurement
The Model 931A can measure and display AC voltages of up to 750 Vrms.
3.5.1.1
Input Connections
Four inputs, labeled “A”, “B”, “C”, and “N” are available for measuring
AC voltage, and each uses identical circuitry. Input multiplexing circuitry
allows measurement of the value at inputs “A”, “B”, or “C”, relative to
any other input. For example, to measure a voltage between terminals
“A” and “N” simply connect the leads to those two terminals.
44
NOTE: The Model 931A does not provide for measurement of voltage
between voltage inputs and chassis ground lug. Make all measurements
between two (or more) of the voltage inputs. The ground lug is included
for safety purposes only, especially during battery operation.
See Sec-
tion 3.2.1.
3.5.1.2
Configuring the Channels
Configure the chosen measurement channel after connecting the voltage
to the appropriate input terminals.
If measuring only one AC voltage
(e.g. single-phase), use Channel 1, since this channel is used for frequency
measurements.
Press the CHANNEL 1 SELECT key to configure the measurement
channel and to display the following menu:
Arrows form the cursor, highlighting one of the selections. Press the
arrow keys to locate the measurement value. For example, using the arrow
keys move the cursor to Van to measure an AC voltage between inputs “A”
and “N”. Press the ENTER key to confirm the selection.
Measure two separate voltages concurrently by configuring both Chan-
nels 1 and 2. For example, use the selection method above to use Channel
1 to measure “Van” and use Channel 2 to measure “Vcn”. The two voltage
signals must have the same fundamental frequency.
3.5.1.3
Performing the Measurement
Press the VOLTS/AMPS key to display the measured AC voltage and
produce a display similar to the one shown below:
The large number at the top of the display indicates the voltage
45
value measured by measurement Channel 1. The large number below it
corresponds to the voltage value for measurement Channel 2.
The display indicates the general measurement bandwidth near the
lower left-hand corner. The Model 931A uses either wide-band or narrow-
band mode to measure and display AC voltage.
Press the SHIFT key then BAND-WIDE to change the measurement
mode to wide-band RMS and include all frequencies up to 3.05 kHz.
Press the SHIFT key then NARROW-BAND to measure the fundamental
magnitude only, using DSP algorithms; harmonics are ignored.
The Model 931A displays dashes for Channel 1 and Channel 2, when
in narrow-band mode, if the signal present on Channel 1 is below a value,
which can be accurately measured.
NOTE: Channel 1 is used as the internal reference; if only one
signal is measured, Channel 1 must be used. If both a current
and a voltage are measured, Channel 1 should be used for the
voltage and Channel 2 for the current.
3.5.2
AC Current Measurement
The Model 931A can directly measure and display AC currents of up to
20 Arms.
It can measure higher currents using a current transformer
(CT) and with direct readout using the scaling feature (see “Scale” in
Section 3.3.2.17).
3.5.2.1
Input Connections
The Model 931A provides three sets of input connectors for measuring AC
current: labeled “A”, “B”, and “C”. All three inputs use identical circuitry
and are electrically isolated from all others: the voltage inputs, and chassis
ground. The input multiplexing circuitry allows measurement of the value
at any one the inputs. The Neutral Current, In = −(Ia + Ib + Ic), is
available for measurement on Channel 2.
3.5.2.2
Configuring the Channel
Configure the chosen measurement channel after connecting the current
to the appropriate input terminals.
If measuring only one AC current
(e.g. single-phase), use Channel 1, since this channel is used for frequency
measurements.
46
To configure measurement Channel 1 and view the menu selection
options, press the CHANNEL 1 SELECT key.
Arrows form the cursor and highlight one of the selections. Press the
arrow keys to locate the measurement value. For example, using the arrow
keys move the cursor to Ia to measure an AC current at the two “A”
terminals. Confirm selection by pressing ENTER.
3.5.2.3
Performing the Measurement
Press the VOLTS/AMPS key to display the measured AC current, and
produce a display similar to the one shown below:
The large number at the top of the display indicates the current value
measured by Channel 1. The number below it corresponds to the current
value measured by Channel 2.
The display indicates the general measurement bandwidth (i.e. Wide-
Band) near the lower left-hand corner. The Model 931A uses either wide-
band or narrow-band mode to measure and display AC voltage.
Select measurement bandwidth by pressing SHIFT, followed by either
NARROW-BAND or BAND-WIDE.
Press SHIFT then BAND-WIDE to change the measurement mode to
wide-band RMS and include all frequencies up to 3.05 kHz.
Press SHIFT then NARROW-BAND to measure the fundamental mag-
nitude only, using proprietary DSP algorithms. Harmonics are ignored.
If the signal at Channel 1 is too low to be accurately measured, when
in narrow-band mode, the Model 931A displays dashes for both Channel
1 and Channel 2.
47
DC Voltage Measurement
The Model 931A can directly measure and display DC voltages of up to
1000 Vdc.
3.5.3.1
Input Connections
The Model 931A provides four connectors for measuring dc voltage.
Labeled “A”, “B”, “C”, and “N”, all four inputs use identical circuitry.
Additionally, input multiplexing circuitry allows referencing the voltage
across any two, voltage terminals. For example, to measure a voltage from
“A to N”, connect the leads between those two terminals.
NOTE: The Model 931A does not have a provision for measurement of
voltage between any of the voltage inputs and the chassis ground lug. Make
all voltage measurements between two (or more) of the voltage terminals.
The ground lug is included for safety purposes only.
3.5.3.2
Configuring the Channels
Configure the chosen measurement channel after connecting the voltage
to the appropriate input terminals. Configure Channel 1 by first pressing
the CHANNEL 1 SELECT key, and the following menu will appear on the
display:
Arrows form the cursor, and highlight one of the selections. Press the
arrow keys to locate the measurement value. For example, using the arrow
keys move the cursor to highlight Van to measure a DC voltage between
inputs “A” and “N” (“Van” is in the third row up from the bottom).
Confirm the selection by pressing ENTER.
3.5.3.3
Performing the Measurement
Press the VOLTS/AMPS key to display the measured DC voltage and
view a display similar to the one shown below:
48
The large number at the top of the display indicates the dc voltage value
measured by Channel 1. The display below it corresponds to Channel 2,
which is not used in this example.
The display indicates the general measurement bandwidth near the
lower left-hand corner. However, the bandwidth setting has no effect on
DC measurements.
3.5.4
Frequency Measurement
The Model 931A measures fundamental frequencies within the range of
20 Hz to 500 Hz. The following paragraphs describe the steps required to
perform Frequency measurements.
3.5.4.1
Input Connections
The Model 931A can measure the frequency of AC voltages or currents
connected only on Channel 1.
Make connections in the same manner
as for magnitude measurements (see Section 3.2.2 for AC voltages, and
Section 3.2.3 for AC currents).
3.5.4.2
Configuring the Channels
Frequency measurement is permitted only on signals routed to measure-
ment Channel 1.
Configure Channel 1 by first pressing CHANNEL 1
SELECT; the following menu will appear on the display:
Use the arrow keys to locate the measurement value and press ENTER.
For example, using the arrow keys move the cursor to highlight Van to
measure an AC voltage between inputs “A” and “N”.
For frequency
measurement of an AC current at input “A”, select “Ia” in the top row.
49
Performing the Measurement
Press the PHASE/FREQUENCY key to display the measured frequency
and produce a display similar to the one shown below:
The large number in the middle of the display indicates the frequency
of the signal on Channel 1. The indication for phase angle may consist of
dashes because only one signal is being input or the signal level is too low,
making phase comparison impossible.
The display shows dashes when the signal at Channel 1 is below a value
that can be accurately measured, indicating that the signal is insufficient.
3.5.5
Harmonic Measurement
The Model 931A can measure harmonic content up to the 50th harmonic
for fundamental signals of 50 or 60 Hz.
Use either Channel 1 or 2 to
measure harmonics, but on only one channel at a time.
3.5.5.1
Input Connections
Make connections for harmonic measurement in the same manner as for AC
voltage or current magnitude measurements. Since the Model 931A derives
the harmonic value from the same inputs, simply press the HARMONICS
key to view them. See Section 3.2.2 (AC voltages) and Section 3.2.3 (AC
currents) for descriptions of AC Input connections.
3.5.5.2
Configuring the Channel(s)
To configure the Model 931A for harmonic measurement, press either the
CHANNEL 1 SELECT or CHANNEL 2 SELECT key and use the cursor
keys to select the measurement signal from the channel menu. The Model
931A measures harmonics on signals processed by either channel.
3.5.5.3
Performing the Measurement
Press the harmonics key to display harmonics.
By default, Channel
1 initially displays harmonics.
To switch between harmonics on either
50
channel, press the CHANNEL 1 SELECT or CHANNEL 2 SELECT keys.
The harmonics display appears as follows:
In the example above, the display shows the harmonic content of the
AC current at the input of a switching power supply. While all harmonics
are shown, only the odd harmonics have enough amplitude to be displayed.
The first, vertical bar (on the left) represents the fundamental. An
arrow, below the second bar, represents the cursor, and lies under the third
harmonic. Move the cursor in increments of 1 harmonic with the right and
left arrow keys. Change the vertical scale to better view harmonics with
the up and down arrow keys. The harmonic magnitude factor applied from
using the up/down arrow keys appears in the upper right corner.
The second and third lines of display text describe individual harmonic
information, highlighted by the cursor. These values include the following:
The channel being measured
The input configuration for the channel
The harmonic number
The harmonic amplitude as a percentage of fundamental amplitude
The rms amplitude of the harmonic
The phase angle of the harmonic, relative to the fundamental
The frequency of the harmonic
The top line of text shows THD and K-factor, which relate to the
overall input signal, and do not change when the cursor is moved.
The Model 931A analyzes harmonics by first determining the AC
fundamental and the DC components of the signal. It then removes them
algebraically from the digitized waveform. Fast Fourier Transform (FFT)
analysis determines the residual for the spectral display, K-factor, and
individual harmonic measurements.
Total Harmonic Distortion (THD)
is determined by dividing the rms of the residual by the wide-band rms
amplitude. With these techniques, harmonic measurement accuracy does
not depend upon fundamental frequency.
51
With two separate measurement channels, the Model 931A can compare
and combine the signals from each channel. Combination measurements
of power quantities include:
Phase
Active Power
Reactive Power
Apparent Power
Power Factor
Waveform Display
The following sections provide instructions for performing measure-
ments of parameters within this group.
Connecting the Inputs
When comparing two signals, configure the inputs of the Model 931A
individually, as specified in earlier sections. See Section 3.2.2 to set up
voltage connections and Section 3.2.3 for current connections. Make any
comparison of voltage-to-voltage, voltage-to-current, or current-to-current
in this manner.
For phase angle and/or power quantity measurements, route the
voltage signal to Channel 1, and the current signal to Channel 2. Since
the voltage in a power system is usually more stable and less distorted
than the current, the Model 931A uses Channel 1 as a reference for phase
measurements. Both a voltage and current input signal are required to
measure all power quantities.
3.6.1
Phase Angle Measurement
The Model 931A can measure and display the phase angle between two
AC signals routed to channels 1 and 2. A narrow-band quantity, phase is
the difference between the two fundamental signal components. A signal
at Channel 1 provides the reference to which the signal at Channel 2
is compared. For correct comparison, both signals must have the same
fundamental frequency.
52
Configuring the Channels
NOTE: See Section 3.2.2 and 3.2.3 for input connection description.
Connect the signals to the appropriate input terminals and configure
the measurement channel by pressing CHANNEL 1 SELECT and CHAN-
NEL 2 SELECT. See channel selection screens below.
3.6.1.2
Performing the Measurement
Press the PHASE/FREQUENCY key to produce a display similar to the
one shown below:
The large number at the top of the display shows the phase angle of
the signal routed to Channel 2, relative to that of Channel 1. It also shows
the frequency of the signal at Channel 1. Dashes will appear for phase
angle if signals of sufficient amplitude are not routed to both Channel 1
and Channel 2.
For a more detailed description of Frequency Measurement, see Sec-
tion 3.5.4.
3.6.1.3
Phase Preference
If the value displayed for Phase Angle does not appear correct, the phase
preference may need changing. Choose either ±180◦ or 0−360◦. Also, set
the phase to read negative or positive for Channel 2 lagging Channel 1.
53
The selected phase preference effects only the displayed phase angle, but
none of the power quantities.
Press the MENU key and select Phase Preference (Section 3.3.1.13)
to set the phase preference. Table 3.8 describes the four possible phase
settings and the resultant displays for each, when the signals, shown in
Figure 3.13, are applied. See Section 3.6 for input connection description.
Range
Polarity Setting
Resultant
Setting
for Ch 2 lagging Ch 1
Reading
±180◦
negative
-60 ◦
±180◦
positive
+60 ◦
0 − 360◦
negative
300◦
0 − 360◦
positive
60◦
Table 3.8:
Phase Convention
Figure 3.13: Phase Angle Example
3.6.2
Active Power – Reactive Power
The Model 931A can measure the active power (rms watts) and reactive
power (vars) from the combination of an AC voltage routed to measure-
ment Channel 1 and an AC current routed to Channel 2.
NOTE: Refer to Section 3.6 for input connection description.
54
Configuring the Channels
Configure the chosen measurement channels after connecting the voltage
and current to the appropriate input terminals (see Figure 2.1 for instru-
ment locations).
Press CHANNEL 1 SELECT to begin configuring channel 1.
The
following menu will appear on the display:
Arrows form the cursor, which highlights one of the selections. Press
the arrow keys to locate the measurement value. For example, using the
arrow keys move the cursor to “Van” to measure an AC voltage between
inputs “A” and “N”.
Press ENTER to confirm the selection.
Press
CHANNEL 2 SELECT to configure channel 2 current (e.g. Ia).
Move the cursor to the desired measurement value and press ENTER to
confirm the selection. For example, using the arrow keys move the cursor
to “Ia” to measure an AC current at the “A” input terminals.
3.6.2.2
Performing the Measurement
Pressing POWER/VARS will produce a display similar to the one shown
below:
The large number at the top of the display shows the active power
measured.
The lower number shows the reactive power.
Also, the
display indicates if the Model 931A is making wide-band or narrow-band
measurements.
55
The DSP computes wide-band (i.e.
to 3.05 kHz) active power in
Watts by taking the average of instantaneous values of voltage and current
multiplied by each other. Wide-band reactive power (VARS) is determined
by taking the vector difference of the product of the wide-band rms
voltage and current (wide-band apparent power) less the active power.
The formula is shown in 3.4 below:
(3.4)
ReactivePower =
�
(V A)2 − (ActivePower)2
The polarity of the wide-band reactive power is determined by the
narrow-band result. Press SHIFT then NARROW-BAND to switch the
measurement mode from wide-band to narrow-band. Narrow-band mode
measures the fundamental magnitude of the voltage and current only,
using proprietary DSP algorithms. Harmonics are ignored. Dashes will
appear in the display if insufficient signals are present during measurements
performed in narrow-band mode. Narrow band results are computed in 3.5
and 3.6.
(3.5)
ActivePower = Vfund × Ifund × cos(θ)
(3.6)
ReactivePower = Vfund × Ifund × sin(−θ)
3.6.3
Apparent Power – Power Factor
The Model 931A can measure the apparent power (volt-amps, or VA) and
power factor from the combination of an AC voltage routed to Channel 1
and an AC current routed to Channel 2.
NOTE: See Section 3.6 for input connection description
3.6.3.1
Configuring the Channels
Configure the chosen measurement channels after connecting the voltage
and current to the appropriate input terminals (see Figure 2.1 for instru-
ment locations).
Press CHANNEL 1 SELECT to configure measurement channel 1 and
to view the following menu:
56
Arrows form the cursor, which highlight one of the selections. Press
the arrow keys to locate the measurement value. For example, using the
arrow keys move the cursor to “Van” to measure an AC voltage between
inputs “A” and “N”. Press ENTER to confirm selection.
Press CHANNEL 2 SELECT to configure Channel 2 in the same way
as for channel 1. An almost identical menu (except for In) will appear:
Move the cursor to the desired measurement value and press ENTER to
confirm the selection. For example, using the arrow keys move the cursor
to “Ia” to measure an AC current at the “A” input terminals.
3.6.3.2
Performing the Measurement
Press VA/PF to produce a display similar to the one shown below:
The large number at the top of the display shows the apparent power
measured. The lower number shows the power factor. Also, the display
indicates whether the values are wide-band or narrow-band measurements.
Press SHIFT then BAND-WIDE to change the measurement mode to
wide-band RMS, including all frequencies up to 3.05 kHz.
Wide-band
apparent power is determined by multiplying the wide-band voltage and
current as shown below. Power factor is the quotient of the Active Power
divided by the Apparent Power as seen in 3.7 and 3.8.
Wide-Band:
(3.7)
V A = Vrms × Irms
(3.8)
PF = ActivePower ÷ V A
Press SHIFT then NARROW-BAND to change the measurement mode
to measure the fundamental magnitude of the voltage and current only,
using proprietary DSP algorithms.
This measurement mode ignores
57
harmonics, and also displays dashes with insufficient signal levels. Narrow-
band apparent power is determined by multiplying the fundamental
voltage by the fundamental current as seen in 3.9. Power Factor is the
cosine of the angle between Vfund and Ifund as seen in 3.10.
Narrow-Band:
(3.9)
V A = Vfund × Ifund
(3.10)
PF = Cos(θ)
3.6.4
Waveform Display
Press the WAVEFORM key at any time to display waveforms for the
signals at measurement channels 1 and 2. Initially, waveforms for both
channels will be displayed.
Display individual channels by pressing
CHANNEL 1 SELECT or CHANNEL 2 SELECT. Press the WAVEFORM
key again to display both wave shapes simultaneously.
The Model 931A Waveform Display includes a text display showing
the rms magnitudes for the two signals and the frequency of the signal at
Channel 1. The following example shows a typical Waveform Display:
Signals are aligned so that the zero crossings of each channel appear at
the left-hand edge of the display.
3.7
Timer Measurements
The Model 931A includes a timer for measuring events such as relay
contact timing. The timer has two channels, which are optically isolated
from the instrument common and from each other. Both inputs can accept
various triggering inputs, including:
Contact opening or closure,
AC applied or removed (20 - 300 Vrms),
DC applied or removed (4 - 300 Vdc).
See Section 3.7.2.4, “Select Timer Trigger A” for more information.
58
Connecting the Inputs
The two timer inputs are labeled “A” and “B”, with one black terminal
and one red terminal for each input. Apply AC or DC input signals to
either channel without regard to polarity.
NOTE: In contact closure or opening mode, external voltage should not
be applied to the inputs; only DRY contacts should be used.
3.7.2
Configuring the Timer
Press the CONFIG key to invoke the timer configuration menu, which will
be similar in appearance to the following:
Select timer functions using the arrow keys; highlight the desired item
and press ENTER to confirm the selection. The following sections describe
the individual selections from this menu.
3.7.2.1
Select Timer Function
Select Function from the Timer Configuration menu and press ENTER to
view the following display:
“Time A to B” configures the timer circuitry to display the time
elapsed between a valid trigger for the “A” input and a valid trigger
for the “B” input.
“Time A For X Counts” configures the timer to display the time
elapsed between a valid trigger for the “A” input and the Xth valid
trigger for the “A” input.
“Time Width of A” sets the timer circuitry to measure the
duration of the triggering event on the “A” input.
59
“Rate of A” causes the timer to display the rate of a valid triggering
event at the “A” input.
NOTE: The timer triggers without regard to polarity. If selecting
DC Applied as the trigger and a symmetric signal of greater than 6
Vpp is applied, the rate displayed will be double the actual frequency.
“Count A Events” configures the timer circuitry to display the
number of valid trigger events, which occur on the “input”. These
may be periodic or random.
“Count A Gated By B” sets the timer circuitry to count events
on input “A” only during the time in which a valid trigger condition
exists on input “B”. The events counted during successive valid “B”
input trigger periods are cumulative.
3.7.2.2
Timer Display Choices
To select whether time data is displayed in seconds or in cycles, select
Display Choice from the Timer CONFIG main menu and press ENTER.
For cycles, the data may be based on 50 Hz, 60 Hz, or the fundamental
frequency of the signal present at measurement Channel 1 (Ch 1 Hz).
Select Display Choice from the Timer Configuration Menu to view the
following display:
Seconds sets the timer to display measurement results in seconds.
Cycles (50 Hz) causes the timer to display the measurement result
in cycles, assuming a frequency of 50 Hertz.
Cycles (60 Hz) causes the timer to display the measurement result
in cycles, assuming a frequency of 60 Hertz.
Cycles (Ch 1 Hz) causes display of measurement results in cycles,
using the signal present at Channel 1 as the reference frequency.
60
Hold Mode on Stop
Select Hold Mode On Stop from the Timer Configuration Menu and press
ENTER to view the following sub-menu:
Use this sub-menu to leave the instrument in the measure hold mode
at the end of a timer cycle.
Select Disable to continue normal operation, with all measured param-
eters being updated continuously.
Select Enable to continue in the measure hold mode at the end of the
timer cycle. It then retains values for all measured parameters as of the
end of the timer cycle.
3.7.2.4
Select Timer Trigger A
Select Trigger A from the Timer Configuration Menu and press ENTER
to view the following display:
This sub-menu allows selection of the type of input to be used for the
trigger for timer “Channel A”. The following are descriptions of each of
the choices:
“DC Applied” configures the timer input to trigger with a ± 3
volts DC or greater signal.
“DC Removed” configures the timer input to trigger with removal
of a ± 3 volts DC or greater signal.
“AC Applied” configures the timer input to trigger with an AC
voltage. The minimum triggering voltage is frequency dependent,
but must be greater than 3 volts rms at any frequency. Slight errors
may occur, when using this mode of triggering, that depend on the
61
instantaneous voltage. The minimum trigger voltage, as a function
of frequency, is shown in the following graph:
NOTE: The minimum rms voltage at 60 Hz is (approx.) 11 volts.
“AC Removed” configures the timer to trigger on the removal of
an ac voltage, as described above. The point in time at which the
signal last falls below the threshold is interpreted as the trigger.
Slight errors may occur, when using this mode of triggering, that
depend on the instantaneous trigger voltage.
However, this error
should not exceed 1 millisecond.
“Contact Open” configures the timer input to recognize the
opening of an electrical contact as a trigger event. The threshold
is (approx.)
2.9 volts, with a pull-up impedance of (approx.)
47
kilohm to a source voltage of (approx.) 8 volts.
“Contact Closed configures the timer input to recognize the closing
of an electrical contact as a trigger event. The threshold is (approx.)
2.6 volts, with a pull-up impedance of (approx.)
47 kilohm to a
source voltage of (approx.) 8 volts.
3.7.2.5
Select Timer Trigger B
Press the Timer CONFIG key and select Trigger B from the Timer
Configuration Menu and press ENTER. Select the appropriate trigger
signal type for timer “Channel B” from this menu. The choices for input
“B” are exactly the same as those for input “A”. See Section 3.7.2.4.
3.7.3
Timer Measurement Categories
All measurements performed by the timer section of the Model 931A can be
classified as either time or count measurements. The following paragraphs
describe both categories.
62
The Timer has four states of operation: Standby, Armed, Active, and
Stopped. Initially, the timer will be in Standby. After configuring the
timer, press the ARM/RESET key to Arm the timer.
A timing cycle begins with a start trigger, and the Timer switches
from Armed to Active. When the predetermined stop trigger occurs, the
timing cycle ceases, and the timer Stops (except in Count Modes, where
it switches to Standby).
The ARM/RESET key functions as a reset key, when the timer stops
in time measurement modes, or at any time in count measurement modes.
Press ARM/RESET to clear the timer data and reset the display to
zero. Pressing ARM/RESET also switches the timer from the Stopped
to Standby.
The Model 931A displays the timer-state below the word “Timer.” A
blank status indicator signifies the instrument is in Standby.
3.7.3.2
Time Measurements
Time Measurement Timer functions return a time value with finite start
and stop points. Measurements falling in this category are:
Time A to B
Time A for X Counts
Time Width of A
During these modes of operation, the timer cycles through all four
timer states.
3.7.3.3
Count Measurements
Count Measurement Timer functions result in measurements having a
finite starting point, then are continuously updated. Measurements falling
into this category are:
Rate of A
Count A Events
Count A Gated by B
In these modes of operation, the timer can only be in the Standby,
Armed or Active states as described in Section 3.7.3.1. The Stopped State
is invalid with these modes.
63
Displaying the Timed Value
The Timer reports a time measurement after the timer stops (the Stopped
State).
The Model 931A then displays this value until pressing the
ARM/RESET key (which returns the timer to the Standby state).
During count measurements, the display continuously updates the
count during the measurement cycle.
Pressing the ARM/RESET key
resets the count display back to zero, and also re-arms the timer.
3.8
Transducer Testing
Testing transducers with the Model 931A is straightforward using an
external source, such as a calibrator or source and load box. Also perform
live, in-circuit tests. Prior to starting a transducer test the Model 931A
automatically makes a self-calibration.
Use the main measurement inputs to precisely monitor the transducer
input values. Transducer output may be set to either Measured Quantity,
Percent Full Scale, or Percent Error, while simultaneously displaying
the transducer inputs.
This provides a look at the input and output
quantities for better control during the measurement, and fewer chances
for measurement or setup errors.
The Model 931A Transducer input uses accurate, optically isolated
input sections to accept transducer outputs in the range of 0 − 10 Vdc or
0 − 100 mA. Alternatively, transducer custom pulse outputs may also be
tested using the Model 931A Timer A input.
3.8.1
Configuring the Transducer
Press SHIFT > CONFIG to configure transducer measurement section via
a series of menus (a second function of TRANSDUCER). The main menu,
in the series, is the Transducer Configuration menu, which is similar in
appearance to the display shown below:
The following paragraphs describe the functions and capabilities of each
of the Transducer Configuration menu selections.
64
Select Input Mode from the Transducer Configuration menu and press
ENTER to view the following sub-menu:
Select any of the available input modes for testing transducers from
this menu. For 3-phase measurements, see description in Section 3.3.2.5.
Menu selections are described below and help explain how these selections
apply when performing Transducer Testing.
“1Ph 2Wire 1E” sets the Model 931A to measure values in a single-
phase circuit, having a hot wire and a neutral wire. Since sequential
measurements are not necessary, the internal operating software for
the Model 931A utilizes whichever inputs are currently routed to
measurement channels 1 and 2.
For a voltage or frequency transducer, use Channel 1 for the
transducer input.
For a current transducer, use Channel 2 for
the transducer input, and route a voltage or current of the same
frequency to Channel 1.
Do not select the same input for both
Channel 1 and Channel 2. See Figure 3.14.
“1Ph 3Wire 2E” sets the Model 931A to measure values in a
circuit having two hot wires and a neutral wire. Commonly referred
to as Split-Phase, this type of circuit is generally used to supply
residential service.
This particular configuration is intended for
testing 2-element transducers. See Figure 3.15.
Use internal operating software definitions for inputs as follows:
”VanIa”, “VcnIc” (i.e., a sequential measurement of the following
two combinations: voltage “A” to “N” with current “A”, and voltage
“C” to “N” with current “C”).
“3Ph 3Wire 2E” sets the Model 931A to measure values on a
3-phase delta circuit, for comparison with a 2-element transducer.
Use internal operating software definitions for inputs as follows:
“VabIa”, “VcbIc” (i.e., a sequential measurement of the following
two combinations: voltage “A” to “B” with current “A”, and voltage
“C” to “B” with current “C”).
65
“3Ph 4Wire 2.5E” sets the Model 931A to measure values on a
3-phase delta circuit, for comparison with a 2.5-element transducer.
See Figure 3.16.
Use the internal operating software definitions for inputs as follows:
“VanIa”; “VbIb”; and “VcnIc” (i.e., a sequential measurement of the
following three combinations: voltage “A” to “N” with current “A”,
voltage “b” with current “B”, and voltage “C” to “N” with current
“C”). To create voltage “b”, connect the “B” voltage input to the
“N” voltage input.
“3Ph 4 Wire 3E” sets the Model 931A to measure values on a
3-phase Y circuit, for comparison to a 3-element transducer.
See
Figure 3.17. Use internal operating software definitions for inputs
as follows:
“VanIa”; “VbnIb”; and “VcnIc” (i.e., a sequential
measurement of the following three combinations: voltage “A” to
“N” with current “A”; voltage “B” to “N” with current “B”; and
voltage “C” to “N” with current “C”).
Three-phase display and percent error calculations use the average
for V, A, θ (phase), and PF, and the total for W, VAR, and VA.
3.8.1.2
Input Type
Select Input Type from the Transducer Configuration menu and press
ENTER to view the following sub-menu:
“Volts” sets the Model 931A to make Voltage measurements at
the predefined input routed to Channel 1, for comparison to a
voltage transducer. For 3-phase configurations, the display shows
average voltage. See Section 3.2.2 for a description of AC voltage
measurements.
“Phase” sets the Model 931A to measure the Phase Angle between
the voltage and current at the predefined inputs, for comparison to
a phase angle transducer. For 3-phase configurations, the display
shows average phase angle.
See Section 3.6.1 for a description of
phase measurements.
66
“Power” sets the Model 931A to calculate active power (watts).
Based on voltage and current measurements from the predefined
inputs, the results are compared to an active power transducer. For
three-phase configurations, the display shows total active power. See
Section 3.6.2 for a description of power measurements.
“Volt-Amps” sets the Model 931A to calculate apparent power
(VA). Based on voltage and current measurements from the pre-
defined inputs, the results are compared to an apparent power
transducer. For three-phase configurations, the display shows the
total apparent power. See Section 3.6.3 for a description of apparent
power measurements.
“Amps” sets the Model 931A to make current measurements on the
predefined input routed to Channel 2 and compares it to a current
transducer. Route input to measurement Channels 1 and 2 if only a
current signal is available.
If available, route synchronous voltage signal to channel 1.
For
three-phase configurations, the display shows average current. See
Section 3.2.3 for a description of AC current measurements.
“Frequency” sets the Model 931A to measure frequency at (prede-
fined) channel 1, for comparison to a frequency transducer.
The
displayed frequency actually represents the instantaneous value,
which is updated with each measurement cycle. See Section 3.5.4
for a description of frequency measurements.
“Vars” sets the Model 931A to calculate reactive power (vars) based
on voltage, current, and phase measurements from the predefined
inputs. The results are compared to a reactive power transducer.
For three-phase configurations, the display shows the total reactive
power. See Section 3.6.2 for a description of reactive power.
“Power Factor” sets the Model 931A to calculate power factor
based on voltage and current from the predefined inputs.
The
results are compared to a power factor transducer.
For three-
phase configurations, the display shows average power factor. See
Section 3.6.3 for a description of power factor measurements.
3.8.1.3
Input Range
Select Input Range from the Transducer Configuration menu and press
the ENTER key to view the available input ranges.
The displayed
67
range selection menu varies and depends on the selected input type (see
Section 3.8.1.2 for a description of available Input Types).
When the
Model 931A is configured to test a voltage transducer, the display shows
following selection menu:
Custom allows the user to determine the upper and lower limits of the
measurement range. Determine a custom range, as a part of this sub-menu,
for all input types. See Section 3.3.3 for Data Entry Function description.
3.8.1.4
Output Range
Select Output Range from the Transducer Configuration menu to view the
following sub-menu:
The Model 931A allows these output ranges when the transducer
outputs are connected to the transducer terminals on the front panel.
Within the ranges shown, the Model 931A accepts either voltage or
current signals. Refer to Section 3.8 for details on connecting transducer
inputs, and Section 3.3.3 for a description on data entry.
Custom V allows the user to enter a voltage range within the limits
of 0 to 10 volts DC.
Custom mA allows the user to enter a current range within the limits
of 0 to 100 milliamperes DC.
Custom Pulse allows the user to setup the Model 931A to accept
a calibrated pulse from the transducer that is proportional to the
measured transducer value.
3.8.1.5
Display Input As
Select Display Input As from the Transducer Configuration menu and press
the ENTER key to view the following sub-menu:
68
“Measured Quantity” displays the value present at the Model 931A
measurement inputs in actual measurement units (e.g. volts, amps).
“Percent Full Scale” displays the value present at the Model 931A
measurement inputs as a percentage of full-scale. Full-scale is defined
by the lower and the upper limit of the currently selected input range
(see Section 3.8.1.3 for a description of Input Ranges).
3.8.1.6
Display Output As
Select Display Output As from the Transducer Configuration menu to
display the following sub-menu:
“Measured Quantity” sets the Model 931A to display the actual
value measured at the output of the transducer under test (i.e., volts
or milliamperes).
“Percent Full Scale” displays the measured value (at the output
of the transducer under test) as a percentage of full-scale. Full-scale
is defined by the lower and the upper limit of the selected output
range. Does not apply for Custom Pulse.
“Percent Error” displays the measured error of the transducer
based on the measured input and output quantities.
To properly utilize the Percent Error feature, enter the following: (1)
the upper and lower transducer input quantities and (2) the upper
and lower transducer output range limits. Setting the output range
limits are critical for transducers having a lower output range limit of
other than zero. For example a typical transducer may have a 4−20
mA output. With such a transducer, zero at the input corresponds
to 4 mA at the output.
69
Connecting the Inputs
If needed, use the main measurement inputs on the Model 931A as the
input for transducer tests at any value up to their rated maximum (see
Specifications in Section 4).
Connect the voltage and current measurement inputs according to the
type of transducer being tested.
The operating software defines which
combination of inputs to use for testing of each type of transducer (except
1-Phase 2-Wire). These definitions are described in the Transducer Mode
Selection menu, shown in Section 3.8.1.1.
Figures 3.14 through 3.17 illustrate various examples of connections for
transducer testing.
Use any of the voltage and current inputs to measure single-phase, two-
wire transducers since they do not require sequential measurements. Use
channel 1 for voltage and channel 2 for current, as channel 1 is used as a
reference channel, as the voltage signal is typically the most stable signal.
70
���� ��� ����� �������������� ����� ���
�������� ����������� �������������
������� ���� ������ ������ � ����������
���� ��� ���� �� �������� �������� � ���
� ���� ��� ���� �� �������� ������� ���� ���
������ � ������ ��� ����� ���� ����� ��������
Figure 3.14: 1-Phase, 2-Wire, 1-Element Transducer Test
71
931A POWER SYSTEM ANALYZER
CURRENT
VOLTAGE
TRANSDUCER
SETUP 1
SETUP 2
SETUP 3
SETUP 4
SETUP 5
SETUP 6
NARROW-BAND-WIDE
MEAS 3 PHASE CH1 RANGE
RESTART
CONFIG
SHIFT
HELP
REVIEW
PRINT LOG
STORE SETUP
SCALE
ESCAPE
ENTER
VOLTS
AMPS
PHASE
FREQUENCY
POWER
VARS
VA
PF
HARMONICS
WAVEFORM
CHANNEL 1
SELECT
CHANNEL 2
SELECT
MEASURE
HOLD
CH2 RANGE
MIN
MAX
TRANSDUCER
MENU
LOG DATA
PRINT
LAST SETUP
CH1 / CH2
ON/OFF
FUSE
1AF/250V
85-264 Vac
47-440 Hz
110-250 Vdc
RS-232
GROUND
BEFORE
USE
A
B
C
N
750 Vrms / 1000 Vdc MAX
20 Arms MAX
10Vdc
MAX
100mAdc
MAX
A
B
C
DISPLAY
CONFIG
ARM / RESET
A
B
300V
MAX
L1
L2
L1
L2
N
N
Iout
LOAD
SOURCE
{
+
-
{
I1
+
-
{
I2
+
-
{
V1
+
-
{
V2
+
-
Figure 3.15: 1-Phase, 3-Wire, 2-Element Transducer Test
72
931A POWER SYSTEM ANALYZER
CURRENT
VOLTAGE
TRANSDUCER
SETUP 1
SETUP 2
SETUP 3
SETUP 4
SETUP 5
SETUP 6
NARROW-BAND-WIDE
MEAS 3 PHASE CH1 RANGE
RESTART
CONFIG
SHIFT
HELP
REVIEW
PRINT LOG
STORE SETUP
SCALE
ESCAPE
ENTER
VOLTS
AMPS
PHASE
FREQUENCY
POWER
VARS
VA
PF
HARMONICS
WAVEFORM
CHANNEL 1
SELECT
CHANNEL 2
SELECT
MEASURE
HOLD
CH2 RANGE
MIN
MAX
TRANSDUCER
MENU
LOG DATA
PRINT
LAST SETUP
CH1 / CH2
ON/OFF
FUSE
1AF/250V
85-264 Vac
47-440 Hz
110-250 Vdc
RS-232
GROUND
BEFORE
USE
A
B
C
N
750 Vrms / 1000 Vdc MAX
20 Arms MAX
10Vdc
MAX
100mAdc
MAX
A
B
C
A
N
C
C
A
N
B
B
DISPLAY
CONFIG
ARM / RESET
A
B
300V
MAX
Iout
LOAD
SOURCE
{
+
-
{
I1
+
-
{
V1
+
-
{
V3
+
-
{
I2
+
-
{
I3
+
-
NOTES:
In 3-Phase 4-Wire 2.5 Element Mode,
the Model 931A voltage input 'B' must
be connected to voltage input 'N'.
Figure 3.16: 3-Phase, 4-Wire, 2.5-Element Transducer Test
73
Figure 3.17: 3-Phase, 4-Wire, 3-Element Transducer Test
74
Connecting the Outputs
Figures 3.14 through 3.17 illustrate the Transducer Signal Outputs con-
nected between the transducer current input (far right) and common
(middle).
If testing transducers with voltage outputs, connect them
between the transducer voltage input (left) and common (middle).
NOTE: Be certain to configure the Model 931A to accept the type of
transducer signal and range, whether voltage or current output.
Sec-
tion 3.8.1.4 describes available Output Ranges.
3.8.4
Performing the Measurement
Once in the Transducer Configuration Menu, press the ESCAPE key to
automatically place the unit in the transducer measurement mode.
To
access the Transducer Configuration Menu, press SHIFT then CONFIG.
Instrument configuration determines the appearance of the display
during transducer measurements.
The upper number represents the
transducer input, and the lower number represents the transducer output.
Display configuration determines whether measurement results are pre-
sented as a measured value, or as a percent of full-scale. Sections 3.8.1.5
and 3.8.1.6 describe the Display Modes.
Additionally, the Model 931A can present the lower number as a
percentage of error in the transducer. Percentage error is determined by
comparing the ratio of the input and output values to the ratio of the input
and output ranges. Section 3.8.1.6 describes how to set the Model 931A
to display percentage error in transducer measurements.
3.8.5
Custom Pulse, or Contact Output Tests
3.8.5.1
Choosing a Test Method
Testing transducers with contact outputs can be accomplished by using the
Custom Pulse feature of the Model 931A. By following the steps outlined
below, most transducers with contact outputs may be tested simply and
accurately.
1. Determine the type of transducer output.
2. Configure the Transducer menu, on the Model 931A.
3. Configure the Timer menu, on the Model 931A.
4. Setup the required test equipment and transducer.
5. Test the transducer.
75
Determine the Transducer Type
Most transducers with contact (or pulse) outputs use either an electrome-
chanical or a solid-state relay. If the transducer has an electromechanical
relay at the output, it is important to use the Debounce feature on the
Model 931A. Otherwise, do not use it.
3.8.5.3
Configuring in the Transducer Menu
Press SHIFT then CONFIG to access the Transducer Configuration menu.
Set each of the six categories in the Transducer Configuration menu that
best fits the transducer being tested. Use the arrow keys and ENTER to
make and confirm selections. As each of the six categories is setup, the
arrow cursor moves down to the next category.
The sample menu shown below pertains to a 3-phase power transducer
illustrated in Figure 3.18.
Make these selections as follows (as shown in the screen above).
1. Input Mode – select the Phase, number of Wires and Elements
(e.g. 3P 4W 3E).
2. Input Type – select Volts, Phase, Power, Volt-Amps, Amps,
Frequency, Vars, or Power Factor (e.g. Power).
3. Input Range – select the transducer range being tested (e.g. 0 -
1500).
4. Output Range – this selects the Custom Pulse feature. Choose
Custom Pulse (only) for this menu item. Note that after Custom
Pulse is selected (under the Transducer Output menu) the bottom
line will clear and read ”Watt-hours per pulse = 0.00000”. Use the
right and left arrows to move the cursor and the up and down arrows
to change the digit value. 100 (watt hours per pulse) is the largest
acceptable value
5. Display Input As – select either Measured Quantity or Percent
Full Scale (e.g. the above settings will display Measured Quantity in
kWatts).
76
6. Display Output As – select either Measured Quantity or Percent
Error. Although the menu choices include Percent Full Scale, only
Measured Quantity and Percent Error pertain to Custom Pulse.
The sample Transducer Configuration Menu shown below illustrates
settings for a different transducer using the “Rate of A” Function instead
of “Time A to X Counts.” Notice the large difference in Output Range
compared to the “Time A to X Counts” configuration above.
When all of the six categories are set up correctly, press ESCAPE to
return to the main menu. If initially setting up a transducer custom pulse
test, proceed to the section on Timer Configuration below.
3.8.5.4
Configuring in the Timer Menu
Press the Timer CONFIG key to access the Timer Menu. A sample menu
is shown below.
Only two selections under Timer Function apply to the Custom Pulse
feature: “Time A For X Counts” and “Rate of A.”
Make the Timer Configuration selections as follows:
1. Function – select either Time A For X Counts, or Rate Of A. Use
Time A for X counts if the contact closure rate is < 1/sec. Use Rate
of A if the contact closure rate is > 1/sec. For more details on which
function to choose, see below under “Contact Closures < 1/second”,
or “Contact Closures > 1/second.”
77
2. If choosing “Time A For X Counts”, a numerical value will replace
X awaiting confirmation. Use the Up or Down arrow keys to change
this value.
3. Display choice – select Seconds
4. Hold Mode On Stop – select Disable
5. Trigger A – select Contact Closed or Contact Open
6. Trigger B – do not use this item for the Custom Pulse function.
7. Debounce A – select “ON” for electromechanical contacts, “OFF”
for solid-state contacts.
8. Debounce B – do not use this item for the Custom Pulse function.
3.8.5.5
Contact Closures < 1/second
The best selection for contact closures < 1/second is Time A For X Counts.
This function allows the Model 931A to measure transducers with contact
outputs that are relatively slow – in the range of seconds between pulses.
Typical devices that fit into this category could be transducers.
1. Select Function, in the Timer Configuration Menu, and press
ENTER.
2. Select Time A For X Counts in the Select Timer Function menu,
using the arrow keys and press ENTER.
3. When ENTER is pressed, a numerical value replaces X and awaits
adjustment or confirmation.
4. Use the UP or Down arrow keys to increase or decrease the number
of contacts.
5. Press ENTER to confirm the selection and return to the Timer
Configuration menu.
78
Any time X is set to a value greater than ”1”, in the ”Time A to X
Counts” function, the Model 931A computes average output values, or the
% error. It does this by measuring the overall time for multiple contacts
(defined by X) and divides that time by the number of contact closures.
At the end of a test, the Model 931A displays and holds the Input and
Output values until pressing ARM/RESET, which begins a new test.
3.8.5.6
Contact Closures > 1/second
“Rate of A” is generally used for calibration standards (transducers) with
output rates normally much greater than 1 Hz. Notice the values listed in
the Timer Configuration Menu. Remember that Trigger B and Debounce
B are not used in Custom Pulse transducer measurement functions.
1. Press the Timer CONFIG key to access the Timer Configuration
Menu.
With the cursor, select “Function” and press ENTER to
access the Timer Function menu.
2. In the Timer Function menu select “Rate of A” and press ENTER.
3. The ”Rate of A” Function also continuously updates the transducer
measurements during a test.
In this example, “Rate of A” was chosen based on the nameplate rating
of 0.00001 Whr/pulse. Dividing the number of Transducer Input Watts
by 0.00001 Whr/pulse and dividing by 3600 sec/hour gives a pulse rate of
approximately 20,000 pulses per second. The calculation is shown in 3.11
below.
(3.11) (718.8W ÷ 0.00001Whr/pulse) ÷ 3600sec/hr = 19, 966pulses/sec
79
Connect the transducer pulse output to the Model 931A Timer A input
terminals with suitable cables. The Custom Pulse function works only with
Timer Input A. Connect the transducer and the Model 931A to a source
providing the required output levels for testing the transducer. Refer to
Figure 3.18 for an illustration of using a power transducer.
Note: Check the Model 931A maximum ratings prior to applying power,
to avoid damaging the equipment.
Always consult the manufacturers original documentation for the power
source and the transducer for proper test setup. This may be a manual,
or simply be the nameplate on the transducer.
3.8.6
Performing a Test
3.8.6.1
For Contact Closures < 1/second
Use Time A For X Counts.
After setting up the test and configuring
the Model 931A, apply the input power source to the transducer and
Model 931A. Refer to Figure 3.18. Press the TRANSDUCER key to view
the standard measurement screen. Initially, the Model 931A display will
appear similar to the screen below.
1. Allow a few seconds for the Transducer Input value to stabilize.
2. Press the ARM/RESET key twice to reset and arm the timer
function. For X = 1, the first pulse starts the timer and the next
pulse concludes the timing interval.
If using multiple counts per
measurement (X > 1), the timer will begin counting on the first
pulse and stop with the last pulse.
3. During the custom pulse test the OUTPUT value will change to
dashes, as shown below and the date (in the lower right) will be
replaced with a timer value, incrementing in seconds.
80
4. When the test is complete the OUTPUT measurement value will
replace the dashes, and the timer value will freeze, indicating the
transducer input, transducer output and the number of seconds. The
Model 931A will be placed in Hold Mode.
5. To repeat the test with the same or different transducer input, press
the ARM/RESET key, adjust the source as necessary, allow the
transducer input display to stabilize and press the ARM/RESET
key again.
6. To configure new test parameters, press either SHIFT then CON-
FIG (transducer) or CONFIG (timer) to change the measurement
settings. After re-configuring the test parameters, press the TRANS-
DUCER key and the Model 931A is ready for another test. To start
the next test, press the ARM/RESET key twice.
3.8.6.2
For Contact Closures > 1/second
After setting up the test and configuring the Model 931A, apply the input
power source to the transducer and Model 931A. Refer to Figure 3.18.
1. Press the TRANSDUCER key to view the standard measurement
screen.
Press the ARM/RESET key again if the display is not
indicating a reasonable output value, as illustrated below.
81
2. If date and time information is showing (found in the lower right
corner of the display) press the ARM/RESET key.
It should
immediately begin measuring the transducer.
Also, the Timer
information (including the contact or pulse output rate in Hertz)
should appear and replace the date and time information. The screen
below illustrates the Model 931A measuring a transducer using “Rate
of A.”
3. Using the “Rate of A” Function, the Model 931A should continually
update the measurement values.
The Model 931A also cycles
between each measured phase indicated in the lower left corner of
the display.
4. The Transducer Input value indicates the total input, in this case
three-phase power.
5. Adjust the source for subsequent tests to be performed.
82
Figure 3.18: 3-Phase, 4-Wire, 3-Element Custom Pulse Transducer Test
83
Using External PT’s and CT’s
Use an external current transformer (CT) and potential transformer (PT)
to extend the measurement range of the Model 931A. If used, however, do
not exceed the input range of the instrument (refer to Chapter 4, Specifica-
tions). Using an external PT and/or CT by directly displaying measured
primary CT and PT values greatly simplifies measurement. Programming
the scaling feature of the Model 931A, whether for magnitude or phase,
effectively cancels offset errors.
To activate and configure the scaling
function, press SHIFT then SCALE. See Section 3.3.2.17 for details on
using the Scale feature.
Measure the ratio and phase error of a CT or a PT by using the
CH1/CH2 function included in the Model 931A. Press the CH1/CH2 key
to display the phase difference and magnitude ratio of the signals measured
by Channel 1 to the signal measured by Channel 2. Further discussion of
the CH1/CH2 function can be found in Section 3.3.1.17.
Example: measure the ratio of a PT by performing the following steps:
1. Use Channel 1 to configure the Model 931A to measure the voltage
at the input of the PT.
2. Use Channel 2 to configure the Model 931A to measure the output
of the PT.
3. Apply the operating voltage to the input of the PT, and press the
CH1/CH2 key.
4. The resultant display shows the voltage at Channel 1 divided by the
voltage at Channel 2, along with the phase angle between the two.
3.10
Data Logging
The Model 931A data-logging feature greatly simplifies recording measure-
ments, either from the front panel or through the serial interface for later
review. The following paragraphs describe how to record and review data.
3.10.1
Capturing Data
Use the LOG DATA function to record four different data type measure-
ment results in internal memory. These data types are:
Standard data includes all of the Narrow-Band and Wide-Band
parameters for Channels 1 and 2, along with Timer and Transducer
results. All logged data is tagged with the time and date. This type
84