MR ETOS ED Operating Instructions Manual

Text of the manual

© All rights reserved by Maschinenfabrik Reinhausen

Dissemination and reproduction of this document and use and disclosure of its content are strictly prohibited unless expressly permitted. Infringements will result in liability for compensation. All rights reserved in the event of the granting of patents, utility models or designs. The product may have been altered since this document was published. We reserve the right to change the technical data, design and scope of supply. Generally the information provided and agreements made when processing the individual quotations and orders are binding. The original operating instructions were written in German.

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 3 6385142/08 EN ETOS® ED Table of contents 1 Introduction....................................................................................................................... 12 1.1 Manufacturer.....................................................................................................................................  12 1.2 Completeness...................................................................................................................................  12 1.3 Safekeeping......................................................................................................................................  12 1.4 Notation conventions ........................................................................................................................  12 1.4.1 Hazard communication system........................................................................................................................... 12 1.4.2 Information system.............................................................................................................................................. 14 1.4.3 Instruction system ............................................................................................................................................... 14 1.4.4 Typographic conventions .................................................................................................................................... 15 2 Safety................................................................................................................................. 16 2.1 Appropriate use ................................................................................................................................  16 2.2 Fundamental safety instructions.......................................................................................................  17 2.3 Personnel qualification......................................................................................................................  20 2.4 Personal protective equipment .........................................................................................................  21 3 IT security.......................................................................................................................... 22 4 Product description.......................................................................................................... 26 4.1 Scope of delivery ..............................................................................................................................  26 4.2 Function description..........................................................................................................................  26 4.3 Performance features .......................................................................................................................  26 4.4 Variants.............................................................................................................................................  28 4.4.1 ETOS® ED L/ETOS® ED L-S............................................................................................................................. 28 4.4.2 ETOS® ED XL .................................................................................................................................................... 29 4.5 Design...............................................................................................................................................  30 4.5.1 Indication field ..................................................................................................................................................... 32 4.5.2 Anti-condensation heater .................................................................................................................................... 32 4.5.3 Swing frame/terminal rail..................................................................................................................................... 32 4.5.4 Position transmitter equipment............................................................................................................................ 33 4.5.5 Transmission gear cover plate............................................................................................................................ 33 4.5.6 Ambient temperature sensor............................................................................................................................... 34 4.5.7 ISM assemblies................................................................................................................................................... 35 4.6 Nameplate ........................................................................................................................................  41 4.7 Protective devices.............................................................................................................................  42

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 4 6385142/08 EN ETOS® ED 4.8 Safety markings................................................................................................................................  43 4.9 Emergency operation during switching blocking (X100 bridge)........................................................  43 4.10 Visualization......................................................................................................................................  44 4.10.1 Main screen......................................................................................................................................................... 44 4.10.2 Additional operating controls and display elements when using the MControl touch panel (optional)................ 49 4.10.3 Operating concept............................................................................................................................................... 49 5 Packaging, transport and storage .................................................................................. 55 5.1 Packaging.........................................................................................................................................  55 5.1.1 Suitability............................................................................................................................................................. 55 5.1.2 Markings.............................................................................................................................................................. 56 5.2 Transportation, receipt and handling of shipments...........................................................................  56 5.3 Storage of shipments........................................................................................................................  57 5.4 Unpacking shipments and checking for transportation damages .....................................................  58 6 Mounting ........................................................................................................................... 60 6.1 Attaching the control cabinet to the transformer...............................................................................  60 6.2 Mounting drive shafts and bevel gear...............................................................................................  63 6.3 Centering on-load tap-changer and motor-drive unit........................................................................  63 6.4 Connecting the ISM® assemblies ....................................................................................................  70 6.4.1 Cable recommendation (ISM® assemblies)........................................................................................................ 70 6.4.2 Information about connecting serial interfaces RS232 and RS485..................................................................... 71 6.4.3 Notes on connecting to the MR sensor bus ........................................................................................................ 73 6.4.4 Information about connecting analog sensors .................................................................................................... 78 6.4.5 Electromagnetic compatibility.............................................................................................................................. 81 6.4.6 Connecting cables to the system periphery ........................................................................................................ 84 6.4.7 Wiring the device................................................................................................................................................. 84 6.4.8 Mounting terminating resistor of CAN bus .......................................................................................................... 86 6.5 Connecting the motor-drive unit........................................................................................................  86 6.5.1 Cable recommendation....................................................................................................................................... 87 6.5.2 Electrical connection ........................................................................................................................................... 88 7 Commissioning................................................................................................................. 89 7.1 Starting up motor-drive unit ..............................................................................................................  89 7.2 Tests on motor-drive unit..................................................................................................................  90 7.2.1 Checking correct electric switch-off..................................................................................................................... 90 7.2.2 Checking mechanical and electric end stop of on-load tap-changer/de-energized tap-changer and motor-drive unit ...................................................................................................................................................................... 91

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 5 6385142/08 EN ETOS® ED 7.2.3 Checking tripping of motor protective switch....................................................................................................... 91 7.2.4 Checking functional reliability.............................................................................................................................. 92 7.3 Tests on the transformer...................................................................................................................  92 7.3.1 High-voltage tests on the transformer................................................................................................................. 92 7.3.2 Dielectric tests on transformer wiring.................................................................................................................. 93 7.4 Transporting transformer to the operating site..................................................................................  93 7.5 Commissioning the transformer at the operating site .......................................................................  93 7.6 Visualization......................................................................................................................................  94 7.6.1 Establishing connection to visualization.............................................................................................................. 94 7.6.2 Setting the language ........................................................................................................................................... 97 7.6.3 Setting date and time .......................................................................................................................................... 98 7.6.4 Commissioning wizard ........................................................................................................................................ 98 7.6.5 Checking measured values and status of digital inputs and outputs .................................................................. 99 7.6.6 Checking the temperature measurement............................................................................................................ 99 8 Operation......................................................................................................................... 101 8.1 Operating the motor-drive unit remotely .........................................................................................  101 8.2 Operating motor-drive unit locally...................................................................................................  101 8.3 Operating the motor-drive unit with the hand crank........................................................................  102 9 Visualization.................................................................................................................... 104 9.1 Establishing connection to visualization .........................................................................................  104 9.2 General...........................................................................................................................................  107 9.2.1 Setting general device functions ....................................................................................................................... 108 9.2.2 Set up automatic logout .................................................................................................................................... 109 9.2.3 Activating/deactivating service user access...................................................................................................... 110 9.3 Configuring the network..................................................................................................................  111 9.4 MQTT..............................................................................................................................................  114 9.5 Setting the device time ...................................................................................................................  116 9.5.1 Time synchronization via PTP........................................................................................................................... 117 9.6 Configuring syslog ..........................................................................................................................  118 9.7 Setting the screensaver..................................................................................................................  120 9.8 SCADA ...........................................................................................................................................  121 9.8.1 Configuring IEC 61850 (optional)...................................................................................................................... 122 9.8.2 Configuring IEC 60870-5-101 (optional) ........................................................................................................... 124 9.8.3 Configuring IEC 60870-5-103 (optional) ........................................................................................................... 127 9.8.4 Configuring IEC 60870-5-104 (optional) ........................................................................................................... 129

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 6 6385142/08 EN ETOS® ED 9.8.5 Configuring Modbus (optional).......................................................................................................................... 131 9.8.6 Configuring DNP3 (optional) ............................................................................................................................. 133 9.8.7 Configuring GOOSE (optional).......................................................................................................................... 135 9.8.8 Configure data points (optional)........................................................................................................................ 140 9.8.9 Display status of the SCADA connection.......................................................................................................... 147 9.9 Name plate .....................................................................................................................................  148 9.9.1 Enter the name plate data................................................................................................................................. 148 9.9.2 Displaying the name plate................................................................................................................................. 149 9.10 Linking signals and events..............................................................................................................  149 9.10.1 Linking functions ............................................................................................................................................... 150 9.10.2 Linking digital outputs........................................................................................................................................ 151 9.10.3 Linking control system messages ..................................................................................................................... 151 9.11 Cooling system control (optional) ...................................................................................................  152 9.11.1 Configuring cooling stages................................................................................................................................ 153 9.11.2 Set the operating mode..................................................................................................................................... 155 9.11.3 Deactivating cooling system control.................................................................................................................. 155 9.11.4 Configuring load-dependent mode.................................................................................................................... 155 9.11.5 Configuring periodic mode ................................................................................................................................ 157 9.11.6 Configuring alternating mode............................................................................................................................ 158 9.11.7 Configuring the frequency-based cooling system control ................................................................................. 159 9.11.8 Displaying status of cooling stages................................................................................................................... 162 9.12 Cooling system monitoring (optional) .............................................................................................  163 9.12.1 Setting the cooling system monitoring function................................................................................................. 163 9.12.2 Cooling efficiency monitoring (optional) ............................................................................................................ 164 9.12.3 Cooling system flow monitoring (optional) ........................................................................................................ 165 9.13 Control of the motor-drive unit (optional) ........................................................................................  169 9.13.1 Setting the switching pulse for controlling the motor-drive unit......................................................................... 170 9.13.2 Setting motor runtime monitoring...................................................................................................................... 171 9.13.3 Setting the switching direction........................................................................................................................... 172 9.14 Drive overview ................................................................................................................................  173 9.15 Regulation.......................................................................................................................................  174 9.15.1 Response to control system disconnection (optional)....................................................................................... 174 9.15.2 Setting control variable (optional)...................................................................................................................... 176 9.16 Voltage regulation (optional)...........................................................................................................  177 9.16.1 Setting the desired value................................................................................................................................... 177 9.17 Reactive power regulation (optional) ..............................................................................................  193

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 7 6385142/08 EN ETOS® ED 9.18 Transformer data ............................................................................................................................  196 9.18.1 Setting transformer data.................................................................................................................................... 197 9.18.2 Circuit examples for voltage transformers and current transformers ................................................................ 199 9.19 Measurement..................................................................................................................................  212 9.19.1 UI measuring channels ..................................................................................................................................... 212 9.19.2 Control variable................................................................................................................................................. 213 9.19.3 Regulation mode............................................................................................................................................... 213 9.19.4 Display power factor negative........................................................................................................................... 213 9.20 Line drop compensation .................................................................................................................  214 9.20.1 R&X compensation ........................................................................................................................................... 214 9.20.2 Z compensation................................................................................................................................................. 215 9.21 Parallel operation (optional)............................................................................................................  216 9.21.1 Parallel operation methods ............................................................................................................................... 217 9.21.2 Configuring parallel operation ........................................................................................................................... 221 9.21.3 TAPCON® 2xx retrofit....................................................................................................................................... 225 9.21.4 Detecting parallel operation via group inputs (optional).................................................................................... 226 9.22 Monitoring functions........................................................................................................................  226 9.22.1 Voltage monitoring ............................................................................................................................................ 226 9.22.2 Current monitoring ............................................................................................................................................ 229 9.22.3 Power monitoring .............................................................................................................................................. 232 9.22.4 Power flow monitoring....................................................................................................................................... 234 9.22.5 Tap position monitoring (optional)..................................................................................................................... 236 9.22.6 U bandwidth monitoring .................................................................................................................................... 237 9.22.7 Q bandwidth monitoring (optional) .................................................................................................................... 239 9.22.8 Phase symmetry monitoring.............................................................................................................................. 241 9.22.9 Temperature monitoring.................................................................................................................................... 242 9.22.10 Switching interval monitoring ............................................................................................................................ 242 9.22.11 Monitoring the gas volume of the Buchholz relay (OLTC) ................................................................................ 244 9.22.12 Monitoring the gas volume of the Buchholz relay (transformer)........................................................................ 245 9.22.13 Monitoring the oil pressure (transformer).......................................................................................................... 245 9.22.14 Monitoring the oil pressure (on-load tap-changer) ............................................................................................ 246 9.23 Target-tap-position operation..........................................................................................................  247 9.24 Measured values ............................................................................................................................  247 9.24.1 Displaying current measured values................................................................................................................. 247 9.24.2 Displaying measured value recorder (optional)................................................................................................. 248 9.24.3 Setting the measured value recorder................................................................................................................ 252

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 8 6385142/08 EN ETOS® ED 9.24.4 Displaying temperature curve (optional) ........................................................................................................... 253 9.24.5 Displaying winding temperatures (optional) ...................................................................................................... 254 9.24.6 Displaying the measured values of the Buchholz relay (optional)..................................................................... 255 9.24.7 Displaying the measured values of the pressure relief device (optional).......................................................... 255 9.24.8 Displaying the measured value trend of the oil level and dehydrating breather (optional)................................ 256 9.25 On-load tap-changer monitoring.....................................................................................................  256 9.25.1 Changing tap position designation (optional).................................................................................................... 256 9.25.2 Setting the TCR calculation factor (optional)..................................................................................................... 257 9.25.3 Displaying tap-change operation statistics (optional)........................................................................................ 257 9.25.4 Motor Current Index (MCI) ................................................................................................................................ 258 9.25.5 Displaying information about contact wear (only OILTAP®)............................................................................. 262 9.25.6 Information about the on-load tap-changer....................................................................................................... 263 9.26 Transformer monitoring (optional) ..................................................................................................  263 9.26.1 Hot-spot calculation (optional)........................................................................................................................... 264 9.26.2 Hot-spot forecast (optional)............................................................................................................................... 267 9.26.3 Setting calculation of transformer's loss of life (optional) .................................................................................. 268 9.26.4 Displaying protective device status (optional)................................................................................................... 269 9.26.5 Asset intelligence .............................................................................................................................................. 269 9.26.6 Transformer statistics........................................................................................................................................ 270 9.26.7 Display current oil level/dehydrating breather values........................................................................................ 271 9.26.8 Displaying the measured value trend of the oil level and dehydrating breather (optional)................................ 273 9.27 Dissolved gas analysis (optional) ...................................................................................................  273 9.27.1 Configuring DGA monitoring ............................................................................................................................. 274 9.27.2 Displaying measured values ............................................................................................................................. 277 9.28 MR sensor bus................................................................................................................................  282 9.28.1 Configuring MR sensor bus............................................................................................................................... 283 9.28.2 Managing sensors............................................................................................................................................. 284 9.28.3 Function assignment......................................................................................................................................... 286 9.28.4 Defining the sensors ......................................................................................................................................... 286 9.28.5 Displaying information on the connected sensors............................................................................................. 291 9.29 Configuring analog inputs and outputs (optional) ...........................................................................  292 9.30 Configuring digital inputs and outputs.............................................................................................  295 9.31 Maintenance (optional) ...................................................................................................................  297 9.31.1 Setting operator interval for OLTC maintenance............................................................................................... 298 9.31.2 Setting operator interval for transformer maintenance...................................................................................... 299 9.31.3 Undertaking and confirming maintenance......................................................................................................... 300

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 9 6385142/08 EN ETOS® ED 9.31.4 Displaying maintenance overview..................................................................................................................... 303 9.31.5 Displaying the maintenance logbook ................................................................................................................ 303 9.31.6 Suppressing a maintenance event.................................................................................................................... 305 9.32 Torque monitoring (optional)...........................................................................................................  306 9.32.1 Tap-change ranges (windows) M1...M8............................................................................................................ 306 9.32.2 Types of tap-change operations........................................................................................................................ 306 9.32.3 Limit values ....................................................................................................................................................... 307 9.32.4 Tap-change supervisory control........................................................................................................................ 308 9.32.5 Evaluated and unevaluated tap-change operations.......................................................................................... 308 9.32.6 Displaying torque monitoring............................................................................................................................. 309 9.33 Event management.........................................................................................................................  311 9.33.1 Displaying and acknowledging events .............................................................................................................. 311 9.33.2 Configuring events ............................................................................................................................................ 312 9.33.3 Displaying event memory.................................................................................................................................. 314 9.34 User administration.........................................................................................................................  315 9.34.1 User roles.......................................................................................................................................................... 315 9.34.2 Changing the password .................................................................................................................................... 317 9.34.3 Creating, editing and deleting users.................................................................................................................. 318 9.34.4 Setting access rights to parameters and events ............................................................................................... 319 9.34.5 User authentication via RADIUS (optional)....................................................................................................... 320 9.35 Information about device ................................................................................................................  322 9.35.1 Hardware........................................................................................................................................................... 322 9.35.2 Software............................................................................................................................................................ 323 9.35.3 Parallel operation .............................................................................................................................................. 324 9.36 Import/export manager ...................................................................................................................  324 9.36.1 Exporting data................................................................................................................................................... 325 9.36.2 Importing data (software version 3.44 and later)............................................................................................... 326 9.37 Configuring media converter with managed switch ........................................................................  327 9.37.1 Commissioning.................................................................................................................................................. 327 9.37.2 Configuration..................................................................................................................................................... 329 9.38 TAPCON® Personal Logic Editor (TPLE).......................................................................................  330 9.38.1 Function ............................................................................................................................................................ 330 9.38.2 Configuring TPLE.............................................................................................................................................. 343 9.39 Calibrating the position sensor .......................................................................................................  346 9.40 Performing trial tap-change operations...........................................................................................  347

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 10 6385142/08 EN ETOS® ED 10 Fault elimination............................................................................................................. 349 10.1 Safety instructions ..........................................................................................................................  349 10.2 General information ........................................................................................................................  349 10.3 Fault in the environment of the motor-drive unit .............................................................................  350 10.4 Fault in the motor-drive unit when the switching operation has not ended.....................................  350 10.5 Fault in the motor-drive unit after the switching operation is ended correctly.................................  351 10.6 Hand crank operation in the event of faults ....................................................................................  351 10.7 Fault elimination ISM (hardware and software) ..............................................................................  352 10.7.1 General faults.................................................................................................................................................... 352 10.7.2 Human-machine interface................................................................................................................................. 353 10.7.3 Torque monitoring............................................................................................................................................. 353 10.7.4 Temperature monitoring.................................................................................................................................... 356 10.7.5 Maintenance messages .................................................................................................................................... 360 10.7.6 Function monitoring........................................................................................................................................... 364 10.7.7 Other faults........................................................................................................................................................ 365 11 Inspection and maintenance ......................................................................................... 367 11.1 Care................................................................................................................................................  367 11.2 Inspection .......................................................................................................................................  367 11.3 Maintenance ...................................................................................................................................  367 12 Removal........................................................................................................................... 369 13 Disposal........................................................................................................................... 372 14 Technical data................................................................................................................. 373 14.1 Motor-drive unit...............................................................................................................................  373 14.2 Control cabinet................................................................................................................................  373 14.2.1 Drawings ........................................................................................................................................................... 375 14.3 Technical data for position transmitter equipment..........................................................................  380 14.4 Permissible ambient conditions ......................................................................................................  380 14.5 ISM® assemblies............................................................................................................................  381 14.5.1 Voltage supply................................................................................................................................................... 381 14.5.2 Voltage supply................................................................................................................................................... 381 14.5.3 Voltage measurement and current measurement............................................................................................. 383 14.5.4 UI 5-4 voltage measurement and current measurement................................................................................... 384 14.5.5 Digital inputs and outputs.................................................................................................................................. 386 14.5.6 Analog inputs and outputs................................................................................................................................. 388

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 11 6385142/08 EN ETOS® ED 14.5.7 AIO 8 analog inputs and outputs....................................................................................................................... 389 14.5.8 CPU (central processing unit) I ......................................................................................................................... 390 14.5.9 System networking............................................................................................................................................ 392 14.5.10 Ambient conditions............................................................................................................................................ 394 14.5.11 Standards and directives................................................................................................................................... 394 Glossary .......................................................................................................................... 397 List of key words ............................................................................................................ 399

Maschinenfabrik Reinhausen GmbH 2020

12 6385142/08 EN ETOS® ED 1 Introduction This technical file contains detailed descriptions on the safe and proper in- stallation, connection, commissioning and monitoring of the product. It also includes safety instructions and general information about the prod- uct. This technical file is intended solely for specially trained and authorized per- sonnel. 1.1 Manufacturer The product is manufactured by: Maschinenfabrik Reinhausen GmbH Falkensteinstraße 8 93059 Regensburg Tel.: (+49) 9 41/40 90-0 E-mail: [email protected] Further information on the product and copies of this technical file are avail- able from this address if required. 1.2 Completeness This technical file is incomplete without the supporting documents. The following documents also apply in addition to this technical file: ▪ Connection diagrams ▪ Routine test report ▪ Supplement Also observe generally valid legislation, standards, and guidelines as well as specifications on accident prevention and environmental protection in the re- spective country of use. 1.3 Safekeeping Keep this technical file and all supporting documents ready at hand and ac- cessible for future use at all times. 1.4 Notation conventions 1.4.1 Hazard communication system Warnings in this technical file are displayed as follows.

Maschinenfabrik Reinhausen GmbH 2020

13 6385142/08 EN ETOS® ED 1.4.1.1 Warning relating to section Warnings relating to sections refer to entire chapters or sections, sub-sec- tions or several paragraphs within this technical file. Warnings relating to sections use the following format: WARNING Type of danger! Source of the danger and outcome. ►Action ►Action 1.4.1.2 Embedded warning information Embedded warnings refer to a particular part within a section. These warn- ings apply to smaller units of information than the warnings relating to sec- tions. Embedded warnings use the following format:  DANGER! Instruction for avoiding a dangerous situation. 1.4.1.3 Signal words and pictograms The following signal words are used: Signal word Definition DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE Indicates measures to be taken to prevent damage to property. Table 1: Signal words in warning notices Pictograms warn of dangers: Pictogram Definition Warning of a danger point Warning of dangerous electrical voltage

Maschinenfabrik Reinhausen GmbH 2020

14 6385142/08 EN ETOS® ED Pictogram Definition Warning of combustible substances Warning of danger of tipping Warning of danger of crushing Table 2: Pictograms used in warning notices 1.4.2 Information system Information is designed to simplify and improve understanding of particular procedures. In this technical file it is laid out as follows: Important information. 1.4.3 Instruction system This technical file contains single-step and multi-step instructions. Single-step instructions Instructions which consist of only a single process step are structured as fol- lows: Aim of action ü Requirements (optional). ►Step 1 of 1. ð Result of step (optional). ð Result of action (optional). Multi-step instructions Instructions which consist of several process steps are structured as follows:

Maschinenfabrik Reinhausen GmbH 2020

15 6385142/08 EN ETOS® ED Aim of action ü Requirements (optional). 1. Step 1. ð Result of step (optional). 2. Step 2. ð Result of step (optional). ð Result of action (optional). 1.4.4 Typographic conventions Typographic convention Purpose Example UPPERCASE Operating controls, switches ON/OFF [Brackets] PC keyboard [Ctrl] + [Alt] Bold Software operating controls Press Continue button …>…>… Menu paths Parameter > Control parameter Italics System messages, error messages, signals Function monitoring alarm triggered [► Number of pages] Cross reference [► Page 41]. Dotted underscore ............................................. Glossary entry, abbreviations, defini- tions, etc. Glossary entry ........................ Table 3: Typographic conventions used in this technical file

Maschinenfabrik Reinhausen GmbH 2020

16 6385142/08 EN ETOS® ED 2 Safety ▪ Read this technical file through to familiarize yourself with the product. ▪ This technical file is a part of the product. ▪ Read and observe the safety instructions provided in this chapter. ▪ Read and observe the warnings in this technical file in order to avoid func- tion-related dangers. ▪ The product is manufactured on the basis of state-of-the-art technology. Nevertheless, risks to life and limb for the user or impairment of the prod- uct and other material assets due to the function may arise in the event of improper use. 2.1 Appropriate use The motor-drive unit adjusts the operating position of on-load tap-changers in regulating transformers to the individual operating requirements. The mo- tor-drive unit is designed solely for use in electrical energy systems and facil- ities. If used as intended and in compliance with the requirements and condi- tions specified in this technical file as well as the warning notices in this tech- nical file and attached to the product, then the motor-drive unit does not present any danger to people, property or the environment. This applies throughout the service life of the product, from delivery, installation and oper- ation to removal and disposal. The following is considered appropriate use: ▪ Only operate the product in accordance with this technical file and the agreed delivery conditions and technical data. ▪ Use the equipment and special tools supplied solely for the intended pur- pose and in accordance with the specifications of this technical file. ▪ Use the product only with the transformer/on-load tap-changer/de-ener- gized tap-changer specified in the order. ▪ You will find the standard valid for the product and the year of issue on the nameplate. ▪ The serial numbers of on-load tap-changer / de-energized tap-changer and on-load tap-changer accessories / de-energized tap-changer acces- sories (drive, drive shaft, bevel gear, protective relay, etc.) must match if these products are supplied as a set for one order. ▪ Electrically operate the motor-drive unit remotely during normal operation. ▪ In special operating cases (such as during maintenance tasks), the motor- drive unit can also be operated electrically on site via control switch S3. ▪ Never operate the motor-drive unit electrically or with the hand crank be- fore the transformer has been disconnected if you think there may be a fault in the transformer or on-load tap-changer/de-energized tap-changer. For more information, refer to the "Troubleshooting" chapter.

Maschinenfabrik Reinhausen GmbH 2020

17 6385142/08 EN ETOS® ED ▪ The provided hand crank is for activating the motor-drive unit during in- stallation and tests in the transformer plant or during maintenance tasks if the transformer has been disconnected. ▪ For details about using the hand crank in emergency operation when the transformer is energized, refer to the "Operation" [►Section 8, Page 101] chapter. 2.2 Fundamental safety instructions To prevent accidents, malfunctions and damage as well as unacceptable ad- verse effects on the environment, those responsible for transport, installa- tion, operation, maintenance and disposal of the product or parts of the prod- uct must ensure the following: Personal protective equipment Loosely worn or unsuitable clothing increases the danger of becoming trapped or caught up in rotating parts and the danger of getting caught on protruding parts. This poses a danger to life and limb. ▪ Wear appropriate personal protective equipment such as a helmet, work gloves, etc. for the respective activity. ▪ Never wear damaged personal protective equipment. ▪ Never wear rings, necklaces, or other jewelry. ▪ If you have long hair, wear a hairnet. Work area Untidy and poorly lit work areas can lead to accidents. ▪ Keep the work area clean and tidy. ▪ Make sure that the work area is well lit. ▪ Observe the applicable laws for accident prevention in the relevant coun- try. Drying the transformer Drying the motor-drive unit will cause damage to property as well as motor- drive unit malfunctions. ▪ Never dry the motor-drive unit. Working during operation The product may only be operated in a sound, operational condition. Other- wise it poses a danger to life and limb. ▪ Regularly check the operational reliability of safety equipment. ▪ Comply with the inspection work, maintenance work and maintenance in- tervals described in this technical file.

Maschinenfabrik Reinhausen GmbH 2020

18 6385142/08 EN ETOS® ED Invisible laser radiation Looking directly into the beam or the reflected beam can cause eye damage. The beam is emitted at the optical connections or at the end of the fiber-optic cables connected to them on the assemblies. Read the chapter "Technical Data" for further information. ▪ Never look directly into the beam or the reflected beam. ▪ Never look into the beam with the aid of optical instruments such as a magnifying glass or a microscope. ▪ In the event that the laser beam strikes your eyes, close your eyes imme- diately and move your head out of the path of the beam. Working with current transformers Dangerous high voltages may occur when a current transformer is operated with an open secondary circuit. This can lead to injuries and property dam- age. ▪ Never operate a current transformer with an open secondary circuit; short- circuit the current transformer to prevent this. ▪ Observe the information in the current transformer operating instructions. Handling electrical components Electrical components can be damaged by electrostatic discharges. ▪ Never touch electrical components during commissioning, operation or maintenance work. ▪ Take suitable measures (e.g. covers) to ensure that personnel cannot touch components. ▪ Wear suitable personal protective equipment (e.g. grounded strap). Hand crank aperture Reaching into the hand crank aperture during a tap-change operation may lead to injuries caused by a rotating drive shaft. ▪ Never reach into the hand crank aperture. Securing the motor-drive unit If you open the motor-drive unit during operation, there is a danger of electric shock due to live components behind the swing frame. ▪ Secure the motor-drive unit against unauthorized opening during opera- tion by using a padlock. ▪ The motor-drive unit may only be opened by an electrically skilled person. Opening the swing frame Opening the swing frame while the motor-drive unit is in operation may result in electric shocks due to live components. ▪ The swing frame may only be opened by an electrically skilled person.

Maschinenfabrik Reinhausen GmbH 2020

19 6385142/08 EN ETOS® ED Explosion protection Highly flammable or explosive gases, vapors and dusts can cause serious explosions and fire. This increases the danger to life and limb. ▪ Do not install, operate or perform maintenance work on the product in ar- eas where a risk of explosion is present. Safety markings Warning signs and safety information plates are safety markings on the product. They are an important aspect of the safety concept. ▪ Observe all safety markings on the product. ▪ Make sure all safety markings on the product remain intact and legible. ▪ Replace safety markings that are damaged or missing. Ambient conditions To ensure reliable and safe operation, the product must only be operated under the ambient conditions specified in the technical data. ▪ Observe the specified operating conditions and requirements for the in- stallation location. Auxiliary materials and operating materials Auxiliary materials and operating materials not approved by the manufac- turer can lead to personal injury, damage to property and malfunctions of the product. ▪ Only use conductive and grounded hoses, pipes, and pump equipment that are approved for flammable liquids. ▪ Only use lubricants and auxiliary materials approved by the manufacturer. ▪ Contact the manufacturer. Modifications and conversions Unauthorized or inappropriate changes to the product may lead to personal injury, material damage and operational faults. ▪ Only modify the product after consultation with Maschinenfabrik Rein- hausen GmbH. Spare parts Spare parts not approved by Maschinenfabrik Reinhausen GmbH may lead to physical injury, damage to the product and malfunctions. ▪ Only use spare parts that have been approved by Maschinenfabrik Rein- hausen GmbH. ▪ Contact Maschinenfabrik Reinhausen GmbH.

Maschinenfabrik Reinhausen GmbH 2020

20 6385142/08 EN ETOS® ED 2.3 Personnel qualification The person responsible for assembly, commissioning, operation, mainte- nance and inspection must ensure that the personnel are sufficiently quali- fied. Electrically skilled person The electrically skilled person has a technical qualification and therefore has the required knowledge and experience, and is also conversant with the ap- plicable standards and regulations. The electrically skilled person is also pro- ficient in the following: ▪ Can identify potential dangers independently and is able to avoid them. ▪ Is able to perform work on electrical systems. ▪ Is specially trained for the working environment in which (s)he works. ▪ Must satisfy the requirements of the applicable statutory regulations for accident prevention. Electrically trained persons An electrically trained person receives instruction and guidance from an electrically skilled person in relation to the tasks undertaken and the poten- tial dangers in the event of inappropriate handling as well as the protective devices and safety measures. The electrically trained person works exclu- sively under the guidance and supervision of an electrically skilled person. Operator The operator uses and operates the product in line with this technical file. The operating company provides the operator with instruction and training on the specific tasks and the associated potential dangers arising from im- proper handling. Technical Service We strongly recommend having maintenance, repairs and retrofitting carried out by our Technical Service department. This ensures that all work is per- formed correctly. If maintenance is not carried out by our Technical Service department, please ensure that the personnel who carry out the mainte- nance are trained and authorized by Maschinenfabrik Reinhausen GmbH to carry out the work. Authorized personnel Authorized personnel are trained by Maschinenfabrik Reinhausen GmbH to carry out special maintenance.

Maschinenfabrik Reinhausen GmbH 2020

21 6385142/08 EN ETOS® ED 2.4 Personal protective equipment Personal protective equipment must be worn during work to minimize risks to health. ▪ Always wear the personal protective equipment required for the job at hand. ▪ Never wear damaged personal protective equipment. ▪ Observe information about personal protective equipment provided in the work area. Protective clothing Close-fitting work clothing with a low tearing strength, with tight sleeves and with no protruding parts. It mainly serves to protect the wearer against being caught by moving machine parts. Safety shoes To protect against falling heavy objects and slipping on slippery surfaces. Safety glasses To protect the eyes from flying parts and splashing liq- uids. Visor To protect the face from flying parts and splashing liq- uids or other dangerous substances. Hard hat To protect against falling and flying parts and materials. Hearing protection To protect against hearing damage. Protective gloves To protect against mechanical, thermal, and electrical hazards. Table 4: Personal protective equipment

3 IT security

Maschinenfabrik Reinhausen GmbH 2020 22 6385142/08 EN ETOS® ED 3 IT security Observe the following recommendations to operate the product safely. General ▪ Ensure that only authorized personnel have access to the device. ▪ Only use the device within an ESP (electronic security perimeter). Do not connect the device to the Internet in an unprotected state. Use mecha- nisms for vertical and horizontal network segmenting and security gate- ways (firewalls) at the transition points. ▪ Ensure that the device is only operated by trained personnel who are fa- miliar with IT security. Commissioning Observe the following recommendations for device commissioning: ▪ User IDs must be unique and assignable. Do not use a "Group account" function or the "Auto login" function. ▪ Activate the "Auto logout [►Section 9.2.2, Page 109]" function. ▪ Restrict the rights of the individual user groups as much as is feasible; this helps avoid errors during operations. A user with the "Operator" role, for example, should only perform operations and should not be able to change any device settings. ▪ Delete or disable the default "admin" user ID. This requires first creating a new user account with the "Administrator" role. You can then use it to delete or disable the default "admin" account. ▪ Deactivate service user access [►Section 9.2.3, Page 110]. ▪ Enable SSL/TLS encryption [►Section 9.2, Page 107]; access to the de- vice is then only possible using the SSL/TLS protocol. In addition to en- crypting communication, this protocol also checks the authenticity of the server. ▪ Use TLS version 1.2 or higher wherever possible. ▪ Integrate the device into a public key infrastructure. Create your own SSL certificates for this if necessary and then import them. ▪ Connect the device to a central log server by using the syslog interface [►Section 9.6, Page 118]. ▪ Only use the SNMP function if you can ensure that the communication is protected by external security equipment. Operation Observe the following recommendations during device operation: ▪ Change the password at regular intervals. ▪ Export the security log [►Section 9.36.1, Page 325] at regular intervals. ▪ Check the log files regularly for unauthorized system access and other se- curity-related events.

3 IT security

Maschinenfabrik Reinhausen GmbH 2020 23 6385142/08 EN ETOS® ED Interfaces The device uses the following interfaces for communication: Figure 1: ETH1.1 interface on the OT1205 assembly Interface Protocol Port Description ETH1.1 TCP 21 FTP service access 1) ETH1.1 TCP 80 Web visualization 1) ETH1.1 TCP 443 SSL-protected web visualization ETH1.1 TCP 990 SSL-protected FTP service access ETH1.1 TCP 8080 Web visualization (alternative port) 1) ETH1.1 TCP 8081 SSL-protected web visualization (alternative port) ETH1.1 UDP 67 DHCP server Table 5: Interfaces and open ports of the OT1205 assembly 1) Port is closed if you activate the device's SSL encryption. CPU CAN 1 1 9 CAN 2 1 9 COM 1 1 9 COM 2 1 9 - + 24V DC RUN INIT ERR USB2.0 4 6 2 A 8 C H TEST PROG RUN 4 6 2 A E 0 8 C L ETH 1 ETH 2.1 ETH 2.2 Figure 2: CPU assembly interfaces Interface Protocol Port Description CAN 1 - - DIO assembly connection CAN 2 - - Communication with other ISM® devices (e.g. parallel operation) COM 1 - - Internal system interface

3 IT security

Maschinenfabrik Reinhausen GmbH 2020 24 6385142/08 EN ETOS® ED Interface Protocol Port Description COM 2 - - Serial interface (SCADA) USB - - Import or export of data ETH 1 TCP 80 HTTP for web-based visualization1), 2) ETH 1 TCP 443 HTTPS for web-based visualization1), 2) ETH 1 TCP 102 IEC 61850 ETH 1 TCP 502 Modbus3) ETH 1 TCP 20000 DNP33) ETH 1 UDP 161 SNMP4) ETH 2.x TCP 21 FTP1) (only for MR service) ETH 2.x TCP 80 HTTP for web-based visualization1) ETH 2.x TCP 443 HTTPS for web-based visualization1) ETH 2.x TCP 990 FTPS (only for MR service) ETH 2.x TCP 8080 HTTP for web-based visualization1) ETH 2.x TCP 8081 HTTPS for web-based visualization1) ETH 2.x UDP 161 SNMP4) Table 6: Interfaces and open ports of the CPU assembly 1) Port is closed if you activate the device's SSL encryption. 2) Depending on the setting of the parameter Visualization release [►Page 113]. 3) Default setting; if you have modified the port for the control system proto- col, only the set port is open. 4) Depending on the setting of the SNMP agent parameter. Encryption standards The device supports the following TLS versions: ▪ TLS 1.0 ▪ TLS 1.1 ▪ TLS 1.2

3 IT security

Maschinenfabrik Reinhausen GmbH 2020 25 6385142/08 EN ETOS® ED The device uses the following cipher suites for a TLS-secured connection: Key exchange Authentication Encryption Key length Operating mode Hash func- tion TLS ECDHE RSA WITH AES 128 CBC SHA1) DHE SHA265 ECDHE ECDSA GCM SHA256 ECDH 256 CBC SHA1) RSA1) SHA256 GCM SHA384 Table 7: Cipher suite 1) Not available with TLS version >= 1.2 The device uses the SHA256 hash function to save passwords.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 26 6385142/08 EN ETOS® ED 4 Product description 4.1 Scope of delivery The motor-drive unit is packaged with protection against moisture and is de- livered as follows: ▪ Motor-drive unit ▪ Product documentation Please note the following: 1. Check the shipment for completeness on the basis of the shipping docu- ments. 2. Store the parts in a dry place until installation. 3. The product must remain in its airtight, protective wrapping and may only be removed immediately before installation. 4.2 Function description The motor-drive unit adjusts the operating position of on-load tap-changers in regulating transformers to the individual operating requirements. The tap-change operation is initiated by activating the motor-drive unit (a sin- gle control impulse is triggered, for example via the optional "Automatic volt- age regulation AVR basic/pro" function package). This adjustment operation is always completed regardless of any other control impulses issued during the tap-change operation. In the standard design, the next tap-change oper- ation can only proceed once all control devices have reached their resting positions. Behavior in the event of a voltage interruption Should the voltage be interrupted during an on-load tap-change operation, once the voltage supply returns, the motor-drive unit completes the started on-load tap-change operation. 4.3 Performance features Depending on your order, the device is equipped with the following optional function packages: ▪ Basic monitoring – Voltage, current, frequency – Active power, reactive power, apparent power, power factor – Temperature monitoring (ambient temperature, temperature of top-oil, temperature of bottom oil (optional), calculation of hot-spot temperature in accordance with IEC 60076-7 or IEEE C57.91) – Optional: Transformer oil level – Loss-of-life and relative aging rate

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 27 6385142/08 EN ETOS® ED – Motor-drive unit status (motor protective switch, motor is running) – Tap position display – Optional: Status of protective devices (Buchholz relay, protective relay, pressure relief device) ▪ ETOS® ED digital ready – Maintenance interval calculation – Tap-change statistics of on-load tap-changer – Motor-drive unit status (motor protective switch, motor is running) ▪ On-load tap-changer monitoring – Contact wear calculation (only for OILTAP® V, M, R, RM, MS, G) – Maintenance interval calculation – Oil carbonization (only for OILTAP® V, M, R) – Monitoring of OLTC temperature (optional) – Tap-change statistics of on-load tap-changer – Optional: on-load tap-changer oil level – Optional: oil filter unit – Motor-drive unit status (motor protective switch, motor is running) – Optional: Motor Current Index ▪ On-load tap-changer monitoring expert – Torque monitoring – Tap-change sequence monitoring – Temperature monitoring (motor-drive unit, surroundings, OLTC, tem- perature difference between OLTC and transformer) – Hand crank monitoring ▪ Automatic voltage regulation AVR basic – Measurement of voltage and current – 1 desired value – Voltage regulation with linear delay time T1 – Motor-drive unit status (motor protective switch, motor is running) ▪ Automatic voltage regulation AVR pro – Measurement of voltage and current – Desired value in accordance with order (1, 3 or 5 desired values, TDSC, analog desired value specification, incremental desired value specification, desired value via BCD) – Automatic voltage regulation with linear or integral delay time T1 and with delay time T2 – Parallel operation – Line drop compensation – Motor-drive unit status (motor protective switch, motor is running) – Bandwidth monitoring

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 28 6385142/08 EN ETOS® ED – Function monitoring – Limit value monitoring (voltage, current, power, phase angle) ▪ Cooling system control – 2, 4 or 6 cooling stages, can be individually parameterized – Load-dependent mode (for early activation of cooling stages) – Periodic mode (for regular activation of cooling stages) – Alternating mode (for equal loading of similar cooling stages) ▪ Cooling stage monitoring (2, 4 or 6 cooling stages) ▪ DGA – Up to 10 gases – Relative moisture in oil – Monitoring of the absolute values and rates of increase – Optional: Rogers, Duval, Dörnenburg and IEC 60599 analyses ▪ MR sensor bus ▪ Calculation of the transformer overload capability (emergency operation) 4.4 Variants The ISM® assemblies are installed as follows (figures show swing frame in- terior, with cover plate with swing frame closed, without cover plate with swing frame open): 4.4.1 ETOS® ED L/ETOS® ED L-S The ISM assemblies are installed as follows (figures show swing frame inte- rior, with cover plate with swing frame closed, without cover plate with swing frame open): Without display X3 M1 S1 S2 S12 S13A S13B S14 S6A S6B S8A S8B S5 S4 R1 S10A E1 S62P AIO 4 1 2 3 4 11 12 13 14 24V DC + - RDY 6 7 8 9 16 17 18 19 CPU I RUN INIT ERR CAN 1 CAN 2 COM 1 COM 2 24V DC + - TEST PROG RUN USB2.0 2 4 6 8 A C H 0 2 4 6 8 A C E L +24V DC typ.22W 128 256 MB ETH 1 ETH 2.1 ETH 2.2 N L1 NC NC k l NC NC NC NC RDY DIO 28-15 ERR INIT RUN CAN H L + - 24V DC DO DO DO DI DI DI DI 1A 1C 1B 2A 2C 2B 3A 3C 3B 4C 4B 5C 5B 6A 6C 6B 7A 7C 7B 8A 8C 8B 9C 9B 10C 10B 11A 11C 11B 12A 12C 12B 13A 13C 13B 14C 14B 15C 15B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Adjust DC OK Overload Power Supply N L S61P S26A S27A S3 S32 X2 X1 X20 Q1 R3 S62M S61M K1 K2 K20 UI 1 PE G1 X1 CT372 CT372 H1 H2 H3 X5.1 X10 X5 F2 B2 F12 F13 F11 S15 S118 A19 A18.1 A10 A17 X6.1 X6 PE Figure 3: ETOS® ED L/ETOS® ED L-S without display

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 29 6385142/08 EN ETOS® ED With display AVR STATUS ALARM REMOTE AVR AUTO AVR MANUAL ENTER BACK TAPCON DIO 28-15 ERR INIT RUN CAN H L + - 24V DC DO DO DO DI DI DI DI 1A 1C 1B 2A 2C 2B 3A 3C 3B 4C 4B 5C 5B 6A 6C 6B 7A 7C 7B 8A 8C 8B 9C 9B 10C 10B 11A 11C 11B 12A 12C 12B 13A 13C 13B 14C 14B 15C 15B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 PE G1 X20:1...49 X1:272 ...313 X1:PE;1...72 X1:80...248 X4: 1...4 S38M S40M S61M PE X6:1...24 X3 M1 S1 S2 S12 S13A S13B S14 S6A S6B S8A S8B S5 S4 R1 S10 E1 S41P A12 A10 A15 A13 A13.1 AIO 1 2 3 4 11 12 13 14 24V DC + - RDY 6 7 8 9 16 17 18 19 UI N L1 L2 L3 k1 l1 k2 l2 k3 l3 RDY AIO 1 2 3 4 11 12 13 14 24V DC + - RDY 6 7 8 9 16 17 18 19 CPU RUN INIT ERR CAN 1 CAN 2 COM 1 COM 2 24V DC + - TEST PROG RUN USB2.0 2 4 6 8 A C H 0 2 4 6 8 A C E L ETH 1 ETH 2.1 ETH 2.2 Figure 4: ETOS® ED L/ETOS® ED L-S with display 4.4.2 ETOS® ED XL The ISM assemblies are installed as follows (figures show swing frame inte- rior, with cover plate with swing frame closed, without cover plate with swing frame open): Without display R1 X3 M1 S1 S2 S12 S13A S13B S14 S6A S6B S8A S8B S5 S4 S10A E1 S62P RUN INIT ERR CAN 1 CAN 2 COM 1 COM 2 24V DC + - TEST PROG RUN USB2.0 2 4 6 8 A C H 0 2 4 6 8 C A E L ETH 1 ETH 2.1 ETH 2.2 ERR INIT RUN CAN H L + - 24V DC DO DO DO DO DI DI DI DI DI DI 1A 1C 1B 2A 2C 2B 3A 3C 3B 4C 4B 5C 5B 6A 6C 6B 7A 7C 7B 8A 8C 8B 9C 9B 10C 10B 11A 11C 11B 12A 12C 12B 13A 13C 13B 14C 14B 15C 15B 16A 16C 16B 17A 17C 17B 18A 18C 18B 19C 19B 20C 20B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 2 3 4 11 12 13 14 24V DC + - RDY 6 7 8 9 16 17 18 19 1 2 3 4 11 12 13 14 24V DC + - RDY 6 7 8 9 16 17 18 19 N L1 L2 L3 RDY k1 l1 k2 l2 k3 l3 X2 X5.1 F2 K20 K2 K1 B2 A10 CPU II A19 DIO 42-20 A23 BEM 1 A24 BES 1 G1 S3 S32 F11F12F13 H3 H2 H1 Q1 F25 X19 S118 S15 S26A S27A S61P X1 X20 X1 >272 A18.2 AIO 4 A18.1 AIO 4 A22 VI 4 A17 UI 3 X8P A16 UI 5 H2 S7 ETH 1 S61M S62M X8S X6.2 X6.1 X6 Figure 5: ETOS® ED XL without display

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 30 6385142/08 EN ETOS® ED With display R1 X3 M1 S1 S2 S12 S13A S13B S14 S6A S6B S8A S8B S5 S4 S10A E1 S62P RUN INIT ERR CAN 1 CAN 2 COM 1 COM 2 24V DC + - TEST PROG RUN USB2.0 2 4 6 8 A C H 0 2 4 6 8 C A E L ETH 1 ETH 2.1 ETH 2.2 ERR INIT RUN CAN H L + - 24V DC DO DO DO DO DI DI DI DI DI DI 1A 1C 1B 2A 2C 2B 3A 3C 3B 4C 4B 5C 5B 6A 6C 6B 7A 7C 7B 8A 8C 8B 9C 9B 10C 10B 11A 11C 11B 12A 12C 12B 13A 13C 13B 14C 14B 15C 15B 16A 16C 16B 17A 17C 17B 18A 18C 18B 19C 19B 20C 20B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 2 3 4 11 12 13 14 24V DC + - RDY 6 7 8 9 16 17 18 19 1 2 3 4 11 12 13 14 24V DC + - RDY 6 7 8 9 16 17 18 19 N L1 L2 L3 RDY k1 l1 k2 l2 k3 l3 X2 X5.1 F2 K20 K2 K1 B2 A10 CPU II A19 DIO 42-20 A5 A23 BEM 1 A24 BES 1 G1 S3 S32 F11F12F13 H3 H2 H1 Q1 F25 X19 S118 S15 S26A S27A S61P X1 X20 X1 >272 A18.2 AIO 4 A18.1 AIO 4 A22 VI 4 A17 UI 3 X8P A16 UI 5 H2 S7 ETH 1 X6.1 X6.2 S61M S62M X8S X6 Figure 6: ETOS® ED XL with display 4.5 Design This chapter contains an overview of the design of the motor-drive unit.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 31 6385142/08 EN ETOS® ED Components not described here in detail are described in the motor-drive unit's technical data. Figure 7: Design 1 Door of the control cabinet 2 Viewing window for indication field 3 Eyebolt 4 Indication field 5 Transmission-gear cover plate 6 Output shaft 7 Hand crank aperture with hand crank interlock switch 8 Hand lamp 9 Fixing lug 10 Hand crank 11 19-inch plug-in housing 12 Motor protective switch Q1 13 S3 control switch 14 Swing frame / anti-condensation heater 15 Briefcase

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 32 6385142/08 EN ETOS® ED 4.5.1 Indication field A clear indication field is fitted in the motor-drive unit. The pointer and opera- tions counter are mechanically driven and indicate the tap-change operation sequence and operating position of the motor-drive unit. The reset wheel on the operations counter is sealed at the factory. Figure 8: Indication field 1 The two drag hands indicate the regulating range currently used 2 Tap position indicator 3 Tap-change indicator: Shows the current position of the control cam (33 tap-change indicator sections per operating position) 4 The mechanical operations counter shows the overall number of tap-change operations 4.5.2 Anti-condensation heater The anti-condensation heater is designed as a panel heater which also acts as the front cover of the swing frame. The design of the motor-drive unit and panel heater ensures that air circu- lates inside the motor-drive unit and therefore that there is a constant interior temperature which is always higher than the outside temperature. 4.5.3 Swing frame/terminal rail The swing frame protects all electrical and mechanical parts of the motor- drive unit behind the swing frame against accidental contact. The terminal rail behind the swing frame enables easy electrical connection of the motor-drive unit. Vertically arranged cap rails with the correspondingly mounted terminal bars ensure that the connection wiring is easy to install.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 33 6385142/08 EN ETOS® ED 4.5.4 Position transmitter equipment NOTICE Damage to the on-load tap-changer and motor-drive unit! Damage to on-load tap-changer and motor-drive unit due to incorrect use of position transmitter equipment. ►Only circuits stated in the chapter Technical data for position transmitter equipment [►Section 14.3, Page 380] may be connected to the position transmitter module connections. ►The switchover point of the position transmitter equipment in the motor- drive unit is not the same as the switchover point of the diverter switch operation. This depends on the type of diverter switch. This fact should be noted when project planning the locking circuits between the motor- drive unit and external equipment (e.g. transformer circuit breaker). ►Therefore, the "Tap changer in operation" position transit contact shown in the connection diagram should be used for external monitoring, locking and control purposes instead of the position transmitter equipment. The position transmitter equipment is used to indicate the operating position of the on-load tap-changer/de-energized tap-changer when idle. The remote displays are available in various versions. The position transmitter module for connection by the customer is located on the terminal rail [►Section 4.5.3, Page 32]. For more information about the position transmitter equipment, see Techni- cal data for position transmitter equipment [►Section 14.3, Page 380]. 4.5.5 Transmission gear cover plate WARNING Danger of death and severe injury from electrical voltage! Danger of death and severe injury from electrical voltage if the transmission gear cover plate is not fitted. ►Never start up motor-drive unit without transmission gear cover plate.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 34 6385142/08 EN ETOS® ED The touch-protected transmission-gear cover plate features an opening for the hand crank used in manual mode. Transmission-gear cover plate 4.5.6 Ambient temperature sensor The device is equipped with a temperature sensor for recording the ambient temperature. The temperature sensor is on the bottom of the protective housing. Ensure that there is sufficient circulation of the ambient air around the tem- perature sensor. Otherwise, there may be errors in torque monitoring. Figure 9: Ambient temperature sensor on the bottom of the protective housing 1 Ambient temperature sensor

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 35 6385142/08 EN ETOS® ED 4.5.7 ISM assemblies Depending on the order, the device is either designed as a 19-inch plug-in housing or supplied as individual components for assembly on a cap rail. The individual device assemblies are described in the following section. Figure 10: 19-inch plug-in housing (OT1205) Figure 11: Individual components for assembly on a cap rail 4.5.7.1 Power supply The OT1205 assembly contains the power supply unit for powering the de- vice. Depending on configuration, the device is equipped with one of the fol- lowing power supply unit variants: ▪ Multi-voltage mains unit 85...265 V AC/V DC ▪ DC voltage power supply unit 20...70 V DC

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 36 6385142/08 EN ETOS® ED 4.5.7.2 CPU (central processing unit) I The CPU I assembly is the central processing unit for the device. It contains the following interfaces: ▪ Internal system interface RS232 (COM1) ▪ Serial interface RS232/485 (COM2) ▪ 3x Ethernet (ETH1, ETH 2.1, ETH 2.2) ▪ USB (USB 2.0) ▪ 2x CAN bus (CAN 1, CAN 2) CPU CAN 1 1 9 CAN 2 1 9 COM 1 1 9 COM 2 1 9 - + 24V DC RUN INIT ERR USB2.0 4 6 2 A 8 C H TEST PROG RUN 4 6 2 A E 0 8 C L ETH 1 ETH 2.1 ETH 2.2 Figure 12: CPU I assembly 4.5.7.3 Voltage measurement and current measurement The UI 1 assembly is used for measuring 1-phase voltage and current. Figure 13: UI 1 assembly

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 37 6385142/08 EN ETOS® ED The UI 3 assembly is used for measuring 3-phase voltage and current. Figure 14: UI 3 assembly Warning of a danger point. Read the information given in the product oper- ating instructions. Warning of dangerous electrical voltage. This assembly is protected via double insulation or reinforced insulation. Table 8: Safety-relevant symbols on the assembly 4.5.7.4 UI 5-4 voltage measurement and current measurement The UI 5-4 assembly is used for measuring 3-phase voltage and current. Figure 15: UI 5-4 assembly

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 38 6385142/08 EN ETOS® ED Warning of a danger point. Read the information given in the product oper- ating instructions. Warning of dangerous electrical voltage. This assembly is protected via double insulation or reinforced insulation. Table 9: Safety-relevant symbols on the assembly 4.5.7.5 Digital inputs and outputs The assemblies DIO 28-15 and DIO 42-20 (HL) provide you with a number of digital inputs and outputs that differs based on the version: ▪ DIO 28-15: 28 inputs, 15 outputs (6 N/O contacts, 9 change-over con- tacts) ▪ DIO 42-20 (HL): 42 inputs, 20 outputs (8 N/O contacts, 12 change-over contacts) Figure 16: DIO 42-20 assembly Warning of a danger point. Read the information given in the product oper- ating instructions. Warning of dangerous electrical voltage. Table 10: Safety-relevant symbols on the assembly 4.5.7.6 Analog inputs and outputs The AIO 2 and AIO 4 assemblies provide analog inputs and outputs: ▪ AIO 2: 2 channels ▪ AIO 4: 4 channels

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 39 6385142/08 EN ETOS® ED In accordance with the device configuration, the AIO assembly supports one of the following signal types: Input Output Voltage Current Voltage Current 0...10 V 0...20 mA 4...20 mA 0...10 V 0...20 mA 4...20 mA Resistance measurement (such as PT100, resistor contact series) Table 11: Signal types supported by the AIO assembly Figure 17: AIO 4 assembly 4.5.7.7 Analog inputs and outputs (AIO 8) The AIO 8 assembly provides 8 channels for analog inputs. In accordance with the device configuration, the AIO assembly supports one of the follow- ing signal types: ▪ Voltage: 0...10 V ▪ Current: 0/4...20 mA (only channels 1, 2, 7 and 8) ▪ Resistance measurement (e.g. PT100)

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 40 6385142/08 EN ETOS® ED Figure 18: AIO 8 assembly 4.5.7.8 Media converter The MC 2-2 assembly is a media converter, which converts 2 electrical con- nections (RJ45) to one fiber-optic cable connection each. Each is converted independently of the other. The following interfaces are available: ▪ 2x RJ45 (ETH12, ETH22) ▪ 2x Duplex-LC (SFP module) (ETH11, ETH21) The media converter is designed to be transparent for the network and does not have its own IP address. Figure 19: MC 2-2 assembly

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 41 6385142/08 EN ETOS® ED 4.5.7.9 Media converter with managed switch The assembly SW 3-3 is a media converter with managed switch. It com- bines two independent functions and provides you with the following inter- faces: ▪ A media converter converts an electric connection (RJ45) into a fiber-optic cable connection – RJ45 (ETH12) – Duplex-LC (SFP module) (ETH11) ▪ Managed switch with redundancy function (PRP or RSTP) – 2x RJ45 (ETH23, ETH24), device-internal connection – 2x Duplex-LC (SFP module) (ETH21, ETH22), redundancy connection The following redundancy functions are available to you according to your order: ▪ PRP (standard setting) ▪ RSTP Figure 20: SW 3-3 assembly 4.6 Nameplate Depending on the version, the nameplate is in the control cabinet and/or out- side of the control cabinet.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 42 6385142/08 EN ETOS® ED Inside: ETOS® ED L, ETOS® ED L-S and ETOS® ED XL Figure 21: Nameplate in the control cabinet 1 Nameplate Outside: ETOS® ED XL Figure 22: Nameplate on the control cabinet door 1 Nameplate 4.7 Protective devices The following protective devices are fitted in the motor-drive unit: ▪ End stop device (mechanical and electric) ▪ Device protecting against unintentional passage ▪ Motor protection device ▪ Protection against accidental contact

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 43 6385142/08 EN ETOS® ED 4.8 Safety markings The following safety markings are used on the product: Figure 23: Overview of safety markings 1 Warning of rotating parts 2 Warning of dangerous electrical voltage 3 Warning of hot surface 4 Read the documentation 4.9 Emergency operation during switching blocking (X100 bridge) The monitoring function of the on-load tap-changer is only active when the device is ready for operation and issues a signal at the digital output Status OK. If your device is equipped with the OLTC monitoring expert function pack- age, the monitoring system can block further tap-change operations where necessary. In this case, the monitoring system will report the event Blocking active. If operation needs to be resumed despite the cause of the event not being eliminated, you can activate emergency operation by inserting the X100 bridge. If the X100 bridge is inserted, drive blocking by the monitoring system is switched to inactive. All operating values continue to be recorded and stored by the monitoring system.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 44 6385142/08 EN ETOS® ED NOTICE Damage to the transformer and/or on-load tap-changer If the Blocking active event is present in the monitoring system, then the cause of the event has to be analyzed before activating emergency opera- tion. Performing additional tap-change operations on the motor-drive unit without analyzing the cause may lead to on-load tap-changer and/or trans- former damage. ►Check what caused the Blocking active event and decide whether to con- tinue operating the on-load tap-changer based on the cause. ►Export the service data and contact Maschinenfabrik Reinhausen GmbH. 4.10 Visualization 4.10.1 Main screen The web-based visualization is split into various areas. Figure 24: Main screen 1 Display area 2 Secondary navigation 3 Primary navigation 4 Status bar The most important measured values of the transformer are displayed on the main screen. The individual status displays of the transformer shown can be selected directly when accessing them via the web browser. They act as links to the corresponding menu items. If you are operating the device via the front panel, you are only able to call up the elements via the Information menu.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 45 6385142/08 EN ETOS® ED If the device does not have one of the optional functions, this will be indi- cated in the main screen via a small padlock . Depending on the device configuration, the main screen displays the schematic representation of a transformer for network applications or a transformer for industrial applications. 4.10.1.1 Transformer for network applications Figure 25: Transformer data 1 DGA (status) 2 Top-oil temperature 3 Hot-spot temperature 4 Cooling system (status) 5 Load current and load voltage of phases L1, L2, L3 6 Transformer name

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 46 6385142/08 EN ETOS® ED Figure 26: Apparent power, oil level, and ambient temperature 1 Asset intelligence 2 Total apparent power 3 Ambient temperature 4 Oil level (transformer on left, on- load tap-changer on right) Figure 27: On-load tap-changer and motor-drive unit 1 OLTC oil temperature 2 Current tap position 3 Voltage regulator 4 Tap-change operation statistics 5 OLTC status message (collective message)

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 47 6385142/08 EN ETOS® ED 4.10.1.2 Transformer for industrial applications Figure 28: Transformer data 1 DGA (status) 2 Top-oil temperature 3 Hot-spot temperature 4 Cooling system (status) 5 Load current an load voltage of the phases L1, L2, L3 (high-voltage side) 6 Transformer name Figure 29: Apparent power, oil level, and ambient temperature 1 Asset intelligence 2 Total apparent power 3 Ambient temperature 4 Oil level (transformer on left, on- load tap-changer on right)

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 48 6385142/08 EN ETOS® ED Figure 30: On-load tap-changer and motor-drive unit 1 OLTC oil temperature 2 Current tap position 3 Voltage regulator 4 Tap-change operation statistics 5 OLTC status message (collective message)

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 49 6385142/08 EN ETOS® ED 4.10.2 Additional operating controls and display elements when using the MControl touch panel (optional) If you are using the device with the optionally available MControl touch panel, additional operating controls and display elements are displayed on the left edge of the screen. Depending on the device configuration, a variety of keys are available: Figure 31: Additional display elements and operating controls Status LED status Status display 1) REMOTE key Select the operating mode: ▪ On: REMOTE ▪ Off: LOCAL 2) AVR AUTO key Activate auto mode. 2) RAISE key Send a control command to the motor-drive unit to increase the voltage. Only possible in manual mode. 2) AVR Manual key Activate manual mode. 2) LOWER key Send a control command to the motor-drive unit to reduce the voltage. Only possible in manual mode. 1) Not available if local/remote is toggled using a digital input. 2) Only available in the "Automatic voltage regulation" function package. 4.10.3 Operating concept You can operate the device using the controls on the front panel or using the web-based ISM™ Intuitive Control Interface visualization on a PC. The scope of function and structure of both options is virtually identical.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 50 6385142/08 EN ETOS® ED User rights and user roles The device is equipped with a rights system and a roles system. The display and access rights to device settings or events can therefore be controlled at the user level. You can configure the rights system and roles system to meet your require- ments. You will find more information on user rights in the User administra- tion [►Section 9.34, Page 315] section. You can only modify the device settings or parameters if you have the nec- essary user rights. Logging on, logging off and changing users The control of access rights to device settings and parameters is user- based. Various users can log in at the same time (e.g. via the visualization) and access the device. If you want to operate the device via the controls and visualization at the same time, you have to log in on the device and via the visualization. 1. Select the LOGIN or CHANGE button in the status line. 2. Enter your user name and password and select the OK button. ð The name of the logged-in user appears in the status line. To log out as a user, proceed as follows: ►Press the LOGOUT button in the status line. Navigation If you are operating the device using the controls on the front panel, you can use the rotary knob to navigate through the entire menu. The menu currently selected has a blue border. To open the highlighted menu, you have to press the key. Pressing the key returns you to the previous menu level. If you are operating the device using the web-based visualization, you can navigate by clicking on the appropriate buttons. Example 1. Go to Settings. 2. Go to Parameters. 3. Go to System. 4. Go to Time synchronization. 5. Select Time.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 51 6385142/08 EN ETOS® ED In these operating instructions, the path for navigating to a parameter is al- ways shown in an abridged form: Go to Settings > Parameters > System > Time synchronization. Setting parameters There are various ways to configure the settings, depending on the parame- ter. Selecting from a list To select a list entry, proceed as follows: 1. Use the rotary knob to navigate to the list and press the key. Figure 32: Select an entry from a list 2. Use the rotary knob to highlight the list entry and press the key. 3. Press the Accept button to save the modified parameter.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 52 6385142/08 EN ETOS® ED Entering a value To enter a value, proceed as follows: 1. Use the rotary knob to select the value field and press the key. ð If operating via the front panel, the numerical keypad appears. Figure 33: Entering a value 2. Enter the desired value and confirm with . 3. Press the Accept button to save the modified parameter. Entering text 1. Use the rotary knob to select the text box and press the key. ð If operating via the front panel, the keyboard appears. Figure 34: Entering text 2. Enter the desired text and confirm with . 3. Press the Accept button to save the modified parameter.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 53 6385142/08 EN ETOS® ED Parameter search You can use the quick search function in the parameter menu to search for a parameter. Enter the name of the desired parameter in the Search entry field. Figure 35: Quick search Expert mode The device has an expert mode for entering the parameters. You can enter the parameters directly on the overview screen of the respective menu in this mode. Figure 36: Expert mode 1. Go to Settings > Parameters. 2. Select the Expert mode checkbox. ð Expert mode is active.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 54 6385142/08 EN ETOS® ED Hiding/showing parameters Depending on how you set the parameters, the device will hide or show ad- ditional parameters related to this function.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2020 55 6385142/08 EN ETOS® ED 5 Packaging, transport and storage 5.1 Packaging The products are sometimes supplied with sealed packaging and sometimes in a dry state, depending on requirements. Sealed packaging surrounds the packaged goods with plastic foil on all sides. Products that have also been dried are identified by a yellow label on the sealed packaging. In the dry state, delivery is also possible in a transport container. The information in the following sections should be applied as appropriate. 5.1.1 Suitability NOTICE Property damage due to incorrectly stacked crates! Stacking the crates incorrectly can lead to damage to the packaged goods. ►The outer marking on the packaging states if, for example, the on-load tap-changer or selector has been packed upright. Never stack these crates. ►General rule: Do not stack crates above a height of 1.5 m. ►For other crates: Only stack up to 2 equally sized crates on top of one an- other. The packaging is suitable to ensure undamaged and fully functional means of transportation in compliance with local transportation laws and regula- tions. The packaged goods are packed in a sturdy crate. This crate ensures that, when in the intended transportation position, the packaged goods are stabi- lized to prevent impermissible changes in position, and that none of the parts touch the loading surface of the means of transport or touch the ground after unloading. Sealed packaging surrounds the packaged goods with plastic foil on all sides. The packaged goods are protected from humidity using a desiccant. The plastic foil was bonded after the desiccant is added.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2020 56 6385142/08 EN ETOS® ED 5.1.2 Markings The packaging bears a signature with instructions for safe transport and cor- rect storage. The following symbols apply to the shipment of non-hazardous goods. Adherence to these symbols is mandatory. Protect against moisture Top Fragile Attach lifting gear here Center of mass Table 12: Shipping pictograms 5.2 Transportation, receipt and handling of shipments WARNING Danger of death or severe injury! Danger of death or serious injuries due to tipping or falling load. ►Only transport the crate when closed. ►Do not remove the securing material used in the crate during transport. ►If the product is delivered on a pallet, secure it sufficiently. ►Only trained and authorized persons may select the sling gear and se- cure the load. ►Do not walk under the suspended load. ►Use means of transport and lifting gear with a sufficient carrying capacity in accordance with the weight stated on the delivery slip. In addition to oscillation stress, jolts must also be expected during trans- portation. In order to prevent possible damage, avoid dropping, tipping, knocking over and colliding with the product. If a crate tips over, falls from a certain height (e.g. when slings tear) or is subject to an unbroken fall, damage must be expected regardless of the weight. Every delivered shipment must be checked for the following by the recipient before acceptance (acknowledgment of receipt): ▪ Completeness based on the delivery slip ▪ External damage of any type The checks must take place after unloading when the crate or transport con- tainer can be accessed from all sides.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2020 57 6385142/08 EN ETOS® ED Visible damage If external transport damage is found upon receipt of the shipment, proceed as follows: ▪ Immediately record the identified transport damage in the shipping docu- ments and have this countersigned by the carrier. ▪ In the event of severe damage, total loss or high damage costs, immedi- ately notify the manufacturer and the relevant insurance company. ▪ After identifying damage, do not modify the condition of the shipment fur- ther and retain the packaging material until an inspection decision has been made by the transport company or the insurance company. ▪ Record the details of the damage immediately on site together with the carrier involved. This is essential for any claim for damages. ▪ Photograph damage to packaging and packaged goods. This also applies to signs of corrosion on the packaged goods due to moisture inside the packaging (rain, snow, condensation). ▪ NOTICE! Damage to packaged goods due to damaged sealed packag- ing. If the product is delivered in sealed packaging, check the sealed packaging immediately. If the sealed packaging is damaged, do not under any circumstances install or commission the packaged goods. Either re- dry the dried packaged goods as per the operating instructions, or contact the manufacturer to agree on how to proceed. ▪ Identify the damaged parts. Hidden damage When damages are not determined until unpacking after receipt of the ship- ment (hidden damage), proceed as follows: ▪ Make the party responsible for the damage liable as soon as possible by telephone and in writing, and prepare a damage report. ▪ Observe the time periods applicable to such actions in the respective country. Inquire about these in good time. With hidden damage, it is very hard to make the transportation company (or other responsible party) liable. Any insurance claims for such damages can only be successful if relevant provisions are expressly included in the insur- ance terms and conditions. 5.3 Storage of shipments Packaged goods dried by Maschinenfabrik Reinhausen Upon receipt of the shipment, immediately remove the packaged goods dried by Maschinenfabrik Reinhausen from the sealed packaging and store air-tight in dry insulating fluid until used if the packaged goods were not sup- plied in insulating fluid. Non-dried packaged goods Non-dried packaged goods but with a functional sealed packaging can be stored outdoors when the following conditions are complied with.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2020 58 6385142/08 EN ETOS® ED When selecting and setting up the storage location, ensure the following: ▪ Protect stored goods against moisture (flooding, water from melting snow and ice), dirt, pests such as rats, mice, termites and so on, and against unauthorized access. ▪ Store the crates on timber beams and planks as a protection against ris- ing damp and for better ventilation. ▪ Ensure sufficient carrying capacity of the ground. ▪ Keep entrance paths free. ▪ Check stored goods at regular intervals. Also take appropriate action after storms, heavy rain or snow and so on. Protect the packaging foil from direct sunlight so that it does not disintegrate under the influence of UV rays, which would cause the packaging to lose its sealing function. If the product is installed more than 6 months after delivery, suitable mea- sures must be taken without delay. The following measures can be used: ▪ Correctly regenerate the drying agent and restore the sealed packaging. ▪ Unpack the packed goods and store in a suitable storage space (well ven- tilated, as dust-free as possible, humidity < 50% where possible). 5.4 Unpacking shipments and checking for transportation damages ▪ NOTICE! Transport the packaged crate to the place where the packaged goods are to be installed. Do not open the sealed packaging until just be- fore installation. Otherwise, damage to the packaged goods may occur due to ineffectively sealed packaging. ▪  WARNING! When unpacking, check the condition of the packaged goods. Place the packaged goods in an upright crate and protect it from tipping out. Otherwise, the packaged goods may become damaged and serious injuries may result. ▪ Check the completeness of the accessories kit using the delivery slip. Attachment points for lifting gear WARNING Danger of death and damage to property! Danger of death and damage to property due to tipping or falling load! ►Only trained and authorized persons may select the sling gear and se- cure the load. ►Do not walk under the suspended load. ►Use means of transport and lifting gear with a sufficient carrying capacity in accordance with the weight stated in the Technical data section.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2020 59 6385142/08 EN ETOS® ED ▪  WARNING! Serious injuries and damage to the control cabinet due to falling load. Attach the lifting gear such that the cable angle is always less than 45° in relation to the vertical. Figure 37: Maximum permissible cable angle for the lifting-gear limit stop of the control cabinet ▪  WARNING! Serious injuries due to the control cabinet tipping and damage to the cable gland if the control cabinet is set down, transported or stored upright. Only set down, transport and store the control cabinet on its back. ▪ Only remove the control cabinet from the crane once it has been fully con- nected to the transformer.

Maschinenfabrik Reinhausen GmbH 2020

60 6385142/08 EN ETOS® ED 6 Mounting This chapter describes how to correctly install and connect the device. WARNING Danger of death or severe injury! An energized transformer and energized on-load tap-changer components can cause death or serious injuries during installation of the drive! ►Ensure the de-energized state of the transformer and on-load tap- changer components during installation of the drive. 6.1 Attaching the control cabinet to the transformer The control cabinet has four fixing attachments on the rear to secure it. 1. Attach four stud bolts (not supplied by MR) to the transformer tank. Figure 38: Fastening the stud bolts A 675±2 B 500±2

Maschinenfabrik Reinhausen GmbH 2020

61 6385142/08 EN ETOS® ED 2. For control cabinets with vibration damper: Attach the inner bracket to the control cabinet. Attach the outer bracket to the transformer wall. The com- plete contact surfaces of the brackets must be in contact. 1 1 1 Bracket contact surfaces 3. Use the fixing attachments to attach the control cabinet to the stud bolts and align it vertically on the transformer tank. Figure 39: Attaching the control cabinet

Maschinenfabrik Reinhausen GmbH 2020

62 6385142/08 EN ETOS® ED 4. NOTICE! Damage to the control cabinet due to mechanical tension. Se- cure the control cabinet without subjecting it to mechanical tension. Figure 40: Securing the drive 5. Connect the grounding cable to the control cabinet and the transformer tank, holding it against the control cabinet using a wrench (wrench size 36). Figure 41: Connecting the grounding cable to the control cabinet

Maschinenfabrik Reinhausen GmbH 2020

63 6385142/08 EN ETOS® ED 6.2 Mounting drive shafts and bevel gear The process of mounting the drive shafts and bevel gear is described in the installation and commissioning instructions for the on-load tap-changer / de- energized tap-changer. 6.3 Centering on-load tap-changer and motor-drive unit WARNING Danger of death or severe injury! Danger of death or severe injury due to motor-drive unit starting up by acci- dent and due to electric voltage! ►Before starting any coupling work make sure that the motor protective switch is tripped. ►Carry out any adjustment work in manual mode only. ►When manually operating the motor-drive unit only use the hand crank provided for this purpose. ►Note that the hand crank safety switch causes a 2-pole disconnection of the motor circuit but that the control circuit is not interrupted. NOTICE Damage to property! The on-load tap-changer will be damaged by incorrectly centering the mo- tor-drive unit. ►Do not perform more than 250 tap-change operations on the on-load tap- changer. If more than 250 tap-change operations are performed, com- pletely fill oil compartment with insulating oil and lubricate sliding surfaces of contacts on selector and selector gear with insulating oil. The following steps for centering the on-load tap-changer and motor-drive unit do not apply to the DEETAP® DU or COMTAP® ARS devices. The process for centering the motor-drive unit and DEETAP® DU or COMTAP® ARS devices is described in the relevant operating instructions. One on-load tap-change operation is represented by one rotation of the tap- change indicator. This indicator is divided into 33 tap-change indicator sec- tions, each of which corresponds to one hand crank revolution in the stan- dard motor-drive unit design. The time of the switchover depends on the on- load tap-changer / de-energized tap-changer type, but is always 2 tap- change indicator sections upstream of the area marked in gray on the tap- change indicator at the latest. To center the on-load tap-changer and motor-drive unit, proceed as follows. 1. NOTICE! Move the on-load tap-changer / de-energized tap-changer and the motor-drive unit into the adjustment position before commencing any adjustment work. Ensure that the tap position indicators for the motor-

Maschinenfabrik Reinhausen GmbH 2020

64 6385142/08 EN ETOS® ED drive unit and the on-load tap-changer / de-energized tap-changer match. Otherwise damage to the on-load tap-changer and transformer may re- sult. Figure 42: Adjustment position 2. Attach the hand crank in the motor-drive unit to the shaft end located in the upper cover plate. This activates a hand crank interlock switch, which disconnects the motor circuit at 2 poles. Figure 43: Hand crank

Maschinenfabrik Reinhausen GmbH 2020

65 6385142/08 EN ETOS® ED 3. Turn the hand crank clockwise until the diverter switch operation begins. When turning the hand crank, observe the tap-change indicator, which mechanically reflects the progress of the tap-change operation. Figure 44: Turning the hand crank 4. Once the diverter switch operation begins, continue to turn in the same di- rection while counting the tap-change indicator sections required for the pointer to reach the mid-position of the area marked in gray on the tap- change indicator. Note the number counted (value A) and the direction of rotation (example: A=2). Figure 45: Counting the tap changes needed to reach the mid-position 5. If value A is greater than 8 tap-change indicator sections, the tap-change operation has been completed correctly. If value A is less than 8 tap- change indicator sections, turn another 8-A tap-change indicator sections

Maschinenfabrik Reinhausen GmbH 2020

66 6385142/08 EN ETOS® ED in the same direction (example: 8-2=6) to complete the tap-change opera- tion. Then turn in the opposite direction until the pointer is in the mid-posi- tion of the area marked in gray on the tap-change indicator. Figure 46: Completing the diverter switch operation 6. Turn the hand crank counter-clockwise until the diverter switch operation begins. Figure 47: Turning the hand crank in the opposite direction

Maschinenfabrik Reinhausen GmbH 2020

67 6385142/08 EN ETOS® ED 7. Once the diverter switch operation begins, continue to turn in the same di- rection while counting the tap-change indicator sections required for the pointer to reach the mid-position of the area marked in gray on the tap- change indicator. Note the number counted (value B) and the direction of rotation (example: B=5). Figure 48: Counting the tap-change indicator sections needed to reach the mid-position 8. If value B is greater than 8 tap-change indicator sections, the tap-change operation has been completed correctly. If value B is less than 8 tap- change indicator sections, turn another 8 B tap-change indicator sections in the same direction (example: 8-5=3) to complete the tap-change opera- tion. Then turn in the opposite direction until the pointer is in the mid-posi- tion of the area marked in gray on the tap-change indicator. Figure 49: Completing the diverter switch operation 9. If the values obtained for A and B are identical, the on-load tap-changer and the motor-drive unit are correctly coupled (a slight imbalance of maxi- mum 1 tap-change indicator section is permitted). If the values obtained for A and B are different, establish correction value C by halving the differ- ence between A and B: C=|(A-B) x 0.5| Example: C=|(2-5) x 0.5|=|-1.5|=1.5

Maschinenfabrik Reinhausen GmbH 2020

68 6385142/08 EN ETOS® ED Also take numbers after the decimal point into account. 10. If the correction value |C| is less than 0.5 tap-change indicator sections, no further action is required. Refer to item 18 for how to proceed next. 11. Use the hand crank to crank in the direction in which the determined value A or B was higher (example: counter-clockwise, because B > A) until the diverter switch operation begins. 12. Once the diverter switch operation begins, continue turning another 8 hand crank revolutions in the same direction to correctly complete the di- verter switch operation.

Maschinenfabrik Reinhausen GmbH 2020

69 6385142/08 EN ETOS® ED 13. Uncouple the motor-drive unit and vertical drive shaft by removing the coupling brackets. After uncoupling, do not turn the drive shaft any fur- ther. Figure 50: Uncoupling the motor-drive unit and drive shaft 14. Operate the motor-drive unit using the hand crank in the same direction, continuing by C tap-change indicator sections on the tap-change indica- tor (example: 1.5 tap-change indicator sections). 15. Couple the motor-drive unit and on-load tap-changer by refitting the verti- cal drive shaft (tightening torque 9 Nm). Do not turn the drive shaft or output shaft of the bevel gear or motor-drive unit any further. 16. Continue to turn in the same direction while counting the tap-change in- dicator sections required for the pointer to reach the mid-position of the area marked in gray on the tap-change indicator. Note the number counted (value A) and the direction of rotation. If value A is greater than 8 tap-change indicator sections, the tap-change operation has been completed correctly. If value A is less than 8 tap-change indicator sec-

Maschinenfabrik Reinhausen GmbH 2020

70 6385142/08 EN ETOS® ED tions, turn another 8 A tap-change indicator sections in the same direc- tion (example: 8-4=4) to complete the tap-change operation. Then turn in the opposite direction until the indicator is in the mid-position of the area marked in gray on the tap-change indicator. Check the coupling again as described previously. 17. The pointer of the tap-change indicator must be in the mid-position of the area marked in gray once the on-load tap-change operation with the hand crank is complete. Figure 51: Pointer in the mid-position 18. Once coupling is complete in both directions, check by carrying out sev- eral on-load tap-change operations and check that the on-load tap- changer and motor-drive unit are in the same tap position. 6.4 Connecting the ISM® assemblies WARNING Electric shock! Risk of fatal injury due to connection errors. ►Ground the device using the grounding screw on the housing. 6.4.1 Cable recommendation (ISM® assemblies) Please note the following Maschinenfabrik Reinhausen GmbH recommenda- tion when wiring the device. ▪ Excessive line capacitance can prevent the relay contacts from interrupt- ing the contact current. In control circuits operated with alternating current, take into account the effect of the line capacitance of long control cables on the function of the relay contacts. ▪ If you want to route Ethernet connections from a control cabinet or build- ing, we recommend using fiber-optic cables (in accordance with the IEC 61850-90-4 recommendation). ▪ Ensure that the copper cables used have a temperature resistance of 70°C.

Maschinenfabrik Reinhausen GmbH 2020

71 6385142/08 EN ETOS® ED Cable Assembly Cable type Conductor cross-section Conductor material Max. length Voltage measurement UI 1, UI 3, UI 5-4 Shielded 2.5 mm² Copper - Current measurement UI 1, UI 3, UI 5-4 Unshielded 4 mm² Copper - Signal inputs DIO 28-15, DIO 42-20 Shielded 1.5 mm2 Copper 400 m (<25 Ω/km) Signal outputs* DIO 28-15, DIO 42-20 Shielded 1.5 mm2 Copper - Signal inputs AIO 2, AIO 4, AIO 8 Shielded 1 mm2 Copper 400 m (<25 Ω/km) Signal outputs AIO 2, AIO 4, AIO 8 Shielded 1 mm2 Copper - RS232, SUB-D CPU I, CPU II Shielded 0.25 mm2 - 25 m RS485; SUB-D CPU I, CPU II Shielded 0.25 mm2 - 140 m CAN bus CPU I Shielded 0.75 mm² - 2,000 m (total CAN bus) Ethernet RJ45 CPU I Min. CAT5, shielded S/FTP For ETOS® ED XL Angle plug rec- ommended - - 100 m Ethernet FO MC 2-2, SW 3-3 Duplex LC Multimode, OM3, 1310 nm - - 2000 m Table 13: Recommendation for connection cables *) Observe line capacitance, see note above. 6.4.2 Information about connecting serial interfaces RS232 and RS485 NOTICE Damage to the device! Using the wrong data cable may damage the device. ►Only use data cables which comply with the description below.

Maschinenfabrik Reinhausen GmbH 2020

72 6385142/08 EN ETOS® ED RS232 (D-SUB 9-pole) For connecting the device via the RS232 interface (COM2), use a data cable with the following structure: Figure 52: RS232 data cable (9-pole) RS485 (D-SUB 9-pole) To connect the device via the RS485 interface (COM2), use a data cable with the following structure: Figure 53: RS485 data cable

Maschinenfabrik Reinhausen GmbH 2020

73 6385142/08 EN ETOS® ED D-SUB 9-pole plug connection Only use 9-pole D-SUB plugs with the following characteristics: ▪ Plug housing is metallic or metal-plated ▪ Cable shielding is connected with the plug using one of the two following variants: – Shielding is screwed down with traction relief. – Shielding is soldered with plug housing. Figure 54: Example of a soldered shielding on a plug housing 6.4.3 Notes on connecting to the MR sensor bus The optionally available MR sensor bus function lets you connect digital and analog sensors to the device over Modbus RTU. The MR sensor bus sup- ports the connection of up to 31 sensors (Modbus slaves). The ISM® device operates as the Modbus master. Ensure that no other Modbus master is connected over the MR sensor bus. Assign a unique Modbus address to each sensor you are connecting over MR sensor bus. The MR sensor bus may experience errors if multiple sen- sors are using the same Modbus address. Observe the following notes for connecting the sensors: ▪ NOTICE! Damage to the device or sensor. Connect all of the sensors to the potential equalization rail to avoid circulating currents over the MR sensor bus. ▪ The MR sensor bus uses Modbus in a 2-wire configuration (2W). The 4- wire configuration (4W) is not supported. ▪ You must connect the sensors via a shielded line with 3 conductors (D0, D1, Common). The data lines (D0, D1) must be in twisted pairs. Note the cable recommendation. ▪ Stub lines from the bus node to the respective device must be shorter than 20 m.

Maschinenfabrik Reinhausen GmbH 2020

74 6385142/08 EN ETOS® ED ▪ The CPU assembly contains a terminating resistor (120 Ω) at the COM2 interface. Install another terminating resistor (120 Ω, 0.5 W) at the other end of the bus. ▪ The CPU assembly contains a pull-up resistor and a pull-down resistor (each of 680 Ω in accordance with the Modbus specification). No addi- tional pull-up/pull-down resistors are needed. CPU-COM2 Sensor 1 Sensor x D0 (A) D1 (B) Com. (C) 1 2 3 4 5 6 7 8 9 D0 (A) D1 (B) Com. (C) D0 (A) D1 (B) Com. (C) 120 Ω Figure 55: MR sensor bus

Maschinenfabrik Reinhausen GmbH 2020

75 6385142/08 EN ETOS® ED 6.4.3.1 MSENSE® DGA If you would like to use an MSENSE® DGA sensor, you must connect the sensor to the MR sensor bus in accordance with the following connection ex- amples. If the MSENSE® DGA sensor is the only bus device or the last bus device, you must use a terminating resistor (120 Ω, 0.5 W). CPU-COM2 MSENSE DGA 2/3 D0 (A) D1 (B) Com. (C) 1 2 3 4 5 6 7 8 9 D0 (A) D1 (B) Com. (C) 1 4 2 3 5 1 2 3 4 5 D1 (B) D0 (A) Figure 56: Connection example MSENSE® DGA 2/3 (connector M12, type A, 5-pole in accor- dance with IEC 61076-2-101) CPU-COM2 MSENSE DGA 5 D0 (A) D1 (B) Com. (C) 1 2 3 4 5 6 7 8 9 (PhoneB) (GND) X302:5 X302:4 X302:3 X302:2 X302:1 (OUTA) (OUTB) (PhoneA) Figure 57: Connection example MSENSE® DGA 5 (terminal X302)

Maschinenfabrik Reinhausen GmbH 2020

76 6385142/08 EN ETOS® ED CPU-COM2 MSENSE DGA 9 D0 (A) D1 (B) Com. (C) 1 2 3 4 5 6 7 8 9 (PhoneB) (GND) X304:5a X304:4b X304:3 X304:1a X304:1b (OUTA) (OUTB) (PhoneA) Figure 58: Connection example MSENSE® DGA 9 (terminal X304) 6.4.3.2 MESSKO® MTeC® EPT303 FO If you would like to use a MESSKO® MTeC® EPT303 FO sensor, you must connect the sensor to the RS485 plug terminals on the sensor bus. Use a shielding clamp to apply the shield to the cable. You can directly connect ad- ditional MESSKO® MTeC® EPT303 FO sensors to the plug terminal. The EPT303 FO sensor module contains a terminating resistor. If you would like to use the EPT303 FO sensor together with other sensor types on an MR sensor bus, then we recommend connecting the EPT303 FO sensor to the end of the bus. CPU-COM2 EPT303 FO D0 (A) D1 (B) Com. (C) 1 2 3 4 5 6 7 8 9 D+ (B) GND D- (A) D+ (B) GND D- (A) 1 2 3 4 5 6 1 6 Figure 59: Connection example MESSKO® MTeC® EPT303 FO (terminal RS485)

Maschinenfabrik Reinhausen GmbH 2020

77 6385142/08 EN ETOS® ED 6.4.3.3 MESSKO® MTRAB® 2.5 If you would like to use a MESSKO® MTRAB® 2.5 sensor, you must con- nect the sensor to the RS485 plug terminals on the sensor bus. CPU-COM2 MTRAB 2.5 D0 (A) D1 (B) Com. (C) 1 2 3 4 5 6 7 8 9 D+ | Rx+ D- | Rx- Comm Tx- Tx+ Shield Figure 60: Connection example MESSKO® MTRAB® 2.5 (terminal RS485) You must enable the half-duplex operating mode on the sensor by switching the "Duplex mode" switch to the "HALF" setting. If the MESSKO® MTRAB® 2.5 sensor is the only bus device or the last bus device, you must activate the sensor terminating resistor by switching the "BUS termination 120 ohms" switch to the position "1 = ON" and "2 = OFF". Figure 61: MESSKO® MTRAB® 2.5 Modbus configuration 1 Terminating resistor: in half duplex mode: 1 = ON, 2 = OFF; in full du- plex mode: 1 = ON, 2 = ON 2 Operating mode: HALF = half du- plex, FULL = full duplex 3 Modbus address

Maschinenfabrik Reinhausen GmbH 2020

78 6385142/08 EN ETOS® ED 6.4.3.4 MSENSE®-FO ECU-I/S If you would like to use an MSENSE®-FO ECU-I or ECU-S sensor, you must connect the sensor to the RS485 plug terminals on the sensor bus. Use a shielding clamp to apply the shield to the cable. If the MSENSE®-FO sensor is the only bus device or the last bus device, you must use a terminating re- sistor (120 Ω, 0.5 W). You must activate the half-duplex, 2-conductor operat- ing mode on the sensor via the MSET-FO configuration software. CPU-COM2 MSENSE®-FO D0 (A) D1 (B) Com. (C) 1 2 3 4 5 6 7 8 9 Tx+ 1 2 3 4 5 Tx- Rx+ Rx- GND Figure 62: Connection example MSENSE®-FO ECU-I and ECU-S (terminal RS485) 6.4.4 Information about connecting analog sensors NOTICE Damage to the device and sensors! Incorrectly connected and configured analog inputs/outputs may result in damage to the device and sensor. ►Follow information about connecting analog sensors [►Section 6.4.4, Page 78]. ►Configure analog inputs and outputs according to the connected sensors.

Maschinenfabrik Reinhausen GmbH 2020

79 6385142/08 EN ETOS® ED The AIO assembly has a separate plug connector for each channel (input or output). The plugs are assigned as follows: 1 3 2 4 5 11 13 12 14 15 6 8 7 9 10 16 18 17 19 20 RDY AIO + - 24V DC 1 3 2 4 5 1 2 3 4 5 Figure 63: Plug assignment of the AIO module (illustration using module AIO 4 as an example) Interface Pin Description 1 6 11 16 I OUT (+): Current output + 2 7 12 17 I/U IN (+) U OUT (+): Voltage input +, current input +, voltage output + 3 8 13 18 I/U IN (-): Voltage input -, current in- put - 4 9 14 19 I/U OUT (-): Voltage output -, current output - 5 10 15 20 Not used Table 14: Analog inputs and outputs You can connect the following types of analog sensors: ▪ 4...20 mA ▪ PT100/PT1000 (2-wire, 3-wire, 4-wire)

Maschinenfabrik Reinhausen GmbH 2020

80 6385142/08 EN ETOS® ED 4...20 mA sensor You must connect a 4...20 mA sensor to the pins and . You must also connect the supplied bridge to the pins , , and . I OUT (+) I/U IN (+) U OUT (+) I/U IN (-) I/U OUT (+) 1 2 3 4 5 --- 4...20 mA signal source Figure 64: Connection example for a 4...20 mA sensor PT100/PT1000 sensor Depending on type, you must connect a PT100 sensor or PT1000 sensor as follows: ▪ 2-wire: pin and ▪ 3-wire: pin , and ▪ 4-wire: pin , , , and I OUT (+) I/U IN (+) U OUT (+) I/U IN (-) I/U OUT (+) 1 2 3 4 5 --- 2-wire I OUT (+) I/U IN (+) U OUT (+) I/U IN (-) I/U OUT (+) 1 2 3 4 5 --- 3-wire I OUT (+) I/U IN (+) U OUT (+) I/U IN (-) I/U OUT (+) 1 2 3 4 5 --- 4-wire PT100/PT1000 Figure 65: Connection example for a PT100/PT1000 sensor

Maschinenfabrik Reinhausen GmbH 2020

81 6385142/08 EN ETOS® ED 6.4.5 Electromagnetic compatibility The device has been developed in accordance with applicable EMC stan- dards. The following points must be noted in order to maintain the EMC standards. 6.4.5.1 Wiring requirement of installation site Note the following when selecting the installation site: ▪ The system's overvoltage protection must be effective. ▪ The system's ground connection must comply with all technical regula- tions. ▪ Separate system parts must be joined by a potential equalization. ▪ The device and its wiring must be at least 10 m away from circuit-break- ers, load disconnectors and busbars. 6.4.5.2 Wiring requirement of operating site Note the following when wiring the operating site: ▪ Route the connecting leads in grounded metal cable ducts. ▪ Do not route lines which cause interference (e.g. power lines) and lines susceptible to interference (e.g. signal lines) in the same cable duct. ▪ Maintain a distance of more than 100 mm between lines which cause in- terference and those which are susceptible to interference. Figure 66: Recommended wiring 1 Cable duct for lines causing inter- ference 3 Cable duct for lines susceptible to interference 2 Line causing interference (e.g. power line) 4 Line susceptible to interference (e.g. signal line) ▪ Short-circuit and ground reserve lines. ▪ Never connect the device with a multi-wire collective pipe.

Maschinenfabrik Reinhausen GmbH 2020

82 6385142/08 EN ETOS® ED ▪ For signal transmission, use shielded lines with individual conductors (out- going conductor / return conductor) twisted in pairs. ▪ Connect full surface of shielding (360º) to device or to a nearby grounding bar. Using single conductors may limit the effectiveness of the shielding. Con- nect close-fitting shielding to cover all areas. Figure 67: Recommended connection of the shielding 1 Connection of the shielding via a single conductor 2 Full-surface connection of the shielding 6.4.5.3 Wiring requirement in control cabinet Note the following when wiring the control cabinet: ▪ The control cabinet where the device will be installed must be prepared in accordance with EMC requirements: – Functional division of control cabinet (physical separation) – Constant potential equalization (all metal parts are joined) – Line routing in accordance with EMC requirements (separation of lines which cause interference and those susceptible to interference) – Optimum shielding (metal housing) – Overvoltage protection (lightning protection) – Collective grounding (main grounding rail) – Cable bushings in accordance with EMC requirements – Any contactor coils present must be interconnected ▪ The device's connection cables must be laid in close contact with the grounded metal housing or in metallic cable ducts with a ground connec- tion. ▪ Signal lines and power lines/switching lines must be laid in separate cable ducts.

Maschinenfabrik Reinhausen GmbH 2020

83 6385142/08 EN ETOS® ED 6.4.5.4 Information about shielding the CAN bus In order for the CAN bus to operate faultlessly, you have to connect the shielding using one of the following variants. If you are not able to use any of the variants detailed below, we recommend using fiber-optic cables. Fiber- optic cables decouple the devices and are not sensitive to electromagnetic interference (surge and burst). NOTICE Damage to the device! If you connect the CAN bus cable to devices with different potentials, cur- rent may flow across the shielding. This current may damage the device. ►Connect the devices to a potential equalization rail to equalize the poten- tial. ►If both devices have different potentials, only connect the CAN bus cable shielding to one device. Variant 1: The connected devices share the same potential If the devices to be connected share the same potential, proceed as follows: 1. Connect all devices to a potential equalization rail to equalize the poten- tial. 2. Connect the CAN bus cable shielding to all connected devices. Variant 2: The connected devices have different potential levels Note that the shielding is less effective with this variant. If the devices to be connected have different potential levels, proceed as fol- lows: ►Connect the CAN bus cable shielding to just one device. Connecting shielding Connect the shielding for the CAN bus cable to the 9-pin D-sub connector: 1 5 9 6 Figure 68: Connection of CAN bus cable shielding to the 9-pin D-sub connector

Maschinenfabrik Reinhausen GmbH 2020

84 6385142/08 EN ETOS® ED 6.4.5.5 Information about shielding the cables for analog signals In order to correctly record the analog signals, you must place the cable screening in the motor-drive unit on the grounding bar. The cable shielding should only be removed just prior to connecting, to ensure that the section with unshielded cables is kept as short as possible. The shielding must be connected with shielding clips. 1 3 2 4 5 11 13 12 14 15 6 8 7 9 10 16 18 17 19 20 RDY AIO 4 + - 24V DC 11 12 13 14 15 16 17 18 20 19 1 2 3 4 5 6 7 8 9 10 Figure 69: Examples of supporting shielding on grounding bar (on left: Direct connection to AIO assembly, on right: Connection using line-up terminal) 6.4.6 Connecting cables to the system periphery To obtain a better overview when connecting cables, only use as many leads as necessary. To connect cables to the system periphery, proceed as follows: ü Use only the specified cables for wiring. Note the cable recommendation. ►Connect the lines to be wired to the device to the system periphery as shown in the connection diagrams supplied. 6.4.7 Wiring the device To obtain a better overview when connecting cables, only use as many leads as necessary. To wire the device, proceed as follows: ü Note the connection diagram. ü Only use the specified cables for wiring. Note the cable recommendation. ü Wire the leads to the system periphery [►Section 6.4.6, Page 84]. 1. Strip insulation from cables and wires.

Maschinenfabrik Reinhausen GmbH 2020

85 6385142/08 EN ETOS® ED 2. Crimp stranded wires with wire end sleeves. 3. Guide the cables into the corresponding plug terminals and fasten them using a screwdriver. Figure 70: Example: Plug for voltage measurement Figure 71: Example: Plug for current measurement 4. Insert the plug into the associated slots and lock or screw the plug in place.

Maschinenfabrik Reinhausen GmbH 2020

86 6385142/08 EN ETOS® ED 6.4.8 Mounting terminating resistor of CAN bus If you want to operate the device in parallel operation, you need to mount a 120 Ω terminating resistor at both ends of the CAN bus. Use the plug con- nector with terminating resistor provided as an option. Figure 72: Terminating resistor of CAN bus 6.5 Connecting the motor-drive unit WARNING Danger of death or severe injury! An energized transformer and energized on-load tap-changer components could cause death or serious injuries when installing the electrics! ►Adherence to the following safety precautions is mandatory. The drive may only be connected to circuits that are equipped with an exter- nal and all-pole isolating device as close to the drive as possible to ensure that the unit can be fully de-energized if required (service, maintenance etc.). Furthermore, a drive without its own overcurrent protective device for the control circuit and the heater circuit may only be connected to circuits that are equipped with an external overcurrent protective device. The protective device must ensure protection against indirect touching. The protection rec- ommended by Maschinenfabrik Reinhausen GmbH close to the drive is 1.6 A C (3.0 A C is to be used in a heater circuit with additional heating and sup- ply voltage <127 V AC/DC). This is to be verified after installation by carrying out a measurement.

Maschinenfabrik Reinhausen GmbH 2020

87 6385142/08 EN ETOS® ED Suitable equipment includes isolating devices in accordance with IEC 60947-1 and IEC60947-3 (e.g. circuit breaker). When selecting the circuit breaker type, the properties of the relevant circuits (voltage, maximum cur- rents) must be observed. The following should also be noted during installa- tion: ▪ It must be easy for the operator to access the isolating device ▪ The isolating device must be labeled for the device and circuits to be iso- lated ▪ The isolating device may not be a part of the power line ▪ The isolating device may not interrupt the main protective conductor Unless specified otherwise, the connections for the supply circuits must have a conductor cross-section of at least 2.5 mm2 (16 AWG). Check applicable standards and directives to ensure that the specified minimum cross-section of the supply line is sufficient. 6.5.1 Cable recommendation NOTICE Damage to the device. Current flow through the shielding of signal lines can cause the device to become damaged. ►For signal lines between the motor-drive unit and transformer, connect the shielding of the signal line to the motor-drive unit only. ►For all other signal lines, connect the shielding on both sides as long as there is no potential difference between the two devices. If there is a po- tential difference, then connect the shielding on one side only even when using these signal lines. Please note the following Maschinenfabrik Reinhausen GmbH recommenda- tion when wiring. ▪ Electromagnetic interference on signal lines, which can be expected due to the transformer's surroundings, can disrupt the proper operation of the motor-drive unit. ▪ Where possible, route signal lines with shielding. ▪ Ensure that the copper cables used have a temperature resistance of 70°C. Circuit Function Type Material Motor circuit Power supply Unshielded, separate cable Copper Control circuit Power supply Unshielded, separate cable Copper Tap-change supervisory con- trol Shielded Copper Pulse circuit, raise/lower Shielded Copper Tripping circuit Q1-Off Shielded Copper Monitoring circuit Temperature sensor Shielded Copper Signaling circuits Signal transmission Shielded Copper

Maschinenfabrik Reinhausen GmbH 2020

88 6385142/08 EN ETOS® ED Circuit Function Type Material Cross wiring between motor- drive units Power supply Unshielded, separate cable Copper Tap-change supervisory con- trol Shielded Copper Pulse circuit, raise/lower Shielded Copper Tripping circuit Q1-Off Shielded Copper Table 15: Recommendation for connection cables 6.5.2 Electrical connection The voltage supply for the motor-drive unit must be able to provide 5…7 times the nominal operating current of the motor-drive unit for one second. A maximum voltage tolerance of -20…+10% of the nominal voltage must be observed to avoid damage to the drive. 1. Switch off the voltage supply. 2. Secure the voltage supply to prevent an unintentional restart. 3. Ensure that everything is de-energized. 4. Visibly ground and short-circuit the motor-drive unit. 5. Cover or cordon off adjacent energized parts. 6. Connect the motor-drive unit in accordance with the connection diagrams provided in the briefcase. Observe the supply voltages (motor circuit, con- trol circuit, heater circuit) and pin assignments stated in the connection di- agram. 7. When operating the motor-drive unit, ensure that a current corresponding to that stated in the Technical Data chapter (Load capacity of micro- switches) flows through the micro-switches in the motor-drive unit at all times to ensure correct functioning of the micro-switches.

Maschinenfabrik Reinhausen GmbH 2020

89 6385142/08 EN ETOS® ED 7 Commissioning 7.1 Starting up motor-drive unit Preparation 1. Make sure that the motor-drive unit is connected as shown in the connec- tion diagram provided. 2. Ensure that all protective conductors are connected correctly. 3. Ensure that the preliminary fuse is selectively configured for the protective devices in the motor-drive unit. 4. Ensure that motor-drive unit and on-load tap-changer are correctly cou- pled and the operating positions of the motor-drive unit and on-load tap- changer match. 5. Ensure that the hand crank is not inserted in the hand crank aperture. 6. Ensure that all signaling contacts provided in the connection diagram are output and monitored in the control room. 7. Ensure that the motor protective switch and control circuit fuse are dis- abled. Commissioning 1. Apply voltage to the motor-drive unit. 2. Measure the voltage and frequency of the motor circuit at terminal X1 and compare with the details on the nameplate. The details must match. 3. As an option with separate control-circuit supply: Measure the voltage and frequency of the control circuit at terminal X1 and compare with the details on the nameplate. The details must match. 4. As an option with separate heating-circuit supply: Measure the voltage of the heater circuit at terminal X1 and compare with the details on the con- nection diagram. The details must match. 5. As an option with three-phase motor: Ensure that the voltage applied to the connection terminals has a clockwise phase sequence. 6. As an option with DC motor: Ensure that the motor voltage has the right potential connection. 7. Engage the motor protective switch and fuses for the control circuit and heater circuit (if present). ð The voltage monitor LED and thermostat LED (if present) on the rear of the swing frame must light up green. 8. Close the motor-drive unit and secure it against unauthorized opening by using a padlock. ð Commissioning is complete. Contact Maschinenfabrik Reinhausen GmbH if anything is not clear or you encounter problems during commissioning.

Maschinenfabrik Reinhausen GmbH 2020

90 6385142/08 EN ETOS® ED 7.2 Tests on motor-drive unit WARNING Electric shock! Risk of death or severe injury due to electrical voltage! ►Make sure that the motor-drive unit is correctly connected as shown in the connection diagrams provided. ►Make sure that the supply voltage is matched to the technical data of the motor-drive unit. ►Ensure contact safety before performing the checks and tests. The trans- mission gear cover plate must be fitted and the motor and swing frame closed. ►Ensure that the motor-drive unit and on-load tap-changer/de-energized tap-changer are correctly coupled and that they are in the same tap posi- tion for each operating position. Please contact Maschinenfabrik Reinhausen GmbH (MR) if any aspect of the tests is not clear. 7.2.1 Checking correct electric switch-off 1. Change over motor-drive unit by moving control switch S3. 2. Check that the pointer of the tap-change indicator stops within the gray field after completing a tap-change operation. 3. Carry out this test in both directions.

Maschinenfabrik Reinhausen GmbH 2020

91 6385142/08 EN ETOS® ED 7.2.2 Checking mechanical and electric end stop of on-load tap- changer/de-energized tap-changer and motor-drive unit 1. Press the S3 control switch to switch the motor-drive unit to the second- to-last operating position. Figure 73: S3 control switch 2. Open the motor-drive unit door and switch off the motor protective switch Q1 (position O). 3. Using the hand crank, operate the motor-drive unit to move it to its last op- erating position. If the last operating position is not reached, check the coupling between the on-load tap-changer / de-energized tap-changer and motor-drive unit. 4. Continue turning the motor-drive unit in the same direction with the hand crank until the motor-drive unit is mechanically blocked. 5. Turn back the motor-drive unit with the hand crank to the mid-position of the tap-change indicator. 6. Remove the hand crank. 7. Switch on motor protective switch Q1 (position I). 8. Check that the motor-drive unit no longer starts up when the S3 switch is turned further in the same operating direction as under item 1. 9. Perform the check for both end positions. 7.2.3 Checking tripping of motor protective switch Proceed as follows to check tripping of the motor protective switch: ü The motor protective switch Q1 is switched on (position I). 1. Close X1:14 - X1:15 Q1 OFF connection to trip the motor protective switch. ð The motor protective switch is tripped (position O). If the motor protec- tive switch is not tripped, contact Maschinenfabrik Reinhausen GmbH. 2. Switch on motor protective switch again (position I). ð The tripping of the motor protective switch is checked.

Maschinenfabrik Reinhausen GmbH 2020

92 6385142/08 EN ETOS® ED 7.2.4 Checking functional reliability To ensure that the device is wired correctly, check its functional reliability. NOTICE Damage to device and system periphery An incorrectly connected device can lead to damage to the device and sys- tem periphery. ►Check the entire configuration before commissioning. Check the following: ▪ The RUN LED on the CPU I assembly lights up. The device is fully mounted and can be configured. The actions required for this are described in the following chapter. 7.3 Tests on the transformer Please contact Maschinenfabrik Reinhausen GmbH (MR) if any aspect of the tests is not clear. 7.3.1 High-voltage tests on the transformer Note the following points before performing high-voltage tests on the trans- former: ▪ Ensure that the oil compartment of the on-load tap-changer is completely filled with insulating fluid. ▪ Ensure that all protective devices for the on-load tap-changer are function- ing correctly and are ready for use. ▪ Ensure that the ground connections on the motor-drive protective housing and protective housing fastening are free of paint. ▪ Only perform high voltage test if motor-drive unit door is closed. ▪ Disconnect external connections to electronic components in the motor- drive unit to prevent damage from overvoltage. ▪ When connecting the motor-drive unit's supply voltage, only use the cable bushings in the protective housing base intended for lead insertion. ▪ Guide all ground connecting leads to one central connection point (estab- lishment of suitable reference earth). ▪ Disconnect all electronic components before the high voltage test. Before a dielectric test of the wiring, remove all devices with a withstand voltage of < 1000 V.

Maschinenfabrik Reinhausen GmbH 2020

93 6385142/08 EN ETOS® ED ▪ Remove leads used for testing before the high voltage test as these func- tion as antennas. ▪ Wherever possible, route the measurement leads and data leads sepa- rately to the energy cables. Contact the manufacturer if you have any questions about possible sources of danger. 7.3.2 Dielectric tests on transformer wiring Note the following points for dielectric tests on the transformer wiring: The motor-drive unit is put through dielectric tests before delivery. ►Before the dielectric test for the transformer wiring, disconnect drive from the section to be tested to rule out increased component loading for those components fitted in the motor-drive unit. 7.4 Transporting transformer to the operating site If the drive must be removed in order to transport the transformer, proceed as follows: 1. Ensure that the drive and the on-load tap-changer are in the adjustment position. 2. Remove the drive. 3. Do not actuate the drive while the on-load tap-changer is uncoupled and do not turn the output shaft. 4. Do not actuate an on-load tap-changer which is uncoupled and do not turn its drive shaft. 5. Transport the drive to the installation site in the MR delivery packaging. 6. Fit drive and drive shaft to transformer at the installation site. 7.5 Commissioning the transformer at the operating site NOTICE Damage to motor-drive unit! Damage to the motor-drive unit due to condensate in protective housing of motor-drive unit. ►Always keep protective housing of the motor-drive unit tightly closed. ►In the event of downtime lasting more than 8 weeks prior to initial com- missioning, connect and operate the anti-condensation heater in the mo- tor-drive unit. If this is not possible, place a sufficient amount of desiccant in the protective housing.

Maschinenfabrik Reinhausen GmbH 2020

94 6385142/08 EN ETOS® ED NOTICE Damage to the on-load tap-changer and motor-drive unit! Damage to on-load tap-changer and motor-drive unit due to incorrect use of position transmitter equipment. ►Only circuits stated in the chapter Technical data for position transmitter equipment [►Section 14.3, Page 380] may be connected to the position transmitter module connections. ►The switchover point of the position transmitter equipment in the motor- drive unit is not the same as the switchover point of the diverter switch operation. This depends on the type of diverter switch. This fact should be noted when project planning the locking circuits between the motor- drive unit and external equipment (e.g. transformer circuit breaker). ►Therefore, the "Tap changer in operation" position transit contact shown in the connection diagram should be used for external monitoring, locking and control purposes instead of the position transmitter equipment. 1. Commission motor-drive unit [►Section 7.1, Page 89]. 2. Ensure correct function of motor-drive unit [►Section 7.2, Page 90]. 3. Commission the transformer. 7.6 Visualization 7.6.1 Establishing connection to visualization Depending on the product version, you can establish a connection to the vi- sualization as follows. ETOS® ED without display You can use the ETH2.1 interface or the optional ETH2.2 interface of the CPU assembly to establish the connection to the visualization. The inter- faces do not use a DHCP server. Therefore, you must assign a static IP ad- dress to your PC. To do this, observe the following configuration example: Interface Configuration Standard ETH2.1 IP address: 192.168.165.1 (not adjustable) PC IP address: 192.168.165.100 Subnet mask: 255.255.255.0 Optional ETH2.2 IP address: 192.0.1.230 (factory setting) [►Section 9.3, Page 111] Subnet mask: 255.255.255.0 PC IP address: 192.0.1.100 Subnet mask: 255.255.255.0 Table 16: Interface configuration example

Maschinenfabrik Reinhausen GmbH 2020

95 6385142/08 EN ETOS® ED To establish a connection, proceed as follows: 1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the ETH2.1 or ETH2.2 interface. Figure 74: Establishing a connection via the ETH2.1 or ETH2.2 interface 2. Assign a unique IP address to the PC. This IP address must be in the same subnet as the device (e.g. ETH2.1: 192.168.165.100). 3. Enter the IP address of the visualization (e.g. ETH2.1: http://192.168.165.1; if SSL encryption is active, enter https://192.168.165.1) in the browser on the PC. ð The visualization is accessed. ETOS® ED with display You can use the ETH1.1 front interface or the optional ETH2.2 interface of the CPU assembly to establish the connection to the visualization. To do this, observe the following configuration example: Interface Configuration Standard ETH1.1 IP address: 192.168.165.1 (not adjustable) PC Automatic configuration via DHCP Optional ETH2.2 IP address: 192.0.1.230 (factory setting) [►Section 9.3, Page 111] Subnet mask: 255.255.255.0 PC IP address: 192.0.1.100 Subnet mask: 255.255.255.0 Table 17: Interface configuration example

Maschinenfabrik Reinhausen GmbH 2020

96 6385142/08 EN ETOS® ED ETH1.1 interface To establish a connection via the ETH1.1 interface, proceed as follows: 1. Connect the PC and the device via the front interface using an Ethernet cable (RJ45 plug). Figure 75: Establishing a connection via the front interface 2. Activate automatic assignment of the IP address via DHCP on the PC. 3. Enter the visualization's IP address http://192.168.165.1, or if SSL encryption is active enter https://192.168.165.1, in the browser on the PC. ð The visualization is accessed. ETH2.2 interface (optional) The device is supplied with the IP address 192.0.1.230 at the factory. If you have changed the IP address, you can view the IP address in the Com- munication menu.

Maschinenfabrik Reinhausen GmbH 2020

97 6385142/08 EN ETOS® ED To connect via the ETH2.2 interface, proceed as follows: 1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the ETH2.2 interface. Figure 76: Establishing a connection via the ETH2.2 interface on the back 2. Assign a unique IP address to the PC in the same subnet as the device (e.g. 192.0.1.100). 3. Enter the visualization's IP address (e.g. http://192.0.1.230, if SSL encryption is active enter https://192.0.1.230) in the browser on the PC. ð The visualization is accessed. 7.6.2 Setting the language You can use this parameter to set the display language for the device. The device comes with a maximum of four languages. English Italian* German Portuguese* French* Russian* Spanish* Chinese* Korean* Polish* Table 18: Available display languages *) Language is available as an option 1. Select the Language button in the status bar, or as an alternative, go to Settings> System > General > Language. Figure 77: Setting the language 2. Select the desired language from the list box. 3. Press the Accept button to save the modified parameter. ð The "Restart device" dialog appears.

Maschinenfabrik Reinhausen GmbH 2020

98 6385142/08 EN ETOS® ED 4. Restart the device to apply the changed language setting. 7.6.3 Setting date and time You can set the date and time in the following ways: ▪ Manually ▪ Time synchronization via control system (SCADA) ▪ Time synchronization via SNTP time server If you are using a control system, the device automatically synchronizes the date and time with the control system. If you would like to use an SNTP time server, you must set the required parameters. For more information, refer to the information in the section Setting the de- vice time [►Section 9.5, Page 116]. 7.6.4 Commissioning wizard If you want the device to help when setting the relevant parameters, you can use the commissioning wizard. The commissioning wizard provides a selec- tion of parameters that you can configure in order. A detailed description of each of the parameters can be found in the Opera- tion chapter. To call up the commissioning wizard, you will need the necessary access rights [►Section 9.34, Page 315]. When in delivery status, you can log in as the administrator as follows: ▪ User name: admin ▪ Password: admin To set the parameters with the help of the commissioning wizard, proceed as follows: 1. Log in as a user with the necessary access rights.

Maschinenfabrik Reinhausen GmbH 2020

99 6385142/08 EN ETOS® ED 2. Go to Settings > Commissioning wizard. Figure 78: Calling up the commissioning wizard 3. Press the Next button to launch the commissioning wizard. 4. Follow the on-screen instructions. Once you have entered all of the parameters relevant to commissioning, continue with the function test. 7.6.5 Checking measured values and status of digital inputs and outputs Upon commissioning the device, check whether the measured values and status of digital inputs and outputs are plausible. To do so, use an additional measuring device if necessary in order to check the individual measured val- ues. To display the status of the digital inputs and outputs, proceed as follows: 1. Go to Information > Hardware. 2. Select the individual assemblies one after another and check the individ- ual measured values or the status of digital inputs and outputs. 3. If errors arise, check the measurement path and the wiring. 7.6.6 Checking the temperature measurement To commission the device, check whether the measured temperatures are plausible, the temperature sensors are correctly wired and are assigned to the desired functions. To do so, proceed as follows: 1. Display the temperature curve [►Section 9.24.4, Page 253]. 2. Use a suitable measuring instrument to measure the temperatures at the measurement points and compare these values to the displayed tempera- tures. ð The temperatures must match, though small deviations are permitted due to the measurement tolerances.

Maschinenfabrik Reinhausen GmbH 2020

100 6385142/08 EN ETOS® ED 3. If the temperatures do not match, use the connection diagram to check the wiring. Check configuration of the analog inputs [►Section 9.29, Page 292]. Check the function of the temperature sensors.

Other DC Drives Manuals