ALLTRONIC Micro6R Manual 

Text of the manual

TRIMMER – FUSE – RELAY

P1 WORKING TIME TRIMMER P2 PAUSE TIME TRIMMER P3 PEDESTRIAN TIME TRIMMER F1 = FUSE 5X20 F2A on 24Vac protection : blinker supply 24Vac F2 = FUSE 5X20 T0,8A on 18Vac protection : electronic supply and exit 24Vdc. F3 = FUSE 5X20 T0,8A on 230Vac protection : blinker supplì 230Vac. RL1 LIGHT OF COURTESY RELAY (exit 24Vdc) RL2 BLINKER RELAY OF 24Vac RL3 OPEN RELAY RL4 CLOSE RELAY RL5 BLINKER RELAY 230Vac DECLARATION OF CONFORMITY (according to ISO/IEC Guide 22 and EN 45014) Manufacturer’s Name : ALLTRONIC s.n.c. Manufacturer’s Address : Via Torino. 84—12041 Bene Vagienna (Cn) Italy DECLARES THAT THE FOLLOWING PRODUCT Product Name : Central for Rapid/Rolling Door Model : Micro6R CONFORMS TO THE FOLLOWING EMC SPECIFICATIONS BASED ON SAMPLE TESTING: EN 55011 EN 60335-1 EN 55014-1 EN 60204-1 EN 55014-2 EN 12453 EN 61000-3-2 EN 61000-6-1 EN 61000-3-3 EN 61000-6-3 + A11 The product has been tested in the typical installation configuration and with peripherals which conform to EMC Directive. I the undersigned declare that the product herewith complies with the protection requirements of the EMC Directive 89/336/ EEC, the 73/23/CEE Low Tension Directive and also the Directive 89/392/CEE (Electric Equipment Security of the Devi- ces). Bene Vagienna, 12/07/2017 Allodi Francesco Proprietario Control Type Micro 6R Threephase 400V or Monophase 230V For fast, rolling, sliding and Sectional door

10 POLE TERMINAL BLOCK (M1):

01-02 = Light of Courtesy Exit of 24Vdc. 3W max. 02-03 = N.C. contact enter photocell Low 02-04 = N.C. contact enter photocell High 05-06 = N.C. block enter (electronic block) 07-09 = N.O. button enter of OPEN 08-09 = N.O. button enter of CLOSE 09-10 = Exit 24Vdc. 500mA max. (10 = + 24V) 3 POLE TERMINAL BLOCK (M2): 11-12 = N.C. End-run enter of OPEN (12 = common) - STOP OPEN 12-13 = N.C. End-run enter of CLOSE (12 = common) - STOP CLOSE 2 POLE TERMINAL BLOCK (M3): 14-15 = Blinker exit of 24Vac. max. 25W 2 POLE TERMINAL BLOCK (M4): 19-20 = Exit Blinker 230Vac. max. 30W 4 POLE TERMINAL BLOCK (M5): R-S-T = Input 400Vac or R-S = Input 230Vac 4 POLE TERMINAL BLOCK (M6): U-V-W = Output 400Vac (or 230Vac - V=Commun) 4 POLE TERMINAL BLOCK (M7): 21-22 = Input Arial RX Radio (22 = Hold) 23-24 = Exit from RX Radio Channel 2 6 POLE TERM. BLOCK (M8): 25-26 = Input N.C. Contact MUSHROOM 27-28 = N.O. button enter of OPEN 28-29 = N.O. button enter of CLOSE 28-30 = N.O. button enter of PEDESTRIAN 2 POLE TERMINAL BLOCK (M9): 31-32 = N.C. = semi-automatic - N.O.= automatic 5 POLE TERMINAL BLOCK (M10): 33-34 = LUC = Contact enter N.O. to disable the low photocell and the DW in the last centimetres of closing (when N.C. disable). 34-35 = AP/CH = N.O. Buttom enter of OPEN/CLOSE Dynamic With SW1 - Dip 4 at ON : Dynamic = at every impulse : Open – Block – Close – Open etc.) With SW1 - Dip 4 at OFF: Dynamic = Open - Close (on end-run) 36-37 = TX24V = Supply Exit 24Vdc for photocells (for autotest) Only photocells transmitter +24Vdc. high 0V (-) low 3 POLE TERMINAL BLOCK (M11): If shunt on 16-17 = Input at 230V (Monophase or Treephase) If shunt on 17-18 = Input at 400Vac. (set of factor) = Input EARTH ExitCommand For Front Panel = Output EARTH

DIP FUNCTIONS (Dip Switch SW1)

DIP 1 : ON : LEAF DOOR FUNCTION ACTIVATED ( photocell stops movement in opening) OFF: LEAF DOOR (P. L.) DISACTIVATED DIP 2 : ON : ANTI-DRAGGING FUNCTION ACTIVATED (with low and/or hight photocell obscured, the control does not grasp the opening order) OFF : ANTI-DRAGGING DISACTIVATED DIP 3 : ON : PRESSED BUTTON FUNCTION (look at the instructions next page) OFF : PRESSED BUTTON DISACTIVATED : Automatic or Semiautomatic cycle DIP 4 : ON : DYNAMIC FUNCTION ON BUTTOM : OPEN - BLOCK - CLOSE OFF : DYNAMIC FUNCTION DISACTIVATED (Normal Cycle: Open - Close) DIP 5 : ON : THE BLINKER BLINKS DURING ALL THE CYCLE (il pulsante di blocco – 5 e 6 di M1 - lo spegne) OFF : THE BLINKER FIRST BLINK 4 SEC BEFORE CLOSING (the button of block – 5 and 6 of M1 - switches it off) DIP 6 : ON : AUTO-TEST FUNCTION DW24B ACTIVATED OFF : AUTO-TEST DW24B DISACTIVATED DIP 7: ON : AUTO-TEST FUNCTION LOW PHOTOCELL ACTIVATED OFF : AUTO-TEST LOW PHOTOCELL DISACTIVATED DIP 8 : ON : AUTO-TEST FUNCTION HIGH PHOTOCELL ACTIVATED OFF : AUTO-TEST HIGH PHOTOCELL DISACTIVATED WARNING OF FAILURE AUTOTEST : - If the low photocell does not work, the blinker advises with a blink of 2 seconds and the control does not move. - If the hight photocell does not work, the blinker advises with 2 blink of 2 seconds and the control does not move. - If the DW 24B does not work, the blinker advises with 3 blink of 2 seconds and the control does not move.

DIP (SW1) FUNCTIONS DEEPENING

- DIP 3 ON : “PRESSED BUTTON” FUNCTION ACTIVATED OPENING ORDER = OPENING WITH PRESSED BUTTON CLOSING ORDER = CLOSING WITH PRESSED BUTTON (with close pressed an order of “open” blocks the closing movement) THE PEDESTRIAN ORDER IS NOT CONNECTED DYNAMIC ORDER = OPENING WITH SELF-HOLDING AND CLOSING WITH PRESSED BUTTON At end opening, an impulse to the dynamic order closes with pressed button (closing activated, the order release for 3 sec. (before arrive at FCC) stops the function = an other impulse connects the opening. OPEN END-RUN = STOP THE OPENING CLOSE END-RUN = STOP THE CLOSING BLOCK = BLOCK THE MOVEMENT With DIP8 on ON; “A” HIGH PHOTOCELL = PHOTOCELL BLOCKS IN OPENING With DIP7 on ON; “B” LOW PHOTOCELL = PHOTOCELL BLOCKS IN CLOSING With DIP6 on ON; DW24B (edges) = DW24B BLOCKS IN CLOSING With DIP8 on OFF; “A” HIGH PHOTOCELL = PHOTOCELL NOT CONNECTED (OR DISACTIVATED) With DIP7 on OFF; “B” LOW PHOTOCELL = PHOTOCELL NOT CONNECTED With DIP6 on OFF; DW24B (edges) = DW24B NOT CONNECTED - DIP3 OFF : PRESSED BUTTON DISACTIVATED AUTOMATIC OR SEMIAUTOMATIC CYCLE - DIP1 ON : “LOW” PHOTOCELL STOP TEMPORARILY THE MOUVEMENT (stop the movement until the “low” photocell is obscurated, keep the counter of the “Work Time”). ON : “HIGH” PHOTOCELL BLOCK THE MOUVEMENT (CENTRALE BLOCKED)

Regulatin Times (Dip Swich SW2)

WORKING TIME: Dip 1 OFF min. 27 sec. MAX 50 sec. Dip 2 OFF Dip 1 OFF min. 80 sec. MAX 150 sec. Dip 2 ON Dip 1 ON min. 04 sec. MAX 30 sec. (set of factor) Dip 2 OFF Dip 1 ON min. 04 sec. MAX 150 sec. Dip 2 ON PAUSE TIME: min 01 sec. MAX 70 sec. (set of factor) With R11 shunt the max time is 200 sec. PEDESTRIAN TIME: min. 02 sec. MAX 13 sec. REVERSAL TIME: Dip 3 OFF reversal time = 0,5 sec. Dip 4 OFF Dip 3 OFF reversal time = 1 sec. (set of factor) Dip 4 ON Dip 3 ON reversal time = 2 sec. Dip 4 OFF Dip 3 ON reversal time = 4 sec. Dip 4 ON SHUNTS SET W3 - W4 – W5 – W6 – W7 = For predisposition type of Rx Radio (on costumer request) W8 Shunted: DW control not connected Free: DW control connected (insert DW24 in J3 position) W1 Shunted 1-2 (central – left) CH2 of receiver FOR PEDESTRIAN ORDER Shunted 2-3 (central – right) CH2 of receiver FOR CLOSE ORDER W2 Shunted 4-5 (central – left) CH1 of receiver FOR DYNAMIC ORDER Shunted 5-6 (central – right) CH1 of receiver FOR OPEN ORDER

DL1 (yellow led)

LIGHT (On) : DW24B in warning (contact Open) DL2 (green led) SWITCHED ON : power supply insert SWITCHED OFF : lack of supply DL3 ( red led ) SWITCHED ON : pressed OPEN order It remains lighted only during the time while it is pressed DL4 ( red led ) SWITCHED ON : presses CLOSE order It remains lighted only during the time while it is pressed DL5 ( red led ) SWITCHED ON : pressed AP/CH order (Dynamic) DL6 ( red led ) SWITCHED ON : pressed PEDESTRIAN order DL7 (yellow led ) SWITCHED ON : semi automatic cycle activated SWITCHED OFF : automatic cycle activated DL8 ( yellow led ) SWITCHED ON : present LOW PHOTOCELL (Open contact) DL9 ( yellow led ) SWITCHED ON : present HIGH PHOTOCELL (Open contact) DL10 ( yellow led ) SWITCHED ON : present button of BLOCK (Open contact) DL11 ( red led ) SWITCHED ON : present END-RUN OF OPEN (Open contact) DL12 (red led ) SWITCHED ON : present END-RUN OF CLOSE (Open contact) Functionnement Automatic Cycle: Pressing N.O. button of Open the motor will begin to move for the time determinated by the “End-run/working time” combination (P1). The control works with normally closed End-run (N.C.). With the gate opened the pause timer (It can be bypassed pressing the button of close) , after the deter- minated time (P2), will close the door. If during the pause time an object or a person crosses the photo- cell, it resets the the pause time which will start again from the beginning. We get same function, always during the pause time, giving an opening impulse. The contact of Low and Hight Photocell (N.C.) is activated only during the reclosing phase, it opens again the door if there is an obstacle. A possible temporary Block of the control can be obtained by acting on the block button (N.C.), in this case the motor will stop until the open-close button will be pressed again giving movement to the gate in the desired direction. Pedestrian Function : N.A. enter contact which operates the opening door for the time determinated by the P3 trimmer. During the reclosing phase the photocell or an impulse of Open will open the door completely. Semiautomatic Cycle (pass-pass): All the functions are the same of the automatic cycle except the pause time that is not inserted, therefore to reclose you should press the close button once again.

- The motor time of start is istantaneous when the door is on the end-run, the movement reversal time of

the door out of the end-run (and also of starting) is regulated by the Dip-switch “SW2”. Inserting the photocell contact (N.C.) in this control, control the the right functionnement otherwise the control will not close or will always be on block (Autotest). Always check the signalling leds before of every intervention. On this control it is possibile to insert (SW1 dip 2) the function anti-dragging : with close end-run ope- ned and the low and/or Hihgt photocell obscurated, an impulse of open does not give movement. In case of damage of the photocells it is possible to make the control working only with “Pressed But- ton” (SW1 dip 3) for opening and closing movement. First intervention on Control drawbacks Problem Likely Cause Solution Control does not move, switched off leds Control does not move, switched off leds Control doesn’t move, DL10 led light Control doesn’t close, DL8-9 led light Control goes on with opening or don’t close in automatic Control opens a little and then stops Control opens but does not reclose Control does not feel end-run of open and close Control gives movement only in one directon Control reverse with low photocell when the motor opens The motor does not open the door com- pletely Control close at once Control reverse the movement bru- squely Photocell stops on Open Control does not open Control does not open Times too long Wrong connection line 18V, check Fuse F5. Short-circuit on output 24Vdc. Check F5. Block contact opened photocell enter opened Open button always pressed (led DL3 or DL5 or DL6 lighted) Safety profile, block, end-run Semiautomatic function insert Wrong connection of the end-run Wrong connection of the Common wire of the end-run Wrong connection of the motor (reverse 2 phases) “Working” time too short “Pause” time short “Reversal” time short P.L. function inserted Failured of the hight or low photocell autotest Anti-dragging acrivated (SW1 Dip 2) Time Regulations SW1 Insert supply like in the scheme Disconnect the controls supplyed from the gate-opener and check wires. Check that the block is N.C. Check that the enters are N.C. Check all the enters (buttons, Rx radio, magnetic spool) Check that there are not false contacts Select function (DL7) Connect in the right way Connect in the right way Connect in the right way Increase the “Time of working” trimmer (P1) Increase the “Time of pause” trimmer (P2) Set the “Reversal Time” (SW2) Check Dip 1 (OFF) Check the photocells Check the photocells Set in the right way The Alltronic s.n.c. will not be responsabile for wrong connections and/or mishandlings of the control which will not be considered under guarantee.

The control should be installed as near the gate as possible.

2) If this is not possible, you should: Use cables with proper sizes. Never use a multiwire cable to connect either the motor or all the services (open, close, block, photocell, end-run), but ALWAYS SEPARATE THE POWER from the Low Tension (controls and securities) using more cables. In case of threephase 400V supply it is necessary to place the control near the gate in order to have the shortest way of the power wires , always separating the low from the very low tension. If it is not possible, so it is necessary to use screened cables, remembering to earth the cable screen at the two ends. 3) After every installation check, with a tester Vac., that there isn’t any induction tension on the en- ters, measuring between the earth and one end of the “Open button” terminal block. If there is an “Alternating tension” below 20—30 V (induced tension for cable passage with supply) the system is ready to be tested, otherwise it is necessary to overhaul the cable arrangement as described abo- ve. Max Loads and Maintenance The relays set on the control have a load of 9 Amp. And they must be, relating to their load, periodically checked. It is advisable to overhaul the relay contacts every 4 years, but always according to the following condi- tions: Micro 6R control 400V threephase supply Max. load permitted : 2,2kW Threephase motor cosØ = 0,7 N° of possible movement: 500.000 Micro 6R control 230V threephase or monophase supply Max. load permitted : 1,5kW Threephase motor cosØ = 0,7 N° of possible movement: 500.000 WARNING: Reducing the motor cosØ the n° of possible openings decreases (ex. with cosØ = 0,3 the number of movement is halved). Check always the values of the installed motors WARNING : The above specifications are adressed to technicians and/or qualified staff. All checks and works should be made OUTSIDE the electric and electronic details of the controls. Never forget that installations should be made according to law requirements and “Rules of good installation”. It is advisable to protect the control, at least on the upper side, if it could be subject to inclement weather. The ALLTRONIC snc states that the control has been registred. Therefore the central will be protected in all its parts by the law. It is forbidden to riproduce any part of this manual without written authorisation of the Alltronic ALLTRONIC S.N.C.—Via Torino, 84—12041 Bene Vagienna (Cuneo) - Italy