1. Documentation
All the documentation for COUNTIS E13/E14 equipment is available
online at:
www.socomec.com/en/countis-e1x
2. Danger and warning
This equipment must only be installed by professionals.
The manufacturer shall not be held responsible for failure to comply with the instructions in this manual.
2.1. Risk of electrocution, burns or explosion
•� �The�device�must�be�installe
COUNTIS E13/E14 - Ref.: 542 101 A 4. Overview
COUNTIS E13 and E14 are active modular electrical energy meters for monitoring kWh. They are designed for single-
phase networks and enable direct connection up to 80A. They are equipped with a MODBUS communication bus.
4.1. Main functions
•� Measurement and display:
- active and reactive energy (T1 and T2): Ea+/Ea-/Er+/Er-
- of active and reactive power: P1+/P1-/Q1+/Q1-
•� Management of two tariffs:
COUNTIS E13/E14 - Ref.: 542 101 A COUNTIS E13/E14 MODBUS
5. Installation
5.1. Recommendations
•� avoid proximity to systems which generate electromagnetic interference,
•� avoid vibrations with accelerations in excess of 1 G for frequencies below 50 Hz.
5.2. Dimensions (mm)
64
45
6
90
44
L1
N
L1
1 2 3
4
6
5
54
5.3. Terminals
64
45
6
90
44
L1
N
L1
1 2 3
4
6
5
54
0.61 in/15.5 mm
PZ2
flexible or rigid
7 to 50 mm2
2 Nm
0.35 in/9 mm
PZ2
flexible 1.5
COUNTIS E13/E14 - Ref.: 542 101 A 5.4. Connections
5.4.1. 2-wire connection - single-phase load monitoring
L1
L1
N
230 VAC fn = 50 Hz
L1
L’
N
80A
6
1
5
4
3
2
230 VAC
120Ω -
+
NC
T1/2
COM RS485
Modbus/Jbus
MODBUS
1:
Activation of 120 ohm terminating resistors by
connecting terminals 1 and 2.
2:
-
3:
+
4:
NC (not connected).
Tariff
5-6: Change of tariff only for COUNTIS E14:
0 VAC -> Tariff 1
230 VAC -> Tariff 2
(change of tariff via MODBUS f
COUNTIS E13/E14 - Ref.: 542 101 A COUNTIS E13/E14 MODBUS
6. MODBUS communication
6.1. General Information
MODBUS® communication is performed via a RS485 serial port (2- or 3-wire) which enables products to be used
from a PC or an API.
On�a�standard�configuration,�a�RS485�port�can�be�used�to�connect�32�products�to�a�PC�or�a�PLC�across�1200�
meters.
R=120Ω
R=120Ω
R=120Ω
R=120Ω
R=120Ω
R=120Ω
R=120Ω
COUNTIS E13/E14 - Ref.: 542 101 A 7. Programming
7.1. Navigation principle
The�programming�mode�enables�the�communication�parameters�to�be�modified.�The�process�to�navigate�inside�the�
programming mode is described in the following steps:
Access to item to set
> 4 sec
Enter programming mode
(press
button for 4 seconds)
Value to be modified
> 4 sec
Validate the value
7.2. Programming menu overview
By pressing
for 4 seco
COUNTIS E13/E14 - Ref.: 542 101 A COUNTIS E13/E14 MODBUS
7.3. Detailed view of MODBUS programming menu
x 10
Address
4
sec
4
sec
x 1
Communication speed
4
sec
4
sec
x 1
COUNTIS E13/E14 - Ref.: 542 101 A 8. Operation
The total and partial active energy values are accessible via the dedicated buttons. Pressing the appropriate button
several times displays all the available measurements. All the available information and measurements are described
in the following diagram:
Tariff T1
Ea+ (kWh)/P+ (kW)
______________
Tariff T1
Ea- (kWh)/P- (kW)
______________
Tariff T1
Er+ (kvarh)/Q+ (kvar)
______________
Tariff T1
Er- (kva
COUNTIS E13/E14 - Ref.: 542 101 A COUNTIS E13/E14 MODBUS
8.1. Detailed view of menus
Ea+ (kWh)/P (kW) Tariff T1/T2*
or
Ea- (kWh)/P (kW) Tariff T1/T2*
* Depending on the current tariff and energy
x 1
Ea+ (kWh) Tariff T1
Ea- (kWh) Tariff T1
Er+ (kVarh) Tariff T1
Er- (kVarh) Tariff T1
Ea+ (kWh) Tariff T2
Ea- (kWh) Tariff T2
Er+ (kVarh) Tariff T2
Er- (kVarh) Tariff T2
P (kW) and Q (kvar) power values are
only displayed for the current tariff
x 7
MODBUS
x 1
COUNTIS E13/E14 - Ref.: 542 101 A 9. Diagnostic message
•� When these messages are displayed, the meter has malfunctioned and should be replaced.
10. Assistance
Causes
Solutions
Error message
Check that the meter is working correctly
COUNTIS E13/E14 - Ref.: 542 101 A COUNTIS E13/E14 MODBUS
11. Electrical and Technical characteristics
Generalities
Case
3 DIN 43880 modules
Mounting
DIN EN 60715 rail
Width
54 mm
Operating specifications
Connectivity
230V 2-wire single phase
Storage�of�energy�values�and�configuration
Yes: EEPROM
Tariff�display�identifier
T1 and T2
Power supply
Certified�voltage�Un�
230 VAC
Operating voltage range
110 ... 276 VAC
Frequency range
48 ..
COUNTIS E13/E14 - Ref.: 542 101 A 12. MID compliance
The COUNTIS E14 meter complies with the MID directive for connection of single-phase networks (see "5.4.
Connections", page 6).
After�connecting�the�product,�check�that�the�terminal�covers�are�correctly�fitted�and�secured�by�the�two�plastic�seals�
supplied with the product (see "5.5. Sealable covers", page 6). If the terminal covers must be removed, ensure
that se
Ref. 542 101 B - EN- 03/14
www.socomec.com
hEAd offICE
SOCOMEC GROUP
S.A. SOCOMEC capital 10 816 800€
R.C.S. Strasbourg B 548 500 149
B.P. 60010 - 1, rue de Westhouse
F-67235 Benfeld Cedex - FRANCE
Tel. +33 3 88 57 41 41
Fax +33 3 88 74 08 00
[email protected]
Socomec worldwide
BELGIUM
Critical Power / Power Control & Safety /
Energy Efficiency / Solar Power Power
Tel. +32 2 340 02 30
Fax +32 2 346 28 99
[email protected]
FRANCE
Critical Power