CE compliant according

to European regulations With TROXNETCOM as an option ATEX certification Tested to VDI 6022 06/2016 H Y G I E N I S C H G E T E S T E T V D I 6 0 2 2 – DE/en Fire dampers Type FK-EU 1 Rectangular fire damper for the isolation of duct penetrations between fire compartments, for a variety of installation situations, available in many d ...

1.1 – 2

Correct use 1.1 – 10 Order code 1.1 – 16 Installation kit – installation with flexible ceiling joint 1.1 – 18 Installation kit – for installation on the face of solid walls 1.1 – 19 Installation kit – for installation adjacent to solid walls 1.1 ...

06/2016 – DE/en

FK-EU 1 K4 – 1.1 – 3 Variants Product examples FK-EU with fusible link FK-EU with spring return actuator FK-EU with spring return actuator (explosion- proof) FK-EU as air transfer damper ...

– TROX fire dampers of Type FK-EU, with CE

marking and declaration of performance, for the isolation of duct penetrations between fire compartments in the event of a fire – To prevent the propagation of fire and smoke through ductwork to adjacent designated fire compartments Classifi ...

06/2016 – DE/en

FK-EU 1 Other components: – Damper blade shafts and driving linkage made of stainless steel – Brass or stainless steel bearings – Seals of polyurethane or elastomer The construction variants with stainless steel or powder-coated casing meet even more critical requirements for corrosion protection. Deta ...

In the event of a fire, fire dampers shut

automatically to prevent the propagation of fire and smoke through ductwork to adjacent designated fire compartments. In the event of a fire, the damper is triggered at 72 °C or at 95 °C (use in warm air ventilation systems) by a fus ...

06/2016 – DE/en

FK-EU 1 Functional description The spring return actuator enables the motorised opening and closing of the damper blade; it can be activated by the central BMS. In the event of a fire, the damper is triggered thermoelectrically at 72 °C or 95 °C (use in warm air ventilation systems). As long as power is su ...

The fire damper is used as a shut-off device to

prevent fire and smoke from spreading through ducting in areas with potentially explosive atmospheres. The fire damper is suitable for supply air and extract air systems in potentially explosive atmospheres. For details on the op ...

06/2016 – DE/en

FK-EU 1 Functional description Air transfer dampers are designed to shut off openings for air transfer in fire resistant internal walls and ceiling slabs. To prevent smoke from spreading in buildings, it is extremely important that the smoke is detected at an early stage. Duct smoke detector Type RM-O-3-D is ...

– Approved only for use in ventilation and air

conditioning sytems – If the fire damper is installed in a solid wall, solid ceiling slab, lightweight partition wall or shaft wall with a lower fire resistance class than that of the fire damper, the fire resistance class of the wall or ...