Tate SmartAire M Manual 

Text of the manual

Advanced SmartAire M and PowerAire M

Controller Guide Tate’s SmartAire and PowerAire M units are factory configured for optimal performance in a typical data center environment. The installation of these units in most data center space will result in ideal performance without any user intervention. Some sites however have differing requirements, and the ap

Default Home Screen

SEL 74.6 Press and Hold Up and Down Simultaneously for 5 Seconds SEL To enter Advanced Programming Mode Unt Unit Selection Prompt SEL To change Unit Type Unt Unit Type Current Setting SEL To change Unit Type dPr SEL or FaN SEL Press SEL to store the setting noS Number of Installed Sensors SEL To Change the number of sensors noS To ch

Press up or down to change sensor count

Default value is 3. Press SEL to store the setting Default value is 3. Press SEL to store the setting StP Start Point Configuration Prompt SEL To change the Start Point Value 1.5 Start Point Current Setting SEL To change the Start Point Value 0.0 Start Point Configuration Adjustment SEL

High Point Configuration

Prompt SEL To change the maximum fan speed or damper opening setting 10.0 High Point Current Setting SEL To change the Start Point Value 9.0 High Point Configuration Adjustment SEL Default value is 10.0. Adjust the value from the Lo setting to 10.0 (represents percentage) press SEL to save setting ctr Controller Type Configuratio

Proportional Term Current

Setting SEL The default Pb value is 45, if the unit seems too slow in responding in your environment, decrease the value to achieve a quicker response 45.0 SEL Default value is 45.0. Adjust the Proportional term as required, higher numbers reduce the effect of the proportional term, lower values increase the effect. Press SEL t

Dead Band Value

Configuration Prompt SEL This value allows the user to adjust the dead band of the temperature values before any action is taken by the controller to adjust the settings. This dead band is +/- the current temperature setpoint 1.0 Dead Band Value Current Setting SEL This value represents the current dead band of the controller where no acti