MR ETOS ED Operating Instructions Manual
Text of the manual
© All rights reserved by Maschinenfabrik Reinhausen
Dissemination and reproduction of this document and use and disclosure of its content are strictly prohibited
unless expressly permitted.
Infringements will result in liability for compensation. All rights reserved in the event of the granting of patents,
utility models or designs.
The product may have been altered since this document was published.
We reserve the right to change the technical data, design and scope of supply.
Generally the information provided and agreements made when processing the individual quotations and orders
are binding.
The original operating instructions were written in German.
Table of contents
Maschinenfabrik Reinhausen GmbH 2020
3
6385142/08 EN
ETOS® ED
Table of contents
1
Introduction....................................................................................................................... 12
1.1
Manufacturer..................................................................................................................................... 12
1.2
Completeness................................................................................................................................... 12
1.3
Safekeeping...................................................................................................................................... 12
1.4
Notation conventions ........................................................................................................................ 12
1.4.1
Hazard communication system........................................................................................................................... 12
1.4.2
Information system.............................................................................................................................................. 14
1.4.3
Instruction system ............................................................................................................................................... 14
1.4.4
Typographic conventions .................................................................................................................................... 15
2
Safety................................................................................................................................. 16
2.1
Appropriate use ................................................................................................................................ 16
2.2
Fundamental safety instructions....................................................................................................... 17
2.3
Personnel qualification...................................................................................................................... 20
2.4
Personal protective equipment ......................................................................................................... 21
3
IT security.......................................................................................................................... 22
4
Product description.......................................................................................................... 26
4.1
Scope of delivery .............................................................................................................................. 26
4.2
Function description.......................................................................................................................... 26
4.3
Performance features ....................................................................................................................... 26
4.4
Variants............................................................................................................................................. 28
4.4.1
ETOS® ED L/ETOS® ED L-S............................................................................................................................. 28
4.4.2
ETOS® ED XL .................................................................................................................................................... 29
4.5
Design............................................................................................................................................... 30
4.5.1
Indication field ..................................................................................................................................................... 32
4.5.2
Anti-condensation heater .................................................................................................................................... 32
4.5.3
Swing frame/terminal rail..................................................................................................................................... 32
4.5.4
Position transmitter equipment............................................................................................................................ 33
4.5.5
Transmission gear cover plate............................................................................................................................ 33
4.5.6
Ambient temperature sensor............................................................................................................................... 34
4.5.7
ISM assemblies................................................................................................................................................... 35
4.6
Nameplate ........................................................................................................................................ 41
4.7
Protective devices............................................................................................................................. 42
Table of contents
Maschinenfabrik Reinhausen GmbH 2020
4
6385142/08 EN
ETOS® ED
4.8
Safety markings................................................................................................................................ 43
4.9
Emergency operation during switching blocking (X100 bridge)........................................................ 43
4.10
Visualization...................................................................................................................................... 44
4.10.1
Main screen......................................................................................................................................................... 44
4.10.2
Additional operating controls and display elements when using the MControl touch panel (optional)................ 49
4.10.3
Operating concept............................................................................................................................................... 49
5
Packaging, transport and storage .................................................................................. 55
5.1
Packaging......................................................................................................................................... 55
5.1.1
Suitability............................................................................................................................................................. 55
5.1.2
Markings.............................................................................................................................................................. 56
5.2
Transportation, receipt and handling of shipments........................................................................... 56
5.3
Storage of shipments........................................................................................................................ 57
5.4
Unpacking shipments and checking for transportation damages ..................................................... 58
6
Mounting ........................................................................................................................... 60
6.1
Attaching the control cabinet to the transformer............................................................................... 60
6.2
Mounting drive shafts and bevel gear............................................................................................... 63
6.3
Centering on-load tap-changer and motor-drive unit........................................................................ 63
6.4
Connecting the ISM® assemblies .................................................................................................... 70
6.4.1
Cable recommendation (ISM® assemblies)........................................................................................................ 70
6.4.2
Information about connecting serial interfaces RS232 and RS485..................................................................... 71
6.4.3
Notes on connecting to the MR sensor bus ........................................................................................................ 73
6.4.4
Information about connecting analog sensors .................................................................................................... 78
6.4.5
Electromagnetic compatibility.............................................................................................................................. 81
6.4.6
Connecting cables to the system periphery ........................................................................................................ 84
6.4.7
Wiring the device................................................................................................................................................. 84
6.4.8
Mounting terminating resistor of CAN bus .......................................................................................................... 86
6.5
Connecting the motor-drive unit........................................................................................................ 86
6.5.1
Cable recommendation....................................................................................................................................... 87
6.5.2
Electrical connection ........................................................................................................................................... 88
7
Commissioning................................................................................................................. 89
7.1
Starting up motor-drive unit .............................................................................................................. 89
7.2
Tests on motor-drive unit.................................................................................................................. 90
7.2.1
Checking correct electric switch-off..................................................................................................................... 90
7.2.2
Checking mechanical and electric end stop of on-load tap-changer/de-energized tap-changer and motor-drive
unit ...................................................................................................................................................................... 91
Table of contents
Maschinenfabrik Reinhausen GmbH 2020
5
6385142/08 EN
ETOS® ED
7.2.3
Checking tripping of motor protective switch....................................................................................................... 91
7.2.4
Checking functional reliability.............................................................................................................................. 92
7.3
Tests on the transformer................................................................................................................... 92
7.3.1
High-voltage tests on the transformer................................................................................................................. 92
7.3.2
Dielectric tests on transformer wiring.................................................................................................................. 93
7.4
Transporting transformer to the operating site.................................................................................. 93
7.5
Commissioning the transformer at the operating site ....................................................................... 93
7.6
Visualization...................................................................................................................................... 94
7.6.1
Establishing connection to visualization.............................................................................................................. 94
7.6.2
Setting the language ........................................................................................................................................... 97
7.6.3
Setting date and time .......................................................................................................................................... 98
7.6.4
Commissioning wizard ........................................................................................................................................ 98
7.6.5
Checking measured values and status of digital inputs and outputs .................................................................. 99
7.6.6
Checking the temperature measurement............................................................................................................ 99
8
Operation......................................................................................................................... 101
8.1
Operating the motor-drive unit remotely ......................................................................................... 101
8.2
Operating motor-drive unit locally................................................................................................... 101
8.3
Operating the motor-drive unit with the hand crank........................................................................ 102
9
Visualization.................................................................................................................... 104
9.1
Establishing connection to visualization ......................................................................................... 104
9.2
General........................................................................................................................................... 107
9.2.1
Setting general device functions ....................................................................................................................... 108
9.2.2
Set up automatic logout .................................................................................................................................... 109
9.2.3
Activating/deactivating service user access...................................................................................................... 110
9.3
Configuring the network.................................................................................................................. 111
9.4
MQTT.............................................................................................................................................. 114
9.5
Setting the device time ................................................................................................................... 116
9.5.1
Time synchronization via PTP........................................................................................................................... 117
9.6
Configuring syslog .......................................................................................................................... 118
9.7
Setting the screensaver.................................................................................................................. 120
9.8
SCADA ........................................................................................................................................... 121
9.8.1
Configuring IEC 61850 (optional)...................................................................................................................... 122
9.8.2
Configuring IEC 60870-5-101 (optional) ........................................................................................................... 124
9.8.3
Configuring IEC 60870-5-103 (optional) ........................................................................................................... 127
9.8.4
Configuring IEC 60870-5-104 (optional) ........................................................................................................... 129
Table of contents
Maschinenfabrik Reinhausen GmbH 2020
6
6385142/08 EN
ETOS® ED
9.8.5
Configuring Modbus (optional).......................................................................................................................... 131
9.8.6
Configuring DNP3 (optional) ............................................................................................................................. 133
9.8.7
Configuring GOOSE (optional).......................................................................................................................... 135
9.8.8
Configure data points (optional)........................................................................................................................ 140
9.8.9
Display status of the SCADA connection.......................................................................................................... 147
9.9
Name plate ..................................................................................................................................... 148
9.9.1
Enter the name plate data................................................................................................................................. 148
9.9.2
Displaying the name plate................................................................................................................................. 149
9.10
Linking signals and events.............................................................................................................. 149
9.10.1
Linking functions ............................................................................................................................................... 150
9.10.2
Linking digital outputs........................................................................................................................................ 151
9.10.3
Linking control system messages ..................................................................................................................... 151
9.11
Cooling system control (optional) ................................................................................................... 152
9.11.1
Configuring cooling stages................................................................................................................................ 153
9.11.2
Set the operating mode..................................................................................................................................... 155
9.11.3
Deactivating cooling system control.................................................................................................................. 155
9.11.4
Configuring load-dependent mode.................................................................................................................... 155
9.11.5
Configuring periodic mode ................................................................................................................................ 157
9.11.6
Configuring alternating mode............................................................................................................................ 158
9.11.7
Configuring the frequency-based cooling system control ................................................................................. 159
9.11.8
Displaying status of cooling stages................................................................................................................... 162
9.12
Cooling system monitoring (optional) ............................................................................................. 163
9.12.1
Setting the cooling system monitoring function................................................................................................. 163
9.12.2
Cooling efficiency monitoring (optional) ............................................................................................................ 164
9.12.3
Cooling system flow monitoring (optional) ........................................................................................................ 165
9.13
Control of the motor-drive unit (optional) ........................................................................................ 169
9.13.1
Setting the switching pulse for controlling the motor-drive unit......................................................................... 170
9.13.2
Setting motor runtime monitoring...................................................................................................................... 171
9.13.3
Setting the switching direction........................................................................................................................... 172
9.14
Drive overview ................................................................................................................................ 173
9.15
Regulation....................................................................................................................................... 174
9.15.1
Response to control system disconnection (optional)....................................................................................... 174
9.15.2
Setting control variable (optional)...................................................................................................................... 176
9.16
Voltage regulation (optional)........................................................................................................... 177
9.16.1
Setting the desired value................................................................................................................................... 177
9.17
Reactive power regulation (optional) .............................................................................................. 193
Table of contents
Maschinenfabrik Reinhausen GmbH 2020
7
6385142/08 EN
ETOS® ED
9.18
Transformer data ............................................................................................................................ 196
9.18.1
Setting transformer data.................................................................................................................................... 197
9.18.2
Circuit examples for voltage transformers and current transformers ................................................................ 199
9.19
Measurement.................................................................................................................................. 212
9.19.1
UI measuring channels ..................................................................................................................................... 212
9.19.2
Control variable................................................................................................................................................. 213
9.19.3
Regulation mode............................................................................................................................................... 213
9.19.4
Display power factor negative........................................................................................................................... 213
9.20
Line drop compensation ................................................................................................................. 214
9.20.1
R&X compensation ........................................................................................................................................... 214
9.20.2
Z compensation................................................................................................................................................. 215
9.21
Parallel operation (optional)............................................................................................................ 216
9.21.1
Parallel operation methods ............................................................................................................................... 217
9.21.2
Configuring parallel operation ........................................................................................................................... 221
9.21.3
TAPCON® 2xx retrofit....................................................................................................................................... 225
9.21.4
Detecting parallel operation via group inputs (optional).................................................................................... 226
9.22
Monitoring functions........................................................................................................................ 226
9.22.1
Voltage monitoring ............................................................................................................................................ 226
9.22.2
Current monitoring ............................................................................................................................................ 229
9.22.3
Power monitoring .............................................................................................................................................. 232
9.22.4
Power flow monitoring....................................................................................................................................... 234
9.22.5
Tap position monitoring (optional)..................................................................................................................... 236
9.22.6
U bandwidth monitoring .................................................................................................................................... 237
9.22.7
Q bandwidth monitoring (optional) .................................................................................................................... 239
9.22.8
Phase symmetry monitoring.............................................................................................................................. 241
9.22.9
Temperature monitoring.................................................................................................................................... 242
9.22.10 Switching interval monitoring ............................................................................................................................ 242
9.22.11 Monitoring the gas volume of the Buchholz relay (OLTC) ................................................................................ 244
9.22.12 Monitoring the gas volume of the Buchholz relay (transformer)........................................................................ 245
9.22.13 Monitoring the oil pressure (transformer).......................................................................................................... 245
9.22.14 Monitoring the oil pressure (on-load tap-changer) ............................................................................................ 246
9.23
Target-tap-position operation.......................................................................................................... 247
9.24
Measured values ............................................................................................................................ 247
9.24.1
Displaying current measured values................................................................................................................. 247
9.24.2
Displaying measured value recorder (optional)................................................................................................. 248
9.24.3
Setting the measured value recorder................................................................................................................ 252
Table of contents
Maschinenfabrik Reinhausen GmbH 2020
8
6385142/08 EN
ETOS® ED
9.24.4
Displaying temperature curve (optional) ........................................................................................................... 253
9.24.5
Displaying winding temperatures (optional) ...................................................................................................... 254
9.24.6
Displaying the measured values of the Buchholz relay (optional)..................................................................... 255
9.24.7
Displaying the measured values of the pressure relief device (optional).......................................................... 255
9.24.8
Displaying the measured value trend of the oil level and dehydrating breather (optional)................................ 256
9.25
On-load tap-changer monitoring..................................................................................................... 256
9.25.1
Changing tap position designation (optional).................................................................................................... 256
9.25.2
Setting the TCR calculation factor (optional)..................................................................................................... 257
9.25.3
Displaying tap-change operation statistics (optional)........................................................................................ 257
9.25.4
Motor Current Index (MCI) ................................................................................................................................ 258
9.25.5
Displaying information about contact wear (only OILTAP®)............................................................................. 262
9.25.6
Information about the on-load tap-changer....................................................................................................... 263
9.26
Transformer monitoring (optional) .................................................................................................. 263
9.26.1
Hot-spot calculation (optional)........................................................................................................................... 264
9.26.2
Hot-spot forecast (optional)............................................................................................................................... 267
9.26.3
Setting calculation of transformer's loss of life (optional) .................................................................................. 268
9.26.4
Displaying protective device status (optional)................................................................................................... 269
9.26.5
Asset intelligence .............................................................................................................................................. 269
9.26.6
Transformer statistics........................................................................................................................................ 270
9.26.7
Display current oil level/dehydrating breather values........................................................................................ 271
9.26.8
Displaying the measured value trend of the oil level and dehydrating breather (optional)................................ 273
9.27
Dissolved gas analysis (optional) ................................................................................................... 273
9.27.1
Configuring DGA monitoring ............................................................................................................................. 274
9.27.2
Displaying measured values ............................................................................................................................. 277
9.28
MR sensor bus................................................................................................................................ 282
9.28.1
Configuring MR sensor bus............................................................................................................................... 283
9.28.2
Managing sensors............................................................................................................................................. 284
9.28.3
Function assignment......................................................................................................................................... 286
9.28.4
Defining the sensors ......................................................................................................................................... 286
9.28.5
Displaying information on the connected sensors............................................................................................. 291
9.29
Configuring analog inputs and outputs (optional) ........................................................................... 292
9.30
Configuring digital inputs and outputs............................................................................................. 295
9.31
Maintenance (optional) ................................................................................................................... 297
9.31.1
Setting operator interval for OLTC maintenance............................................................................................... 298
9.31.2
Setting operator interval for transformer maintenance...................................................................................... 299
9.31.3
Undertaking and confirming maintenance......................................................................................................... 300
Table of contents
Maschinenfabrik Reinhausen GmbH 2020
9
6385142/08 EN
ETOS® ED
9.31.4
Displaying maintenance overview..................................................................................................................... 303
9.31.5
Displaying the maintenance logbook ................................................................................................................ 303
9.31.6
Suppressing a maintenance event.................................................................................................................... 305
9.32
Torque monitoring (optional)........................................................................................................... 306
9.32.1
Tap-change ranges (windows) M1...M8............................................................................................................ 306
9.32.2
Types of tap-change operations........................................................................................................................ 306
9.32.3
Limit values ....................................................................................................................................................... 307
9.32.4
Tap-change supervisory control........................................................................................................................ 308
9.32.5
Evaluated and unevaluated tap-change operations.......................................................................................... 308
9.32.6
Displaying torque monitoring............................................................................................................................. 309
9.33
Event management......................................................................................................................... 311
9.33.1
Displaying and acknowledging events .............................................................................................................. 311
9.33.2
Configuring events ............................................................................................................................................ 312
9.33.3
Displaying event memory.................................................................................................................................. 314
9.34
User administration......................................................................................................................... 315
9.34.1
User roles.......................................................................................................................................................... 315
9.34.2
Changing the password .................................................................................................................................... 317
9.34.3
Creating, editing and deleting users.................................................................................................................. 318
9.34.4
Setting access rights to parameters and events ............................................................................................... 319
9.34.5
User authentication via RADIUS (optional)....................................................................................................... 320
9.35
Information about device ................................................................................................................ 322
9.35.1
Hardware........................................................................................................................................................... 322
9.35.2
Software............................................................................................................................................................ 323
9.35.3
Parallel operation .............................................................................................................................................. 324
9.36
Import/export manager ................................................................................................................... 324
9.36.1
Exporting data................................................................................................................................................... 325
9.36.2
Importing data (software version 3.44 and later)............................................................................................... 326
9.37
Configuring media converter with managed switch ........................................................................ 327
9.37.1
Commissioning.................................................................................................................................................. 327
9.37.2
Configuration..................................................................................................................................................... 329
9.38
TAPCON® Personal Logic Editor (TPLE)....................................................................................... 330
9.38.1
Function ............................................................................................................................................................ 330
9.38.2
Configuring TPLE.............................................................................................................................................. 343
9.39
Calibrating the position sensor ....................................................................................................... 346
9.40
Performing trial tap-change operations........................................................................................... 347
Table of contents
Maschinenfabrik Reinhausen GmbH 2020
10
6385142/08 EN
ETOS® ED
10
Fault elimination............................................................................................................. 349
10.1
Safety instructions .......................................................................................................................... 349
10.2
General information ........................................................................................................................ 349
10.3
Fault in the environment of the motor-drive unit ............................................................................. 350
10.4
Fault in the motor-drive unit when the switching operation has not ended..................................... 350
10.5
Fault in the motor-drive unit after the switching operation is ended correctly................................. 351
10.6
Hand crank operation in the event of faults .................................................................................... 351
10.7
Fault elimination ISM (hardware and software) .............................................................................. 352
10.7.1
General faults.................................................................................................................................................... 352
10.7.2
Human-machine interface................................................................................................................................. 353
10.7.3
Torque monitoring............................................................................................................................................. 353
10.7.4
Temperature monitoring.................................................................................................................................... 356
10.7.5
Maintenance messages .................................................................................................................................... 360
10.7.6
Function monitoring........................................................................................................................................... 364
10.7.7
Other faults........................................................................................................................................................ 365
11
Inspection and maintenance ......................................................................................... 367
11.1
Care................................................................................................................................................ 367
11.2
Inspection ....................................................................................................................................... 367
11.3
Maintenance ................................................................................................................................... 367
12
Removal........................................................................................................................... 369
13
Disposal........................................................................................................................... 372
14
Technical data................................................................................................................. 373
14.1
Motor-drive unit............................................................................................................................... 373
14.2
Control cabinet................................................................................................................................ 373
14.2.1
Drawings ........................................................................................................................................................... 375
14.3
Technical data for position transmitter equipment.......................................................................... 380
14.4
Permissible ambient conditions ...................................................................................................... 380
14.5
ISM® assemblies............................................................................................................................ 381
14.5.1
Voltage supply................................................................................................................................................... 381
14.5.2
Voltage supply................................................................................................................................................... 381
14.5.3
Voltage measurement and current measurement............................................................................................. 383
14.5.4
UI 5-4 voltage measurement and current measurement................................................................................... 384
14.5.5
Digital inputs and outputs.................................................................................................................................. 386
14.5.6
Analog inputs and outputs................................................................................................................................. 388
Table of contents
Maschinenfabrik Reinhausen GmbH 2020
11
6385142/08 EN
ETOS® ED
14.5.7
AIO 8 analog inputs and outputs....................................................................................................................... 389
14.5.8
CPU (central processing unit) I ......................................................................................................................... 390
14.5.9
System networking............................................................................................................................................ 392
14.5.10 Ambient conditions............................................................................................................................................ 394
14.5.11 Standards and directives................................................................................................................................... 394
Glossary .......................................................................................................................... 397
List of key words ............................................................................................................ 399
Maschinenfabrik Reinhausen GmbH 2020
12
6385142/08 EN
ETOS® ED
1 Introduction
This technical file contains detailed descriptions on the safe and proper in-
stallation, connection, commissioning and monitoring of the product.
It also includes safety instructions and general information about the prod-
uct.
This technical file is intended solely for specially trained and authorized per-
sonnel.
1.1 Manufacturer
The product is manufactured by:
Maschinenfabrik Reinhausen GmbH
Falkensteinstraße 8
93059 Regensburg
Tel.: (+49) 9 41/40 90-0
E-mail: [email protected]
Further information on the product and copies of this technical file are avail-
able from this address if required.
1.2 Completeness
This technical file is incomplete without the supporting documents.
The following documents also apply in addition to this technical file:
▪ Connection diagrams
▪ Routine test report
▪ Supplement
Also observe generally valid legislation, standards, and guidelines as well as
specifications on accident prevention and environmental protection in the re-
spective country of use.
1.3 Safekeeping
Keep this technical file and all supporting documents ready at hand and ac-
cessible for future use at all times.
1.4 Notation conventions
1.4.1 Hazard communication system
Warnings in this technical file are displayed as follows.
Maschinenfabrik Reinhausen GmbH 2020
13
6385142/08 EN
ETOS® ED
1.4.1.1
Warning relating to section
Warnings relating to sections refer to entire chapters or sections, sub-sec-
tions or several paragraphs within this technical file. Warnings relating to
sections use the following format:
WARNING
Type of danger!
Source of the danger and outcome.
►Action
►Action
1.4.1.2
Embedded warning information
Embedded warnings refer to a particular part within a section. These warn-
ings apply to smaller units of information than the warnings relating to sec-
tions. Embedded warnings use the following format:
DANGER! Instruction for avoiding a dangerous situation.
1.4.1.3
Signal words and pictograms
The following signal words are used:
Signal word
Definition
DANGER
Indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result
in minor or moderate injury.
NOTICE
Indicates measures to be taken to prevent damage to property.
Table 1: Signal words in warning notices
Pictograms warn of dangers:
Pictogram
Definition
Warning of a danger point
Warning of dangerous electrical voltage
Maschinenfabrik Reinhausen GmbH 2020
14
6385142/08 EN
ETOS® ED
Pictogram
Definition
Warning of combustible substances
Warning of danger of tipping
Warning of danger of crushing
Table 2: Pictograms used in warning notices
1.4.2 Information system
Information is designed to simplify and improve understanding of particular
procedures. In this technical file it is laid out as follows:
Important information.
1.4.3 Instruction system
This technical file contains single-step and multi-step instructions.
Single-step instructions
Instructions which consist of only a single process step are structured as fol-
lows:
Aim of action
ü Requirements (optional).
►Step 1 of 1.
ð Result of step (optional).
ð Result of action (optional).
Multi-step instructions
Instructions which consist of several process steps are structured as follows:
Maschinenfabrik Reinhausen GmbH 2020
15
6385142/08 EN
ETOS® ED
Aim of action
ü Requirements (optional).
1. Step 1.
ð Result of step (optional).
2. Step 2.
ð Result of step (optional).
ð Result of action (optional).
1.4.4 Typographic conventions
Typographic convention
Purpose
Example
UPPERCASE
Operating controls, switches
ON/OFF
[Brackets]
PC keyboard
[Ctrl] + [Alt]
Bold
Software operating controls
Press Continue button
…>…>…
Menu paths
Parameter > Control parameter
Italics
System messages, error messages,
signals
Function monitoring alarm triggered
[► Number of pages]
Cross reference
[► Page 41].
Dotted underscore
.............................................
Glossary entry, abbreviations, defini-
tions, etc.
Glossary entry
........................
Table 3: Typographic conventions used in this technical file
Maschinenfabrik Reinhausen GmbH 2020
16
6385142/08 EN
ETOS® ED
2 Safety
▪ Read this technical file through to familiarize yourself with the product.
▪ This technical file is a part of the product.
▪ Read and observe the safety instructions provided in this chapter.
▪ Read and observe the warnings in this technical file in order to avoid func-
tion-related dangers.
▪ The product is manufactured on the basis of state-of-the-art technology.
Nevertheless, risks to life and limb for the user or impairment of the prod-
uct and other material assets due to the function may arise in the event of
improper use.
2.1 Appropriate use
The motor-drive unit adjusts the operating position of on-load tap-changers
in regulating transformers to the individual operating requirements. The mo-
tor-drive unit is designed solely for use in electrical energy systems and facil-
ities. If used as intended and in compliance with the requirements and condi-
tions specified in this technical file as well as the warning notices in this tech-
nical file and attached to the product, then the motor-drive unit does not
present any danger to people, property or the environment. This applies
throughout the service life of the product, from delivery, installation and oper-
ation to removal and disposal.
The following is considered appropriate use:
▪ Only operate the product in accordance with this technical file and the
agreed delivery conditions and technical data.
▪ Use the equipment and special tools supplied solely for the intended pur-
pose and in accordance with the specifications of this technical file.
▪ Use the product only with the transformer/on-load tap-changer/de-ener-
gized tap-changer specified in the order.
▪ You will find the standard valid for the product and the year of issue on the
nameplate.
▪ The serial numbers of on-load tap-changer / de-energized tap-changer
and on-load tap-changer accessories / de-energized tap-changer acces-
sories (drive, drive shaft, bevel gear, protective relay, etc.) must match if
these products are supplied as a set for one order.
▪ Electrically operate the motor-drive unit remotely during normal operation.
▪ In special operating cases (such as during maintenance tasks), the motor-
drive unit can also be operated electrically on site via control switch S3.
▪ Never operate the motor-drive unit electrically or with the hand crank be-
fore the transformer has been disconnected if you think there may be a
fault in the transformer or on-load tap-changer/de-energized tap-changer.
For more information, refer to the "Troubleshooting" chapter.
Maschinenfabrik Reinhausen GmbH 2020
17
6385142/08 EN
ETOS® ED
▪ The provided hand crank is for activating the motor-drive unit during in-
stallation and tests in the transformer plant or during maintenance tasks if
the transformer has been disconnected.
▪ For details about using the hand crank in emergency operation when the
transformer is energized, refer to the "Operation" [►Section 8, Page 101]
chapter.
2.2 Fundamental safety instructions
To prevent accidents, malfunctions and damage as well as unacceptable ad-
verse effects on the environment, those responsible for transport, installa-
tion, operation, maintenance and disposal of the product or parts of the prod-
uct must ensure the following:
Personal protective equipment
Loosely worn or unsuitable clothing increases the danger of becoming
trapped or caught up in rotating parts and the danger of getting caught on
protruding parts. This poses a danger to life and limb.
▪ Wear appropriate personal protective equipment such as a helmet, work
gloves, etc. for the respective activity.
▪ Never wear damaged personal protective equipment.
▪ Never wear rings, necklaces, or other jewelry.
▪ If you have long hair, wear a hairnet.
Work area
Untidy and poorly lit work areas can lead to accidents.
▪ Keep the work area clean and tidy.
▪ Make sure that the work area is well lit.
▪ Observe the applicable laws for accident prevention in the relevant coun-
try.
Drying the transformer
Drying the motor-drive unit will cause damage to property as well as motor-
drive unit malfunctions.
▪ Never dry the motor-drive unit.
Working during operation
The product may only be operated in a sound, operational condition. Other-
wise it poses a danger to life and limb.
▪ Regularly check the operational reliability of safety equipment.
▪ Comply with the inspection work, maintenance work and maintenance in-
tervals described in this technical file.
Maschinenfabrik Reinhausen GmbH 2020
18
6385142/08 EN
ETOS® ED
Invisible laser radiation
Looking directly into the beam or the reflected beam can cause eye damage.
The beam is emitted at the optical connections or at the end of the fiber-optic
cables connected to them on the assemblies. Read the chapter "Technical
Data" for further information.
▪ Never look directly into the beam or the reflected beam.
▪ Never look into the beam with the aid of optical instruments such as a
magnifying glass or a microscope.
▪ In the event that the laser beam strikes your eyes, close your eyes imme-
diately and move your head out of the path of the beam.
Working with current transformers
Dangerous high voltages may occur when a current transformer is operated
with an open secondary circuit. This can lead to injuries and property dam-
age.
▪ Never operate a current transformer with an open secondary circuit; short-
circuit the current transformer to prevent this.
▪ Observe the information in the current transformer operating instructions.
Handling electrical components
Electrical components can be damaged by electrostatic discharges.
▪ Never touch electrical components during commissioning, operation or
maintenance work.
▪ Take suitable measures (e.g. covers) to ensure that personnel cannot
touch components.
▪ Wear suitable personal protective equipment (e.g. grounded strap).
Hand crank aperture
Reaching into the hand crank aperture during a tap-change operation may
lead to injuries caused by a rotating drive shaft.
▪ Never reach into the hand crank aperture.
Securing the motor-drive unit
If you open the motor-drive unit during operation, there is a danger of electric
shock due to live components behind the swing frame.
▪ Secure the motor-drive unit against unauthorized opening during opera-
tion by using a padlock.
▪ The motor-drive unit may only be opened by an electrically skilled person.
Opening the swing frame
Opening the swing frame while the motor-drive unit is in operation may result
in electric shocks due to live components.
▪ The swing frame may only be opened by an electrically skilled person.
Maschinenfabrik Reinhausen GmbH 2020
19
6385142/08 EN
ETOS® ED
Explosion protection
Highly flammable or explosive gases, vapors and dusts can cause serious
explosions and fire. This increases the danger to life and limb.
▪ Do not install, operate or perform maintenance work on the product in ar-
eas where a risk of explosion is present.
Safety markings
Warning signs and safety information plates are safety markings on the
product. They are an important aspect of the safety concept.
▪ Observe all safety markings on the product.
▪ Make sure all safety markings on the product remain intact and legible.
▪ Replace safety markings that are damaged or missing.
Ambient conditions
To ensure reliable and safe operation, the product must only be operated
under the ambient conditions specified in the technical data.
▪ Observe the specified operating conditions and requirements for the in-
stallation location.
Auxiliary materials and operating materials
Auxiliary materials and operating materials not approved by the manufac-
turer can lead to personal injury, damage to property and malfunctions of the
product.
▪ Only use conductive and grounded hoses, pipes, and pump equipment
that are approved for flammable liquids.
▪ Only use lubricants and auxiliary materials approved by the manufacturer.
▪ Contact the manufacturer.
Modifications and conversions
Unauthorized or inappropriate changes to the product may lead to personal
injury, material damage and operational faults.
▪ Only modify the product after consultation with Maschinenfabrik Rein-
hausen GmbH.
Spare parts
Spare parts not approved by Maschinenfabrik Reinhausen GmbH may lead
to physical injury, damage to the product and malfunctions.
▪ Only use spare parts that have been approved by Maschinenfabrik Rein-
hausen GmbH.
▪ Contact Maschinenfabrik Reinhausen GmbH.
Maschinenfabrik Reinhausen GmbH 2020
20
6385142/08 EN
ETOS® ED
2.3 Personnel qualification
The person responsible for assembly, commissioning, operation, mainte-
nance and inspection must ensure that the personnel are sufficiently quali-
fied.
Electrically skilled person
The electrically skilled person has a technical qualification and therefore has
the required knowledge and experience, and is also conversant with the ap-
plicable standards and regulations. The electrically skilled person is also pro-
ficient in the following:
▪ Can identify potential dangers independently and is able to avoid them.
▪ Is able to perform work on electrical systems.
▪ Is specially trained for the working environment in which (s)he works.
▪ Must satisfy the requirements of the applicable statutory regulations for
accident prevention.
Electrically trained persons
An electrically trained person receives instruction and guidance from an
electrically skilled person in relation to the tasks undertaken and the poten-
tial dangers in the event of inappropriate handling as well as the protective
devices and safety measures. The electrically trained person works exclu-
sively under the guidance and supervision of an electrically skilled person.
Operator
The operator uses and operates the product in line with this technical file.
The operating company provides the operator with instruction and training
on the specific tasks and the associated potential dangers arising from im-
proper handling.
Technical Service
We strongly recommend having maintenance, repairs and retrofitting carried
out by our Technical Service department. This ensures that all work is per-
formed correctly. If maintenance is not carried out by our Technical Service
department, please ensure that the personnel who carry out the mainte-
nance are trained and authorized by Maschinenfabrik Reinhausen GmbH to
carry out the work.
Authorized personnel
Authorized personnel are trained by Maschinenfabrik Reinhausen GmbH to
carry out special maintenance.
Maschinenfabrik Reinhausen GmbH 2020
21
6385142/08 EN
ETOS® ED
2.4 Personal protective equipment
Personal protective equipment must be worn during work to minimize risks to
health.
▪ Always wear the personal protective equipment required for the job at
hand.
▪ Never wear damaged personal protective equipment.
▪ Observe information about personal protective equipment provided in the
work area.
Protective clothing
Close-fitting work clothing with a low tearing strength,
with tight sleeves and with no protruding parts. It mainly
serves to protect the wearer against being caught by
moving machine parts.
Safety shoes
To protect against falling heavy objects and slipping on
slippery surfaces.
Safety glasses
To protect the eyes from flying parts and splashing liq-
uids.
Visor
To protect the face from flying parts and splashing liq-
uids or other dangerous substances.
Hard hat
To protect against falling and flying parts and materials.
Hearing protection
To protect against hearing damage.
Protective gloves
To protect against mechanical, thermal, and electrical
hazards.
Table 4: Personal protective equipment
3 IT security
Maschinenfabrik Reinhausen GmbH 2020
22
6385142/08 EN
ETOS® ED
3 IT security
Observe the following recommendations to operate the product safely.
General
▪ Ensure that only authorized personnel have access to the device.
▪ Only use the device within an ESP (electronic security perimeter). Do not
connect the device to the Internet in an unprotected state. Use mecha-
nisms for vertical and horizontal network segmenting and security gate-
ways (firewalls) at the transition points.
▪ Ensure that the device is only operated by trained personnel who are fa-
miliar with IT security.
Commissioning
Observe the following recommendations for device commissioning:
▪ User IDs must be unique and assignable. Do not use a "Group account"
function or the "Auto login" function.
▪ Activate the "Auto logout [►Section 9.2.2, Page 109]" function.
▪ Restrict the rights of the individual user groups as much as is feasible; this
helps avoid errors during operations. A user with the "Operator" role, for
example, should only perform operations and should not be able to
change any device settings.
▪ Delete or disable the default "admin" user ID. This requires first creating a
new user account with the "Administrator" role. You can then use it to
delete or disable the default "admin" account.
▪ Deactivate service user access [►Section 9.2.3, Page 110].
▪ Enable SSL/TLS encryption [►Section 9.2, Page 107]; access to the de-
vice is then only possible using the SSL/TLS protocol. In addition to en-
crypting communication, this protocol also checks the authenticity of the
server.
▪ Use TLS version 1.2 or higher wherever possible.
▪ Integrate the device into a public key infrastructure. Create your own SSL
certificates for this if necessary and then import them.
▪ Connect the device to a central log server by using the syslog interface
[►Section 9.6, Page 118].
▪ Only use the SNMP function if you can ensure that the communication is
protected by external security equipment.
Operation
Observe the following recommendations during device operation:
▪ Change the password at regular intervals.
▪ Export the security log [►Section 9.36.1, Page 325] at regular intervals.
▪ Check the log files regularly for unauthorized system access and other se-
curity-related events.
3 IT security
Maschinenfabrik Reinhausen GmbH 2020
23
6385142/08 EN
ETOS® ED
Interfaces
The device uses the following interfaces for communication:
Figure 1: ETH1.1 interface on the OT1205 assembly
Interface
Protocol
Port
Description
ETH1.1
TCP
21
FTP service access 1)
ETH1.1
TCP
80
Web visualization 1)
ETH1.1
TCP
443
SSL-protected web visualization
ETH1.1
TCP
990
SSL-protected FTP service access
ETH1.1
TCP
8080
Web visualization (alternative port) 1)
ETH1.1
TCP
8081
SSL-protected web visualization (alternative
port)
ETH1.1
UDP
67
DHCP server
Table 5: Interfaces and open ports of the OT1205 assembly
1) Port is closed if you activate the device's SSL encryption.
CPU
CAN 1
1
9
CAN 2
1
9
COM 1
1
9
COM 2
1
9
-
+
24V DC
RUN
INIT
ERR
USB2.0
4 6
2
A
8
C
H
TEST
PROG
RUN
4 6
2
A
E
0
8
C
L
ETH 1
ETH 2.1
ETH 2.2
Figure 2: CPU assembly interfaces
Interface
Protocol
Port
Description
CAN 1
-
-
DIO assembly connection
CAN 2
-
-
Communication with other ISM® devices
(e.g. parallel operation)
COM 1
-
-
Internal system interface
3 IT security
Maschinenfabrik Reinhausen GmbH 2020
24
6385142/08 EN
ETOS® ED
Interface
Protocol
Port
Description
COM 2
-
-
Serial interface (SCADA)
USB
-
-
Import or export of data
ETH 1
TCP
80
HTTP for web-based visualization1), 2)
ETH 1
TCP
443
HTTPS for web-based visualization1), 2)
ETH 1
TCP
102
IEC 61850
ETH 1
TCP
502
Modbus3)
ETH 1
TCP
20000
DNP33)
ETH 1
UDP
161
SNMP4)
ETH 2.x
TCP
21
FTP1) (only for MR service)
ETH 2.x
TCP
80
HTTP for web-based visualization1)
ETH 2.x
TCP
443
HTTPS for web-based visualization1)
ETH 2.x
TCP
990
FTPS (only for MR service)
ETH 2.x
TCP
8080
HTTP for web-based visualization1)
ETH 2.x
TCP
8081
HTTPS for web-based visualization1)
ETH 2.x
UDP
161
SNMP4)
Table 6: Interfaces and open ports of the CPU assembly
1) Port is closed if you activate the device's SSL encryption.
2) Depending on the setting of the parameter Visualization release [►Page
113].
3) Default setting; if you have modified the port for the control system proto-
col, only the set port is open.
4) Depending on the setting of the SNMP agent parameter.
Encryption standards
The device supports the following TLS versions:
▪ TLS 1.0
▪ TLS 1.1
▪ TLS 1.2
3 IT security
Maschinenfabrik Reinhausen GmbH 2020
25
6385142/08 EN
ETOS® ED
The device uses the following cipher suites for a TLS-secured connection:
Key exchange
Authentication
Encryption
Key length
Operating
mode
Hash func-
tion
TLS
ECDHE
RSA
WITH
AES
128
CBC
SHA1)
DHE
SHA265
ECDHE
ECDSA
GCM
SHA256
ECDH
256
CBC
SHA1)
RSA1)
SHA256
GCM
SHA384
Table 7: Cipher suite
1) Not available with TLS version >= 1.2
The device uses the SHA256 hash function to save passwords.
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
26
6385142/08 EN
ETOS® ED
4 Product description
4.1 Scope of delivery
The motor-drive unit is packaged with protection against moisture and is de-
livered as follows:
▪ Motor-drive unit
▪ Product documentation
Please note the following:
1. Check the shipment for completeness on the basis of the shipping docu-
ments.
2. Store the parts in a dry place until installation.
3. The product must remain in its airtight, protective wrapping and may only
be removed immediately before installation.
4.2 Function description
The motor-drive unit adjusts the operating position of on-load tap-changers
in regulating transformers to the individual operating requirements.
The tap-change operation is initiated by activating the motor-drive unit (a sin-
gle control impulse is triggered, for example via the optional "Automatic volt-
age regulation AVR basic/pro" function package). This adjustment operation
is always completed regardless of any other control impulses issued during
the tap-change operation. In the standard design, the next tap-change oper-
ation can only proceed once all control devices have reached their resting
positions.
Behavior in the event of a voltage interruption
Should the voltage be interrupted during an on-load tap-change operation,
once the voltage supply returns, the motor-drive unit completes the started
on-load tap-change operation.
4.3 Performance features
Depending on your order, the device is equipped with the following optional
function packages:
▪ Basic monitoring
– Voltage, current, frequency
– Active power, reactive power, apparent power, power factor
– Temperature monitoring (ambient temperature, temperature of top-oil,
temperature of bottom oil (optional), calculation of hot-spot temperature
in accordance with IEC 60076-7 or IEEE C57.91)
– Optional: Transformer oil level
– Loss-of-life and relative aging rate
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
27
6385142/08 EN
ETOS® ED
– Motor-drive unit status (motor protective switch, motor is running)
– Tap position display
– Optional: Status of protective devices (Buchholz relay, protective relay,
pressure relief device)
▪ ETOS® ED digital ready
– Maintenance interval calculation
– Tap-change statistics of on-load tap-changer
– Motor-drive unit status (motor protective switch, motor is running)
▪ On-load tap-changer monitoring
– Contact wear calculation (only for OILTAP® V, M, R, RM, MS, G)
– Maintenance interval calculation
– Oil carbonization (only for OILTAP® V, M, R)
– Monitoring of OLTC temperature (optional)
– Tap-change statistics of on-load tap-changer
– Optional: on-load tap-changer oil level
– Optional: oil filter unit
– Motor-drive unit status (motor protective switch, motor is running)
– Optional: Motor Current Index
▪ On-load tap-changer monitoring expert
– Torque monitoring
– Tap-change sequence monitoring
– Temperature monitoring (motor-drive unit, surroundings, OLTC, tem-
perature difference between OLTC and transformer)
– Hand crank monitoring
▪ Automatic voltage regulation AVR basic
– Measurement of voltage and current
– 1 desired value
– Voltage regulation with linear delay time T1
– Motor-drive unit status (motor protective switch, motor is running)
▪ Automatic voltage regulation AVR pro
– Measurement of voltage and current
– Desired value in accordance with order (1, 3 or 5 desired values,
TDSC, analog desired value specification, incremental desired value
specification, desired value via BCD)
– Automatic voltage regulation with linear or integral delay time T1 and
with delay time T2
– Parallel operation
– Line drop compensation
– Motor-drive unit status (motor protective switch, motor is running)
– Bandwidth monitoring
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
28
6385142/08 EN
ETOS® ED
– Function monitoring
– Limit value monitoring (voltage, current, power, phase angle)
▪ Cooling system control
– 2, 4 or 6 cooling stages, can be individually parameterized
– Load-dependent mode (for early activation of cooling stages)
– Periodic mode (for regular activation of cooling stages)
– Alternating mode (for equal loading of similar cooling stages)
▪ Cooling stage monitoring (2, 4 or 6 cooling stages)
▪ DGA
– Up to 10 gases
– Relative moisture in oil
– Monitoring of the absolute values and rates of increase
– Optional: Rogers, Duval, Dörnenburg and IEC 60599 analyses
▪ MR sensor bus
▪ Calculation of the transformer overload capability (emergency operation)
4.4 Variants
The ISM® assemblies are installed as follows (figures show swing frame in-
terior, with cover plate with swing frame closed, without cover plate with
swing frame open):
4.4.1 ETOS® ED L/ETOS® ED L-S
The ISM assemblies are installed as follows (figures show swing frame inte-
rior, with cover plate with swing frame closed, without cover plate with swing
frame open):
Without display
X3
M1
S1
S2
S12
S13A
S13B
S14
S6A
S6B
S8A
S8B
S5
S4
R1
S10A
E1
S62P
AIO 4
1
2
3
4
11
12
13
14
24V DC
+
-
RDY
6
7
8
9
16
17
18
19
CPU I
RUN
INIT
ERR
CAN 1
CAN 2
COM 1
COM 2
24V DC
+
-
TEST
PROG
RUN
USB2.0
2
4
6
8
A
C
H
0
2
4
6
8
A
C
E
L
+24V DC
typ.22W
128 256
MB
ETH 1
ETH 2.1
ETH 2.2
N
L1
NC
NC
k
l
NC
NC
NC
NC
RDY
DIO 28-15
ERR
INIT
RUN
CAN
H
L
+
-
24V DC
DO
DO
DO
DI
DI
DI
DI
1A
1C
1B
2A
2C
2B
3A
3C
3B
4C
4B
5C
5B
6A
6C
6B
7A
7C
7B
8A
8C
8B
9C
9B
10C
10B
11A
11C
11B
12A
12C
12B
13A
13C
13B
14C
14B
15C
15B
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Adjust
DC OK
Overload
Power Supply
N L
S61P
S26A
S27A
S3
S32
X2
X1
X20
Q1
R3
S62M
S61M
K1
K2
K20
UI 1
PE
G1
X1
CT372
CT372
H1
H2
H3
X5.1
X10
X5
F2
B2
F12 F13
F11
S15
S118
A19
A18.1
A10
A17
X6.1
X6
PE
Figure 3: ETOS® ED L/ETOS® ED L-S without display
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
29
6385142/08 EN
ETOS® ED
With display
AVR STATUS
ALARM
REMOTE
AVR AUTO
AVR MANUAL
ENTER
BACK
TAPCON
DIO 28-15
ERR
INIT
RUN
CAN
H
L
+
-
24V DC
DO
DO
DO
DI
DI
DI
DI
1A
1C
1B
2A
2C
2B
3A
3C
3B
4C
4B
5C
5B
6A
6C
6B
7A
7C
7B
8A
8C
8B
9C
9B
10C
10B
11A
11C
11B
12A
12C
12B
13A
13C
13B
14C
14B
15C
15B
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
PE
G1
X20:1...49
X1:272
...313
X1:PE;1...72
X1:80...248
X4:
1...4
S38M
S40M
S61M
PE
X6:1...24
X3
M1
S1
S2
S12
S13A
S13B
S14
S6A
S6B
S8A
S8B
S5
S4
R1
S10
E1
S41P
A12
A10
A15
A13
A13.1
AIO
1
2
3
4
11
12
13
14
24V DC
+
-
RDY
6
7
8
9
16
17
18
19
UI
N
L1
L2
L3
k1
l1
k2
l2
k3
l3
RDY
AIO
1
2
3
4
11
12
13
14
24V DC
+
-
RDY
6
7
8
9
16
17
18
19
CPU
RUN
INIT
ERR
CAN 1
CAN 2
COM 1
COM 2
24V DC
+
-
TEST
PROG
RUN
USB2.0
2
4
6
8
A
C
H
0
2 4
6
8
A
C
E
L
ETH 1
ETH 2.1
ETH 2.2
Figure 4: ETOS® ED L/ETOS® ED L-S with display
4.4.2 ETOS® ED XL
The ISM assemblies are installed as follows (figures show swing frame inte-
rior, with cover plate with swing frame closed, without cover plate with swing
frame open):
Without display
R1
X3
M1
S1
S2
S12
S13A
S13B
S14
S6A
S6B
S8A
S8B
S5
S4
S10A
E1
S62P
RUN
INIT
ERR
CAN 1
CAN 2
COM 1
COM 2
24V DC
+
-
TEST
PROG
RUN
USB2.0
2
4
6
8
A
C
H
0
2
4
6
8
C A
E
L
ETH 1
ETH 2.1
ETH 2.2
ERR
INIT
RUN
CAN
H
L
+
-
24V DC
DO
DO
DO
DO
DI
DI
DI
DI
DI
DI
1A
1C
1B
2A
2C
2B
3A
3C
3B
4C
4B
5C
5B
6A
6C
6B
7A
7C
7B
8A
8C
8B
9C
9B
10C
10B
11A
11C
11B
12A
12C
12B
13A
13C
13B
14C
14B
15C
15B
16A
16C
16B
17A
17C
17B
18A
18C
18B
19C
19B
20C
20B
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
1
2
3
4
11
12
13
14
24V DC
+
-
RDY
6
7
8
9
16
17
18
19
1
2
3
4
11
12
13
14
24V DC
+
-
RDY
6
7
8
9
16
17
18
19
N
L1
L2
L3
RDY
k1
l1
k2
l2
k3
l3
X2
X5.1
F2
K20
K2
K1
B2
A10
CPU II
A19
DIO 42-20
A23
BEM 1
A24
BES 1
G1
S3
S32
F11F12F13
H3
H2
H1
Q1
F25
X19
S118
S15
S26A
S27A
S61P
X1
X20
X1 >272
A18.2
AIO 4
A18.1
AIO 4
A22
VI 4
A17
UI 3
X8P
A16
UI 5
H2
S7
ETH 1
S61M
S62M
X8S
X6.2
X6.1
X6
Figure 5: ETOS® ED XL without display
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
30
6385142/08 EN
ETOS® ED
With display
R1
X3
M1
S1
S2
S12
S13A
S13B
S14
S6A
S6B
S8A
S8B
S5
S4
S10A
E1
S62P
RUN
INIT
ERR
CAN 1
CAN 2
COM 1
COM 2
24V DC
+
-
TEST
PROG
RUN
USB2.0
2
4
6
8
A
C
H
0
2
4
6
8
C A
E
L
ETH 1
ETH 2.1
ETH 2.2
ERR
INIT
RUN
CAN
H
L
+
-
24V DC
DO
DO
DO
DO
DI
DI
DI
DI
DI
DI
1A
1C
1B
2A
2C
2B
3A
3C
3B
4C
4B
5C
5B
6A
6C
6B
7A
7C
7B
8A
8C
8B
9C
9B
10C
10B
11A
11C
11B
12A
12C
12B
13A
13C
13B
14C
14B
15C
15B
16A
16C
16B
17A
17C
17B
18A
18C
18B
19C
19B
20C
20B
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
1
2
3
4
11
12
13
14
24V DC
+
-
RDY
6
7
8
9
16
17
18
19
1
2
3
4
11
12
13
14
24V DC
+
-
RDY
6
7
8
9
16
17
18
19
N
L1
L2
L3
RDY
k1
l1
k2
l2
k3
l3
X2
X5.1
F2
K20
K2
K1
B2
A10
CPU II
A19
DIO 42-20
A5
A23
BEM 1
A24
BES 1
G1
S3
S32
F11F12F13
H3
H2
H1
Q1
F25
X19
S118
S15
S26A
S27A
S61P
X1
X20
X1 >272
A18.2
AIO 4
A18.1
AIO 4
A22
VI 4
A17
UI 3
X8P
A16
UI 5
H2
S7
ETH 1
X6.1
X6.2
S61M
S62M
X8S
X6
Figure 6: ETOS® ED XL with display
4.5 Design
This chapter contains an overview of the design of the motor-drive unit.
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
31
6385142/08 EN
ETOS® ED
Components not described here in detail are described in the motor-drive
unit's technical data.
Figure 7: Design
1 Door of the control cabinet
2 Viewing window for indication field
3 Eyebolt
4 Indication field
5 Transmission-gear cover plate
6 Output shaft
7 Hand crank aperture with hand
crank interlock switch
8 Hand lamp
9 Fixing lug
10 Hand crank
11 19-inch plug-in housing
12 Motor protective switch Q1
13 S3 control switch
14 Swing frame / anti-condensation
heater
15 Briefcase
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
32
6385142/08 EN
ETOS® ED
4.5.1 Indication field
A clear indication field is fitted in the motor-drive unit. The pointer and opera-
tions counter are mechanically driven and indicate the tap-change operation
sequence and operating position of the motor-drive unit. The reset wheel on
the operations counter is sealed at the factory.
Figure 8: Indication field
1 The two drag hands indicate the
regulating range currently used
2 Tap position indicator
3 Tap-change indicator: Shows the
current position of the control cam
(33 tap-change indicator sections
per operating position)
4 The mechanical operations
counter shows the overall number
of tap-change operations
4.5.2 Anti-condensation heater
The anti-condensation heater is designed as a panel heater which also acts
as the front cover of the swing frame.
The design of the motor-drive unit and panel heater ensures that air circu-
lates inside the motor-drive unit and therefore that there is a constant interior
temperature which is always higher than the outside temperature.
4.5.3 Swing frame/terminal rail
The swing frame protects all electrical and mechanical parts of the motor-
drive unit behind the swing frame against accidental contact.
The terminal rail behind the swing frame enables easy electrical connection
of the motor-drive unit. Vertically arranged cap rails with the correspondingly
mounted terminal bars ensure that the connection wiring is easy to install.
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
33
6385142/08 EN
ETOS® ED
4.5.4 Position transmitter equipment
NOTICE
Damage to the on-load tap-changer and motor-drive unit!
Damage to on-load tap-changer and motor-drive unit due to incorrect use of
position transmitter equipment.
►Only circuits stated in the chapter Technical data for position transmitter
equipment [►Section 14.3, Page 380] may be connected to the position
transmitter module connections.
►The switchover point of the position transmitter equipment in the motor-
drive unit is not the same as the switchover point of the diverter switch
operation. This depends on the type of diverter switch. This fact should
be noted when project planning the locking circuits between the motor-
drive unit and external equipment (e.g. transformer circuit breaker).
►Therefore, the "Tap changer in operation" position transit contact shown
in the connection diagram should be used for external monitoring, locking
and control purposes instead of the position transmitter equipment.
The position transmitter equipment is used to indicate the operating position
of the on-load tap-changer/de-energized tap-changer when idle.
The remote displays are available in various versions.
The position transmitter module for connection by the customer is located on
the terminal rail [►Section 4.5.3, Page 32].
For more information about the position transmitter equipment, see Techni-
cal data for position transmitter equipment [►Section 14.3, Page 380].
4.5.5 Transmission gear cover plate
WARNING
Danger of death and severe injury from electrical voltage!
Danger of death and severe injury from electrical voltage if the transmission
gear cover plate is not fitted.
►Never start up motor-drive unit without transmission gear cover plate.
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
34
6385142/08 EN
ETOS® ED
The touch-protected transmission-gear cover plate features an opening for
the hand crank used in manual mode.
Transmission-gear cover plate
4.5.6 Ambient temperature sensor
The device is equipped with a temperature sensor for recording the ambient
temperature. The temperature sensor is on the bottom of the protective
housing.
Ensure that there is sufficient circulation of the ambient air around the tem-
perature sensor. Otherwise, there may be errors in torque monitoring.
Figure 9: Ambient temperature sensor on the bottom of the protective housing
1 Ambient temperature sensor
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
35
6385142/08 EN
ETOS® ED
4.5.7 ISM assemblies
Depending on the order, the device is either designed as a 19-inch plug-in
housing or supplied as individual components for assembly on a cap rail.
The individual device assemblies are described in the following section.
Figure 10: 19-inch plug-in housing (OT1205)
Figure 11: Individual components for assembly on a cap rail
4.5.7.1
Power supply
The OT1205 assembly contains the power supply unit for powering the de-
vice. Depending on configuration, the device is equipped with one of the fol-
lowing power supply unit variants:
▪ Multi-voltage mains unit 85...265 V AC/V DC
▪ DC voltage power supply unit 20...70 V DC
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
36
6385142/08 EN
ETOS® ED
4.5.7.2
CPU (central processing unit) I
The CPU I assembly is the central processing unit for the device. It contains
the following interfaces:
▪ Internal system interface RS232 (COM1)
▪ Serial interface RS232/485 (COM2)
▪ 3x Ethernet (ETH1, ETH 2.1, ETH 2.2)
▪ USB (USB 2.0)
▪ 2x CAN bus (CAN 1, CAN 2)
CPU
CAN 1
1
9
CAN 2
1
9
COM 1
1
9
COM 2
1
9
-
+
24V DC
RUN
INIT
ERR
USB2.0
4 6
2
A
8
C
H
TEST
PROG
RUN
4 6
2
A
E
0
8
C
L
ETH 1
ETH 2.1
ETH 2.2
Figure 12: CPU I assembly
4.5.7.3
Voltage measurement and current measurement
The UI 1 assembly is used for measuring 1-phase voltage and current.
Figure 13: UI 1 assembly
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
37
6385142/08 EN
ETOS® ED
The UI 3 assembly is used for measuring 3-phase voltage and current.
Figure 14: UI 3 assembly
Warning of a danger point. Read the information given in the product oper-
ating instructions.
Warning of dangerous electrical voltage.
This assembly is protected via double insulation or reinforced insulation.
Table 8: Safety-relevant symbols on the assembly
4.5.7.4
UI 5-4 voltage measurement and current measurement
The UI 5-4 assembly is used for measuring 3-phase voltage and current.
Figure 15: UI 5-4 assembly
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
38
6385142/08 EN
ETOS® ED
Warning of a danger point. Read the information given in the product oper-
ating instructions.
Warning of dangerous electrical voltage.
This assembly is protected via double insulation or reinforced insulation.
Table 9: Safety-relevant symbols on the assembly
4.5.7.5
Digital inputs and outputs
The assemblies DIO 28-15 and DIO 42-20 (HL) provide you with a number
of digital inputs and outputs that differs based on the version:
▪ DIO 28-15: 28 inputs, 15 outputs (6 N/O contacts, 9 change-over con-
tacts)
▪ DIO 42-20 (HL): 42 inputs, 20 outputs (8 N/O contacts, 12 change-over
contacts)
Figure 16: DIO 42-20 assembly
Warning of a danger point. Read the information given in the product oper-
ating instructions.
Warning of dangerous electrical voltage.
Table 10: Safety-relevant symbols on the assembly
4.5.7.6
Analog inputs and outputs
The AIO 2 and AIO 4 assemblies provide analog inputs and outputs:
▪ AIO 2: 2 channels
▪ AIO 4: 4 channels
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
39
6385142/08 EN
ETOS® ED
In accordance with the device configuration, the AIO assembly supports one
of the following signal types:
Input
Output
Voltage
Current
Voltage
Current
0...10 V
0...20 mA
4...20 mA
0...10 V
0...20 mA
4...20 mA
Resistance measurement (such as PT100, resistor contact series)
Table 11: Signal types supported by the AIO assembly
Figure 17: AIO 4 assembly
4.5.7.7
Analog inputs and outputs (AIO 8)
The AIO 8 assembly provides 8 channels for analog inputs. In accordance
with the device configuration, the AIO assembly supports one of the follow-
ing signal types:
▪ Voltage: 0...10 V
▪ Current: 0/4...20 mA (only channels 1, 2, 7 and 8)
▪ Resistance measurement (e.g. PT100)
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
40
6385142/08 EN
ETOS® ED
Figure 18: AIO 8 assembly
4.5.7.8
Media converter
The MC 2-2 assembly is a media converter, which converts 2 electrical con-
nections (RJ45) to one fiber-optic cable connection each. Each is converted
independently of the other. The following interfaces are available:
▪ 2x RJ45 (ETH12, ETH22)
▪ 2x Duplex-LC (SFP module) (ETH11, ETH21)
The media converter is designed to be transparent for the network and does
not have its own IP address.
Figure 19: MC 2-2 assembly
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
41
6385142/08 EN
ETOS® ED
4.5.7.9
Media converter with managed switch
The assembly SW 3-3 is a media converter with managed switch. It com-
bines two independent functions and provides you with the following inter-
faces:
▪ A media converter converts an electric connection (RJ45) into a fiber-optic
cable connection
– RJ45 (ETH12)
– Duplex-LC (SFP module) (ETH11)
▪ Managed switch with redundancy function (PRP or RSTP)
– 2x RJ45 (ETH23, ETH24), device-internal connection
– 2x Duplex-LC (SFP module) (ETH21, ETH22), redundancy connection
The following redundancy functions are available to you according to your
order:
▪ PRP (standard setting)
▪ RSTP
Figure 20: SW 3-3 assembly
4.6 Nameplate
Depending on the version, the nameplate is in the control cabinet and/or out-
side of the control cabinet.
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
42
6385142/08 EN
ETOS® ED
Inside: ETOS® ED L, ETOS® ED L-S and ETOS® ED XL
Figure 21: Nameplate in the control cabinet
1 Nameplate
Outside: ETOS® ED XL
Figure 22: Nameplate on the control cabinet door
1 Nameplate
4.7 Protective devices
The following protective devices are fitted in the motor-drive unit:
▪ End stop device (mechanical and electric)
▪ Device protecting against unintentional passage
▪ Motor protection device
▪ Protection against accidental contact
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
43
6385142/08 EN
ETOS® ED
4.8 Safety markings
The following safety markings are used on the product:
Figure 23: Overview of safety markings
1 Warning of rotating parts
2 Warning of dangerous electrical
voltage
3 Warning of hot surface
4 Read the documentation
4.9 Emergency operation during switching blocking (X100
bridge)
The monitoring function of the on-load tap-changer is only active when the
device is ready for operation and issues a signal at the digital output Status
OK.
If your device is equipped with the OLTC monitoring expert function pack-
age, the monitoring system can block further tap-change operations where
necessary. In this case, the monitoring system will report the event Blocking
active. If operation needs to be resumed despite the cause of the event not
being eliminated, you can activate emergency operation by inserting the
X100 bridge.
If the X100 bridge is inserted, drive blocking by the monitoring system is
switched to inactive. All operating values continue to be recorded and stored
by the monitoring system.
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
44
6385142/08 EN
ETOS® ED
NOTICE
Damage to the transformer and/or on-load tap-changer
If the Blocking active event is present in the monitoring system, then the
cause of the event has to be analyzed before activating emergency opera-
tion. Performing additional tap-change operations on the motor-drive unit
without analyzing the cause may lead to on-load tap-changer and/or trans-
former damage.
►Check what caused the Blocking active event and decide whether to con-
tinue operating the on-load tap-changer based on the cause.
►Export the service data and contact Maschinenfabrik Reinhausen GmbH.
4.10 Visualization
4.10.1 Main screen
The web-based visualization is split into various areas.
Figure 24: Main screen
1 Display area
2 Secondary navigation
3 Primary navigation
4 Status bar
The most important measured values of the transformer are displayed on the
main screen. The individual status displays of the transformer shown can be
selected directly when accessing them via the web browser. They act as
links to the corresponding menu items. If you are operating the device via
the front panel, you are only able to call up the elements via the Information
menu.
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
45
6385142/08 EN
ETOS® ED
If the device does not have one of the optional functions, this will be indi-
cated in the main screen via a small padlock
.
Depending on the device configuration, the main screen displays the
schematic representation of a transformer for network applications or a
transformer for industrial applications.
4.10.1.1
Transformer for network applications
Figure 25: Transformer data
1 DGA (status)
2 Top-oil temperature
3 Hot-spot temperature
4 Cooling system (status)
5 Load current and load voltage of
phases L1, L2, L3
6 Transformer name
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
46
6385142/08 EN
ETOS® ED
Figure 26: Apparent power, oil level, and ambient temperature
1 Asset intelligence
2 Total apparent power
3 Ambient temperature
4 Oil level (transformer on left, on-
load tap-changer on right)
Figure 27: On-load tap-changer and motor-drive unit
1 OLTC oil temperature
2 Current tap position
3 Voltage regulator
4 Tap-change operation statistics
5 OLTC status message (collective
message)
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
47
6385142/08 EN
ETOS® ED
4.10.1.2
Transformer for industrial applications
Figure 28: Transformer data
1 DGA (status)
2 Top-oil temperature
3 Hot-spot temperature
4 Cooling system (status)
5 Load current an load voltage of the
phases L1, L2, L3 (high-voltage
side)
6 Transformer name
Figure 29: Apparent power, oil level, and ambient temperature
1 Asset intelligence
2 Total apparent power
3 Ambient temperature
4 Oil level (transformer on left, on-
load tap-changer on right)
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
48
6385142/08 EN
ETOS® ED
Figure 30: On-load tap-changer and motor-drive unit
1 OLTC oil temperature
2 Current tap position
3 Voltage regulator
4 Tap-change operation statistics
5 OLTC status message (collective
message)
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
49
6385142/08 EN
ETOS® ED
4.10.2 Additional operating controls and display elements when using
the MControl touch panel (optional)
If you are using the device with the optionally available MControl touch
panel, additional operating controls and display elements are displayed on
the left edge of the screen. Depending on the device configuration, a variety
of keys are available:
Figure 31: Additional display elements and operating controls
Status
LED status
Status display
1)
REMOTE key
Select the operating mode:
▪
On: REMOTE
▪
Off: LOCAL
2)
AVR AUTO key
Activate auto mode.
2)
RAISE key
Send a control command to the motor-drive
unit to increase the voltage. Only possible in
manual mode.
2)
AVR Manual key
Activate manual mode.
2)
LOWER key
Send a control command to the motor-drive
unit to reduce the voltage. Only possible in
manual mode.
1) Not available if local/remote is toggled using a digital input.
2) Only available in the "Automatic voltage regulation" function package.
4.10.3 Operating concept
You can operate the device using the controls on the front panel or using the
web-based ISM™ Intuitive Control Interface visualization on a PC. The
scope of function and structure of both options is virtually identical.
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
50
6385142/08 EN
ETOS® ED
User rights and user roles
The device is equipped with a rights system and a roles system. The display
and access rights to device settings or events can therefore be controlled at
the user level.
You can configure the rights system and roles system to meet your require-
ments. You will find more information on user rights in the User administra-
tion [►Section 9.34, Page 315] section.
You can only modify the device settings or parameters if you have the nec-
essary user rights.
Logging on, logging off and changing users
The control of access rights to device settings and parameters is user-
based. Various users can log in at the same time (e.g. via the visualization)
and access the device.
If you want to operate the device via the controls and visualization at the
same time, you have to log in on the device and via the visualization.
1. Select the LOGIN or CHANGE button in the status line.
2. Enter your user name and password and select the OK button.
ð The name of the logged-in user appears in the status line.
To log out as a user, proceed as follows:
►Press the LOGOUT button in the status line.
Navigation
If you are operating the device using the controls on the front panel, you can
use the rotary knob to navigate through the entire menu. The menu currently
selected has a blue border. To open the highlighted menu, you have to
press the
key. Pressing the
key returns you to the previous menu
level.
If you are operating the device using the web-based visualization, you can
navigate by clicking on the appropriate buttons.
Example
1. Go to Settings.
2. Go to Parameters.
3. Go to System.
4. Go to Time synchronization.
5. Select Time.
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
51
6385142/08 EN
ETOS® ED
In these operating instructions, the path for navigating to a parameter is al-
ways shown in an abridged form: Go to Settings > Parameters > System >
Time synchronization.
Setting parameters
There are various ways to configure the settings, depending on the parame-
ter.
Selecting from a list
To select a list entry, proceed as follows:
1. Use the rotary knob to navigate to the list and press the
key.
Figure 32: Select an entry from a list
2. Use the rotary knob to highlight the list entry and press the
key.
3. Press the Accept button to save the modified parameter.
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
52
6385142/08 EN
ETOS® ED
Entering a value
To enter a value, proceed as follows:
1. Use the rotary knob to select the value field and press the
key.
ð If operating via the front panel, the numerical keypad appears.
Figure 33: Entering a value
2. Enter the desired value and confirm with
.
3. Press the Accept button to save the modified parameter.
Entering text
1. Use the rotary knob to select the text box and press the
key.
ð If operating via the front panel, the keyboard appears.
Figure 34: Entering text
2. Enter the desired text and confirm with
.
3. Press the Accept button to save the modified parameter.
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
53
6385142/08 EN
ETOS® ED
Parameter search
You can use the quick search function in the parameter menu to search for a
parameter. Enter the name of the desired parameter in the Search entry
field.
Figure 35: Quick search
Expert mode
The device has an expert mode for entering the parameters. You can enter
the parameters directly on the overview screen of the respective menu in
this mode.
Figure 36: Expert mode
1. Go to Settings > Parameters.
2. Select the Expert mode checkbox.
ð Expert mode is active.
4 Product description
Maschinenfabrik Reinhausen GmbH 2020
54
6385142/08 EN
ETOS® ED
Hiding/showing parameters
Depending on how you set the parameters, the device will hide or show ad-
ditional parameters related to this function.
5 Packaging, transport and storage
Maschinenfabrik Reinhausen GmbH 2020
55
6385142/08 EN
ETOS® ED
5 Packaging, transport and storage
5.1 Packaging
The products are sometimes supplied with sealed packaging and sometimes
in a dry state, depending on requirements.
Sealed packaging surrounds the packaged goods with plastic foil on all
sides.
Products that have also been dried are identified by a yellow label on the
sealed packaging. In the dry state, delivery is also possible in a transport
container.
The information in the following sections should be applied as appropriate.
5.1.1 Suitability
NOTICE
Property damage due to incorrectly stacked crates!
Stacking the crates incorrectly can lead to damage to the packaged goods.
►The outer marking on the packaging states if, for example, the on-load
tap-changer or selector has been packed upright. Never stack these
crates.
►General rule: Do not stack crates above a height of 1.5 m.
►For other crates: Only stack up to 2 equally sized crates on top of one an-
other.
The packaging is suitable to ensure undamaged and fully functional means
of transportation in compliance with local transportation laws and regula-
tions.
The packaged goods are packed in a sturdy crate. This crate ensures that,
when in the intended transportation position, the packaged goods are stabi-
lized to prevent impermissible changes in position, and that none of the parts
touch the loading surface of the means of transport or touch the ground after
unloading.
Sealed packaging surrounds the packaged goods with plastic foil on all
sides. The packaged goods are protected from humidity using a desiccant.
The plastic foil was bonded after the desiccant is added.
5 Packaging, transport and storage
Maschinenfabrik Reinhausen GmbH 2020
56
6385142/08 EN
ETOS® ED
5.1.2 Markings
The packaging bears a signature with instructions for safe transport and cor-
rect storage. The following symbols apply to the shipment of non-hazardous
goods. Adherence to these symbols is mandatory.
Protect against
moisture
Top
Fragile
Attach lifting
gear here
Center of mass
Table 12: Shipping pictograms
5.2 Transportation, receipt and handling of shipments
WARNING
Danger of death or severe injury!
Danger of death or serious injuries due to tipping or falling load.
►Only transport the crate when closed.
►Do not remove the securing material used in the crate during transport.
►If the product is delivered on a pallet, secure it sufficiently.
►Only trained and authorized persons may select the sling gear and se-
cure the load.
►Do not walk under the suspended load.
►Use means of transport and lifting gear with a sufficient carrying capacity
in accordance with the weight stated on the delivery slip.
In addition to oscillation stress, jolts must also be expected during trans-
portation. In order to prevent possible damage, avoid dropping, tipping,
knocking over and colliding with the product.
If a crate tips over, falls from a certain height (e.g. when slings tear) or is
subject to an unbroken fall, damage must be expected regardless of the
weight.
Every delivered shipment must be checked for the following by the recipient
before acceptance (acknowledgment of receipt):
▪ Completeness based on the delivery slip
▪ External damage of any type
The checks must take place after unloading when the crate or transport con-
tainer can be accessed from all sides.
5 Packaging, transport and storage
Maschinenfabrik Reinhausen GmbH 2020
57
6385142/08 EN
ETOS® ED
Visible damage
If external transport damage is found upon receipt of the shipment, proceed
as follows:
▪ Immediately record the identified transport damage in the shipping docu-
ments and have this countersigned by the carrier.
▪ In the event of severe damage, total loss or high damage costs, immedi-
ately notify the manufacturer and the relevant insurance company.
▪ After identifying damage, do not modify the condition of the shipment fur-
ther and retain the packaging material until an inspection decision has
been made by the transport company or the insurance company.
▪ Record the details of the damage immediately on site together with the
carrier involved. This is essential for any claim for damages.
▪ Photograph damage to packaging and packaged goods. This also applies
to signs of corrosion on the packaged goods due to moisture inside the
packaging (rain, snow, condensation).
▪
NOTICE! Damage to packaged goods due to damaged sealed packag-
ing. If the product is delivered in sealed packaging, check the sealed
packaging immediately. If the sealed packaging is damaged, do not under
any circumstances install or commission the packaged goods. Either re-
dry the dried packaged goods as per the operating instructions, or contact
the manufacturer to agree on how to proceed.
▪ Identify the damaged parts.
Hidden damage
When damages are not determined until unpacking after receipt of the ship-
ment (hidden damage), proceed as follows:
▪ Make the party responsible for the damage liable as soon as possible by
telephone and in writing, and prepare a damage report.
▪ Observe the time periods applicable to such actions in the respective
country. Inquire about these in good time.
With hidden damage, it is very hard to make the transportation company (or
other responsible party) liable. Any insurance claims for such damages can
only be successful if relevant provisions are expressly included in the insur-
ance terms and conditions.
5.3 Storage of shipments
Packaged goods dried by Maschinenfabrik Reinhausen
Upon receipt of the shipment, immediately remove the packaged goods
dried by Maschinenfabrik Reinhausen from the sealed packaging and store
air-tight in dry insulating fluid until used if the packaged goods were not sup-
plied in insulating fluid.
Non-dried packaged goods
Non-dried packaged goods but with a functional sealed packaging can be
stored outdoors when the following conditions are complied with.
5 Packaging, transport and storage
Maschinenfabrik Reinhausen GmbH 2020
58
6385142/08 EN
ETOS® ED
When selecting and setting up the storage location, ensure the following:
▪ Protect stored goods against moisture (flooding, water from melting snow
and ice), dirt, pests such as rats, mice, termites and so on, and against
unauthorized access.
▪ Store the crates on timber beams and planks as a protection against ris-
ing damp and for better ventilation.
▪ Ensure sufficient carrying capacity of the ground.
▪ Keep entrance paths free.
▪ Check stored goods at regular intervals. Also take appropriate action after
storms, heavy rain or snow and so on.
Protect the packaging foil from direct sunlight so that it does not disintegrate
under the influence of UV rays, which would cause the packaging to lose its
sealing function.
If the product is installed more than 6 months after delivery, suitable mea-
sures must be taken without delay. The following measures can be used:
▪ Correctly regenerate the drying agent and restore the sealed packaging.
▪ Unpack the packed goods and store in a suitable storage space (well ven-
tilated, as dust-free as possible, humidity < 50% where possible).
5.4 Unpacking shipments and checking for transportation
damages
▪
NOTICE! Transport the packaged crate to the place where the packaged
goods are to be installed. Do not open the sealed packaging until just be-
fore installation. Otherwise, damage to the packaged goods may occur
due to ineffectively sealed packaging.
▪
WARNING! When unpacking, check the condition of the packaged
goods. Place the packaged goods in an upright crate and protect it from
tipping out. Otherwise, the packaged goods may become damaged and
serious injuries may result.
▪ Check the completeness of the accessories kit using the delivery slip.
Attachment points for lifting gear
WARNING
Danger of death and damage to property!
Danger of death and damage to property due to tipping or falling load!
►Only trained and authorized persons may select the sling gear and se-
cure the load.
►Do not walk under the suspended load.
►Use means of transport and lifting gear with a sufficient carrying capacity
in accordance with the weight stated in the Technical data section.
5 Packaging, transport and storage
Maschinenfabrik Reinhausen GmbH 2020
59
6385142/08 EN
ETOS® ED
▪
WARNING! Serious injuries and damage to the control cabinet due to
falling load. Attach the lifting gear such that the cable angle is always less
than 45° in relation to the vertical.
Figure 37: Maximum permissible cable angle for the lifting-gear limit stop of the control cabinet
▪
WARNING! Serious injuries due to the control cabinet tipping and
damage to the cable gland if the control cabinet is set down, transported
or stored upright. Only set down, transport and store the control cabinet
on its back.
▪ Only remove the control cabinet from the crane once it has been fully con-
nected to the transformer.
Maschinenfabrik Reinhausen GmbH 2020
60
6385142/08 EN
ETOS® ED
6 Mounting
This chapter describes how to correctly install and connect the device.
WARNING
Danger of death or severe injury!
An energized transformer and energized on-load tap-changer components
can cause death or serious injuries during installation of the drive!
►Ensure the de-energized state of the transformer and on-load tap-
changer components during installation of the drive.
6.1 Attaching the control cabinet to the transformer
The control cabinet has four fixing attachments on the rear to secure it.
1. Attach four stud bolts (not supplied by MR) to the transformer tank.
Figure 38: Fastening the stud bolts
A 675±2
B 500±2
Maschinenfabrik Reinhausen GmbH 2020
61
6385142/08 EN
ETOS® ED
2. For control cabinets with vibration damper: Attach the inner bracket to the
control cabinet. Attach the outer bracket to the transformer wall. The com-
plete contact surfaces of the brackets must be in contact.
1
1
1 Bracket contact surfaces
3. Use the fixing attachments to attach the control cabinet to the stud bolts
and align it vertically on the transformer tank.
Figure 39: Attaching the control cabinet
Maschinenfabrik Reinhausen GmbH 2020
62
6385142/08 EN
ETOS® ED
4. NOTICE! Damage to the control cabinet due to mechanical tension. Se-
cure the control cabinet without subjecting it to mechanical tension.
Figure 40: Securing the drive
5. Connect the grounding cable to the control cabinet and the transformer
tank, holding it against the control cabinet using a wrench (wrench
size 36).
Figure 41: Connecting the grounding cable to the control cabinet
Maschinenfabrik Reinhausen GmbH 2020
63
6385142/08 EN
ETOS® ED
6.2 Mounting drive shafts and bevel gear
The process of mounting the drive shafts and bevel gear is described in the
installation and commissioning instructions for the on-load tap-changer / de-
energized tap-changer.
6.3 Centering on-load tap-changer and motor-drive unit
WARNING
Danger of death or severe injury!
Danger of death or severe injury due to motor-drive unit starting up by acci-
dent and due to electric voltage!
►Before starting any coupling work make sure that the motor protective
switch is tripped.
►Carry out any adjustment work in manual mode only.
►When manually operating the motor-drive unit only use the hand crank
provided for this purpose.
►Note that the hand crank safety switch causes a 2-pole disconnection of
the motor circuit but that the control circuit is not interrupted.
NOTICE
Damage to property!
The on-load tap-changer will be damaged by incorrectly centering the mo-
tor-drive unit.
►Do not perform more than 250 tap-change operations on the on-load tap-
changer. If more than 250 tap-change operations are performed, com-
pletely fill oil compartment with insulating oil and lubricate sliding surfaces
of contacts on selector and selector gear with insulating oil.
The following steps for centering the on-load tap-changer and motor-drive
unit do not apply to the DEETAP® DU or COMTAP® ARS devices. The
process for centering the motor-drive unit and DEETAP® DU or COMTAP®
ARS devices is described in the relevant operating instructions.
One on-load tap-change operation is represented by one rotation of the tap-
change indicator. This indicator is divided into 33 tap-change indicator sec-
tions, each of which corresponds to one hand crank revolution in the stan-
dard motor-drive unit design. The time of the switchover depends on the on-
load tap-changer / de-energized tap-changer type, but is always 2 tap-
change indicator sections upstream of the area marked in gray on the tap-
change indicator at the latest.
To center the on-load tap-changer and motor-drive unit, proceed as follows.
1. NOTICE! Move the on-load tap-changer / de-energized tap-changer and
the motor-drive unit into the adjustment position before commencing any
adjustment work. Ensure that the tap position indicators for the motor-
Maschinenfabrik Reinhausen GmbH 2020
64
6385142/08 EN
ETOS® ED
drive unit and the on-load tap-changer / de-energized tap-changer match.
Otherwise damage to the on-load tap-changer and transformer may re-
sult.
Figure 42: Adjustment position
2. Attach the hand crank in the motor-drive unit to the shaft end located in
the upper cover plate. This activates a hand crank interlock switch, which
disconnects the motor circuit at 2 poles.
Figure 43: Hand crank
Maschinenfabrik Reinhausen GmbH 2020
65
6385142/08 EN
ETOS® ED
3. Turn the hand crank clockwise until the diverter switch operation begins.
When turning the hand crank, observe the tap-change indicator, which
mechanically reflects the progress of the tap-change operation.
Figure 44: Turning the hand crank
4. Once the diverter switch operation begins, continue to turn in the same di-
rection while counting the tap-change indicator sections required for the
pointer to reach the mid-position of the area marked in gray on the tap-
change indicator. Note the number counted (value A) and the direction of
rotation (example: A=2).
Figure 45: Counting the tap changes needed to reach the mid-position
5. If value A is greater than 8 tap-change indicator sections, the tap-change
operation has been completed correctly. If value A is less than 8 tap-
change indicator sections, turn another 8-A tap-change indicator sections
Maschinenfabrik Reinhausen GmbH 2020
66
6385142/08 EN
ETOS® ED
in the same direction (example: 8-2=6) to complete the tap-change opera-
tion. Then turn in the opposite direction until the pointer is in the mid-posi-
tion of the area marked in gray on the tap-change indicator.
Figure 46: Completing the diverter switch operation
6. Turn the hand crank counter-clockwise until the diverter switch operation
begins.
Figure 47: Turning the hand crank in the opposite direction
Maschinenfabrik Reinhausen GmbH 2020
67
6385142/08 EN
ETOS® ED
7. Once the diverter switch operation begins, continue to turn in the same di-
rection while counting the tap-change indicator sections required for the
pointer to reach the mid-position of the area marked in gray on the tap-
change indicator. Note the number counted (value B) and the direction of
rotation (example: B=5).
Figure 48: Counting the tap-change indicator sections needed to reach the mid-position
8. If value B is greater than 8 tap-change indicator sections, the tap-change
operation has been completed correctly. If value B is less than 8 tap-
change indicator sections, turn another 8 B tap-change indicator sections
in the same direction (example: 8-5=3) to complete the tap-change opera-
tion. Then turn in the opposite direction until the pointer is in the mid-posi-
tion of the area marked in gray on the tap-change indicator.
Figure 49: Completing the diverter switch operation
9. If the values obtained for A and B are identical, the on-load tap-changer
and the motor-drive unit are correctly coupled (a slight imbalance of maxi-
mum 1 tap-change indicator section is permitted). If the values obtained
for A and B are different, establish correction value C by halving the differ-
ence between A and B: C=|(A-B) x 0.5|
Example: C=|(2-5) x 0.5|=|-1.5|=1.5
Maschinenfabrik Reinhausen GmbH 2020
68
6385142/08 EN
ETOS® ED
Also take numbers after the decimal point into account.
10. If the correction value |C| is less than 0.5 tap-change indicator sections,
no further action is required. Refer to item 18 for how to proceed next.
11. Use the hand crank to crank in the direction in which the determined
value A or B was higher (example: counter-clockwise, because B > A)
until the diverter switch operation begins.
12. Once the diverter switch operation begins, continue turning another 8
hand crank revolutions in the same direction to correctly complete the di-
verter switch operation.
Maschinenfabrik Reinhausen GmbH 2020
69
6385142/08 EN
ETOS® ED
13. Uncouple the motor-drive unit and vertical drive shaft by removing the
coupling brackets. After uncoupling, do not turn the drive shaft any fur-
ther.
Figure 50: Uncoupling the motor-drive unit and drive shaft
14. Operate the motor-drive unit using the hand crank in the same direction,
continuing by C tap-change indicator sections on the tap-change indica-
tor (example: 1.5 tap-change indicator sections).
15. Couple the motor-drive unit and on-load tap-changer by refitting the verti-
cal drive shaft (tightening torque 9 Nm). Do not turn the drive shaft or
output shaft of the bevel gear or motor-drive unit any further.
16. Continue to turn in the same direction while counting the tap-change in-
dicator sections required for the pointer to reach the mid-position of the
area marked in gray on the tap-change indicator. Note the number
counted (value A) and the direction of rotation. If value A is greater than
8 tap-change indicator sections, the tap-change operation has been
completed correctly. If value A is less than 8 tap-change indicator sec-
Maschinenfabrik Reinhausen GmbH 2020
70
6385142/08 EN
ETOS® ED
tions, turn another 8 A tap-change indicator sections in the same direc-
tion (example: 8-4=4) to complete the tap-change operation. Then turn in
the opposite direction until the indicator is in the mid-position of the area
marked in gray on the tap-change indicator. Check the coupling again as
described previously.
17. The pointer of the tap-change indicator must be in the mid-position of the
area marked in gray once the on-load tap-change operation with the
hand crank is complete.
Figure 51: Pointer in the mid-position
18. Once coupling is complete in both directions, check by carrying out sev-
eral on-load tap-change operations and check that the on-load tap-
changer and motor-drive unit are in the same tap position.
6.4 Connecting the ISM® assemblies
WARNING
Electric shock!
Risk of fatal injury due to connection errors.
►Ground the device using the grounding screw on the housing.
6.4.1 Cable recommendation (ISM® assemblies)
Please note the following Maschinenfabrik Reinhausen GmbH recommenda-
tion when wiring the device.
▪ Excessive line capacitance can prevent the relay contacts from interrupt-
ing the contact current. In control circuits operated with alternating current,
take into account the effect of the line capacitance of long control cables
on the function of the relay contacts.
▪ If you want to route Ethernet connections from a control cabinet or build-
ing, we recommend using fiber-optic cables (in accordance with the
IEC 61850-90-4 recommendation).
▪ Ensure that the copper cables used have a temperature resistance of
70°C.
Maschinenfabrik Reinhausen GmbH 2020
71
6385142/08 EN
ETOS® ED
Cable
Assembly
Cable type
Conductor
cross-section
Conductor
material
Max. length
Voltage measurement
UI 1, UI 3, UI 5-4
Shielded
2.5 mm²
Copper
-
Current measurement
UI 1, UI 3, UI 5-4
Unshielded
4 mm²
Copper
-
Signal inputs
DIO 28-15,
DIO 42-20
Shielded
1.5 mm2
Copper
400 m (<25 Ω/km)
Signal outputs*
DIO 28-15,
DIO 42-20
Shielded
1.5 mm2
Copper
-
Signal inputs
AIO 2, AIO 4,
AIO 8
Shielded
1 mm2
Copper
400 m (<25 Ω/km)
Signal outputs
AIO 2, AIO 4,
AIO 8
Shielded
1 mm2
Copper
-
RS232, SUB-D
CPU I, CPU II
Shielded
0.25 mm2
-
25 m
RS485; SUB-D
CPU I, CPU II
Shielded
0.25 mm2
-
140 m
CAN bus
CPU I
Shielded
0.75 mm²
-
2,000 m (total
CAN bus)
Ethernet RJ45
CPU I
Min. CAT5,
shielded S/FTP
For
ETOS® ED XL
Angle plug rec-
ommended
-
-
100 m
Ethernet FO
MC 2-2, SW 3-3
Duplex LC
Multimode, OM3,
1310 nm
-
-
2000 m
Table 13: Recommendation for connection cables
*) Observe line capacitance, see note above.
6.4.2 Information about connecting serial interfaces RS232 and RS485
NOTICE
Damage to the device!
Using the wrong data cable may damage the device.
►Only use data cables which comply with the description below.
Maschinenfabrik Reinhausen GmbH 2020
72
6385142/08 EN
ETOS® ED
RS232 (D-SUB 9-pole)
For connecting the device via the RS232 interface (COM2), use a data cable
with the following structure:
Figure 52: RS232 data cable (9-pole)
RS485 (D-SUB 9-pole)
To connect the device via the RS485 interface (COM2), use a data cable
with the following structure:
Figure 53: RS485 data cable
Maschinenfabrik Reinhausen GmbH 2020
73
6385142/08 EN
ETOS® ED
D-SUB 9-pole plug connection
Only use 9-pole D-SUB plugs with the following characteristics:
▪ Plug housing is metallic or metal-plated
▪ Cable shielding is connected with the plug using one of the two following
variants:
– Shielding is screwed down with traction relief.
– Shielding is soldered with plug housing.
Figure 54: Example of a soldered shielding on a plug housing
6.4.3 Notes on connecting to the MR sensor bus
The optionally available MR sensor bus function lets you connect digital and
analog sensors to the device over Modbus RTU. The MR sensor bus sup-
ports the connection of up to 31 sensors (Modbus slaves). The ISM® device
operates as the Modbus master.
Ensure that no other Modbus master is connected over the MR sensor bus.
Assign a unique Modbus address to each sensor you are connecting over
MR sensor bus. The MR sensor bus may experience errors if multiple sen-
sors are using the same Modbus address.
Observe the following notes for connecting the sensors:
▪
NOTICE! Damage to the device or sensor. Connect all of the sensors to
the potential equalization rail to avoid circulating currents over the MR
sensor bus.
▪ The MR sensor bus uses Modbus in a 2-wire configuration (2W). The 4-
wire configuration (4W) is not supported.
▪ You must connect the sensors via a shielded line with 3 conductors (D0,
D1, Common). The data lines (D0, D1) must be in twisted pairs. Note the
cable recommendation.
▪ Stub lines from the bus node to the respective device must be shorter
than 20 m.
Maschinenfabrik Reinhausen GmbH 2020
74
6385142/08 EN
ETOS® ED
▪ The CPU assembly contains a terminating resistor (120 Ω) at the COM2
interface. Install another terminating resistor (120 Ω, 0.5 W) at the other
end of the bus.
▪ The CPU assembly contains a pull-up resistor and a pull-down resistor
(each of 680 Ω in accordance with the Modbus specification). No addi-
tional pull-up/pull-down resistors are needed.
CPU-COM2
Sensor 1
Sensor x
D0 (A)
D1 (B)
Com. (C)
1
2
3
4
5
6
7
8
9
D0 (A)
D1 (B)
Com. (C)
D0 (A)
D1 (B)
Com. (C)
120 Ω
Figure 55: MR sensor bus
Maschinenfabrik Reinhausen GmbH 2020
75
6385142/08 EN
ETOS® ED
6.4.3.1
MSENSE® DGA
If you would like to use an MSENSE® DGA sensor, you must connect the
sensor to the MR sensor bus in accordance with the following connection ex-
amples. If the MSENSE® DGA sensor is the only bus device or the last bus
device, you must use a terminating resistor (120 Ω, 0.5 W).
CPU-COM2
MSENSE DGA 2/3
D0 (A)
D1 (B)
Com. (C)
1
2
3
4
5
6
7
8
9
D0 (A)
D1 (B)
Com. (C)
1
4
2
3
5
1
2
3
4
5
D1 (B)
D0 (A)
Figure 56: Connection example MSENSE® DGA 2/3 (connector M12, type A, 5-pole in accor-
dance with IEC 61076-2-101)
CPU-COM2
MSENSE DGA 5
D0 (A)
D1 (B)
Com. (C)
1
2
3
4
5
6
7
8
9
(PhoneB)
(GND)
X302:5
X302:4
X302:3
X302:2
X302:1
(OUTA)
(OUTB)
(PhoneA)
Figure 57: Connection example MSENSE® DGA 5 (terminal X302)
Maschinenfabrik Reinhausen GmbH 2020
76
6385142/08 EN
ETOS® ED
CPU-COM2
MSENSE DGA 9
D0 (A)
D1 (B)
Com. (C)
1
2
3
4
5
6
7
8
9
(PhoneB)
(GND)
X304:5a
X304:4b
X304:3
X304:1a
X304:1b
(OUTA)
(OUTB)
(PhoneA)
Figure 58: Connection example MSENSE® DGA 9 (terminal X304)
6.4.3.2
MESSKO® MTeC® EPT303 FO
If you would like to use a MESSKO® MTeC® EPT303 FO sensor, you must
connect the sensor to the RS485 plug terminals on the sensor bus. Use a
shielding clamp to apply the shield to the cable. You can directly connect ad-
ditional MESSKO® MTeC® EPT303 FO sensors to the plug terminal.
The EPT303 FO sensor module contains a terminating resistor. If you would
like to use the EPT303 FO sensor together with other sensor types on an
MR sensor bus, then we recommend connecting the EPT303 FO sensor to
the end of the bus.
CPU-COM2
EPT303 FO
D0 (A)
D1 (B)
Com. (C)
1
2
3
4
5
6
7
8
9
D+ (B)
GND
D- (A)
D+ (B)
GND
D- (A)
1
2
3
4
5
6
1
6
Figure 59: Connection example MESSKO® MTeC® EPT303 FO (terminal RS485)
Maschinenfabrik Reinhausen GmbH 2020
77
6385142/08 EN
ETOS® ED
6.4.3.3
MESSKO® MTRAB® 2.5
If you would like to use a MESSKO® MTRAB® 2.5 sensor, you must con-
nect the sensor to the RS485 plug terminals on the sensor bus.
CPU-COM2
MTRAB 2.5
D0 (A)
D1 (B)
Com. (C)
1
2
3
4
5
6
7
8
9
D+ | Rx+
D- | Rx-
Comm
Tx-
Tx+
Shield
Figure 60: Connection example MESSKO® MTRAB® 2.5 (terminal RS485)
You must enable the half-duplex operating mode on the sensor by switching
the "Duplex mode" switch to the "HALF" setting. If the MESSKO® MTRAB®
2.5 sensor is the only bus device or the last bus device, you must activate
the sensor terminating resistor by switching the "BUS termination 120 ohms"
switch to the position "1 = ON" and "2 = OFF".
Figure 61: MESSKO® MTRAB® 2.5 Modbus configuration
1 Terminating resistor: in half duplex
mode: 1 = ON, 2 = OFF; in full du-
plex mode: 1 = ON, 2 = ON
2 Operating mode: HALF = half du-
plex, FULL = full duplex
3 Modbus address
Maschinenfabrik Reinhausen GmbH 2020
78
6385142/08 EN
ETOS® ED
6.4.3.4
MSENSE®-FO ECU-I/S
If you would like to use an MSENSE®-FO ECU-I or ECU-S sensor, you must
connect the sensor to the RS485 plug terminals on the sensor bus. Use a
shielding clamp to apply the shield to the cable. If the MSENSE®-FO sensor
is the only bus device or the last bus device, you must use a terminating re-
sistor (120 Ω, 0.5 W). You must activate the half-duplex, 2-conductor operat-
ing mode on the sensor via the MSET-FO configuration software.
CPU-COM2
MSENSE®-FO
D0 (A)
D1 (B)
Com. (C)
1
2
3
4
5
6
7
8
9
Tx+ 1
2
3
4
5
Tx-
Rx+
Rx-
GND
Figure 62: Connection example MSENSE®-FO ECU-I and ECU-S (terminal RS485)
6.4.4 Information about connecting analog sensors
NOTICE
Damage to the device and sensors!
Incorrectly connected and configured analog inputs/outputs may result in
damage to the device and sensor.
►Follow information about connecting analog sensors [►Section 6.4.4,
Page 78].
►Configure analog inputs and outputs according to the connected sensors.
Maschinenfabrik Reinhausen GmbH 2020
79
6385142/08 EN
ETOS® ED
The AIO assembly has a separate plug connector for each channel (input or
output). The plugs are assigned as follows:
1
3
2
4
5
11
13
12
14
15
6
8
7
9
10
16
18
17
19
20
RDY
AIO
+
-
24V DC
1
3
2
4
5
1
2
3
4
5
Figure 63: Plug assignment of the AIO module (illustration using module AIO 4 as an example)
Interface
Pin
Description
1
6
11
16
I OUT (+): Current output +
2
7
12
17
I/U IN (+) U OUT (+): Voltage input
+, current input +, voltage output +
3
8
13
18
I/U IN (-): Voltage input -, current in-
put -
4
9
14
19
I/U OUT (-): Voltage output -, current
output -
5
10
15
20
Not used
Table 14: Analog inputs and outputs
You can connect the following types of analog sensors:
▪ 4...20 mA
▪ PT100/PT1000 (2-wire, 3-wire, 4-wire)
Maschinenfabrik Reinhausen GmbH 2020
80
6385142/08 EN
ETOS® ED
4...20 mA sensor
You must connect a 4...20 mA sensor to the pins
and
. You must also
connect the supplied bridge to the pins
,
, and
.
I OUT (+)
I/U IN (+)
U OUT (+)
I/U IN (-)
I/U OUT (+)
1
2
3
4
5
---
4...20 mA signal source
Figure 64: Connection example for a 4...20 mA sensor
PT100/PT1000 sensor
Depending on type, you must connect a PT100 sensor or PT1000 sensor as
follows:
▪ 2-wire: pin
and
▪ 3-wire: pin
,
and
▪ 4-wire: pin
,
,
, and
I OUT (+)
I/U IN (+)
U OUT (+)
I/U IN (-)
I/U OUT (+)
1
2
3
4
5
---
2-wire
I OUT (+)
I/U IN (+)
U OUT (+)
I/U IN (-)
I/U OUT (+)
1
2
3
4
5
---
3-wire
I OUT (+)
I/U IN (+)
U OUT (+)
I/U IN (-)
I/U OUT (+)
1
2
3
4
5
---
4-wire
PT100/PT1000
Figure 65: Connection example for a PT100/PT1000 sensor
Maschinenfabrik Reinhausen GmbH 2020
81
6385142/08 EN
ETOS® ED
6.4.5 Electromagnetic compatibility
The device has been developed in accordance with applicable EMC stan-
dards. The following points must be noted in order to maintain the EMC
standards.
6.4.5.1
Wiring requirement of installation site
Note the following when selecting the installation site:
▪ The system's overvoltage protection must be effective.
▪ The system's ground connection must comply with all technical regula-
tions.
▪ Separate system parts must be joined by a potential equalization.
▪ The device and its wiring must be at least 10 m away from circuit-break-
ers, load disconnectors and busbars.
6.4.5.2
Wiring requirement of operating site
Note the following when wiring the operating site:
▪ Route the connecting leads in grounded metal cable ducts.
▪ Do not route lines which cause interference (e.g. power lines) and lines
susceptible to interference (e.g. signal lines) in the same cable duct.
▪ Maintain a distance of more than 100 mm between lines which cause in-
terference and those which are susceptible to interference.
Figure 66: Recommended wiring
1 Cable duct for lines causing inter-
ference
3 Cable duct for lines susceptible to
interference
2 Line causing interference (e.g.
power line)
4 Line susceptible to interference
(e.g. signal line)
▪ Short-circuit and ground reserve lines.
▪ Never connect the device with a multi-wire collective pipe.
Maschinenfabrik Reinhausen GmbH 2020
82
6385142/08 EN
ETOS® ED
▪ For signal transmission, use shielded lines with individual conductors (out-
going conductor / return conductor) twisted in pairs.
▪ Connect full surface of shielding (360º) to device or to a nearby grounding
bar.
Using single conductors may limit the effectiveness of the shielding. Con-
nect close-fitting shielding to cover all areas.
Figure 67: Recommended connection of the shielding
1 Connection of the shielding via a
single conductor
2 Full-surface connection of the
shielding
6.4.5.3
Wiring requirement in control cabinet
Note the following when wiring the control cabinet:
▪ The control cabinet where the device will be installed must be prepared in
accordance with EMC requirements:
– Functional division of control cabinet (physical separation)
– Constant potential equalization (all metal parts are joined)
– Line routing in accordance with EMC requirements (separation of lines
which cause interference and those susceptible to interference)
– Optimum shielding (metal housing)
– Overvoltage protection (lightning protection)
– Collective grounding (main grounding rail)
– Cable bushings in accordance with EMC requirements
– Any contactor coils present must be interconnected
▪ The device's connection cables must be laid in close contact with the
grounded metal housing or in metallic cable ducts with a ground connec-
tion.
▪ Signal lines and power lines/switching lines must be laid in separate cable
ducts.
Maschinenfabrik Reinhausen GmbH 2020
83
6385142/08 EN
ETOS® ED
6.4.5.4
Information about shielding the CAN bus
In order for the CAN bus to operate faultlessly, you have to connect the
shielding using one of the following variants. If you are not able to use any of
the variants detailed below, we recommend using fiber-optic cables. Fiber-
optic cables decouple the devices and are not sensitive to electromagnetic
interference (surge and burst).
NOTICE
Damage to the device!
If you connect the CAN bus cable to devices with different potentials, cur-
rent may flow across the shielding. This current may damage the device.
►Connect the devices to a potential equalization rail to equalize the poten-
tial.
►If both devices have different potentials, only connect the CAN bus cable
shielding to one device.
Variant 1: The connected devices share the same potential
If the devices to be connected share the same potential, proceed as follows:
1. Connect all devices to a potential equalization rail to equalize the poten-
tial.
2. Connect the CAN bus cable shielding to all connected devices.
Variant 2: The connected devices have different potential levels
Note that the shielding is less effective with this variant.
If the devices to be connected have different potential levels, proceed as fol-
lows:
►Connect the CAN bus cable shielding to just one device.
Connecting shielding
Connect the shielding for the CAN bus cable to the 9-pin D-sub connector:
1
5
9
6
Figure 68: Connection of CAN bus cable shielding to the 9-pin D-sub connector
Maschinenfabrik Reinhausen GmbH 2020
84
6385142/08 EN
ETOS® ED
6.4.5.5
Information about shielding the cables for analog signals
In order to correctly record the analog signals, you must place the cable
screening in the motor-drive unit on the grounding bar. The cable shielding
should only be removed just prior to connecting, to ensure that the section
with unshielded cables is kept as short as possible. The shielding must be
connected with shielding clips.
1
3
2
4
5
11
13
12
14
15
6
8
7
9
10
16
18
17
19
20
RDY
AIO 4
+
-
24V DC
11
12
13
14
15
16
17
18
20
19
1
2
3
4
5
6
7
8
9
10
Figure 69: Examples of supporting shielding on grounding bar (on left: Direct connection to AIO
assembly, on right: Connection using line-up terminal)
6.4.6 Connecting cables to the system periphery
To obtain a better overview when connecting cables, only use as many
leads as necessary.
To connect cables to the system periphery, proceed as follows:
ü Use only the specified cables for wiring. Note the cable recommendation.
►Connect the lines to be wired to the device to the system periphery as
shown in the connection diagrams supplied.
6.4.7 Wiring the device
To obtain a better overview when connecting cables, only use as many
leads as necessary.
To wire the device, proceed as follows:
ü Note the connection diagram.
ü Only use the specified cables for wiring. Note the cable recommendation.
ü Wire the leads to the system periphery [►Section 6.4.6, Page 84].
1. Strip insulation from cables and wires.
Maschinenfabrik Reinhausen GmbH 2020
85
6385142/08 EN
ETOS® ED
2. Crimp stranded wires with wire end sleeves.
3. Guide the cables into the corresponding plug terminals and fasten them
using a screwdriver.
Figure 70: Example: Plug for voltage measurement
Figure 71: Example: Plug for current measurement
4. Insert the plug into the associated slots and lock or screw the plug in
place.
Maschinenfabrik Reinhausen GmbH 2020
86
6385142/08 EN
ETOS® ED
6.4.8 Mounting terminating resistor of CAN bus
If you want to operate the device in parallel operation, you need to mount a
120 Ω terminating resistor at both ends of the CAN bus. Use the plug con-
nector with terminating resistor provided as an option.
Figure 72: Terminating resistor of CAN bus
6.5 Connecting the motor-drive unit
WARNING
Danger of death or severe injury!
An energized transformer and energized on-load tap-changer components
could cause death or serious injuries when installing the electrics!
►Adherence to the following safety precautions is mandatory.
The drive may only be connected to circuits that are equipped with an exter-
nal and all-pole isolating device as close to the drive as possible to ensure
that the unit can be fully de-energized if required (service, maintenance etc.).
Furthermore, a drive without its own overcurrent protective device for the
control circuit and the heater circuit may only be connected to circuits that
are equipped with an external overcurrent protective device. The protective
device must ensure protection against indirect touching. The protection rec-
ommended by Maschinenfabrik Reinhausen GmbH close to the drive is 1.6
A C (3.0 A C is to be used in a heater circuit with additional heating and sup-
ply voltage <127 V AC/DC). This is to be verified after installation by carrying
out a measurement.
Maschinenfabrik Reinhausen GmbH 2020
87
6385142/08 EN
ETOS® ED
Suitable equipment includes isolating devices in accordance with IEC
60947-1 and IEC60947-3 (e.g. circuit breaker). When selecting the circuit
breaker type, the properties of the relevant circuits (voltage, maximum cur-
rents) must be observed. The following should also be noted during installa-
tion:
▪ It must be easy for the operator to access the isolating device
▪ The isolating device must be labeled for the device and circuits to be iso-
lated
▪ The isolating device may not be a part of the power line
▪ The isolating device may not interrupt the main protective conductor
Unless specified otherwise, the connections for the supply circuits must have
a conductor cross-section of at least 2.5 mm2 (16 AWG). Check applicable
standards and directives to ensure that the specified minimum cross-section
of the supply line is sufficient.
6.5.1 Cable recommendation
NOTICE
Damage to the device.
Current flow through the shielding of signal lines can cause the device to
become damaged.
►For signal lines between the motor-drive unit and transformer, connect
the shielding of the signal line to the motor-drive unit only.
►For all other signal lines, connect the shielding on both sides as long as
there is no potential difference between the two devices. If there is a po-
tential difference, then connect the shielding on one side only even when
using these signal lines.
Please note the following Maschinenfabrik Reinhausen GmbH recommenda-
tion when wiring.
▪ Electromagnetic interference on signal lines, which can be expected due
to the transformer's surroundings, can disrupt the proper operation of the
motor-drive unit.
▪ Where possible, route signal lines with shielding.
▪ Ensure that the copper cables used have a temperature resistance of
70°C.
Circuit
Function
Type
Material
Motor circuit
Power supply
Unshielded, separate cable
Copper
Control circuit
Power supply
Unshielded, separate cable
Copper
Tap-change supervisory con-
trol
Shielded
Copper
Pulse circuit, raise/lower
Shielded
Copper
Tripping circuit Q1-Off
Shielded
Copper
Monitoring circuit
Temperature sensor
Shielded
Copper
Signaling circuits
Signal transmission
Shielded
Copper
Maschinenfabrik Reinhausen GmbH 2020
88
6385142/08 EN
ETOS® ED
Circuit
Function
Type
Material
Cross wiring between motor-
drive units
Power supply
Unshielded, separate cable
Copper
Tap-change supervisory con-
trol
Shielded
Copper
Pulse circuit, raise/lower
Shielded
Copper
Tripping circuit Q1-Off
Shielded
Copper
Table 15: Recommendation for connection cables
6.5.2 Electrical connection
The voltage supply for the motor-drive unit must be able to provide 5…7
times the nominal operating current of the motor-drive unit for one second.
A maximum voltage tolerance of -20…+10% of the nominal voltage must be
observed to avoid damage to the drive.
1. Switch off the voltage supply.
2. Secure the voltage supply to prevent an unintentional restart.
3. Ensure that everything is de-energized.
4. Visibly ground and short-circuit the motor-drive unit.
5. Cover or cordon off adjacent energized parts.
6. Connect the motor-drive unit in accordance with the connection diagrams
provided in the briefcase. Observe the supply voltages (motor circuit, con-
trol circuit, heater circuit) and pin assignments stated in the connection di-
agram.
7. When operating the motor-drive unit, ensure that a current corresponding
to that stated in the Technical Data chapter (Load capacity of micro-
switches) flows through the micro-switches in the motor-drive unit at all
times to ensure correct functioning of the micro-switches.
Maschinenfabrik Reinhausen GmbH 2020
89
6385142/08 EN
ETOS® ED
7 Commissioning
7.1 Starting up motor-drive unit
Preparation
1. Make sure that the motor-drive unit is connected as shown in the connec-
tion diagram provided.
2. Ensure that all protective conductors are connected correctly.
3. Ensure that the preliminary fuse is selectively configured for the protective
devices in the motor-drive unit.
4. Ensure that motor-drive unit and on-load tap-changer are correctly cou-
pled and the operating positions of the motor-drive unit and on-load tap-
changer match.
5. Ensure that the hand crank is not inserted in the hand crank aperture.
6. Ensure that all signaling contacts provided in the connection diagram are
output and monitored in the control room.
7. Ensure that the motor protective switch and control circuit fuse are dis-
abled.
Commissioning
1. Apply voltage to the motor-drive unit.
2. Measure the voltage and frequency of the motor circuit at terminal X1 and
compare with the details on the nameplate. The details must match.
3. As an option with separate control-circuit supply: Measure the voltage and
frequency of the control circuit at terminal X1 and compare with the details
on the nameplate. The details must match.
4. As an option with separate heating-circuit supply: Measure the voltage of
the heater circuit at terminal X1 and compare with the details on the con-
nection diagram. The details must match.
5. As an option with three-phase motor: Ensure that the voltage applied to
the connection terminals has a clockwise phase sequence.
6. As an option with DC motor: Ensure that the motor voltage has the right
potential connection.
7. Engage the motor protective switch and fuses for the control circuit and
heater circuit (if present).
ð The voltage monitor LED and thermostat LED (if present) on the rear of
the swing frame must light up green.
8. Close the motor-drive unit and secure it against unauthorized opening by
using a padlock.
ð Commissioning is complete.
Contact Maschinenfabrik Reinhausen GmbH if anything is not clear or you
encounter problems during commissioning.
Maschinenfabrik Reinhausen GmbH 2020
90
6385142/08 EN
ETOS® ED
7.2 Tests on motor-drive unit
WARNING
Electric shock!
Risk of death or severe injury due to electrical voltage!
►Make sure that the motor-drive unit is correctly connected as shown in
the connection diagrams provided.
►Make sure that the supply voltage is matched to the technical data of the
motor-drive unit.
►Ensure contact safety before performing the checks and tests. The trans-
mission gear cover plate must be fitted and the motor and swing frame
closed.
►Ensure that the motor-drive unit and on-load tap-changer/de-energized
tap-changer are correctly coupled and that they are in the same tap posi-
tion for each operating position.
Please contact Maschinenfabrik Reinhausen GmbH (MR) if any aspect of
the tests is not clear.
7.2.1 Checking correct electric switch-off
1. Change over motor-drive unit by moving control switch S3.
2. Check that the pointer of the tap-change indicator stops within the gray
field after completing a tap-change operation.
3. Carry out this test in both directions.
Maschinenfabrik Reinhausen GmbH 2020
91
6385142/08 EN
ETOS® ED
7.2.2 Checking mechanical and electric end stop of on-load tap-
changer/de-energized tap-changer and motor-drive unit
1. Press the S3 control switch to switch the motor-drive unit to the second-
to-last operating position.
Figure 73: S3 control switch
2. Open the motor-drive unit door and switch off the motor protective switch
Q1 (position O).
3. Using the hand crank, operate the motor-drive unit to move it to its last op-
erating position. If the last operating position is not reached, check the
coupling between the on-load tap-changer / de-energized tap-changer
and motor-drive unit.
4. Continue turning the motor-drive unit in the same direction with the hand
crank until the motor-drive unit is mechanically blocked.
5. Turn back the motor-drive unit with the hand crank to the mid-position of
the tap-change indicator.
6. Remove the hand crank.
7. Switch on motor protective switch Q1 (position I).
8. Check that the motor-drive unit no longer starts up when the S3 switch is
turned further in the same operating direction as under item 1.
9. Perform the check for both end positions.
7.2.3 Checking tripping of motor protective switch
Proceed as follows to check tripping of the motor protective switch:
ü The motor protective switch Q1 is switched on (position I).
1. Close X1:14 - X1:15 Q1 OFF connection to trip the motor protective
switch.
ð The motor protective switch is tripped (position O). If the motor protec-
tive switch is not tripped, contact Maschinenfabrik Reinhausen GmbH.
2. Switch on motor protective switch again (position I).
ð The tripping of the motor protective switch is checked.
Maschinenfabrik Reinhausen GmbH 2020
92
6385142/08 EN
ETOS® ED
7.2.4 Checking functional reliability
To ensure that the device is wired correctly, check its functional reliability.
NOTICE
Damage to device and system periphery
An incorrectly connected device can lead to damage to the device and sys-
tem periphery.
►Check the entire configuration before commissioning.
Check the following:
▪ The RUN LED on the CPU I assembly lights up.
The device is fully mounted and can be configured. The actions required for
this are described in the following chapter.
7.3 Tests on the transformer
Please contact Maschinenfabrik Reinhausen GmbH (MR) if any aspect of
the tests is not clear.
7.3.1 High-voltage tests on the transformer
Note the following points before performing high-voltage tests on the trans-
former:
▪ Ensure that the oil compartment of the on-load tap-changer is completely
filled with insulating fluid.
▪ Ensure that all protective devices for the on-load tap-changer are function-
ing correctly and are ready for use.
▪ Ensure that the ground connections on the motor-drive protective housing
and protective housing fastening are free of paint.
▪ Only perform high voltage test if motor-drive unit door is closed.
▪ Disconnect external connections to electronic components in the motor-
drive unit to prevent damage from overvoltage.
▪ When connecting the motor-drive unit's supply voltage, only use the cable
bushings in the protective housing base intended for lead insertion.
▪ Guide all ground connecting leads to one central connection point (estab-
lishment of suitable reference earth).
▪ Disconnect all electronic components before the high voltage test. Before
a dielectric test of the wiring, remove all devices with a withstand voltage
of < 1000 V.
Maschinenfabrik Reinhausen GmbH 2020
93
6385142/08 EN
ETOS® ED
▪ Remove leads used for testing before the high voltage test as these func-
tion as antennas.
▪ Wherever possible, route the measurement leads and data leads sepa-
rately to the energy cables.
Contact the manufacturer if you have any questions about possible sources
of danger.
7.3.2 Dielectric tests on transformer wiring
Note the following points for dielectric tests on the transformer wiring:
The motor-drive unit is put through dielectric tests before delivery.
►Before the dielectric test for the transformer wiring, disconnect drive from
the section to be tested to rule out increased component loading for those
components fitted in the motor-drive unit.
7.4 Transporting transformer to the operating site
If the drive must be removed in order to transport the transformer, proceed
as follows:
1. Ensure that the drive and the on-load tap-changer are in the adjustment
position.
2. Remove the drive.
3. Do not actuate the drive while the on-load tap-changer is uncoupled and
do not turn the output shaft.
4. Do not actuate an on-load tap-changer which is uncoupled and do not turn
its drive shaft.
5. Transport the drive to the installation site in the MR delivery packaging.
6. Fit drive and drive shaft to transformer at the installation site.
7.5 Commissioning the transformer at the operating site
NOTICE
Damage to motor-drive unit!
Damage to the motor-drive unit due to condensate in protective housing of
motor-drive unit.
►Always keep protective housing of the motor-drive unit tightly closed.
►In the event of downtime lasting more than 8 weeks prior to initial com-
missioning, connect and operate the anti-condensation heater in the mo-
tor-drive unit. If this is not possible, place a sufficient amount of desiccant
in the protective housing.
Maschinenfabrik Reinhausen GmbH 2020
94
6385142/08 EN
ETOS® ED
NOTICE
Damage to the on-load tap-changer and motor-drive unit!
Damage to on-load tap-changer and motor-drive unit due to incorrect use of
position transmitter equipment.
►Only circuits stated in the chapter Technical data for position transmitter
equipment [►Section 14.3, Page 380] may be connected to the position
transmitter module connections.
►The switchover point of the position transmitter equipment in the motor-
drive unit is not the same as the switchover point of the diverter switch
operation. This depends on the type of diverter switch. This fact should
be noted when project planning the locking circuits between the motor-
drive unit and external equipment (e.g. transformer circuit breaker).
►Therefore, the "Tap changer in operation" position transit contact shown
in the connection diagram should be used for external monitoring, locking
and control purposes instead of the position transmitter equipment.
1. Commission motor-drive unit [►Section 7.1, Page 89].
2. Ensure correct function of motor-drive unit [►Section 7.2, Page 90].
3. Commission the transformer.
7.6 Visualization
7.6.1 Establishing connection to visualization
Depending on the product version, you can establish a connection to the vi-
sualization as follows.
ETOS® ED without display
You can use the ETH2.1 interface or the optional ETH2.2 interface of the
CPU assembly to establish the connection to the visualization. The inter-
faces do not use a DHCP server. Therefore, you must assign a static IP ad-
dress to your PC. To do this, observe the following configuration example:
Interface
Configuration
Standard
ETH2.1
IP address: 192.168.165.1 (not adjustable)
PC
IP address: 192.168.165.100
Subnet mask: 255.255.255.0
Optional
ETH2.2
IP address: 192.0.1.230 (factory setting) [►Section
9.3, Page 111]
Subnet mask: 255.255.255.0
PC
IP address: 192.0.1.100
Subnet mask: 255.255.255.0
Table 16: Interface configuration example
Maschinenfabrik Reinhausen GmbH 2020
95
6385142/08 EN
ETOS® ED
To establish a connection, proceed as follows:
1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the
ETH2.1 or ETH2.2 interface.
Figure 74: Establishing a connection via the ETH2.1 or ETH2.2 interface
2. Assign a unique IP address to the PC. This IP address must be in the
same subnet as the device (e.g. ETH2.1: 192.168.165.100).
3. Enter the IP address of the visualization (e.g. ETH2.1:
http://192.168.165.1; if SSL encryption is active, enter
https://192.168.165.1) in the browser on the PC.
ð The visualization is accessed.
ETOS® ED with display
You can use the ETH1.1 front interface or the optional ETH2.2 interface of
the CPU assembly to establish the connection to the visualization. To do
this, observe the following configuration example:
Interface
Configuration
Standard
ETH1.1
IP address: 192.168.165.1 (not adjustable)
PC
Automatic configuration via DHCP
Optional
ETH2.2
IP address: 192.0.1.230 (factory setting) [►Section
9.3, Page 111]
Subnet mask: 255.255.255.0
PC
IP address: 192.0.1.100
Subnet mask: 255.255.255.0
Table 17: Interface configuration example
Maschinenfabrik Reinhausen GmbH 2020
96
6385142/08 EN
ETOS® ED
ETH1.1 interface
To establish a connection via the ETH1.1 interface, proceed as follows:
1. Connect the PC and the device via the front interface using an Ethernet
cable (RJ45 plug).
Figure 75: Establishing a connection via the front interface
2. Activate automatic assignment of the IP address via DHCP on the PC.
3. Enter the visualization's IP address http://192.168.165.1, or if SSL
encryption is active enter https://192.168.165.1, in the browser on
the PC.
ð The visualization is accessed.
ETH2.2 interface (optional)
The device is supplied with the IP address 192.0.1.230 at the factory. If
you have changed the IP address, you can view the IP address in the Com-
munication menu.
Maschinenfabrik Reinhausen GmbH 2020
97
6385142/08 EN
ETOS® ED
To connect via the ETH2.2 interface, proceed as follows:
1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the
ETH2.2 interface.
Figure 76: Establishing a connection via the ETH2.2 interface on the back
2. Assign a unique IP address to the PC in the same subnet as the device
(e.g. 192.0.1.100).
3. Enter the visualization's IP address (e.g. http://192.0.1.230, if SSL
encryption is active enter https://192.0.1.230) in the browser on the
PC.
ð The visualization is accessed.
7.6.2 Setting the language
You can use this parameter to set the display language for the device. The
device comes with a maximum of four languages.
English
Italian*
German
Portuguese*
French*
Russian*
Spanish*
Chinese*
Korean*
Polish*
Table 18: Available display languages
*) Language is available as an option
1. Select the Language button in the status bar, or as an alternative, go to
Settings> System > General > Language.
Figure 77: Setting the language
2. Select the desired language from the list box.
3. Press the Accept button to save the modified parameter.
ð The "Restart device" dialog appears.
Maschinenfabrik Reinhausen GmbH 2020
98
6385142/08 EN
ETOS® ED
4. Restart the device to apply the changed language setting.
7.6.3 Setting date and time
You can set the date and time in the following ways:
▪ Manually
▪ Time synchronization via control system (SCADA)
▪ Time synchronization via SNTP time server
If you are using a control system, the device automatically synchronizes the
date and time with the control system. If you would like to use an SNTP time
server, you must set the required parameters.
For more information, refer to the information in the section Setting the de-
vice time [►Section 9.5, Page 116].
7.6.4 Commissioning wizard
If you want the device to help when setting the relevant parameters, you can
use the commissioning wizard. The commissioning wizard provides a selec-
tion of parameters that you can configure in order.
A detailed description of each of the parameters can be found in the Opera-
tion chapter.
To call up the commissioning wizard, you will need the necessary access
rights [►Section 9.34, Page 315].
When in delivery status, you can log in as the administrator as follows:
▪ User name: admin
▪ Password: admin
To set the parameters with the help of the commissioning wizard, proceed
as follows:
1. Log in as a user with the necessary access rights.
Maschinenfabrik Reinhausen GmbH 2020
99
6385142/08 EN
ETOS® ED
2. Go to Settings > Commissioning wizard.
Figure 78: Calling up the commissioning wizard
3. Press the Next button to launch the commissioning wizard.
4. Follow the on-screen instructions.
Once you have entered all of the parameters relevant to commissioning,
continue with the function test.
7.6.5 Checking measured values and status of digital inputs and
outputs
Upon commissioning the device, check whether the measured values and
status of digital inputs and outputs are plausible. To do so, use an additional
measuring device if necessary in order to check the individual measured val-
ues.
To display the status of the digital inputs and outputs, proceed as follows:
1. Go to Information > Hardware.
2. Select the individual assemblies one after another and check the individ-
ual measured values or the status of digital inputs and outputs.
3. If errors arise, check the measurement path and the wiring.
7.6.6 Checking the temperature measurement
To commission the device, check whether the measured temperatures are
plausible, the temperature sensors are correctly wired and are assigned to
the desired functions. To do so, proceed as follows:
1. Display the temperature curve [►Section 9.24.4, Page 253].
2. Use a suitable measuring instrument to measure the temperatures at the
measurement points and compare these values to the displayed tempera-
tures.
ð The temperatures must match, though small deviations are permitted
due to the measurement tolerances.
Maschinenfabrik Reinhausen GmbH 2020
100
6385142/08 EN
ETOS® ED
3. If the temperatures do not match, use the connection diagram to check
the wiring. Check configuration of the analog inputs [►Section 9.29, Page
292]. Check the function of the temperature sensors.