Siemens FSV Instructions, Installation, Operation, Maintenance

Text of the manual

Vacuum Circuit Breakers (Vehicle)

Type FSV 5kV to 15kV

These instructions do not purport to cover all details or variations in equip-

ment, nor to provide for every possible contingency to be met in connec- tion with installation, operation, or maintenance. Should further informa- tion be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the m

Table of Contents

Vacuum Circuit Breakers (Vehicle) 1 Introduction and Safety ........................................................... 2 Introduction ................................................................................. 2 Qualified Person .......................................................................... 2 Signal Words ................

Introduction and Safety

Introduction The FSV family of vacuum circuit breakers is designed to meet all the applicable ANSI, NEMA and IEEE standards. Successful application and operation of this equipment de- pends as much upon proper installation and maintenance by the user as it does upon the careful design and fabrica- tion by Siemens. The purpose of this

Receiving, Handling and Storage

Introduction This manual covers the Receiving, Handling and Storage instructions for vacuum circuit breakers shipped separately from the switchgear. This section of the manual is intended to help the user identify, inspect and protect the circuit breaker prior to its installation. Receiving Procedure Make a physical inspect

Vehicle Function and Operational Interlocks

Type FSV vacuum circuit breakers are comprised of the interrupter/operator module fitted to a vehicle. This inter- rupter/operator module is an integral arrangement of op- erating mechanism, dielectric system, vacuum interrupt- ers, and means of connecting the primary circuit. The ve- hicle su

Details of Closed Circuit Breaker Racking Interlock

5 Vehicle Description Continued full CCW rotation of the interlock bell crank causes the plunger to clear the cubicle rail allowing the “open trip free circuit breaker” to be moved from the con- nected position. The lower interlock bell crank is returned to the plunger engaged position, fully

As the push rod rises, its “mushroom” headed append-

age, within the circuit breaker mechanism enclosure, causes the “interlock” levers to rotate, elevating the “trip free push rod and cam”. This cam encounters the “trip latch lever”, and after typically 8 to 12mm (0.3 to 0.5 inches) of motion forces the mechanism, throug

Figure 4. 1200, 2000, and 3000 Amp Continuous Current Interlock Orientation

Figure 5. Control Cable Connection Detail Plunger Position Mechanical Interlock Switch