Siemens FSV Instructions, Installation, Operation, Maintenance
Text of the manual
Vacuum Circuit Breakers (Vehicle)
Type FSV
5kV to 15kV
These instructions do not purport to cover all details or variations in equip-
ment, nor to provide for every possible contingency to be met in connec-
tion with installation, operation, or maintenance. Should further informa-
tion be desired or should particular problems arise which are not covered
sufficiently for the purchaser’s purposes, the m
Table of Contents
Vacuum Circuit Breakers (Vehicle)
1
Introduction and Safety ........................................................... 2
Introduction ................................................................................. 2
Qualified Person .......................................................................... 2
Signal Words ................
Introduction and Safety
Introduction
The FSV family of vacuum circuit breakers is designed to
meet all the applicable ANSI, NEMA and IEEE standards.
Successful application and operation of this equipment de-
pends as much upon proper installation and maintenance
by the user as it does upon the careful design and fabrica-
tion by Siemens.
The purpose of this
Receiving, Handling and Storage
Introduction
This manual covers the Receiving, Handling and Storage
instructions for vacuum circuit breakers shipped separately
from the switchgear. This section of the manual is intended
to help the user identify, inspect and protect the circuit
breaker prior to its installation.
Receiving Procedure
Make a physical inspect
Vehicle Function and Operational Interlocks
Type FSV vacuum circuit breakers are comprised of the
interrupter/operator module fitted to a vehicle. This inter-
rupter/operator module is an integral arrangement of op-
erating mechanism, dielectric system, vacuum interrupt-
ers, and means of connecting the primary circuit. The ve-
hicle su
Details of Closed Circuit Breaker Racking Interlock
5
Vehicle Description
Continued full CCW rotation of the interlock bell crank
causes the plunger to clear the cubicle rail allowing the
“open trip free circuit breaker” to be moved from the con-
nected position.
The lower interlock bell crank is returned to the plunger
engaged position, fully
As the push rod rises, its “mushroom” headed append-
age, within the circuit breaker mechanism enclosure,
causes the “interlock” levers to rotate, elevating the “trip
free push rod and cam”. This cam encounters the “trip
latch lever”, and after typically 8 to 12mm (0.3 to 0.5 inches)
of motion forces the mechanism, throug
Figure 4. 1200, 2000, and 3000 Amp Continuous Current Interlock Orientation
Figure 5. Control Cable Connection Detail
Plunger Position Mechanical Interlock Switch