socomec COUNTIS E13 Operating Instructions Manual

Text of socomec COUNTIS E13 Operating Instructions Manual

COUNTIS E13/E14 - Ref.: 542 101 A

Contents 1. DOCUMENTATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 2. DANGER AND WARNING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 2.1. RISK OF ELECTROCUTION, BURNS OR EXPLOSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 2.2.
COUNTIS E13/E14 - Ref.: 542 101 A COUNTIS E13/E14 MODBUS 1. Documentation All the documentation for COUNTIS E13/E14 equipment is available online at: www.socomec.com/en/countis-e1x 2. Danger and warning This equipment must only be installed by professionals. The manufacturer shall not be held responsible for failure to comply with the instructions in this manual. 2.1. Risk of electrocution, burns or explosion •� �The�device�must�be�installe
COUNTIS E13/E14 - Ref.: 542 101 A 4. Overview COUNTIS E13 and E14 are active modular electrical energy meters for monitoring kWh. They are designed for single- phase networks and enable direct connection up to 80A. They are equipped with a MODBUS communication bus. 4.1. Main functions •� Measurement and display: - active and reactive energy (T1 and T2): Ea+/Ea-/Er+/Er- - of active and reactive power: P1+/P1-/Q1+/Q1- •� Management of two tariffs:
COUNTIS E13/E14 - Ref.: 542 101 A COUNTIS E13/E14 MODBUS 5. Installation 5.1. Recommendations •� avoid proximity to systems which generate electromagnetic interference, •� avoid vibrations with accelerations in excess of 1 G for frequencies below 50 Hz. 5.2. Dimensions (mm) 64 45 6 90 44 L1 N L1 1 2 3 4 6 5 54 5.3. Terminals 64 45 6 90 44 L1 N L1 1 2 3 4 6 5 54 0.61 in/15.5 mm PZ2 flexible or rigid 7 to 50 mm2 2 Nm 0.35 in/9 mm PZ2 flexible 1.5
COUNTIS E13/E14 - Ref.: 542 101 A 5.4. Connections 5.4.1. 2-wire connection - single-phase load monitoring L1 L1 N 230 VAC fn = 50 Hz L1 L’ N 80A 6 1 5 4 3 2 230 VAC 120Ω - + NC T1/2 COM RS485 Modbus/Jbus MODBUS 1: Activation of 120 ohm terminating resistors by connecting terminals 1 and 2. 2: - 3: + 4: NC (not connected). Tariff 5-6: Change of tariff only for COUNTIS E14: 0 VAC -> Tariff 1 230 VAC -> Tariff 2 (change of tariff via MODBUS f
COUNTIS E13/E14 - Ref.: 542 101 A COUNTIS E13/E14 MODBUS 6. MODBUS communication 6.1. General Information MODBUS® communication is performed via a RS485 serial port (2- or 3-wire) which enables products to be used from a PC or an API. On�a�standard�configuration,�a�RS485�port�can�be�used�to�connect�32�products�to�a�PC�or�a�PLC�across�1200� meters. R=120Ω R=120Ω R=120Ω R=120Ω R=120Ω R=120Ω R=120Ω
COUNTIS E13/E14 - Ref.: 542 101 A 7. Programming 7.1. Navigation principle The�programming�mode�enables�the�communication�parameters�to�be�modified.�The�process�to�navigate�inside�the� programming mode is described in the following steps: Access to item to set > 4 sec Enter programming mode (press button for 4 seconds) Value to be modified > 4 sec Validate the value 7.2. Programming menu overview By pressing for 4 seco
COUNTIS E13/E14 - Ref.: 542 101 A COUNTIS E13/E14 MODBUS 7.3. Detailed view of MODBUS programming menu x 10 Address 4 sec 4 sec x 1 Communication speed 4 sec 4 sec x 1
COUNTIS E13/E14 - Ref.: 542 101 A 8. Operation The total and partial active energy values are accessible via the dedicated buttons. Pressing the appropriate button several times displays all the available measurements. All the available information and measurements are described in the following diagram: Tariff T1 Ea+ (kWh)/P+ (kW) ______________ Tariff T1 Ea- (kWh)/P- (kW) ______________ Tariff T1 Er+ (kvarh)/Q+ (kvar) ______________ Tariff T1 Er- (kva
COUNTIS E13/E14 - Ref.: 542 101 A COUNTIS E13/E14 MODBUS 8.1. Detailed view of menus Ea+ (kWh)/P (kW) Tariff T1/T2* or Ea- (kWh)/P (kW) Tariff T1/T2* * Depending on the current tariff and energy x 1 Ea+ (kWh) Tariff T1 Ea- (kWh) Tariff T1 Er+ (kVarh) Tariff T1 Er- (kVarh) Tariff T1 Ea+ (kWh) Tariff T2 Ea- (kWh) Tariff T2 Er+ (kVarh) Tariff T2 Er- (kVarh) Tariff T2 P (kW) and Q (kvar) power values are only displayed for the current tariff x 7 MODBUS x 1
COUNTIS E13/E14 - Ref.: 542 101 A 9. Diagnostic message •� When these messages are displayed, the meter has malfunctioned and should be replaced. 10. Assistance Causes Solutions Error message Check that the meter is working correctly
COUNTIS E13/E14 - Ref.: 542 101 A COUNTIS E13/E14 MODBUS 11. Electrical and Technical characteristics Generalities Case 3 DIN 43880 modules Mounting DIN EN 60715 rail Width 54 mm Operating specifications Connectivity 230V 2-wire single phase Storage�of�energy�values�and�configuration Yes: EEPROM Tariff�display�identifier T1 and T2 Power supply Certified�voltage�Un� 230 VAC Operating voltage range 110 ... 276 VAC Frequency range 48 ..
COUNTIS E13/E14 - Ref.: 542 101 A 12. MID compliance The COUNTIS E14 meter complies with the MID directive for connection of single-phase networks (see "5.4. Connections", page 6). After�connecting�the�product,�check�that�the�terminal�covers�are�correctly�fitted�and�secured�by�the�two�plastic�seals� supplied with the product (see "5.5. Sealable covers", page 6). If the terminal covers must be removed, ensure that se

Ref. 542 101 B - EN- 03/14

www.socomec.com hEAd offICE SOCOMEC GROUP S.A. SOCOMEC capital 10 816 800€ R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse F-67235 Benfeld Cedex - FRANCE Tel. +33 3 88 57 41 41 Fax +33 3 88 74 08 00 [email protected] Socomec worldwide BELGIUM Critical Power / Power Control & Safety / Energy Efficiency / Solar Power Power Tel. +32 2 340 02 30 Fax +32 2 346 28 99 [email protected] FRANCE Critical Power