YASKAWA GPD-506V Technical Manual
Read Online
Read the YASKAWA GPD-506V Technical Manual online using the built-in PDF viewer.
Key Pages of Document
CONTENTS SUBJECT PARAGRAPH PAGE WARNING/CAUTION STATEMENTS ................................................... ii GPD 506/P5 SIMPLIFIED START-UP PROCEDURE ........................... v QUICK REFERENCE FOR GPD506/P5 PARAMETERS ......................xi CURRENT RATINGS & HORSEPOWER RANGE ............................... xii 1 INSTALLATION ................................................................................... 1-1 1.1 General ................. ...
5.15 Jog Reference ..................................................................................... 5-20 5.15.1 Local/Remote Changeover ................................................................. 5-21 5.16 Modbus Control ................................................................................... 5-22 5.16.1 Miscellaneous Protective Functions .................................................... 5-25 5.17 Momentary Power Loss Ride-t ...
YASKAWA manufactures component parts that can be used in a wide variety of industrial applications. The selection and application of YASKAWA products remain the responsibility of the equipment designer or end user. YASKAWA accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any YASKAWA product be incorporated into any product or design as the exclusive o ...
parameter must be set to " 0 ", " 1 ", " 2 ", or " 3 " to operate the drive. (See paragraph 5.23 for additional information.) 8 = Factory 2-Wire Control Initialization (Maintained RUN Contact) 9 = Factory 3-Wire Control Initialization (Momentary START/STOP Contact) Entering either Initialization code resets all parameters, and automatically returns n001 setting to " 1 " ...
- v - This procedure is a simplified step by step guide to installing, programming, and using a GPD506/P5 drive. It highlights several common installation configurations. INSTALLATION 1. Be certain your input voltage source, motor and drive nameplates are all marked either 230V, 460V or 600V. Other voltages can be used, but require additional programming. CAUTION: Verify that the input voltage matches the drive� ...
4. Replace cover and apply input power – digital operator shows “Frequency Ref 00.0 Hz”; DRIVE, SEQ, REF & STOP LEDs are on. Press the LOCAL / REMOTE button. The SEQ & REF LEDs should go off. Press and hold the UP ARROW button until the display shows “6.0 Hz, then press the ENTER button. Press the RUN button and note the direction of motor rotation. If rotation is incorrect, remove power, wait for charge light to go out, then switch ...
- vii - When the drive is set up with the sequence and the reference coming from the digital operator, it is in “Local” control. Local control is often used during startup to verify motor operation, rotation, etc. The drive can be temporarily placed in “Local” control simply by pressing the LOCAL / REMOTE key. When the drive is in “Local” control, the SEQ and REF LEDs are off. If p ...
(4 – 20 mA) - viii - This configuration is used when the start & stop signals and the frequency reference come from a remote source, such as a PLC. It can also be used with a maintained switch when it is desirable to have the drive restart on restoration of power. It should not be used where safety of attending personnel might be threatened by a restart. OPERATION: • Close (K ...
- ix - This configuration is best when a person rather than an external controller (PLC, relay, etc.) controls the drive. Both potentiometers ((R1) & (R2)) should have a resistance value between 2000Ω and 3000Ω and be rated for at least 1 Watt. The trim pot is optional, but without it the manual speed pot will output 10V (60 Hz) at just two- thirds of its rotation. OPERATION: • Close pushbu ...
Sequence – refers to how the drive is started, stopped, and told which direction to run. When the sequence comes from the digital operator (local), the drive is started and stopped using the “RUN” and “STOP” keys on the digital operator, and direction is given via the “FWD/REV” key. Sequence can also come from the drive’s control terminals (remote) using either two-wire or three–wire control. The sequence inputs to ...
n001 1 5.23 n002 SEQ = TRM REF = TRM (3) p. A1-1 230.0 (230V) or n003 460.0 5.28 B (460V) or 575.0 (575V) n004 Ramp to STOP (0) 5.25 n005 Rotate C.C.W. (0) p. A1-1 n006 REV Allowed (0) p. A1-2 n007 Enabled (1) p. A1-2 n008 Enabled (1) p. A1-2 n009 Enter Key Used (1) p. A1-2 n010 1 5.28 A n011 60.0 (Note 2) 5.28 230.0 (230V) or n012 460.0 (Note 2) p. A1-2 (460V) or 575.0 (575V) n013 60.0 (Note 2) p. A1-2 n014 3.0 (Note 2) p. A1-3 n015 17.2 (Note 2) p ...
Current Ratings & Horsepower Range RATED CURRENT NOMINAL HORSEPOWER NEW DRIVE OLD DRIVE INPUT RATING (AMPS) (120% OL) MODEL NO. MODEL NO. CIMR-P5M GPD506V- 3.2 0.75 20P41F A003 6 1 & 1.5 20P71F A006 8 2 21P51F A008 11 3 22P21F A011 17.5 5 23P71F A017 27 7.5 & 10 25P51F A027 2 36 15 27P51F A036 3 54 20 20111F A054 0 68 25 20151F A068 V 80 30 20181F A080 104 40 20221F A104 130 50 20300F A130 160 60 20370F A160 192 75 20450F A192 248 100 20550F A248 3 ...
width modulated special purpose AC motor drive which generates an adjustable voltage/frequency three phase output for complete speed control of most conventional squirrel cage induction motors. Automatic stall prevention and voltage boost prevents nuisance tripping during load or line side transient conditions. The drive will not induce any voltage line notching di ...
1.4.1 Main Circuit Input/Output Complete wire interconnections according to Table 1-2, Figure 1-3 and Figure 1-4. Be sure to observe the following: • Use 600V vinyl-sheathed wire or equivalent. Wire size and type should be determined by local electrical codes. • Avoid routing power wiring near equipment sensitive to electrical noise. • Avoid running input and ...
RATING TERMINAL SYMBOL SCREW AWG MM2 20P41F, A003, L1 (R), L2 (S), L3 (T), - , ⊕1, ⊕2, B1, B2, T1 (U), T2 (V), T3 (W), M4 14 - 10 2 - 5.5 20P71F A006 21P51F A008 L1 (R), L2 (S), L3 (T), - , ⊕1, ⊕2, B1, B2, T1 (U), T2 (V), T3 (W) M4 14 - 10 2 - 5.5 M4 12 - 10 3.5 - 5.5 22P21F A011 L1 (R), L2 (S), L3 (T), - , ⊕1, ⊕2, B1, B2, T1 (U), T2 (V), T3 (W), M4 12 - 10 3.5 - 5.5 23P71F A017 L1 (R), L2 (S) ...
MODEL NO. TERMINAL SYMBOL SCREW AWG mm2 45P51F B014 L1 (R), L2 (S), L3 (T), - , ⊕1, ⊕2, B1, B2, T1 (U), T2 (V), T3 (W) M4 12 - 10 3.5 - 5.5 M4 12 - 10 3.5 - 5.5 47P51F B021 L1 (R), L2 (S), L3 (T), - , ⊕1, ⊕2, B1, B2, T1 (U), T2 (V), T3 (W) M4 8 - 6 8 - 14 M4 8 - 6 8 - 14 40111F B027 L1 (R), L2 (S), L3 (T), - , ⊕1, ⊕2, B1, B2, T1 (U), T2 (V), T3 (W) M5 8 - 6 8 - 14 M6 8 8 40151F B034 L1 (R), L2 (S) ...
MODEL NO. TERMINAL SYMBOL SCREW AWG mm2 51P51F L1 (R), L2 (S), L3 (T), - , ⊕1, ⊕2, B1, B2, T1 (U), T2 (V), T3 (W) M4 14 - 10 2 - 5.5 52P21F 53P71F L1 (R), L2 (S), L3 (T), - ,⊕1, ⊕2, B1, B2, T1 (U), T2 (V), T3 (W) M4 14-10 2-5.5 12-10 3.5-5.5 55P51F L1 (R), L2 (S), L3 (T), - , ⊕1, ⊕2, B1, B2, T1 (U), T2 (V), T3 (W) M4 12-10 3.5-5.5 57P51F L1 (R), L2 (S), L3 (T), - , ⊕1, ⊕2, B1, B2, T1 (U), T2 ( ...
TERMINAL FUNCTION P 3 TO 40 HP L1 (R) Three phase Main circuit input power supply L2 (S) 200 / 208 / 220V at 50 Hz; 200 / 208 / 220 / 230V at 60 Hz L3 (T) L11 Three phase Main circuit L21 – – – – – – input power supply L31 (same as at L1, L2 & L3) T1 (U) Three phase AC output to motor T2 (V) 0V to max. input voltage level T3 (W) B1 B2 DB Unit terminals (B1 & B2) – – – – – – - ⊕1 DC Reactor terminals (⊕1 & ⊕2) ...
FUNCTION TERMINAL CIMR-P5M51P51F to P5M50151F CIMR-P5M50181F to P5M50221F CIMR-P5M50301F to P5M51600F L1 (R) Three phase Main circuit input power supply L2 (S) 500 / 575 / 600V at 50 Hz / 60HZ L3 (T) T1 (U) Three phase AC output to motor T2 (V) 0V to max. input voltage level T3 (W) DB Resistor terminals (B1 & B2) - ⊕1 ⊕2 l1 (r) Power for heat sink fan: l2 (s) l1 to l2 : 600 VAC Table 1-2. Terminal Functions and Voltages of Main Ci ...