Text of the manual

Condition Monitor with integrated Gateway

for the connection of Bender devices to PROFIBUS DP and Ethernet-TCP/IP networks Software version: D472 V2.0x COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 COMTRAXX® COM465IP/COM465DP

Bender GmbH & Co. KG

P.O. Box 1161 • 35301 Gruenberg • Germany Londorfer Straße 65 • 35305 Gruenberg • Germany Tel.: +49 6401 807-0 • Fax: +49 6401 807-259 E-mail: [email protected] • www.bender.de © Bender GmbH & Co. KG All rights reserved. Reprinting only with permission of the publisher. Subject to change! Photos: Bender archives and bendersystembau archives.

Table of Contents

COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 1. Making effective use of this documentation ..................................................... 7 1.1 How to use this manual ......................................................................................................... 7 1.2 Terms used ................................................................................................................................. 8 1.3 Explanations of symbols and notes ................................................................................... 8 2. Safety instructions .................................................................................................. 9 2.1 Work on electrical installations ........................................................................................... 9 2.2 Intended use .............................................................................................................................. 9 2.3 Address configuration and termination .......................................................................... 9 2.4 Delivery conditions, guarantee, warranty and liability ........................................... 10 3. Product description ............................................................................................. 11 3.1 Scope of delivery ................................................................................................................... 11 3.2 Device features ...................................................................................................................... 11 3.2.1 Function scope of COM465IP and COM465DP Basic device (without function modules) ..................................................................... 11 3.2.2 Function module A ............................................................................................................... 12 3.2.3 Function module B .............................................................................................................. 12 3.2.4 Function module C ............................................................................................................... 13 3.2.5 Function module D* ............................................................................................................ 13 3.3 Applications ............................................................................................................................ 13 3.4 Function ................................................................................................................................... 14 3.5 Software products used ...................................................................................................... 14 3.6 Description of function ....................................................................................................... 15 3.6.1 Interfaces .................................................................................................................................. 15 3.6.2 Process image ........................................................................................................................ 16 3.6.3 List of BMS devices compatible with the COM465… .............................................. 16 3.7 BMS side of the COM465… ............................................................................................... 16 4. Installation, connection and commissioning .................................................. 17 4.1 Preliminary considerations ................................................................................................ 17 4.2 Installation and connection .............................................................................................. 18 4.3 Installing the device ............................................................................................................. 18 4.3.1 Dimensions diagram ............................................................................................................ 18

Table of Contents

4 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 4.4 Connecting the device ......................................................................................................... 19 4.5 Display and operating elements ...................................................................................... 20 4.6 COM465… web user interface .......................................................................................... 20 4.7 Commissioning of the device ............................................................................................ 20 4.7.1 Addresses and their factory settings .............................................................................. 21 4.7.2 Installing GSD file for PROFIBUS DP master (COM465DP only) ............................ 22 5. PROFIBUS DP (COM465DP only) ....................................................................... 23 5.1 PROFIBUS DP side of the COMTRAXX® COM465DP .................................................. 23 5.1.1 Cyclic data exchange ............................................................................................................ 23 5.1.2 Correct control of the timing on the COM465DP using PROFIBUS commands is necessary. ................................................................................................................................. 24 5.1.3 COM465DP communicates as "BMS master" with the PROFIBUS DP master .. 24 5.1.4 Formats of the output and input data ........................................................................... 24 5.1.5 Data access using PROFIBUS DP ...................................................................................... 25 5.1.5.1 Type 1: Requesting measured data from devices on the bus ......................... 25 5.1.5.2 Type 2: Requesting registers in devices on the bus ........................................... 26 5.1.5.3 Type 3: Writing to registers in devices on the bus .............................................. 27 5.2 Programming examples ...................................................................................................... 29 5.2.1 Type 1: Requesting measured data from devices on the bus ............................... 29 5.2.1.1 Example 1: Requesting measured value from the RCMS490-D ............................................ 29 5.2.1.2 Example 2: Requesting measured value in the event of an IRDH375 alarm .................... 31 5.2.1.3 Example 3: Requesting IRDH375 device fault ....................................................... 33 5.2.2 Type 2: Requesting registers in devices on the bus .................................................. 35 5.2.2.1 Example: Requesting a register on the RCMS490-D .......................................... 35 5.2.3 Type 3: Writing to registers in devices on the bus ..................................................... 36 5.2.3.1 Example: Writing to a register on the RCMS490-D ............................................. 36 6. Modbus TCP server .............................................................................................. 37 6.1 Data access using Modbus TCP protocol ...................................................................... 37 6.1.1 Exception code ....................................................................................................................... 37 6.1.2 Modbus requests ................................................................................................................... 37 6.1.3 Modbus responses ................................................................................................................ 38 6.1.4 Structure of the exception code ...................................................................................... 38 6.1.5 Modbus address structure for BMS devices ................................................................. 38 6.2 Modbus process image in the memory of the COM465… ..................................... 39 6.2.1 Requesting data ..................................................................................................................... 39 6.2.1.1 Modbus function code .................................................................................................. 39 6.2.1.2 How are the memory areas organised? .................................................................. 39

Table of Contents

5 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 6.2.2 Memory scheme of the process image ......................................................................... 40 6.2.2.1 BMS device address assignment on the Modbus ............................................... 40 6.2.2.2 Memory scheme of an individual BMS device ..................................................... 40 6.2.2.3 Device type ....................................................................................................................... 42 6.2.2.4 Time stamp ....................................................................................................................... 42 6.2.2.5 C = Common alarm and D = Device lost (device failure) ................................. 42 6.2.2.6 Channels 1 to 32 with analogue and/or digital values ..................................... 42 6.2.2.7 Floating point value of the BMS channels ............................................................ 43 6.2.2.8 A&T = Alarm type and test type (internal/external) .......................................... 43 6.2.2.9 R&U = Range and unit .................................................................................................. 44 6.2.2.10 Channel description ...................................................................................................... 45 6.2.2.11 Channel 33 to 64 ............................................................................................................ 46 6.2.3 Reference data records of the process image ............................................................ 47 6.2.3.1 Address assignment of the reference data record ............................................. 47 6.2.3.2 Reference value on channel 1 ................................................................................... 47 6.2.3.3 Reference value on channel 2 ................................................................................... 48 6.2.3.4 Explanation of how to access floating point values .......................................... 48 6.2.4 Channel descriptions for the process image .............................................................. 49 6.2.5 Modbus control commands .............................................................................................. 54 7. Troubleshooting ................................................................................................... 57 7.1 Damage in transit .................................................................................................................. 57 7.2 Malfunctions ........................................................................................................................... 57 7.2.1 What should be checked? .................................................................................................. 57 7.2.2 Frequently asked questions .............................................................................................. 57 7.2.3 Where do you get help? ..................................................................................................... 58 7.3 Maintenance ........................................................................................................................... 58 7.4 Cleaning ................................................................................................................................... 58 7.5 Disposal .................................................................................................................................... 58 8. Technical data ....................................................................................................... 59 8.1 Tabular data ............................................................................................................................ 59 8.2 Ordering information .......................................................................................................... 62 8.3 Standards, approvals and certificates ............................................................................ 62 INDEX ........................................................................................................................... 63

1. Making effective use of this documentation

1.1 How to use this manual This manual describes  The Condition Monitor with integrated gateway COMTRAXX® COM465IP and  The Condition Monitor with integrated gateway COMTRAXX® COM465DP with the software version stated on the front page. The functions and processes described may vary from those featured in other versions. The manual is aimed at qualified experts in electrical en- gineering and communications technology! Before using the devices please read:  This manual. It describes – the properties of the gateways COMTRAXX® COM465IP and COMTRAXX® COM465DP, – the connection of the devices – and the PROFIBUS DP interface of the COMTRAXX® COM465DP.  The manual "COMTRAXX". It describes the functions of the web user interface for Bender gateways.  The sheet "Important safety instructions for BENDER products".  The manuals for the system components. As well as, if the related interface is used:  The manual "BCOM". It describes the new Bender interface.  The instruction leaflet "BMS bus". This document must be kept in an easily accessible location near to the device. The manuals are available at: http://www.bender.de > Service & support > Download > Operating manuals. If you have any questions, please do not hesitate to contact us. For this purpose contact our Techni- cal Sales Department. We are also happy to provide on-site service. Please contact our Service De- partment for more information. Although great care has been taken in drafting this manual, it may nevertheless contain errors and mistakes. The Bender Group cannot accept any liability for injury to persons or damage to property resulting from errors or mistakes in this manual. COMTRAXX® COM465IP is also referred to in this manual as "COM465IP" for short. COMTRAXX® COM465DP is also referred to in this manual as "COM465DP" for short. The devices are called "COM465…" or "gateway" in texts that apply to both. COMTRAXX® is a registered trademark of Bender GmbH & Co. KG.

Making effective use of this documentation

8 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 1.2 Terms used This manual explains Bender-specific terms and functions in detail. Familiarisation with general specialist IT and network terminology is considered a prerequisite. These terms are therefore only explained briefly in this manual. You will find more detailed explana- tions in the related specialist literature and on the Internet. BCOM Protocol for the communication between Bender devices via an IP-based network BMS Bender measuring device interface (RS-485 interface with BMS protocol) 1.3 Explanations of symbols and notes The following terms and symbols are used to denote hazards and instructions in Bender documen- tation: This signal word indicates that there is a high risk of danger, which will result in death or serious injury if not avoided. This signal word indicates a medium risk of danger that may lead to death or serious injury if not avoided.. This signal word indicates a low level risk, which may result in minor or moder- ate injury or damage to property if not avoided.. This symbol denotes information intended to assist the user in making optimum use of the product. DANGER WARNING CAUTION

2. Safety instructions

2.1 Work on electrical installations  Compliance with applicable regulations governing work on electrical installations, and with the regulations derived from and associated with them, is mandatory. EN 50110 is of particular importance in this regard.  If the device is used in a location outside the Federal Republic of Germany, the applicable local standards and regulations must be observed. European standard EN 50110 can be used as a guide. 2.2 Intended use The gateway connects the following devices to Ethernet TCP/IP and PROFIBUS DP networks:  Bender devices with BMS bus or BCOM interface  Bender universal measuring devices PEM… with Modbus RTU or Modbus TCP. The COM465… converts alarms, measured values and statuses from the devices to the Modbus TCP and HTTP protocols. This conversion permits coupling to Modbus TCP networks as well as data dis- play and evaluation using standard web browsers. COM465DP only: The gateway transfers information from the BMS bus and BCOM interface to the PROFIBUS DP and vice versa. It is operated and configured using the web user interface integrated into the device. 2.3 Address configuration and termination To ensure the correct function of the COM465…, correct address assignment and termination is of utmost importance. Risk of fatal injury from electric shock Any work on electrical installations that is not carried out properly can lead to death and injury! ► Only skilled persons are permitted to carry out the work necessary to install, commission and run a device or system. Malfunction due to duplicated addresses! The duplicate assignment of addresses can cause serious malfunctions in the bus systems affected. ► Ensure the COM465… is correctly addressed and terminated. DANGER CAUTION

Delivery conditions, guarantee, warranty and liability

The delivery and payment conditions set out by Bender apply. The delivery and payment conditions can be obtained from Bender in printed or electronic format.

3. Product description

3.1 Scope of delivery You will receive:  The gateway COM465…  A printed quick reference guide  The manuals "COMTRAXX® COM465IP/COM465DP", "COMTRAXX" and "BCOM" as pdf files. You can obtain the manuals at: http://www.bender.de > Service & support > Download > Operating manuals  The configuration file for PROFIBUS DP: "BEND0F27.gsd" (COM465DP only) You can obtain the latest version of the file at: http://www.bender.de > Service & support > Download > Software Only registered users can download software. Please register with your e-mail address. 3.2 Device features Condition Monitor for Bender systems:  An integrated modular gateway between the Bender system and TCP/IP allows remote access via LAN, WAN or the Internet.  Features adjustable by means of the function modules.  Ethernet (10/100 MBit/s) for remote access via LAN, WAN or the Internet.  Support for devices that are connected to the internal BMS bus via BCOM, Modbus RTU or Modbus TCP  Additional to COM465DP only: An integrated gateway between the Bender system and PROFIBUS DP 3.2.1 Function scope of COM465IP and COM465DP Basic device (without function modules)  Condition Monitor with a web interface for use with Bender BMS and BCOM devices and universal measuring devices.  Supports devices that are connected: – to the internal (max. 139 devices) or external* BMS bus (max. 98 * 139 devices) – via the BCOM interface (see the BCOM operating manual) – via Modbus RTU or via Modbus TCP (max. 247 devices)  Remote display of the latest measured values, operation/alarm messages and parameters*  COM465DP only: Coupling gateway for PROFIBUS DP devices  Reading the latest subsystem measured values, operation/alarm messages from addresses 1 ... 10 via Modbus TCP  Ethernet interface with 10/100 MBit/s for remote access via LAN, WAN or the Internet

 Setting internal parameters and the configuration of Bender universal measuring devices and

energy meters.**  Time synchronisation for all assigned devices  History memory (1,000 entries)  Data loggers, freely configurable (30 * 10,000 entries)  50 data points from third-party devices (via Modbus RTU or Modbus TCP) can be assigned. *) Displaying the parameters of BMS bus devices is only possible if the gateway is connected to the in- ternal BMS bus. **) Individual parameters can be set via a web-based application and externally (via BMS/ICOM/BCOM), but NOT via Modbus or PROFIBUS. Only the parameters of assigned devices can be read; in order to change settings, function module C is required! No reports can be generated, not even for your own device. Additional to COM465DP only:  Support for external applications (e.g. visualisation programs or PLCs) by means of the PROFI- BUS DP protocol.  Reading the latest measured values, operation/alarm messages from all assigned devices. Uniform access to all assigned devices by means of PROFIBUS DP via integrated server.  Control commands: From an external application (e.g. visualisation software or PLC), com- mands can be sent to devices by means of PROFIBUS DP. 3.2.2 Function module A  Allocation of individual texts for devices, channels (measuring points) and alarms.  Device failure monitoring.  E-mail notification in the event of alarms and system faults to different users.  Configuration of e-mail notifications.*  The Report function** saves measured values and settings of assigned devices. Stored settings can be compared with the current settings of the device. The report function is available for the gateway and for every assigned Bender device. *) In version 2.0, the MS Silverlight web interface is required. **) Generating reports from BMS bus devices is only possible if the gateway is connected to the internal BMS bus. 3.2.3 Function module B  Supports external applications (e.g. visualisation programs or PLCs) by means of the Modbus TCP protocol  Reads the latest measured values, operation/alarm messages from all assigned devices. Uniform access to all assigned devices by means of Modbus TCP via integrated server.  Control commands: From an external application (e.g. visualisation software or PLC), com- mands can be sent to devices by means of Modbus TCP.  Access to alarms and measured values via SNMP protocol (V1, V2c or V3).

Function module C

 Quick and easy parameterisation of all assigned gateway devices * by means of a web browser.  The report function** documents and saves settings and measured values. Stored settings can be compared with the current settings of the device. The stored settings can be uploaded into the device again.***  The report function is available for both the gateway and each assigned Bender device. *) The parameterisation of BMS bus devices is only possible if the gateway is connected to the internal BMS bus. **) Generating reports from BMS bus devices and uploading settings from reports in BMS bus devices is only possible if the gateway is connected to the internal BMS bus. ***) In version 2.0, the MS Silverlight web interface is required. 3.2.5 Function module D*  Fast, simple visualisation without programming. Device statuses, alarms or measured values can be arranged and displayed (e.g. a spatial plan) in front of a background image. – Display an overview of several pages. Jump to another page view and back to overview page. – Graphical display of the data loggers with scaling of the time axis. – System visualisation: Several gateways (COM460IP, COM465IP, COM465DP, CP700) are dis- played on a web page. Display of common gateway alarms. Clicking on the depicted gate- way opens its web user interface. *) In version 2.0, the MS Silverlight web interface is required. Example:  To write parameters via Modbus, function modules B and C are required.  To read parameters via Modbus, function module B is required.  Parameterisation via PROFIBUS is only possible with COM465DP and function module C. 3.3 Applications  Optimum display and visualisation of device and plant statuses in the web browser  Observing and analysing compatible BENDER products (ISOMETER®, ATICS®, RCMS, EDS, Linetraxx® and MEDICS systems, universal measuring devices and energy meters)  Customised plant overview by means of an individual plant description  Notifying different users in the event of alarms  Using professional visualisation programs, which are implemented on the Modbus TCP or PROFIBUS DP protocol  Clear and simple parameterisation of devices, saving, documenting and restoring parameters  Commissioning and diagnosis of Bender systems  Remote diagnosis and maintenance

The COM465… are integrated into the existing EDP structure like PCs. After connecting to the net-

work and compatible Bender products, all system devices can be accessed from any PC using a standard web browser (e.g. Google Chrome, Mozilla Firefox, Internet Explorer). In this way, all impor- tant system information is directly available. The COM465DP has an additional connection that enables it to be integrated as a slave in PROFIBUS DP systems. The PROFIBUS master, for example a PC with a PROFIBUS card or a PLC, must be programmed so that the appropriate reactions are triggered via the COM465DP and responses are received. To achieve this, a good knowledge of PROFIBUS is required. The necessary documen- tation with the complete command syntax can be found in the chapter "PROFIBUS DP (COM465DP only)" on page 23. 3.5 Software products used You will find this chapter in the manual "COMTRAXX".

Description of function

3.6.1 Interfaces COM465… communicates with the devices and systems assigned via various interfaces:  BMS (RS-485) for Bender systems such as EDS46x/49x, RCMS46x/49x and MEDICS. COM465… can be operated as a master or as a slave. Requests are answered more quickly on operation of the COM465… as a master. The COM465… can be operated on the internal and external BMS bus.  BCOM for new and future Bender systems, e.g. ISOMETER® iso685-D.  Modbus RTU (RS-485): COM465… on operation as a master for Bender universal measuring devices PEM..3 and also PEM..5 with restricted functionality (full functionality of PEM..5 only via Modbus TCP).  Modbus TCP (Ethernet) for Bender universal measuring devices PEM..5  COM465DP only: Coupling with PROFIBUS DP. For this purpose the gateway is connected to the PROFIBUS DP network as a PROFIBUS DP slave. 120 Ω A B A B A B max. 1200 m B A 120 Ω BMS bus LAN Web- Browser Internet Firewall PC1 PC2 PC3 Web- Browser TCP/IP via ISDN, DSL, ... TCP/IP via Ethernet RJ45 10/100 Mbit/s RS485 Modbus/TCP Modbus/TCP Client OPC Modbus/TCP BACnet max. 1200 m PROFIBUS-DP (COM465DP only) PROFIBUS- Slave PROFIBUS-Master PROFIBUS- Slave PROFIBUS- Slave COM465… B A 120 Ω 120 Ω A B A B max. 1200 m Modbus/RTU PEM..3 PEM..5* PEM..5* iso685...

The gateway prepares and saves a process image from the communication with the devices as-

signed. This process image contains alarms, status information and measured values from the devic- es assigned. The gateway combines the information from the different interfaces and makes it available for:  Operation and data display via the web user interface on a PC  Transfer to external data display programs or PLCs using Modbus TCP or PROFIBUS DP. The COM465… provides a common user interface for the devices assigned via different interfaces. On this user interface each device is given an individual address by which it can be identified. BMS, BCOM and Modbus RTU devices (PROFIBUS DP devices with the COM465DP) receive the address necessary for their interface. Modbus TCP devices are assigned a virtual address. COM465DP only: The gateway is a slave on the PROFIBUS DP. For this reason only the gateway can be represented as a PROFIBUS device. 3.6.3 List of BMS devices compatible with the COM465… You will find a current list of devices on which parameters can be set at: http://www.bender.de > Products > Communication > Gateways > COMTRAXX COM465 or COM460 3.7 BMS side of the COM465… Internal and external BMS bus The majority of Bender devices communicate via the internal BMS bus. Individual devices, such as MK800, TM 800 or Bender panels can communicate via both the internal BMS bus (BMS i) and the ex- ternal BMS bus (BMS e). The COM465… is capable of communicating either via the internal BMS bus (BMS i) or the external BMS bus (BMS e). The related protocol must be set on the menu "Interface" > "BMS". If the COM465… is operated on the external bus, it is not possible to set the parameters on any other bus devices. The parameters on the COM460IP itself can, however, be set via the LAN connected. COM465… can be operated as a master or as a slave. COM465… is to be operated as a master if - Parameters are requested or changed - Or certain control commands are issued Please note that not all BMS masters can surrender their master function!

4. Installation, connection and commissioning

The BMS Ethernet gateway is normally integrated into existing LAN structures, but can also be oper- ated via a single PC on the Ethernet side. 4.1 Preliminary considerations 1. Have all the questions regarding the installation been answered by the technician responsible for the installation? 2. Will the device be operated on the internal or external BMS bus? Do you know the BMS address to be set? Can COM465… be operated as the master (BMS address 1)? If, apart from the COM465…, an alarm indicator and test combination MK800 is connected to the internal bus, the COM465… must not have the address 1 (master). You will find more detailed information on the topic of BMS, in particular about the wiring of bus devices, in the separate document "BMS bus". You can obtain this document at: http:// www.bender.de > Service & support > Download > Operating manuals. 3. Does the computer network comprise a DHCP server? Otherwise, the network data such as the IP address and subnet allocated by the person respon- sible for the electrical installation have to be set manually. 4. Ask for the IP address of the NTP server, which is required for automatic time setting. 5. Are suitable PC hardware and software available for commissioning? - System requirements (minimum): 1.6 GHz processor /512 MB RAM / Windows XP/Vista/7/10/web browser. 6. COM465DP only: Is the PROFIBUS DP address to be set known? Is a terminating resistor required? If you are familiar with the configuration of computer networks, you can carry out the connection of the COM465… yourself. Otherwise please contact your IT administrator! For initial connection, the basic configuration of the COM465… is to be under- taken outside the installation, depending on the specific situation. CAUTION

Installation, connection and commissioning

18 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 4.2 Installation and connection 4.3 Installing the device The device is suitable for the following types of installation:  DIN rail mounting according to IEC 60715 or  Screw mounting using 2 x M4 4.3.1 Dimensions diagram COM465… is in a series J460 enclosure. Risk of fatal injury from electric shock! Parts of the system are live. During installation and connection: ► Do not touch parts of the system. ► Disconnect the system from the power supply and protect the system against accidental switch-on. Risk of fatal injury and destruction due to moisture! ► The device must be installed so that it is protected against humidity. Consider the installation site When installing the device, please take into consideration that the device can only be used in locations which are protected from unauthorised entry, such as in a switchboard cabinet for example. DANGER DANGER CAUTION 107,5 40 62 33 45 14,4 11 62,9 93

Installation, connection and commissioning

19 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 4.4 Connecting the device Make the connection as follows: 1. BMS connection: Connect the terminals ABMS and BBMS (4) to the BMS bus (A to A, B to B). J-Y(St)Y min. 2x0.8 for example is a suitable cable type. If the COM465… is at the end of the BMS bus, you must switch the terminating switch on the device (7) to "ON". 1. Modbus RTU connection: Connect the terminals AMB and BMB (3) to the Modbus RTU (A to A, B to B). J-Y(St)Y min. 2x0.8 for example is a suitable cable type. If the COM465… is at the end of the bus, you must switch the terminating switch on the device (6) to "ON". 2. Establish connection with PC and BCOM: Connect Ethernet cable (RJ45) to the COM465… (5) and connect to the PC network. 3. PROFIBUS DP connection: Connect the corresponding connector on the PROFIBUS cable to the 9-pin Sub-D socket (2). If the COM465DP is at the end of the PROFIBUS DP network, you must switch the terminating switch on the PROFIBUS connector to "ON". 4. Connect power supply: Connect the terminals A1/+ and A2/- (1) to a supply of power (see nameplate). 1 Power supply: see nameplate and order information 2 PROFIBUS DP connection (COM465DP only) 3 Modbus RTU interface Plug X1 4 BMS bus (Bender measuring device interface) 5 Ethernet connection (RJ45) for the connection to the PC network as well as to BCOM Plug X2 6 Modbus RTU terminating resistor switch 7 BMS bus terminating resistor switch 8 Micro-USB interface (currently without function) Plug X3 9 Mini-HDMI interface (currently without function) Plug X4 COMTRAXX A1/+ X1 X2 X3 X4 A2/- ON PROFIBUS ETHERNET/IP MODBUS/RTU BMS PROFIBUS DP COM465DP 1 4 3 2 OFF ON RMB OFF ON RBMS 6 5 9 8 7

Installation, connection and commissioning

20 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 The power supply must be protected using a 6 A fuse. 4.5 Display and operating elements 4.6 COM465… web user interface The device has a web user interface for configuring and operating the device. The many features of the web user interface are described in the manual "COMTRAXX". 4.7 Commissioning of the device 1. Switch on the supply voltage: When the device is supplied with power, all LEDs initially illuminate briefly. During the start process the "ON" LED flashes. After a successful start, the "ON" LED then illuminates continu- ously. The device is now ready for operation. 2. Start web user interface: – Open a web browser. – Type the following IP address to open the web interface for the gateway: –> If your PC is in a 192.168.0.0 IT subnet, you can connect to the gateway using the factory-set IP address, 192.168.0.254. –> If your PC is in a different subnet, you must disconnect the PC from your network. Connect the gateway directly to your PC. You can open the web user interface using the second pre-defined IP address: 169.254.0.1. For this purpose, DHCP must be enabled on the PC. You can configure the IP address for the gateway as required in the web user interface. COM465DP-24V, COM465IP-24V Consider connection polarity! COM465DP-230V, COM465IP-230V Connection polarity is arbitrary. Item Function 1 "ON" LED: Flashes during the start process. The LED illuminates continuously as soon as the device is ready for operation. 2 LEDs indicate activity on the various interfaces. The LED "PROFI- BUS" exists only in the COM465DP. On Profibus Ethernet/IP Modbus/RTU BMS 1 2 ON ETHERNET/IP MODBUS/RTU BMS COM465DP COM465IP

Installation, connection and commissioning

21 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 3. Configure: As a minimum configure all the address data for the gateway. Always configure the BCOM interface (system name, subsystem, device address). The BCOM device address is, at the same time, the address on the internal BMS bus. 4. Integrate devices into the system: – BMS devices are detected automatically – BCOM devices are detected automatically – Modbus devices need to be configured. Start the alternative web user interface (with Silver- light). Then select "Tools" > "Modbus" > "Manage devices". 5. Test connection Connect the gateway to your PC network again. Start the web user interface. You can now make all other settings (specific texts, e-mail notifications etc.). 4.7.1 Addresses and their factory settings The COM465… is supplied with the following factory settings: The settings can be changed using the web user interface. Risk of duplicate addresses if BCOM system name is not changed. The factory setting for the system name on all Bender devices is "SYSTEM". If sev- eral systems are established in the same network, there is a risk that addresses will be assigned more than once. ► Therefore always assign a new BCOM system name. Parameter Factory setting IP address 192.168.0.254 Connection can always be made using the pre-defined IP address (e.g. for commissioning) 169.254.0.1 Subnet mask 255.255.0.0 Default gateway 192.168.0.1 DNS 194.25.2.129 DHCP off toff Timeout for DCHP address assignment 30 s BMS address 2 BMS protocol BMS i BCOM system name SYSTEM Subsystem address 1 BCOM device address 2 PROFIBUS DP address 3

Installation, connection and commissioning

22 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 4.7.2 Installing GSD file for PROFIBUS DP master (COM465DP only) A PROFIBUS DP master requires the device master data (Geräte-Stamm-Daten - GSD) for its slave components distributed in the automation system. Accordingly, you must install the GSD file on the master. It describes the properties of the COM465DP in a standardised format. You can obtain the latest GSD file at: http://www.bender.de > Service & support > Download > Software 1. Select the destination folder to which the GSD file is to be copied. For the exact destination please see the documentation for the program you want to use to program the PROFIBUS mas- ter. 2. Also copy the file BEND0F27.gsd to the folder created for the device master data.

5. PROFIBUS DP (COM465DP only)

5.1 PROFIBUS DP side of the COMTRAXX® COM465DP The gateway and its PROFIBUS address are to be made known to the PROFIBUS master. For this pur- pose you will need the file BEND0F27.gsd (see "Scope of delivery" on page 11) A connection from Bender systems with BMS bus and BCOM to PROFIBUS DP using COM465DP can be necessary for various reasons:  A PROFIBUS DP device is to react to an event in the BMS world  A BMS bus device is to react to an event in the PROFIBUS DP world  The data on the BMS bus are to be displayed, evaluated or depicted together with PROFIBUS DP data on a PC with PROFIBUS DP software  The data on the BMS bus are to be displayed in the software for a building services manage- ment system that has a PROFIBUS DP interface  The devices on the BMS side are to be configured via a PC with PROFIBUS DP interface  Certain actions on the BMS side are to be controlled via PROFIBUS DP. The COM465DP is a PROFIBUS DP slave as per IEC 61158/IEC 61784. This means that there must al- ways be at least one master on the PROFIBUS side.  COM465DP = PROFIBUS DP V0 slave  PROFIBUS DP address = 1…125 (factory setting: 3)  Data transmission rate = 9.6 kbit/s to 1.5 Mbit/s, the baud rate is detected automatically 5.1.1 Cyclic data exchange In this manual the Profibus is considered in principle from the point of view of a PROFIBUS DP master. The communication on the PROFIBUS DP is cyclic. During this process the PROFIBUS master polls all PROFIBUS slaves in sequence using a query-and-response sequence. A query is represented by the output data from the master. The COM465DP then responds to the master. The response is represented by the input data to the master. Due to the large amount of data on the BMS side, all these data cannot be transferred simultaneously during the cyclic exchange of data. The PROFIBUS master must therefore define precisely which data it wants to receive from the BMS device. The assignment between input data and output data, that is between request and response, is de- fined via an ID no. The PROFIBUS DP programmer must ensure the next ID no. is output as soon as the previous request has been answered. COM465DP is always operated as a slave in the PROFIBUS DP side.

PROFIBUS DP (COM465DP only)

24 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 5.1.2 Correct control of the timing on the COM465DP using PROFIBUS commands is necessary. Due to the different times the various devices take to respond to the commands, it may occur that responses from previous requests arrive between a request from the PROFIBUS DP master and the related response from the slave, (COM465DP). For this reason it is very important to compare the ID numbers of the query and the response. 5.1.3 COM465DP communicates as "BMS master" with the PROFIBUS DP master If you have given the COM465DP the BMS address 1, the device operates as a BMS master. In this way it can be used as a master for all BMS systems. Along with requesting alarm and operating messages, it is also possible to issue switching commands and parameter settings directly. 5.1.4 Formats of the output and input data The communication is to be considered from the point of view of the PROFIBUS DP. The PROFIBUS DP master sends to the COM465DP (the PROFIBUS slave) a byte sequence, the output data. As a response the PROFIBUS DP master receives back a byte sequence, the input data. The assign- ment between input bytes and output bytes, that is between request and response, is defined via an ID no. The PROFIBUS DP programmer must ensure the next ID no. is output as soon as the previous request has been answered. For the output data a length of 11 bytes is defined and for the input data a length of 10 bytes. The PROFIBUS programmer is responsible for incrementing the ID no. in compli- ance with system requirements. Incorrect control of the timing will result in the misinterpretation of the responses (PROFIBUS input data)! Take into account the time required to execute the related commands!

PROFIBUS DP (COM465DP only)

25 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 5.1.5 Data access using PROFIBUS DP PROFIBUS DP offers three methods for reading or writing data: – Type 1: Requesting measured data from devices on the bus – Type 2: Requesting registers in devices on the bus – Type 3: Writing to registers in devices on the bus 5.1.5.1 Type 1: Requesting measured data from devices on the bus Request to the gateway: Response from the gateway: Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 Byte 10 ID Msg type System Device Channel 0x00 0x00 0x00 0x00 0x00 0x00 Byte 0: Sequential ID no.: Must be set by the person programming the PROFIBUS DP master. The ID no. must be incremented for the next request as soon as a response has been received to the previous request. Byte 1: Message type: For this request always 0x01 Byte 2: Subsystem address: Depending on how the device is operated, either the BCOM or the external BMS bus address (default for usage on the internal BMS bus: 2) Byte 3: Device address: The internal BMS or BCOM address. Depends on which interface is used to integrate the device. Byte 4: Channel: The channel that is to be requested. Byte 5-10: Always 0x00 Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 ID Data value high high Data value high low Data value low high Data value low low Alarm & test Range & unit Descrip- tion high Descrip- tion low 0xFF Byte 0: Sequential ID no. Byte 1-4: Measured values: The data are output as a floating point value. Byte 5: Alarm type and test type For details see "A&T = Alarm type and test type (internal/external)" on page 43. Alarm type & test Test ext. 7 Test int. 6 State 5 Res. 4 Res. 3 Alarm 2 1 0

PROFIBUS DP (COM465DP only)

26 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 Response from the gateway in the event of an error: 5.1.5.2 Type 2: Requesting registers in devices on the bus A register has a size of one word. Byte 6: Structure of the byte: Range and unit. For details see "R&U = Range and unit" on page 44. Byte 7: Description high: The high byte of the measured value description. For details see "Channel descriptions for the process image" on page 49. Byte 8: Description low: The low byte of the measured value description. For details see "Channel descriptions for the process image" on page 49. Byte 9: Always 0xFF Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 ID 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 Byte 10 ID Msg type System Device Number of registers Address high Address low 0x00 0x00 0x00 0x00 Byte 0: Sequential ID no.: Must be set by the person programming the PROFIBUS DP master. The ID no. must be incremented for the next request as soon as a response has been received to the previous request. Byte 1: Message type: For this request always 0x02 Byte 2: Subsystem address: Depending on how the device is operated, either the BCOM or the external BMS bus address (default for usage on the internal BMS bus: 2) Byte 3: Device address: The internal BMS address Byte 4: Number of registers: Number of registers to be read (min: 1, max: 4) Byte 5: Register start address high byte: Start register starting from which the data are read Byte 6: Register start address low byte: Start register starting from which the data are read Byte 7-10: Always 0x00 Range & unit Range validity 7 6 State 5 Unit 4 3 2 1 0

PROFIBUS DP (COM465DP only)

27 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 Response from the gateway: Response from the gateway in the event of an error: 5.1.5.3 Type 3: Writing to registers in devices on the bus Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 ID Numb er of regis- ters Reg. 0 high Reg. 0 low Reg. 1 high Reg. 1 low Reg. 2 high Reg. 2 low Reg. 3 high Reg. 3 low Byte 0: Sequential ID no. Byte 1: Number of registers: Number of registers read (min: 1, max: 4) Byte 2-9: Register values: The data from the registers read. Bytes not requested are filled with 0xFF. Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 ID 0 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 Byte 10 ID Msg type System Device Number of regis- ters Address high Address low Reg. 0 high Reg. 0 low Reg. 1 high Reg. 1 low Byte 0: Sequential ID no.: Must be set by the person programming the PROFIBUS DP master. The ID no. must be incremented for the next request as soon as a response has been received to the previous request. Byte 1: Message type: For this request always 0x03 Byte 2: Subsystem address: Depending on how the device is operated, either the BCOM or the external BMS bus address (default for usage on the internal BMS bus: 2) Byte 3: Device address: The internal BMS address Byte 4: Number of registers: Number of registers to be written (min: 1, max: 2) Byte 5: Register start address high byte: Start register starting from which the data are written. Byte 6: Register start address low byte: Start register starting from which the data are written. Byte 7-10: Number of register values to be written: Contents that are to be written to the register. If only one register is written, 0xFF must be entered in the bytes 9 and 10.

PROFIBUS DP (COM465DP only)

28 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 Response from the gateway: Response from the gateway in the event of an error: Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 ID Number of regis- ters 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF Byte 0: Sequential ID no. Byte 1: Number of registers: Number of registers written (min: 1, max: 2) Byte 2…9: Always 0xFF Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 ID 0 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF

PROFIBUS DP (COM465DP only)

29 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 5.2 Programming examples The PROFIBUS master is to be informed of the necessary configuration data for the PROFIBUS DP us- ing the device master data file BEND0F27.gsd before executing the program. You can download the latest gsd file from the following address on our web site: http://www.bender.de > Service & support > Download > Software 5.2.1 Type 1: Requesting measured data from devices on the bus 5.2.1.1 Example 1: Requesting measured value from the RCMS490-D The RCMS490-D has the BMS address 2, channel 1 is requested. It has the measured value 200.13 mA. Request to the gateway For an explanation of the protocol structure see "Type 1: Requesting measured data from devices on the bus" on page 25. Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 Byte 10 ID Msg type System Device Channel 0x00 0x00 0x00 0x00 0x00 0x00 0x01 0x01 0x02 0x02 0x01 0x00 0x00 0x00 0x00 0x00 0x00 Byte 0: Sequential ID no. Byte 1: Message type: For this request always 0x01 Byte 2: Subsystem address: 2 Byte 3: BMS device address: 2 Byte 4: Channel: 1 Byte 5-10: Always 0x00

PROFIBUS DP (COM465DP only)

30 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 Response from the gateway: For an explanation of the protocol structure see "Type 1: Requesting measured data from devices on the bus" on page 25. Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 ID Data value high high Data value high low Data value low high Data value low low Alarm & test Range & unit Descrip- tion high Descrip- tion low 0xFF 0x01 0x3E 0x4C 0xEE 0xE1 0x00 0x03 0x00 0x4B 0xFF Byte 0: Sequential ID no. Byte 1-4: Floating point value = 0.20013 Byte 5: Alarm type and test type = 0x00 (no alarm) Byte 6: Structure of the byte: Range and unit = 0x03 (Ampere) Byte 7-8: 0x4B = Residual current Byte 9: 0xFF Alarm type & test Test ext. 0 7 Test int. 0 6 State 0 5 Res. 0 4 Res. 0 3 Alarm 0 0 0 2 1 0 Range & unit Range validity 0 7 0 6 State 0 5 Unit 0 0 0 1 1 4 3 2 1 0

PROFIBUS DP (COM465DP only)

31 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 5.2.1.2 Example 2: Requesting measured value in the event of an IRDH375 alarm The IRDH375 has the BMS address 3, channel 1 is requested. An insulation fault with the measured value 5 kΩ has occurred (alarm). Request to the gateway For an explanation of the protocol structure see "Type 1: Requesting measured data from devices on the bus" on page 25. Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 Byte 10 ID Msg type System Device Channel 0x00 0x00 0x00 0x00 0x00 0x00 0x02 0x01 0x02 0x03 0x01 0x00 0x00 0x00 0x00 0x00 0x00 Byte 0: Sequential ID no. Byte 1: Message type: For this request always 0x01 Byte 2: Subsystem address: 2 Byte 3: BMS device address: 3 Byte 4: Channel: 1 Byte 5-10: Always 0x00

PROFIBUS DP (COM465DP only)

32 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 Response from the gateway: For an explanation of the protocol structure see "Type 1: Requesting measured data from devices on the bus" on page 25. Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 ID Data value high high Data value high low Data value low high Data value low low Alarm & test Range & unit Descrip- tion high Descrip- tion low 0xFF 0x02 0x45 0x9C 0x40 0x00 0x04 0x02 0x00 0x47 0xFF Byte 0: Sequential ID no. Byte 1-4: Floating point value = 5000 Byte 5: Alarm type and test type = 0x04 (alarm) Byte 6: Structure of the byte: Range and unit = 0x02 (Ω) Byte 7-8: 0x47 = Insulation fault Byte 9: 0xFF Alarm type & test Test ext. 0 7 Test int. 0 6 State 0 5 Res. 0 4 Res. 0 3 Alarm 1 0 0 2 1 0 Range & unit Range validity 0 7 0 6 State 0 5 Unit 0 0 0 1 0 4 3 2 1 0

PROFIBUS DP (COM465DP only)

33 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 5.2.1.3 Example 3: Requesting IRDH375 device fault The IRDH375 has the BMS address 3, channel 4 is requested. There is an "earth connection" device fault. Request to the gateway For an explanation of the protocol structure see "Type 1: Requesting measured data from devices on the bus" on page 25. Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 Byte 10 ID Msg type System Device Channel 0x00 0x00 0x00 0x00 0x00 0x00 0x03 0x01 0x02 0x03 0x04 0x00 0x00 0x00 0x00 0x00 0x00 Byte 0: Sequential ID no. Byte 1: Message type: For this request always 0x01 Byte 2: Subsystem address: 2 Byte 3: BMS device address: 3 Byte 4: Channel: 4 Byte 5-10: Always 0x00

PROFIBUS DP (COM465DP only)

34 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 Response from the gateway: For an explanation of the protocol structure see "Type 1: Requesting measured data from devices on the bus" on page 25. Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 ID Data value high high Data value high low Data value low high Data value low low Alarm & test Range & unit Descrip- tion high Descrip- tion low 0xFF 0x03 0x42 0xCC 0x00 0x00 0x02 0x1E 0x00 0x66 0xFF Byte 0: Sequential ID no. Byte 1-4: Floating point value = 102 (earth connection) Byte 5: Alarm type and test type = 0x02 (device fault) Byte 6: Structure of the byte: Range and unit = 0x1E (code) Byte 7-8: 0x66 = Earth connection Byte 9: 0xFF Alarm type & test Test ext. 0 7 Test int. 0 6 State 0 5 Res. 0 4 Res. 0 3 Alarm 0 1 0 2 1 0 Range & unit Range validity 0 7 0 6 State 0 5 Unit 1 1 1 1 0 4 3 2 1 0

PROFIBUS DP (COM465DP only)

35 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 5.2.2 Type 2: Requesting registers in devices on the bus 5.2.2.1 Example: Requesting a register on the RCMS490-D The RCMS490-D has the BMS address 2. The "Prewarning" menu item is requested. It has the value "50 %". A register has a size of one word. Request to the gateway: Response from the gateway: Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 Byte 10 ID Msg type System Device Number of registers Address high Address low 0x00 0x00 0x00 0x00 0x04 0x02 0x02 0x02 0x02 0x22 0x06 0x00 0x00 0x00 0x00 Byte 0: Sequential ID no. Byte 1: Message type: For this request always 0x02 Byte 2: Subsystem address: 2 Byte 3: BMS device address: 2 Byte 4: Number of registers: 2 Byte 5: Register start address high byte: 0x22 Byte 6: Register start address low byte: 0x06 Byte 7-10: Always 0x00 Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 ID Numb er of regis- ters Reg. 0 high Reg. 0 low Reg. 1 high Reg. 1 low Reg. 2 high Reg. 2 low Reg. 3 high Reg. 3 low 0x04 0x02 0x42 0x48 0x00 0x00 0xFF 0xFF 0xFF 0xFF Byte 0: Sequential ID no. Byte 1: Number of registers: 2 Byte 2 Register 0 high byte: 0x42 Floating point value 50 = Prewarning 50 % Byte 3 Register 0 low byte: 0x48 Byte 4 Register 1 high byte: 0x00 Byte 5 Register 1 low byte: 0x00 Byte 6-9 0xFF

PROFIBUS DP (COM465DP only)

36 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 5.2.3 Type 3: Writing to registers in devices on the bus 5.2.3.1 Example: Writing to a register on the RCMS490-D The RCMS490-D has the BMS address 2. The "Prewarning" menu item is written. It has the value "50 %". The value is changed to "60 %". A register has a size of one word. Request to the gateway: Response from the gateway: Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 Byte 10 ID Msg type System Device Number of registers Address high Address low Reg. 0 High Reg. 0 Low Reg. 1 High Reg. 1 Low 0x05 0x03 0x02 0x02 0x02 0x22 0x06 0x42 0x70 0x00 0x00 Byte 0: Sequential ID no. Byte 1: Message type: For this request always 0x03 Byte 2: Subsystem address: 2 Byte 3: BMS device address: 2 Byte 4: Number of registers: 2 Byte 5: Register start address high byte: 0x22 Byte 6: Register start address low byte: 0x06 Byte 7 Register 0 high byte: 0x42 Floating point value 60 = Prewarn- ing 60 % Byte 8 Register 0 low byte: 0x70 Byte 9 Register 1 high byte: 0x00 Byte 10 Register 1 low byte: 0x00 Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 ID Numb er of regis- ters 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0x05 0x02 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF Byte 0: Sequential ID no. Byte 1: Number of registers: 2 Byte 2-9 0xFF

6. Modbus TCP server

6.1 Data access using Modbus TCP protocol Requests are sent to the Modbus TCP server in the COM465… using function code FC4 (read input register). The server generates a function-related response and sends it to the Modbus client. 6.1.1 Exception code If a request cannot be answered for whatever reason, the server sends a so-called exception code with which possible faults can be narrowed down. 6.1.2 Modbus requests The required words of the process image can be read from the input registers in the COM465… us- ing the function code FC4. For this purpose, the start address and the number of registers to be read need to be entered. Example: The words 0 and 1 are to be read from the input registers 0x100 and 0x101. Exception code Description 0x01 Impermissible function 0x02 Impermissible data access 0x03 Impermissible data value 0x04 Slave device error 0x05 Acknowledgement of receipt (response delayed) 0x06 Request not accepted (repeat request, if necessary) 0x08 Memory: parity error 0x0A Gateway path not available 0x0B Gateway error Byte Name Example Byte 0, 1 Transaction identifier 0x0000 Byte 2, 3 Protocol identifier 0x0000 Byte 4, 5 Length field 0x0006 Byte 6 Unit identifier Subsystem address assignment. 0x01 (corresponds to the subsystem address 1), external BMS bus Byte 7 MODBUS function code 0x04 Byte 8, 9 Device address (BMS int * 0x100) Device address assign- ment. 0x0100 (corresponds to the device address 1) Byte 10, 11 Number of words 0x0002

Modbus TCP server

38 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 6.1.3 Modbus responses The responses consist of 2 bytes per register. The MSB is the first byte. 6.1.4 Structure of the exception code 6.1.5 Modbus address structure for BMS devices Byte Name Example … … … Byte 7 MODBUS function code 0x04 Byte 8 Byte count 0x04 Byte 9, 10 Value register 0 0x1234 (fictitious value) Byte 11, 12 Value register 1 0x2345 (fictitious value) Byte Name Example … … … Byte 7 MODBUS function code 0x84 Byte 8 Exception code 0x01 or 0x02 Function Address range Number of bytes Number of words Device type 0x00…0x09 20 bytes 10 words Time stamp 0x0A…0x0D 8 bytes 4 words Common alarm 0x0E (high byte) 1 byte 0.5 words No BMS bus connection 0x0E (low byte) 1 byte 0.5 words Not used 0x0F 2 bytes 1 word Channel 1…32 0x10…0x8F 32 x 8 bytes 128 words Alarm and test Channel 33…64 0x90…0xFC 218 x 8 bytes 109 words

Modbus TCP server

39 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 6.2 Modbus process image in the memory of the COM465… The device holds a process image in memory. This image represents the current statuses and values of up to 150 BMS devices for each monitored internal BMS bus. 6.2.1 Requesting data 6.2.1.1 Modbus function code The memory in the COM465… can be read using the Modbus function 4 "Read Input Registers". The volume of the data requested depends on the number of bytes selected in the Modbus client used. Up to 125 words (0x7D) can be read with a single request. An individual addressable byte, such as the set bit for a saved common alarm, can also be read. 6.2.1.2 How are the memory areas organised? The assignment of the memory addresses and the associated memory content for one subsystem is described below. Please refer also to the manual "BCOM", which provides information about the en- tire addressable system. Memory utilisation Start address End of memory area Size of memory area Reference values for test purposes 0x0000 0x00FF 0x0100 Process image 0x0100 0x95FF 0x9500 Not used 0x96FF 0xFFFF 0x6900 For some Modbus clients an offset of 1 must be added to the register addresses. Example: process image start address = 0x0101. CAUTION

Modbus TCP server

40 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 6.2.2 Memory scheme of the process image 6.2.2.1 BMS device address assignment on the Modbus As illustrated in the table, the Modbus start address for the respective process image is derived from the BMS device address. 256 (0x100) words or 512 bytes are reserved for each BMS device. They con- tain all the information requested and transmitted from the BMS bus. Table 6.1: Modbus start address for each BMS device for which a request can be sent. 6.2.2.2 Memory scheme of an individual BMS device BMS devices can feature various types of analogue and/or digital channels. Please take into consid- eration that there are device-specific differences:  BMS devices usually feature 12 channels  MK800/TM800 supports up to 64 digital channels in the master mode  The channels 33 to 64 transmit digital messages only Use the tables on page 40 and page 41 to determine the start address to request the following de- vice parameters:  Device type  Time stamp  Common alarm  Device error  BMS channel Modbus address ranges of the process images in the memory BMS Device address Word HiByte LoByte 00 … FF 1 0x01 Device 1 2 0x02 Device 2 3 0x03 Device 3 … … … 32 0x20 Device 32 … … … 150 0x96 Device 150

Modbus TCP server

41 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 Example: In our example, data are to be requested from channel 2 of the device with BMS address 3. How is the start address determined to send the request for the channel? In our example, the relevant cells in the table are marked in bold. 1. For BMS device address 3 the first part of the address, 0x03 (high byte), is taken from table 6.1. 2. For channel 2 the second part of the address, 0x14 (low byte), is taken from table 6.2. For the number of words to be requested the number 4 is taken from the same table: (0x14 to 0x17 = 0x04). 3. The start address 0x0314 is formed from the high byte and low byte. Table 6.2: Modbus address assignment of the channels in a BMS device; Hex representation: horizontal = units, vertical = sixteens Abbreviations for memory contents: C = Common alarm D = Device lost (device failure) R. = Reserved Memory image of a BMS device LoByte 0 1 2 3 4 5 6 7 8 9 A B C D E F 0x00 --------------------------- Device type ---------------------------- ------ Time stamp ------ C D R. 0x10 Channel 1 Channel 2 Channel 3 Channel 4 0x20 Channel 5 Channel 6 Channel 7 Channel 8 0x30 Channel 9 Channel 10 Channel 11 Channel 12 0x40 Channel 13 Channel 14 Channel 15 Channel 16 0x50 Channel 17 Channel 18 Channel 19 Channel 20 0x60 Channel 21 Channel 22 Channel 23 Channel 24 0x70 Channel 25 Channel 26 Channel 27 Channel 28 0x80 Channel 29 Channel 30 Channel 31 Channel 32 0x90 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 0xA0 R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. 0xB0 R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. 0xC0 R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. 0xD0 R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. 0xE0 R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. 0xF0 R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R. R.

Modbus TCP server

42 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 A detailed description of the data formats for the device type, time stamp etc. is given below. 6.2.2.3 Device type The device type is set using a BMS bus scan. 6.2.2.4 Time stamp The time stamp is set according to a datagram received from a transmitting device. 6.2.2.5 C = Common alarm and D = Device lost (device failure) The common alarm bit is set as soon as an alarm status from the respective BMS device is detected. The device error bit is set when communication with the respective BMS device is no longer possible. 6.2.2.6 Channels 1 to 32 with analogue and/or digital values Every analogue BMS device channel can contain alarm messages, operating messages, measured values, test messages and descriptive text. Both analogue and digital information can be transmit- ted. AT&T = Alarm type and test type (internal/external) R&U = Range and unit For details on the channel description refer to chapter "6.2.4 ". Word 0x00 0x01 0x02 0x03 0x04 0x05 0x06 0x07 0x08 0x09 ASCII text, 10 words/20 bytes Word 0x0A 0x0B 0x0C 0x0D HiByte LoByte HiByte LoByte HiByte LoByte HiByte LoByte Year YY Month MM Day TT Hour hh Minute mm Second ss Reserved Word 0x0E HiByte LoByte C D Common alarm, 1 byte: LSB = 0 or 1 Device error, 1 byte: LSB = 0 or 1 Word 0x00 0x01 0x02 0x03 HiByte LoByte HiByte LoByte HiByte LoByte HiByte LoByte Floating point value AT&T R&U Channel description

Modbus TCP server

43 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 6.2.2.7 Floating point value of the BMS channels Representation of the bit order for processing analogue measured values according to IEEE 754 S = Sign E = Exponent M = Mantissa 6.2.2.8 A&T = Alarm type and test type (internal/external) The alarm type is coded by the bits 0 to 2. The bits 3 and 4 are reserved and always have the value 0. Bit 5 usually has the value 0 and represents the digital value of the status This column is relevant for the SMI472 only. Bit 6 or 7 are usually set when an internal or external test has been completed. Other values are reserved. The complete byte is calculated from the sum of the alarm type and the test type. Word 0x00 0x01 Byte HiByte LoByte HiByte LoByte Bit 31 30 24 23 22 16 15 8 7 0 S E E E E E E E E M M M M M M M M M M M M M M M M M M M M M M M Bit 7 6 5 4 3 2 1 0 Meaning Test external Test internal Status Reserved Reserved Alarm Error Alarm type X X X X X 0 0 0 No alarm X X X X X 0 0 1 Prewarning 0 0 X X X 0 1 0 Device error X X X X X 0 1 1 Reserved X X X X X 1 0 0 Alarm (yellow LED), e.g. insulation fault X X X X X 1 0 1 Alarm (red LED) X X X X X 1 1 0 Reserved X X X X X … … … Reserved X X X X X 1 1 1 Reserved Test 0 0 X X X X X X No test 0 1 X X X X X X Internal test 1 0 X X X X X X External test

Modbus TCP server

44 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 6.2.2.9 R&U = Range and unit The unit is coded in the bits 0 to 4. The bits 6 and 7 describe the range of validity of a value. Bit 5 is reserved. The whole byte is calculated from the sum of the unit and the range of validity. Caution! If the unit byte refers to CODE, the recorded value or status will result in a text message. The content of this text message is listed in the table on page 45 or page 49. The floating point value contains an internal CODE but no valid measured value. Bit 7 6 5 4 3 2 1 0 Meaning Unit X X X 0 0 0 0 0 Invalid (init) X X X 0 0 0 0 1 No unit X X X 0 0 0 1 0 Ω X X X 0 0 0 1 1 A X X X 0 0 1 0 0 V X X X 0 0 1 0 1 % X X X 0 0 1 1 0 Hz X X X 0 0 1 1 1 Baud X X X 0 1 0 0 0 F X X X 0 1 0 0 1 H X X X 0 1 0 1 0 °C X X X 0 1 0 1 1 °F X X X 0 1 1 0 0 Second X X X 0 1 1 0 1 Minute X X X 0 1 1 1 0 Hour X X X 0 1 1 1 1 Day X X X 1 0 0 0 0 Month X X X … … … … … Reserved X X X 1 1 1 1 0 CODE X X X 1 1 1 1 1 Reserved X X X … … … … … Reserved X X X 1 1 1 1 1 Reserved Range of validity 0 0 X X X X X X True value 0 1 X X X X X X True value is smaller 1 0 X X X X X X True value is larger 1 1 X X X X X X Invalid value

Modbus TCP server

45 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 6.2.2.10 Channel description A code with the associated descriptive text is available for each channel. The table above only shows an extract from the texts. For a complete list of the available codes or texts refer to page 49. Word 0x03 deci- mal Meaning Byte HiByte LoByte Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Alarms and warnings 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Reserved 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 Insulation fault 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 2 Overload 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 3 Overtemperature 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 4 Failure Line 1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 5 Failure Line 2 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 6 Insulation OP light 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 7 Reserved 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 8 Distribution board failure 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1 9 Oxygen 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 0 10 Vacuum 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 1 11 Anaesthetic gas 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 12 Compressed air 5 bar … … … … … … … … … … … … … … … … … …

Modbus TCP server

46 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 6.2.2.11 Channel 33 to 64 The BMS channels 33 to 64 only provide digital information. The information is coded as an alarm or message type or test type (internal, external). The coding is similar to the data format AT&T for the channels 1 to 32, with the exception of the ad- ditional bit 4. This is used for coding device errors, e.g. connection faults or internal device errors. Bit 7 6 5 4 3 2 1 0 Meaning Test external Test internal Status Reserved Reserved Alarm Error Alarm type X X X X X 0 0 0 No alarm X X X X X 0 0 1 Prewarning 0 0 0 X X 0 1 0 Device error X X X X X 0 1 1 Reserved X X X X X 1 0 0 Alarm (yellow LED), e.g. insulation fault X X X X X 1 0 1 Alarm (red LED) X X X X X 1 1 0 Reserved X X X X X … … … Reserved X X X X X 1 1 1 Reserved Test 0 0 X X X X X X No test 0 1 X X X X X X Internal test 1 0 X X X X X X External test

Modbus TCP server

47 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 6.2.3 Reference data records of the process image To make it easier to check the configuration and the Modbus TCP data access to BMS devices, COM465… provides a reference data record at the virtual BMS address 0. Special features of the Modbus communication are the byte offset and the word and byte order in the memory (Big Endian). At the end of this chapter, a few examples of correct configuration are giv- en, which might be helpful. 6.2.3.1 Address assignment of the reference data record As shown in the following table, the Modbus start address for access to the reference data record is derived from BMS device address 0. Table 6.3: Start addresses for the reference data record request The start addresses provide the following reference values:  0x0000: TEST (device type)  0x000E: 1 (common alarm, LSB of the high byte is set)  0x0010: 230 V undervoltage (reference value on channel 1)  0x0014: 12.34 A overcurrent (reference value on channel 2) 6.2.3.2 Reference value on channel 1 The following reference value is stored in this channel: 230.0 V undervoltage Table 6.4: Reference data stored in channel 1 A real BMS device cannot have BMS address 0! Address 0 only serves to simulate data access. Modbus addresses for reference data record Virtual BMS device address Word LoByte 00 0E 10 14 0 HiByte 0x00 Device type Common alarm Channel 1 Channel 2 Word 0x10 0x11 0x12 0x13 HiByte LoByte HiByte LoByte HiByte LoByte HiByte LoByte 0x43 0x66 0x00 0x00 0x00 0x04 0x00 0x4D Floating point value AT&T R&U Description 230.0 No/No Volt Undervoltage CAUTION

Modbus TCP server

48 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 6.2.3.3 Reference value on channel 2 The following reference value is stored in this channel: 12.34 A Table 6.5: Reference data stored in channel 2 6.2.3.4 Explanation of how to access floating point values The test value 12.34 can be read out via Modbus TCP using Modbus function 4 at the address 0x0014. The test value has a size of 2 words. Proceed as follows: 1. Determine the correct byte offset Interpreting both words as unsigned integer values should result in the following values: Word 1 with address 0x14: unsigned integer value => 16709 (0x4145) Word 2 with address 0x15: unsigned integer value => 28836 (0x70A4) 2. Determine the correct byte or word swap There are four different combinations of swapping. The only correct value is 12.34. All swapping combinations are represented in the following table. Word 0x14 0x15 0x16 0x17 HiByte LoByte HiByte LoByte HiByte LoByte HiByte LoByte 0x41 0x45 0x70 0xA4 0x00 0x03 0x00 0x4A Floating point value AT&T R&U Description 12.34 No/No Ampere Overcurrent Hex value sequence Word 1 Word 2 Floating point value Byte 1 Byte 2 Byte 3 Byte 4 CORRECT A 41 B 45 C 70 D A4 12.34 Word swapping C 70 D A4 A 41 B 45 4.066E+29 Byte swapping B 45 A 41 D A4 C 70 3098.27 Word and byte swapping D A4 C 70 B 45 A 41 -5.21E-17

Modbus TCP server

49 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 6.2.4 Channel descriptions for the process image Value Measured value description Alarm message Operating message Note 0 1 (0x01) Insulation fault 2 (0x02) Overload 3 (0x03) Overtemperature 4 (0x04) Failure Line 1 5 (0x05) Failure Line 2 6 (0x06) Insul. fault OP light Insulation fault operating theatre light 7 (0x07) 8 (0x08) Distribution board failure 9 (0x09) Failure oxygen 10 (0x0A) Failure vacuum 11 (0x0B) Anaesthetic gas 12 (0x0C) Compressed air 5 bar 13 (0x0D) Compressed air 10 bar 14 (0x0E) Failure nitrogen 15 (0x0F) Failure CO2 16 (0x10) Insulation UPS Insulation fault UPS 17 (0x11) Overload UPS 18 (0x12) Converter UPS 19 (0x13) UPS fault 20 (0x14) UPS emergency operation 21 (0x15) UPS test run 22 (0x16) Failure air conditioning 23 (0x17) Batt.op. OP-L Battery operated operating thea- tre light 24 (0x18) Batt.op. OP-S Battery operated Sat OP light 25 (0x19) Fail.norm.supply Line normal power supply 26 (0x1A) Fail.safet.supply Line safety power supply 27 (0x1B) Failure UPS Line additional safety power sup- ply 28 (0x1C) Ins.safety supply 29 (0x1D) Fail.N conductor 30 (0x1E) Short dist.panel Distribution board short-circuit 31 (0x1F) 32 (0x20) 33 (0x21) 34 (0x22) 35 (0x23) Standby function (Measuring function switched off (standby)) 36 (0x24) 37 (0x25)

Modbus TCP server

50 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 38 (0x26) Batt.op. UPS Battery operation, additional safety power supply 39 (0x27) Phase sequ. left 40 (0x28) Failure UPS Battery-supported safety power supply 41 (0x29) 66 (0x42) 67 (0x43) FunctionTest till: Date 68 (0x44) Service till: Date 69 (0x45) Ins.fault locat Insulation fault location 70 (0x46) Peak Fault EDS system 71 (0x47) Insulation fault Insulation resistance in Ω 72 (0x48) Current Measured value in A 73 (0x49) Undercurrent 74 (0x4A) Overcurrent 75 (0x4B) Residual current Measured value in A 76 (0x4C) Voltage Measured value in V 77 (0x4D) Undervoltage 78 (0x4E) Overvoltage 79 (0x4F) Frequency Measured value in Hz 80 (0x50) 81 (0x51) Asymmetry 82 (0x52) Capacitance Measured value in F 83 (0x53) Temperature Measured value in °C 84 (0x54) Overload Measured value in % 85 (0x55) Digital input State 0 or 1 86 (0x56) Insulation fault Impedance 87 (0x57) Insulation fault Alarm from an insulation fault locator 88 (0x58) Load Measured value in % 89 (0x59) Total Hazard Current THC 90 (0x5A) Inductance Measured value in H 97 (0x61) Service code Information about service inter- vals 101 (0x65) Mains power connection 102 (0x66) Earth connection 103 (0x67) Short CT CT short-circuit 104 (0x68) No CT connected Value Measured value description Alarm message Operating message Note

Modbus TCP server

51 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 105 (0x69) Short temp.sensor Temperature sensor short-circuit 106 (0x6A) Temp.sensor open. Connection temperature sensor 107 (0x6B) K1 Fault contactor K1 108 (0x6C) K2 Fault contactor K2 109 (0x6D) 110 (0x6E) 111 (0x6F) No address: Failure BMS device 112 (0x70) 113 (0x71) Failure K1/Q1 Failure contactor K1/Q1 114 (0x72) Failure K2/Q2 Failure contactor K2/Q2 115 (0x73) Device error Fault ISOMETER 116 (0x74) Manual mode K1/2 manual mode 117 (0x75) Open circuit K1on Line to K1 on interrupted 118 (0x76) Open circ. K1off Line to K1 off interrupted 119 (0x77) Open circuit K2 on Line to K2 on interrupted 120 (0x78) Open circ. K2 off Line to K2 off interrupted 121 (0x79) K/Q1on Fault 122 (0x7A) K/Q1off Fault 123 (0x7B) K/Q2on Fault 124 (0x7C) K/Q2off Fault 125 (0x7D) Failure K3 126 (0x7E) Q1 Fault 127 (0x7F) Q2 Fault 128 (0x80) No master 129 (0x81) Device error 130 (0x82) 131 (0x83) Fault RS485 132 (0x84) 133 (0x85) 134 (0x86) 135 (0x87) 136 (0x88) 137 (0x89) Short-circuit Q1 138 (0x8A) Short-circuit Q2 139 (0x8B) CV460 CV460 fault 140 (0x8C) RK4xx Fault RK4xx 141 (0x8D) Address collision BMS address has been assigned several times 142 (0x8E) Invalid address 143 (0x8F) Several masters 144 (0x90) No menu access 145 (0x91) Own address Value Measured value description Alarm message Operating message Note

Modbus TCP server

52 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 201 (0xC9) Line 1 normal op 202 (0xCA) Line 2 normal op 203 (0xCB) Switch. el. 1 on 204 (0xCC) Switch. el. 2 on 205 (0xCD) 206 (0xCE) Auto mode 207 (0xCF) Manual mode 208 (0xD0) 209 (0xD1) 210 (0xD2) Line AV on 211 (0xD3) Line SV on 212 (0xD4) Line UPS on 213 (0xD5) Channel disabled 214 (0xD6) SwitchBackLock Back-interlocking function ena- bled 215 (0xD7) Phase sequ. right 216 (0xD8) Switch. el. pos.0 217 (0xD9) Line BSV on 218 (0xDA) On SMO48x: Alarm, relay Value Measured value description Alarm message Operating message Note

Modbus TCP server

53 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 To convert the data of parameters, you will need data type descriptions. Text representation is not necessary in this case. Value Description of parameters: 1023 (0x3FF) Parameter/measured value invalid. The menu item for this parameter is not displayed 1022 (0x3FE) No measured value/no message 1021 (0x3FD) Measured value/parameter inactive 1020 (0x3FC) Measured value/parameter only temporarily inactive (e.g. during the transfer of a new parameter). Display in the menu "…". 1019 (0x3FB) Parameter/measured value (unit not displayed) 1018 (0x3FA) Parameter (code selection menu) unit not displayed 1017 (0x3F9) String max. 18 characters (e.g. device type, - variant, …) 1016 (0x3F8) 1015 (0x3F7) Time of day 1014 (0x3F6) Date day 1013 (0x3F5) Date month 1012 (0x3F4) Date year 1011 (0x3F3) Register address (unit not displayed) 1010 (0x3F2) Time 1009 (0x3F1) Factor multiplication [*] 1008 (0x3F0) Factor division [/] 1007 (0x3EF) Baud rate

Modbus TCP server

54 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 6.2.5 Modbus control commands Commands can be sent to BMS devices by an external application (e.g. visualisation software). Control via Modbus can be enabled or disabled via the menu "Settings" > 3. Modbus > 1. Control". Command structure Writing to registers:  To write use function code 0x10 "Write Multiple registers".  Start address: 0xFC00  Number: 4 registers  Always set all four registers (word 0xFC00…0xFC03) at the same time. This statement also applies if individual registers remain unchanged.  If there is no external BMS bus, enter value "1" in this register.  If a BMS channel number is not required, enter value "0" (zero) in this register. Reading registers:  To read use function code 0x04 "Read Input Registers". Possible response in register "Status": Write Read Word 0xFC00 0xFC01 0xFC02 0xFC03 0xFC04 External BMS bus address Internal BMS bus address BMS channel Command Status You can also generate control commands via the menu "Tools" > "Modbus control commands". 0 Busy Processing command. 1 Error An error has occurred. 2 Ready Command has been processed successfully. CAUTION

Modbus TCP server

55 COM465IP-COM465DP_D00216_00_M_XXEN/10.2015 Control commands for the internal and external BMS bus int/ext BMS bus Register Ext Register Int Register channel Register command Function INT 1 1-150 0 1 Test Isometer EXT 1-99 INT 1 1-150 0 2 Test changeover device PRC EXT 1-99 0 INT 1 1-150 0 3 Start automatic test changeover 1- >2 End after time T(test) EXT -- -- -- -- INT 1 1-150 0 4 Start test generator without changeover EXT -- -- -- -- INT 1 1-150 0 5 Changeover to line 1 EXT -- -- -- -- INT 1 1-150 0 6 Changeover to line 2 EXT -- -- -- -- INT 1 0 0 7 RESET alarm (broadcast) EXT 1-99 INT 1 0 0 8 RESET alarm EDS (broadcast) EXT -- -- -- -- INT 1 1-150 0 9 Buzzer off [for alarm address] (BC) EXT 1-99 1-192 INT 1 1-150 1-12 10 Switch on relay/switch EXT -- -- -- -- INT 1 1-150 1-12 11 Switch off relay/switch EXT -- -- -- --

Damage in transit

If you find transport damage on receipt of the delivery, have this damage confirmed by the delivery agent on handover. In case of doubt, please contact Bender. 7.2 Malfunctions If the COM465… causes malfunctions in the connected networks, please refer to this manual. 7.2.1 What should be checked? Check whether the COM465…  The device is supplied with the correct supply voltage US  The BMS bus cable is correctly connected and terminated (120 Ω)  The BMS address is correctly configured For the COM465DP, check also whether  The PROFIBUS DP cable is connected correctly and terminated (DIP switch)  The PROFIBUS DP address is correctly configured  The GSD file has been transferred to the PROFIBUS DP master  The PROFIBUS DP command "Device type" to COM465DP: ID no,0,BMS address of the COM465DP,0,20,0,0,0 produces the following correct result: ID no,0,BMS address of the COM465DP,0,20,201,0,0 Otherwise the COM465DP is already operating incorrectly  The PROFIBUS DP commands for COM465DP have the correct syntax 7.2.2 Frequently asked questions How do I access the device if the address data are unknown? 1. Connect the device directly to a Windows PC using a patch cable 2. Activate the DHCP function on the PC. 3. Wait around one minute. 4. Access is now possible using the following pre-defined IP address: 169.254.0.1. 5. Now set the new address data. Write down the new settings. Document and backup all device settings by generating a report (see manual COMTRAXX®).

Can a report be downloaded from another device with more function modules?

Function module C is required in order to download reports. The function can only be executed if the associated function module is installed. Frequently asked questions on the Internet You will find FAQs on many Bender devices at: http://www.bender.de > Service & support > Rapid assistance > FAQ 7.2.3 Where do you get help? If, despite thorough study of the manual and intensive troubleshooting in your installation, you can- not rectify the fault related to the COM465…, please contact our Service department: Tel.: +49 6401 807-760 or 0700BENDERHELP Fax: +49 6401 807-259 Email: [email protected] 7.3 Maintenance The device does not contain any parts that must be maintained. 7.4 Cleaning The device is only allowed to be cleaned using a clean, dry, soft, antistatic cloth. 7.5 Disposal Observe by the national regulations and laws governing the disposal of this device. Ask your supplier if you are not sure how to dispose of the old equipment. Directive 2002/96/EC on waste electrical and electronic equipment and Directive 2002/95/EC on the restriction of certain hazardous substances in electrical and electronic equipment apply in the Euro- pean Community. In Germany, these directives are implemented through the "Elektro- und Elektronikgerätegesetz (German law on electrical and electronic equipment) dated 16 March 2005. According to this law, the following applies:  Electrical and electronic equipment are not to be placed in household waste.  Batteries and accumulators are not to be placed in household waste but must be disposed of in accordance with the regulations.  Waste electrical and electronic equipment (WEEE) from users other than private households that was introduced to the market after 13th August 2005 must be taken back by the manufac- turer and disposed of properly. For more information on the disposal of Bender devices, see our homepage: http://www.bender.de > Service & support > Take-back of old devices

8. Technical data

8.1 Tabular data ( )* = Factory setting Insulation coordination acc. to IEC 60664-1/IEC 60664-3 (For 230 V variant B95061060) Rated insulation voltage ...................................................................................................................................... AC 250 V Rated impulse voltage/overvoltage category .........................................................................................................4 kV/III Pollution degree ................................................................................................................................................................3 Protective separation (reinforced insulation) between ...............................................................(A1/+, A2/-) - [(AMB, BMB), (ABMS, BBMS), (X2), (X3, X4), (PROFIBUS DP)] Insulation coordination acc. to IEC 60664-1/IEC 60664-3 (For 24 V variant B95061061) Rated insulation voltage ......................................................................................................................................... AC 50 V Rated impulse voltage/overvoltage category ..................................................................................................... 0.5 kV/III Pollution degree.................................................................................................................................................................3 Supply voltage Supply voltage Us ...................................................................................................................... See ordering information Frequency range Us ................................................................................................................... See ordering information Power consumption .................................................................................................................. See ordering information Indications LEDs: ON .........................................................................................................................................................Operation indicator PROFIBUS .....................................................................................................................................PROFIBUS DP data traffic ETHERNET/IP ........................................................................................................................................Ethernet data traffic Modbus RTU ........................................................................................................................................Modbus data traffic BMS ............................................................................................................................................................BMS data traffic Ethernet (Terminal X2) ........................................ Illuminates if connected to the network, flashes during data transfer Memory E-mail configuration (function module A only) and device failure monitoring ....................................Max. 250 entries Individual texts (function module A only)......................................Unlimited number of texts with 100 characters each Number of data points for "third-party devices" on the Modbus TCP and Modbus RTU..............................................50 Number of data loggers ...................................................................................................................................................30 Number of data points per data logger....................................................................................................................10,000 Number of entries in the history memory..................................................................................................................1,000 Visualisation Number of pages..............................................................................................................................................................20 Background image size................................................................................................ 50 kByte (is scaled down if larger) Data points (per page).....................................................................................50 devices or channels, 150 text elements Interfaces Ethernet Port.................................................................................................................................................................................RJ45 Data rate ....................................................................................................................................10/100 Mbit/s, autodetect DHCP ............................................................................................................................................................... on/off (on)* toff (DHCP................................................................................................................................................. 5…60 s (30 s)*

IP address ...............................................nnn.nnn.nnn.nnn, can always be reached via: 192.168.0.254, (169.254.0.1)*

Netmask......................................................................................................................... nnn.nnn.nnn.nnn (255.255.0.0)* Protocols (depending on function module selected) ................TCP/ IP, Modbus TCP, Modbus RTU, DHCP, SMTP, NTP SNMP Versions.....................................................................................................................................................................1, 2c, 3 Devices supported..................................................... Requests to all devices (channels) possible (no trap functionality) BMS bus (internal/external) Interface/protocol ......................................................................RS-485/BMS internal or BMS external (BMS internal)* Operating mode ............................................................................................................................Master/slave (master)* Baud rate BMS ........................................................................................................................................Internal 9.6 kbit/s .....................................................................................................................................................External 38.4; 57.6 kbit/s Cable length ....................................................................................................................................................... ≤1200 m Cable: Twisted pair, shielded, one end of shield connected to PE ..........................Recommended: J-Y(St)Y min. 2x0.8 Connection ............................................................................................................................................. X1 (ABMS, BBMS) Connection type ........................................................................................ Refer to connection "Push-wire terminal X1" Terminating resistor .................................................................................120 Ω (0.25 W), can be switched on internally Device address, BMS bus internal/external .................................................................................................... 1…99 (2)* BCOM Interface/protocol .......................................................................................................................................Ethernet/BCOM BCOM subsystem address................................................................................................................................ 1…99 (1)* BCOM device address....................................................................................................................................... 1…99 (2)* Modbus TCP Interface/protocol ...........................................................................................................................Ethernet/Modbus TCP Operating mode..................................................................................Client for PEM and "third-party devices" assigned Operating mode.................................................Server for access to process image and for Modbus control commands Modbus RTU Interface/protocol .............................................................................................................................. RS485/Modbus RTU Operating mode .......................................................................................................................................................Master Baud rate ................................................................................................................................................ 9.6…57.6 kbit/s Cable length ....................................................................................................................................................... ≤1200 m Connection ................................................................................................................................................. X1 (AMB, BMB) Connection type ............................................................................................... See connection "Push-wire terminal X1" Terminating resistor .................................................................................120 Ω (0.25 W), can be switched on internally Supported Modbus RTU slave addresses .............................................................................................................. 2…247 PROFIBUS DP (COM465DP only) Interface/protocol ............................................................................................RS-485 electrically isolated/PROFIBUS DP Operating mode ......................................................................................................................................................... Slave Baud rate .................................................................................. Automatic baud rate detection: 9.6 kbit/s…1.5 Mbit/s .............................................................................................................9.6 / 19.2 / 93.75 / 187.5 / 500 kbit/s , 1.5 Mbit/s Connection ....................................................................................................................................................... Sub D 9-pin Device address, PROFIBUS DP........................................................................................................................1…125 (3)* Environment/EMC EMC .................................................................................................................................................................. EN 61326-1 Ambient temperatures: Operating temperature ............................................................................................................................... -25…+55 °C Transport ..................................................................................................................................................... -40…+85 °C Long-term storage ...................................................................................................................................... -25…+70 °C Classification of climatic conditions acc. to IEC 60721: Stationary use (IEC 60721-3-3) ................................................................... 3K5 (no condensation, no formation of ice) Transport (IEC 60721-3-2) .......................................................................................................................................... 2K3

Long-term storage (IEC 60721-3-1) ........................................................................................................................... 1K4

Classification of mechanical conditions acc. to IEC 60721: Stationary use (IEC 60721-3-3) .................................................................................................................................. 3M4 Transport (IEC 60721-3-2) .......................................................................................................................................... 2M2 Long-term storage (IEC 60721-3-1) .......................................................................................................................... 1M3 Option "W" data different from the standard version Classification of climatic conditions acc. to IEC 60721: Stationary use (IEC 60721-3-3) ..................................................... 3K5 (condensation and formation of ice is possible) Classification of mechanical conditions acc. to IEC 60721: Stationary use (IEC 60721-3-3) .................................................................................................................................. 3M7 Connection Connection type.................................................................................................................pluggable push-wire terminals Push-wire terminals Conductor sizes..................................................................................................................................................AWG 24-12 Stripping length........................................................................................................................................................ 10 mm Rigid/flexible ...............................................................................................................................................0.2…2.5 mm² Flexible with ferrule with/without plastic sleeve.....................................................................................0.25…2.5 mm² Multiple conductor flexible with TWIN ferrule with plastic sleeve........................................................... 0.5…1.5 mm² Push-wire terminal X1 Conductor sizes..................................................................................................................................................AWG 24-16 Stripping length........................................................................................................................................................ 10 mm Rigid/flexible ...............................................................................................................................................0.2…1.5 mm² Flexible with ferrule without plastic sleeve..............................................................................................0.25…1.5 mm² Flexible with ferrule with plastic sleeve .................................................................................................0.25…0.75 mm² Other Operating mode ............................................................................................................................... Continuous operation Mounting position ..............................................................Front-orientated, cooling slots must be ventilated vertically Degree of protection, internal components (IEC 60529) ........................................................................................... IP30 Degree of protection, terminals (IEC 60529) .............................................................................................................. IP20 DIN rail mounting acc. to .................................................................................................................................... IEC 60715 Screw fixing ............................................................................................................................................................. 2 x M4 Type of enclosure ......................................................................................................................................................... J460 Enclosure material........................................................................................................................................ Polycarbonate Flammability class ................................................................................................................................................ UL94V-0 Dimensions (W x H x D)...................................................................................................................107.5 x 93 x 62.9 mm Software version ......................................................................................................................................................... D472 Documentation number..........................................................................................................................................D00216 Weight .................................................................................................................................................................... ≤240 g ( )* = Factory setting

Standards, approvals and certificates

Certification by the PROFIBUS Nutzerorganisation e.V. (PNO) is available. PROFIBUS conformity: Z02007 UL and GL approval in preparation. Type Application Supply voltage/ Frequency range US Power consumption Art. No. COM465DP-230V Condition Monitor with integrated gateway: Bender system/PROFIBUS DP/Ethernet AC/DC 24...240 V 50...60 Hz ≤6.5VA/≤4 W B 9506 1060 COM465DP-24V DC 24 V ≤3 W B 9506 1061 COM465IP-230V Condition Monitor with integrated gateway: Bender system/Ethernet AC/DC 24...240 V 50...60 Hz ≤6.5VA/≤4 W B 9506 1065 COM465IP-24V DC 24 V ≤3 W B 9506 1066 Function module (software licence) Application Art. No. Function module A Individual texts for devices/channels, monitoring for device failure, e-mail notification in the event of alarms B 7506 1011 Function module B Modbus TCP server for max. 98 * 139 BMS nodes as well as BCOM devices and universal measuring devices, SNMP server B 7506 1012 Function module C Setting of parameters on BMS devices as well as on BCOM devices and universal measuring devices B 7506 1013 Function module D Visualisation of Bender systems, system visualisation B 7506 1014

BMS device address assignment on the

Modbus 40 Byte offset 48 Byte or word swapping 48 C Claims under the warranty 58 Connection - BMS 19 - PROFIBUS-DP 19 Connection, preliminary considerations 17 D Damage in transit 57 Displays and controls 16 E Exception code 37 F Factory settings 21 FTC470XDP - as BMS master 24 G GSD file 22 I Installation and connection 17 Installation, preliminary considerations 17 L Loading GSD file from the web site 11 M Malfunctions 57 Measured value descriptions for the proc- ess image, list 49 Memory image of a BMS device 41 Memory scheme of the process image 40 Modbus - address structure for BMS devices 38 - control commands 54 - function code 39 - process image 39 - requests 37 - responses 38 P Process image 40 Programming examples 29 R Reference data records of the process im- age 47 S Sketch with dimensions 62 Support 58 U Using this manual 7 W Work on electrical installations 9 INDEX