Operating and assembly instructions

Medium Pressure Regulator Types 057/058, 070/071 PS 25 bar Contents 1. General 1.1 Information 2. Hazard warnings 2.1 Safety related terms 2.2 Safety advisory notice 2.3 Qualified personnel 2.4 Unauthorized alterations and spare parts 2.5 Permissible operating mode 2.6 Inadmissible operating mode 3. Handling 3.1 Tran

2.4 Unauthorized alterations and spare parts

Modification or alteration of the medium pressure regulator types 057/058, 070/071 is not permitted. Original drawings and accessories authorised by the manufacturer serve for safety. The use of other parts or unauthorised modifications to the medium pressure regulator types 057/058, 070/071 by third parties inva

6.3 Leak test

CAUTION: The control device must not be included in a strength test (design review) of the entire installation. • Close all shut-off valves of the connected devices. • apply test pressure according to TRF 2012 • wait for temperature adjustment • test duration 10 minutes (the pressure must not drop) • spray all connections with foamin

11. Drawing (MDR-057)

1. inlet connection G 1/2“IG 2. pressure regulator 1st stage 3. outlet connection G 1/2"IG 12. Technical Specification (MDR-057) Max. permissible pressure: PS 16 Connection at inlet: G 1/2” Nominal flow Mg: 24 kg/h Connection at outlet: G 1/2” Inlet pressure p: 1,8-16 bar Temperature range -40 °C to +50 °C Nominal outlet pre