Sullair SUPERVISOR CONTROLLER Instruction Manual

Brand: Sullair
Category: Controller
Model: SUPERVISOR CONTROLLER (Instruction Manual)
File Type: PDF
File Size: —
Pages: 37
Text of Sullair SUPERVISOR CONTROLLER Instruction Manual

and WS CONTROLLER

SEQUENCING & PROTOCOL MANUAL (Including Supervisor II Deluxe Controller™) INSTRUCTION MANUAL Part Number 02250161-162 ©Sullair Corporation KEEP FOR FUTURE REFERENCE

Sullair SUPERVISOR CONTROLLER AIR CARE SEMINAR

TRAINING Sullair Air Care Seminars are courses that provide hands-on instruction in the proper operation, maintenance and service of Sullair equipment. Individual seminars on Industrial compressors and compressor electrical systems are presented at regular intervals throughout the year at a dedicated training facility at Sullair’s corporate headquarters in Michigan City, Indiana. Instruction includes discussion of the function and instal

TABLE OF CONTENTS

1. SAFETY AND INTRODUCTION 1 1.1 SAFETY 1 1.2 SUPERVISOR CONTROLLER, SUPERVISOR II AND WS CONTROLLERS 1 1.3 SEQUENCED COMPRESSOR SYSTEMS 1 2. SEQUENCING WITH MULTIPLE CONTROLLERS 3 2.1 NORMAL OPERATION 3 2.2 COMPRESSOR SYSTEM 3 2.3 WIRING AND PIPING 4 2.4 MACHINE PREPARATION PRIOR TO SEQUENCING 4 2.5 SYSTEM OPERATION 5 2.6 SYSTEM SETUP AND TUNING 6 2.6.1 GENERAL SEQUENCING RULES 7 2.7 CHANGING SEQUENCE PARAMETERS 7 2.8 SEQUENCE PARAMETER
TABLE OF CONTENTS 5. SEQUENCING TIMERS FOR EFFICIENT OPERATION 21 5.1 RECOVERY TIME AND DELAYED START TIMER 21 5.2 TIMER OPERATION EXAMPLES 22 5.2.1 EXAMPLE 1– UNLOAD OPERATION 22 5.2.2 EXAMPLE 2– LOAD OPERATION 22 5.2.3 EXAMPLE 3– STARTING EXAMPLE 23 5.2.4 EXAMPLE 4– STARTING EXAMPLE 23 5.3 SEQUENCING TIMERS SUMMARY 24 6. CONTROLLER COMMUNICATION PROTOCOL 25 6.1 RECOVERY TIME AND DELAYED START TIMER - OVERVIEW 25 6.2 ADVANTAGES OF BROADCAST MODE 2

Sullair SUPERVISOR CONTROLLER SAFETY AND INTRODUCTION

1.1 SAFETY 1.2 SUPERVISOR CONTROLLER, SUPERVISOR II AND WS CONTROLLERS This manual describes sequencing of multiple compressors with Supervisor Controller, Supervisor II Deluxe or WS Controller. The term "controller" is used to apply to any of the three devices, however, specific differences will be highlighted in the places where they apply. Although each controller differs considerably in

Sullair SUPERVISOR CONTROLLER master-slave relationship) so the system remains operational even if a member is taken

off-line. Both the Supervisor Controller and WS Controller can be configured with up to 16 machines in a sequence system. When one or more Supervisor II Deluxe Controllers are in the system, the maximum number of machines is eight. Refer to Section 2 for details. A system with one or more variable-speed compressors offers additional

SEQUENCING WITH MULTIPLE CONTROLLERS

2.1 NORMAL OPERATION The Supervisor, Supervisor II Deluxe, and WS Controllers all feature internal functions that enable sequencing of multiple machines. • To enable a Supervisor Controller in the system, press the START pad and REMOTE pad on the keypad. • Enable the Supervisor II Deluxe by simply pressing the AUTO pad. • Enable the WS Controller by simply pre

one machine. DO NOT enable this mode in systems with more than two machines

(See ROTATE hours parameter setting for more information). Digital inputs for remote control are disabled. 2.3 WIRING AND PIPING Control signals are passed along a simple network cable, Belden 9842 or similar. This cable has two twisted pairs with a shield. Twisted pairs usually have one color coded wire twisted with a black or

Sullair SUPERVISOR CONTROLLER BAUD RATE (Supervisor II only). Baud Rate for Supervisor and WS is fixed

at 9600. d. SEQUENCE mode (COM ID or HOURS) e. LAST COM f. LOWEST (minimum pressure before a machine is started) g. RECOVER time (normally set at 10) h. Leave ROTATE hours disabled except for the specific application described in Section 2.8. i. Set all sequence hour parameters the same unless it is desired

Sullair Controller Owners Instructions: