SEQUENCING & PROTOCOL MANUAL
(Including Supervisor II Deluxe Controller™)
INSTRUCTION
MANUAL
Part Number
02250161-162
©Sullair Corporation
KEEP FOR
FUTURE
REFERENCE
Sullair SUPERVISOR CONTROLLER AIR CARE SEMINAR
TRAINING
Sullair Air Care Seminars are courses that provide hands-on instruction in the proper operation, maintenance
and service of Sullair equipment. Individual seminars on Industrial compressors and compressor electrical
systems are presented at regular intervals throughout the year at a dedicated training facility at Sullair’s
corporate headquarters in Michigan City, Indiana.
Instruction includes discussion of the function and instal
TABLE OF CONTENTS
1.
SAFETY AND INTRODUCTION
1
1.1
SAFETY
1
1.2
SUPERVISOR CONTROLLER, SUPERVISOR II AND WS CONTROLLERS
1
1.3
SEQUENCED COMPRESSOR SYSTEMS
1
2.
SEQUENCING WITH MULTIPLE CONTROLLERS
3
2.1
NORMAL OPERATION
3
2.2
COMPRESSOR SYSTEM
3
2.3
WIRING AND PIPING
4
2.4
MACHINE PREPARATION PRIOR TO SEQUENCING
4
2.5
SYSTEM OPERATION
5
2.6
SYSTEM SETUP AND TUNING
6
2.6.1
GENERAL SEQUENCING RULES
7
2.7
CHANGING SEQUENCE PARAMETERS
7
2.8
SEQUENCE PARAMETER
TABLE OF CONTENTS 5.
SEQUENCING TIMERS FOR EFFICIENT OPERATION
21
5.1
RECOVERY TIME AND DELAYED START TIMER
21
5.2
TIMER OPERATION EXAMPLES
22
5.2.1
EXAMPLE 1– UNLOAD OPERATION
22
5.2.2
EXAMPLE 2– LOAD OPERATION
22
5.2.3
EXAMPLE 3– STARTING EXAMPLE
23
5.2.4
EXAMPLE 4– STARTING EXAMPLE
23
5.3
SEQUENCING TIMERS SUMMARY
24
6.
CONTROLLER COMMUNICATION PROTOCOL
25
6.1
RECOVERY TIME AND DELAYED START TIMER - OVERVIEW
25
6.2
ADVANTAGES OF BROADCAST MODE
2
Sullair SUPERVISOR CONTROLLER SAFETY AND INTRODUCTION
1.1
SAFETY
1.2
SUPERVISOR CONTROLLER, SUPERVISOR II AND WS CONTROLLERS
This manual describes sequencing of multiple compressors with Supervisor Controller,
Supervisor II Deluxe or WS Controller. The term "controller" is used to apply to any of
the three devices, however, specific differences will be highlighted in the places where
they apply. Although each controller differs considerably in
Sullair SUPERVISOR CONTROLLER master-slave relationship) so the system remains operational even if a member is taken
off-line. Both the Supervisor Controller and WS Controller can be configured with up to
16 machines in a sequence system. When one or more Supervisor II Deluxe Controllers
are in the system, the maximum number of machines is eight. Refer to Section 2 for
details.
A system with one or more variable-speed compressors offers additional
SEQUENCING WITH MULTIPLE CONTROLLERS
2.1
NORMAL OPERATION
The Supervisor, Supervisor II Deluxe, and WS Controllers all feature internal functions
that enable sequencing of multiple machines.
•
To enable a Supervisor Controller in the system, press the START
pad and
REMOTE
pad on the keypad.
•
Enable the Supervisor II Deluxe by simply pressing the AUTO
pad.
•
Enable the WS Controller by simply pre
one machine. DO NOT enable this mode in systems with more than two machines
(See ROTATE hours parameter setting for more information). Digital inputs for remote
control are disabled.
2.3
WIRING AND PIPING
Control signals are passed along a simple network cable, Belden 9842 or similar. This
cable has two twisted pairs with a shield. Twisted pairs usually have one color coded
wire twisted with a black or
Sullair SUPERVISOR CONTROLLER BAUD RATE (Supervisor II only). Baud Rate for Supervisor and WS is fixed
at 9600.
d.
SEQUENCE mode (COM ID or HOURS)
e.
LAST COM
f.
LOWEST (minimum pressure before a machine is started)
g.
RECOVER time (normally set at 10)
h.
Leave ROTATE hours disabled except for the specific application described
in Section 2.8.
i.
Set all sequence hour parameters the same unless it is desired