Tate SmartAire M Manual
Text of the manual
Advanced SmartAire M and PowerAire M
Controller Guide
Tate’s SmartAire and PowerAire M units are factory configured for
optimal performance in a typical data center environment. The
installation of these units in most data center space will result in ideal
performance without any user intervention.
Some sites however have differing requirements, and the ap
Default Home Screen
SEL
74.6
Press and Hold Up and Down
Simultaneously for 5 Seconds
SEL
To enter Advanced Programming Mode
Unt
Unit Selection Prompt
SEL
To change Unit Type
Unt
Unit Type Current Setting
SEL
To change Unit Type
dPr
SEL
or
FaN
SEL
Press SEL to store the setting
noS
Number of Installed Sensors
SEL
To Change the number of sensors
noS
To ch
Press up or down to change sensor count
Default value is 3. Press SEL to store the setting
Default value is 3. Press SEL to store the setting
StP
Start Point Configuration
Prompt
SEL
To change the Start Point Value
1.5
Start Point Current Setting
SEL
To change the Start Point Value
0.0
Start Point Configuration
Adjustment
SEL
High Point Configuration
Prompt
SEL
To change the maximum fan speed or
damper opening setting
10.0
High Point Current Setting
SEL
To change the Start Point Value
9.0
High Point Configuration
Adjustment
SEL
Default value is 10.0. Adjust the value from the Lo setting to 10.0
(represents percentage) press SEL to save setting
ctr
Controller Type
Configuratio
Proportional Term Current
Setting
SEL
The default Pb value is 45, if the unit seems too slow in responding in your
environment, decrease the value to achieve a quicker response
45.0
SEL
Default value is 45.0. Adjust the Proportional term as required, higher numbers reduce
the effect of the proportional term, lower values increase the effect. Press SEL t
Dead Band Value
Configuration Prompt
SEL
This value allows the user to adjust the dead band of the temperature values before
any action is taken by the controller to adjust the settings. This dead band is +/- the
current temperature setpoint
1.0
Dead Band Value Current Setting
SEL
This value represents the current dead band of the controller where no acti