Startco SE-330 Manual
Text of Startco SE-330 Manual
406 Jessop Avenue
Saskatoon, Saskatchewan
Canada
S7N 2S5
Ph: (306) 373-5505
Fx: (306) 374-2245
www.startco.ca
SE-330 MANUAL
NEUTRAL-GROUNDING-RESISTOR MONITOR
MARCH 11, 2008
REVISION 5
Copyright 2008 Startco Engineering Ltd.
All rights reserved.
Publication: SE-330-M
Document: S95-C330-00000
Printed in Canada.
Startco Engineering Ltd.
Page i
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 3
Pub. SE-330-M, March 11, 2008.
TABLE OF CONTENTS
PAGE
Table of Contents .............................................................. i
List of Figures ................................................................... i
List of Tables..........................................
Startco Engineering Ltd.
Page 1
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 2
Pub. SE-330-M, March 11, 2008.
1. GENERAL
1.1 MODERN RESISTANCE-GROUNDED SYSTEMS
A high-resistance-grounded system uses a neutral-
grounding resistor (NGR) with a low let-through current
to limit ground-fault current. High-resistance grounding
is gaining popularity because a
Startco Engineering Ltd.
Page 2
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 4
Pub. SE-330-M, March 11, 2008.
The SE-330 provides new features and improved
performance over the SE-325 NGR Monitor:
•
SE-330 dc rejection is sufficient for reliable operation
in overhead-line applications.
•
Digital filtering of voltage and current signals
minimizes false
Startco Engineering Ltd.
Page 3
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 2
Pub. SE-330-M, March 11, 2008.
TABLE 2. GROUND-FAULT TRIP LEVELS FOR SELECTED CT’S
GF TRIP
LEVEL
(%)
EFCT-x
5:0.05
(Amperes)
SE-CS30-x
30:0.05
(Amperes)
50:1
50:5
(Amperes)
100:1
100:5
(Amperes)
200:1
200:5
(Amperes)
400:1
400:5
(Amperes)
2
4
6
8
10
15
20
40
60
80
100
0.10
0.
Startco Engineering Ltd.
Page 4
SE-330 Neutral-Grounding-Resistor Monitor
Rev. 3
Pub. SE-330-M, March 11, 2008.
2.1.5.6 FREQUENCY (S6)
Set switch S6 to 50 or 60 Hz to tune the digital filter to
the line frequency of the monitored system.
2.1.5.7 SPARE (S7)
2.1.5.8 UPGRADE ENABLE (S8)
Set switch S8 to RUN for normal operation or to
UPGRADE to enable firm