Puls Dimension CP Series Quick Start Manual
File Specifications
| Brand: | Puls |
| Category: | Power Supply |
| Model: | Dimension CP Series (Quick Start Manual), prXCAhiOnsO1g |
| File Type: | |
| File Size: | — |
| Pages: | 29 pages |
Download PDF
Download Puls Dimension CP Series Manual (29 pages)Read Online:
Read the Puls Dimension CP Series Quick Start Manual online using the built-in PDF viewer.
Key Pages of Document
POWER SUPPLY � AC 100-240V Wide-range Input � Width only 39mm � +10% (5.4A) continuous current up to +60°C � +20% (6A) continuous current up to +45°C � Efficiency up to 95.5% � Excellent Partial Load Efficiency � Safe HiccupPLUS Overload Mode � Active Power Factor Correction (PFC) � M ...
INDEX Page Page 1. Intended Use .......................................................3 2. Installation Requirements...................................3 3. AC-Input...............................................................4 4. DC-Input...............................................................5 ...
1. INTENDED USE This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office, communication, and instrumentation equipment. Do not use this power supply in equipment, where malfunction may cause severe personal injury or t ...
3. AC-INPUT AC input Nom. AC 100-240V Suitable for TN-, TT- and IT mains networks AC input range Min. 85-264Vac Continuous operation Below 90Vac, reduce output current according to Fig. 3-5. Min. 264-300Vac For maximal 500ms Allowed voltage L or N to earth Max. 300Vac Continuous according to IEC 62477-1 ...
Fig. 3-5 Derating requirements C Allowed Output Current at 48V 0 85 264Vdc 1A 2A 3A 4A 5A 6A 90 5.4A A DC Input Voltage A... below 60°C ambient temperature B... below 55°C ambient temperature C... below 45°C ambient temperature B 4. DC-INPUT DC input Nom. DC 110-150V ±20% DC input range Min. 88-180 ...
5. INPUT INRUSH CURRENT An active inrush limitation circuit (NTCs, which are bypassed by a relay contact) limits the input inrush current after turn-on of the input voltage. The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. AC 100V AC 120V AC 2 ...
6. OUTPUT Output voltage Nom. 48V Adjustment range Min. 48-56V Guaranteed value Max. 58.0V This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not a guaranteed value which can be achieved. Factory settings Typ. 48.0V ±0.2%, at fu ...
Fig. 6-1 Output voltage vs. output current, typ. Fig. 6-2 Dynamic output current capability, typ. Output Voltage 0 0 6 8 16 24 56V 32 40 48 10A 4 1 2 5 7 8 3 9 Adjustment Range Output Current Continuous current Factory setting HiccupPLUS mode Output Voltage (dynamic behavior, < 12ms) 0 0 8 16 24 56V ...
8. DC-OK RELAY CONTACT This feature monitors the output voltage on the output terminals of a running power supply. Contact closes As soon as the output voltage reaches typ. 90% of the adjusted output voltage level. Contact opens As soon as the output voltage dips more than 10% below the adjusted output v ...
9. EFFICIENCY AND POWER LOSSES AC 100V AC 120V AC 230V Efficiency Typ. 93.0% 93.8% 95.5% At 48V, 5.4A Typ. 92.7% 93.6% 95.4% At 48V, 6A (Power Boost) Average efficiency*) Typ. 92.8% 93.4% 94.5% 25% at 1.3A, 25% at 2.6A, 25% at 3.9A. 25% at 5.4A Power losses Typ. 2.5W 2.3W 2.0W At 48V, 0A Typ. 10.2W 9.5W ...
⚠️ Download Safety
The Power Supply Quick start manual (29 pages) is completely safe to download (last scan date: 22/07/2026).