406 Jessop Avenue
Saskatoon, Saskatchewan Canada S7N 2S5 Ph: (306) 373-5505 Fx: (306) 374-2245 www.startco.ca SE-330 MANUAL NEUTRAL-GROUNDING-RESISTOR MONITOR MARCH 11, 2008 REVISION 5 Copyright  2008 Startco Engineering Ltd. All rights reserved. Publication: SE-330-M Document: S95-C330-00000 Printed in Canada.
Startco Engineering Ltd.
Page i SE-330 Neutral-Grounding-Resistor Monitor Rev. 3 Pub. SE-330-M, March 11, 2008. TABLE OF CONTENTS PAGE Table of Contents .............................................................. i List of Figures ................................................................... i List of Tables..........................................
Startco Engineering Ltd.
Page 1 SE-330 Neutral-Grounding-Resistor Monitor Rev. 2 Pub. SE-330-M, March 11, 2008. 1. GENERAL 1.1 MODERN RESISTANCE-GROUNDED SYSTEMS A high-resistance-grounded system uses a neutral- grounding resistor (NGR) with a low let-through current to limit ground-fault current. High-resistance grounding is gaining popularity because a
Startco Engineering Ltd.
Page 2 SE-330 Neutral-Grounding-Resistor Monitor Rev. 4 Pub. SE-330-M, March 11, 2008. The SE-330 provides new features and improved performance over the SE-325 NGR Monitor: • SE-330 dc rejection is sufficient for reliable operation in overhead-line applications. • Digital filtering of voltage and current signals minimizes false
Startco Engineering Ltd.
Page 3 SE-330 Neutral-Grounding-Resistor Monitor Rev. 2 Pub. SE-330-M, March 11, 2008. TABLE 2. GROUND-FAULT TRIP LEVELS FOR SELECTED CT’S GF TRIP LEVEL (%) EFCT-x 5:0.05 (Amperes) SE-CS30-x 30:0.05 (Amperes) 50:1 50:5 (Amperes) 100:1 100:5 (Amperes) 200:1 200:5 (Amperes) 400:1 400:5 (Amperes) 2 4 6 8 10 15 20 40 60 80 100 0.10 0.
Startco Engineering Ltd.
Page 4 SE-330 Neutral-Grounding-Resistor Monitor Rev. 3 Pub. SE-330-M, March 11, 2008. 2.1.5.6 FREQUENCY (S6) Set switch S6 to 50 or 60 Hz to tune the digital filter to the line frequency of the monitored system. 2.1.5.7 SPARE (S7) 2.1.5.8 UPGRADE ENABLE (S8) Set switch S8 to RUN for normal operation or to UPGRADE to enable firm

Startco Monitor Owners Instructions: